Sensors as alternative
As an alternative for traditional primary current and voltage measurement
techniques, the use of sensor technique is gaining field. This technique is
typically applied to current and voltage measurement in medium-voltage metal-
enclosed indoor switchgears.
http://electrical-engineering-portal.com/current-and-voltage-sensors-as-an-alternative-to-traditional-cts-and-vts 1/8
4/11/2018 Current and voltage sensors as an alternative to CTs and VTs
Current and voltage sensors as an alternative to traditional CTs and VTs (on photo: The current snsors
type KECA 80 Cxxx are intended for use in current measurement in medium voltage air insulated
switchgear type UniGear ZS1 12/17.5kV)
Non-saturable
High degree of accuracy
Personnel safety
Extensive dynamic range
Small physical size and weight
Possibility to combine current and voltage measurement into one physical
device with compact dimensions
Environmental friendliness (less raw material needed)
The above statements are discussed in more detail in the following paragraphs
while introducing the sensor techniques and the actual related apparatus. Let’s
say a word about each type of sensor and some conclusion at the end:
1. Current sensors
2. Voltage sensors
3. Combined sensors
4. Conclusion and answer on why sensors are not 100% alternative
Current Sensors
http://electrical-engineering-portal.com/current-and-voltage-sensors-as-an-alternative-to-traditional-cts-and-vts 2/8
4/11/2018 Current and voltage sensors as an alternative to CTs and VTs
Figure 1 – Principle of
current measurement based
on Rogowski coil
Uout = M · dip / dt
For a sinusoidal current under steady state conditions the voltage is:
Uout = M · j · ω · Ip
With traditional current transformers, the ratio of the CT is fixed to one value, or
in case of multi-ratio CTs, to several values. These values are chosen
according to the specific application needs and load currents.
With a current sensor, the situation is simpler, since one type of sensor covers
a range of primary currents and in optimum case the whole installation can be
covered with one type only.
http://electrical-engineering-portal.com/current-and-voltage-sensors-as-an-alternative-to-traditional-cts-and-vts 3/8
4/11/2018 Current and voltage sensors as an alternative to CTs and VTs
To give an idea of the secondary-voltage signal level, one fixed point (ratio)
inside the rated current range could be 400 A primary value, typically
corresponding to 150 mV secondary signal level.
http://electrical-engineering-portal.com/current-and-voltage-sensors-as-an-alternative-to-traditional-cts-and-vts 4/8
4/11/2018 Current and voltage sensors as an alternative to CTs and VTs
Due to the compact size of a current sensor (no iron core), there are better
possibilities to integrate the measurement devices inside other constructional
parts of a metal-enclosed switchgear.
Go back to Types ↑
Voltage Sensors
http://electrical-engineering-portal.com/current-and-voltage-sensors-as-an-alternative-to-traditional-cts-and-vts 5/8
4/11/2018 Current and voltage sensors as an alternative to CTs and VTs
As with current sensors, also with voltage sensors it is possible to cover certain
voltage range with one sensor type. To give an idea of the secondary voltage
signal level, one fixed point (ratio) inside the rated voltage range could be
20000/√3V primary value, typically corresponding to 2/√3V secondary-signal
level.
Go back to Types ↑
Combined Sensors
http://electrical-engineering-portal.com/current-and-voltage-sensors-as-an-alternative-to-traditional-cts-and-vts 6/8
4/11/2018 Current and voltage sensors as an alternative to CTs and VTs
The sensor solution being quite compact and space saving, it is possible to
combine both current and voltage sensors in one physical device. This device
can be part of the switchgear’s mechanical basic construction, having
other functions beside the measurement, like being a part of medium-voltage
cable termination or busbar support construction.
Go back to Types ↑
It could also be asked why the sensor approach has not totally taken over the
traditional approach, at least when it comes to medium-voltage indoor
switchgear. This is a very valid question and several answers could be given,
depending on the viewpoint of the person answering.
http://electrical-engineering-portal.com/current-and-voltage-sensors-as-an-alternative-to-traditional-cts-and-vts 7/8
4/11/2018 Current and voltage sensors as an alternative to CTs and VTs
Go back to Types ↑