X XENtestregistrierung
CAV controllers
Type EN
General information EN
Type Page
EN General information 2.1 – 36
Order code 2.1 – 39
Aerodynamic data 2.1 – 40
Quick sizing 2.1 – 42
Dimensions and weight – EN 2.1 – 44
Dimensions and weight – EN-D 2.1 – 45
Specification text 2.1 – 46
2 Basic information and nomenclature 2.3 – 1
Product examples
General information EN
Construction features
(B + H ≤400, class B)
2
– Rectangular casing Maintenance
– Connecting flanges on both ends, suitable for – Maintenance-free as construction and
air duct profiles materials are not subject to wear
EN-D
– Acoustic cladding made of galvanised
sheet steel
– Rubber profile for the insulation of
structure-borne noise
– Lining is made of mineral wool
Mineral wool
– To EN 13501, fire rating class A2,
non-combustible
– RAL quality mark RAL-GZ 388
– Biosoluble and hence hygienically safe
according to the German TRGS 905 (Technical
Rules for Hazardous Substances) and
EU directive 97/69/EG
General information EN
ݢ
ݣ
ݤ
ݩ ݥ
ݦ
ݨ ݧ
Order code EN
Order code EN
Aerodynamic data EN
Volume flow rate Volume flow rate ranges and minimum differential pressure values
ranges
① ②
Nominal
The minimum differential ∆pst min ∆
size
pressure of CAV
l/s m³/h Pa Pa ±%
controllers is an important
factor in designing the 40 144 50 60 13
ductwork and in rating the 80 288 50 80 9
fan including speed 200 × 100
120 432 50 115 6
control.
160 576 50 160 5
Aerodynamic data EN
Volume flow rate ranges Volume flow rate ranges and minimum differential pressure values
① ②
Nominal
The minimum differential ∆pst min ∆
size
pressure of CAV
l/s m³/h Pa Pa ±%
controllers is an important
factor in designing the 420 1512 50 60 13
ductwork and in rating the 840 3024 50 75 9
fan including speed 600 × 300
1260 4536 50 110 6
control.
1680 6048 50 150 5
Sufficient duct pressure
must be ensured for all
420
840
1512
3024
50
50
60
85
13
9
2
operating conditions and 400 × 400
for all terminal units. The 1260 4536 50 120 6
measurement points for 1680 6048 50 175 5
the speed control must be 460 1656 50 60 13
selected accordingly.
920 3312 50 80 9
500 × 400
1380 4968 50 115 6
1840 6624 50 160 5
510 1836 50 60 13
1020 3672 50 80 9
600 × 400
1530 5508 50 115 6
2040 7344 50 160 5
600 2160 50 60 13
1200 4320 50 80 9
500 × 500
1800 6480 50 115 6
2400 8640 50 160 5
640 2304 50 55 13
1280 4608 50 70 9
600 × 500
1920 6912 50 95 6
2560 9216 50 130 5
840 3024 50 60 13
1680 6048 50 75 9
600 × 600
2520 9072 50 105 6
3360 12096 50 145 5
① EN
② EN with secondary silencer TX
Quick sizing EN
Air-regenerated noise Quick sizing: Sound pressure level at differential pressure 150 Pa
Quick sizing EN
Air-regenerated noise Quick sizing: Sound pressure level at differential pressure 150 Pa
ˤ ̔ʹʷʷ
400
ݢ
m³/h
l/s
900
̔ʹʷʷ
1200
360
1500
480
Hˤ
1800
Hˣ
H
600
2100
720
2400
2700
300
0
m³
/h
EN 400 x 200
̔350 ˣ Øʸʺ̍ʹʷ
400
ݢ
m³/h
l/s
900
̔ʹʷʷ
1200
360
1500
480
Hˤ
1800
Hˣ
H
600
2100
720
2400
2700
3000
m³
/h
EN 400 x 200
M8
̔350 ˣ
Specification text EN
Standard text Rectangular volume flow controllers for constant Mineral wool
air volume systems, mechanical self-powered, – To EN 13501, fire rating class A2,
This specification text without external power supply, suitable for supply non-combustible
describes the general or extract air, available in 19 nominal sizes. – RAL quality mark RAL-GZ 388
properties of the product.
Texts for individual
Ready-to-commission unit consists of the casing – Biosoluble and hence hygienically safe
variants can be generated containing a damper blade with low-friction according to the German TRGS 905 (Technical
with our Easy Product bearings, bellows, external cam plate and leaf Rules for Hazardous Substances) and
Finder design spring. EU directive 97/69/EG
programme. Volume flow controllers without actuators are
factory set to a reference volume flow rate Construction
2 (customers can set the required volume flow rate
on site).
– Galvanised sheet steel
– P1: Powder-coated, silver grey (RAL 7001)
Both ends suitable for the connection of air duct
Technical data
profiles.
– Nominal sizes: 200 × 100 to 600 × 600 mm
Casing air leakage to EN 1751, class C
– Volume flow rate range: 40 – 3360 l/s or
(B + H ≤400, class B)
144 – 12096 m³/h
Special features – Volume flow rate control range:
– Volume flow rate can be set using an external approx. 25 – 100 % of the nominal volume flow
scale; no tools required rate
– High volume flow rate control accuracy – Differential pressure: 50 – 1000 Pa
– Any installation orientation
Sizing data
– Correct operation even under unfavourable
– ______________________________ [m³/h]
upstream or downstream conditions (1.5 B
– Δpst ______________________________ [Pa]
straight section required upstream and 0.5 B
– LPA Air-regenerated noise __________ [dB(A)]
required downstream)
– LPA Case-radiated noise ___________ [dB(A)]
Materials and surfaces
– Casing and damper blade made of galvanised
sheet steel
– Leaf spring made of stainless steel
– Polyurethane bellows
– Plain bearings with PTFE coating
EN-D
– Acoustic cladding made of galvanised sheet
steel
– Rubber profile for the insulation of structure-
borne noise
– Lining is made of mineral wool
Product selection
Type
Type of system
Supply air Ѐ Ѐ Ѐ Ѐ Ѐ Ѐ
Extract air Ѐ Ѐ Ѐ Ѐ Ѐ Ѐ
Duct connection,
fan end
2 Circular Ѐ Ѐ Ѐ Ѐ
Rectangular Ѐ Ѐ
Polluted Ͽ Ͽ Ͽ Ͽ Ͽ Ͽ
Contaminated Ͽ Ͽ Ͽ Ͽ Ͽ Ͽ
Control function
Constant Ѐ Ѐ Ѐ Ѐ Ѐ Ѐ
Variable Ͽ Ͽ Ͽ
Min/Max Ͽ Ͽ Ͽ
Acoustic requirements
High < 40 dB (A) Ͽ Ͽ Ͽ Ͽ Ͽ
Low < 50 dB (A) Ѐ Ѐ Ѐ Ѐ Ѐ Ѐ
Special areas
Potentially explosive
Ѐ Ѐ
atmospheres
Ѐ Possible
Ͽ Possible under certain conditions: Robust unit variant and/or specific actuator
or useful additional product
Not possible
2
Inside diameter of the flange screw holes Outside dimension of air duct profile (height)
L [mm] H₃ [mm]
Length of unit including spigot Unit height
L₁ [mm] n[]
Length of casing or acoustic cladding Number of flange screw holes
W [mm] T [mm]
Width of the duct Flange thickness
B₁ [mm] m [kg]
Screw hole pitch of air duct profile (horizontal) Unit weight including the minimum required
attachments (e.g. Compact controller)
B₂ [mm]
Outside dimension of air duct profile (width)
LPA3 [dB(A)]
A-weighted sound pressure level of
case-regenerated noise of the CAV controller with
acoustic cladding, system attenuation taken into
account
ݑ
ݣ ݢ
͍Æst
LPA
① Air-regenerated noise
② Case-radiated noise
The quick sizing tables Reducing the sound pressure level of the air-regenerated noise
show the sound pressure
levels that can be
expected in a room both
for the air-regenerated
noise and for the case-
radiated noise. The sound
pressure level in a room
results from the sound
power level of the
products – for a given
Correction values for Octave correction for the distribution in the ducting,
acoustic quick sizing used to calculate the air-regenerated noise
The correction values for [m³/h] 500 1000 1500 2000 2500 3000 4000 5000 6000
the distribution in the [l/s] 140 280 420 550 700 840 1100 1400 1700
ducting are based on the
number of diffusers [dB] 0 3 5 6 7 8 9 10 11
assigned to any one air
terminal unit. If there is
just one diffuser
(assumption: 140 l/s or
500 m³/h), no correction
is necessary.
One change of direction, System attenuation per octave to VDI 2081 for the calculation of the air-regenerated noise
e.g. at the horizontal
connection of the diffuser Centre 63 125 250 500 1000 2000 4000 8000
plenum box, has been frequency ΔL ΔL
taken into consideration [Hz] dB dB dB dB dB dB dB dB
for the system attenuation
values. Vertical Change of
0 0 1 2 3 3 3 3
connection of the plenum direction
box does not result in a End reflection 10 5 2 0 0 0 0 0
system attenuation.
Room
Additional changes of 5 5 5 5 5 5 5 5
attenuation
direction result in lower
sound pressure levels.
Octave correction for the calculation of case-radiated noise
2
ݥ ݦ ݣ ݦ
ݑ ǎÆst
ݤLPA
ݢ
ݥ ݦ
ݣ
ݑ ǎÆst
ݤLPA2
Sizing with the help of This catalogue provides convenient quick sizing
this catalogue tables for CAV controllers.
The sound pressure levels for air-regenerated
noise and for case-radiated noise are provided for
all nominal sizes. In addition, generally accepted
attenuation and insulation values have been taken
into account.
Sizing data for other volume flow rates and
differential pressures can be determined quickly
and precisely using the Easy Product Finder
2 design programme.
Quick sizing
RN/200
Air-regenerated noise LPA = 47 dB(A)
Case-radiated noise LPA = 39 dB(A)