EN 2.

1 –
TOC

X XENtestregistrierung

CAV controllers
Type EN

For the precise control of normal and


high constant volume flows
Rectangular self-powered volume flow controllers for the control of supply air or
extract air in constant air volume systems
Suitable for volume flow rates up to 12,096 m³/h or 3,360 l/s
Volume flow rate can be set using an external scale, no tools required
High control accuracy
No on-site test measurements required for commissioning
Suitable for airflow velocities of up to 8 m/s
Casing air leakage to EN 1751, class C

Optional equipment and accessories


Actuator for switching
Acoustic cladding for the reduction of case-radiated noise
between setpoint values
Secondary silencer Type TX for the reduction of air-regenerated noise
Hot water heat exchanger Type WT for reheating the airflow
Actuator for switching between setpoint values

Unit with two controllers

04/2013 – DE/en K5 – 2.1 – 35


CAV controllers
TOC

General information EN

Type Page
EN General information 2.1 – 36
Order code 2.1 – 39
Aerodynamic data 2.1 – 40
Quick sizing 2.1 – 42
Dimensions and weight – EN 2.1 – 44
Dimensions and weight – EN-D 2.1 – 45
Specification text 2.1 – 46
2 Basic information and nomenclature 2.3 – 1

Variants Volume flow controller Type EN CAV controller Type EN-D

Product examples

Description Application Attachments


– Rectangular CONSTANTFLOW – Min/Max actuators: Actuators for switching
CAV controllers of Type EN for the precise between minimum and maximum volume flow
supply air or extract air flow control in constant rate setpoint values
air volume systems – Modulating actuators: Actuators for the
– Mechanical self-powered volume flow control stepless adjustment of volume flow rates or to
without external power supply switch between minimum and maximum
Volume flow controller – Simplified project handling with orders based volume flow rate setpoint values
Type EN on nominal size – Retrofit kits: Actuators and installation
accessories
Variants
For detailed information – EN: Volume flow controller Useful additions
on actuators see – EN-D: Volume flow controller with acoustic – Secondary silencer Type TX
Chapter K5 – 2.2. cladding – Heat exchanger Type WT
– Units with acoustic cladding and/or secondary
silencer Type TX for demanding acoustic Special features
requirements – Volume flow rate can be set using an external
– Acoustic cladding cannot be retrofitted scale; no tools required
– High volume flow rate control accuracy
Construction – Any installation orientation
– Galvanised sheet steel – Correct operation even under unfavourable
– P1: Powder-coated, silver grey (RAL 7001) upstream or downstream conditions (1.5 B
straight section required upstream and 0.5 B
Nominal sizes required downstream)
– 19 nominal sizes from 200 × 100 to 600 × 600

K5 – 2.1 – 36 04/2013 – DE/en


CAV controllers
TOC

General information EN

Parts and characteristics Installation and commissioning


– Ready-to-commission controller – Any installation orientation
– Damper blade with low-friction bearings – Volume flow rate can be set using an external
– Bellows that acts as an oscillation damper scale; no tools required
– Cam plate with leaf spring – No repeat measurements or adjustments by an
– Scale with pointer to set the volume flow rate air conditioning engineer are necessary
setpoint
– Aerodynamic function testing of each unit on a Standards and guidelines
special test rig prior to shipping – Casing air leakage to EN 1751, class C

Construction features
(B + H ≤400, class B)
2
– Rectangular casing Maintenance
– Connecting flanges on both ends, suitable for – Maintenance-free as construction and
air duct profiles materials are not subject to wear

Materials and surfaces


– Casing and damper blade made of galvanised
sheet steel
– Leaf spring made of stainless steel
– Polyurethane bellows
– Plain bearings with PTFE coating

EN-D
– Acoustic cladding made of galvanised
sheet steel
– Rubber profile for the insulation of
structure-borne noise
– Lining is made of mineral wool

Mineral wool
– To EN 13501, fire rating class A2,
non-combustible
– RAL quality mark RAL-GZ 388
– Biosoluble and hence hygienically safe
according to the German TRGS 905 (Technical
Rules for Hazardous Substances) and
EU directive 97/69/EG

Technical data Nominal sizes 200 × 100 to 600 × 600 mm


Volume flow rate range 40 – 3360 l/s
Volume flow rate range 144 – 12096 m³/h
Volume flow rate setting range approx. 25 – 100 % of the nominal volume flow rate
Scale accuracy ±4%
Differential pressure 50 – 1000 Pa
Operating temperature 10 – 50 °C

04/2013 – DE/en K5 – 2.1 – 37


CAV controllers
TOC

General information EN

Function Functional description Efficient commissioning


The volume flow controller is a mechanical self- The volume flow rate setpoint value can be set
powered unit and works without external power quickly and easily using the pointer on the
supply. A damper blade with low-friction bearings external scale; no measurements are required.
is adjusted by aerodynamic forces such that the The advantage over flow adjustment dampers is
set volume flow rate is maintained within the that there is no need for repeat measurements or
differential pressure range. adjustments by an air conditioning engineer.
The aerodynamic forces of the airflow create a Should the system pressure change, e.g. by
closing torque on the damper blade. The bellows opening or closing of duct sections, the flow rates
extends and increases this force while at the in the entire system will also change if flow
2 same time acting as an oscillation damper. The
closing force is countered by a leaf spring that
adjustment dampers are used; however, this is not
the case with mechanical self-powered volume
unrolls over a cam plate. The shape of the cam flow controllers. A mechanical self-powered
plate is such that a change in the differential controller reacts immediately and adjusts the
pressure leads to an adjustment of the damper damper blade such that the set constant volume
blade in a way that the volume flow rate is flow rate is maintained.
maintained almost exactly.

Schematic illustration of the EN

‫ݢ‬

‫ݣ‬

‫ݤ‬
‫ݩ‬ ‫ݥ‬
‫ݦ‬
‫ݨ‬ ‫ݧ‬

① Volume flow rate scale ⑤ Leaf spring


② Volume flow rate scale lock ⑥ Bellows inlet
③ Crossbar ⑦ Bellows
④ Cam plate ⑧ Damper blade

K5 – 2.1 – 38 04/2013 – DE/en


CAV controllers
TOC

Order code EN

Order code EN

EN – D – P1 / 400×200 / B50 / 800 – 3000


݇ ݈ ݉ ݊ ‫݋‬ ‫݌‬

 Type  Nominal size [mm]


EN Volume flow controller B×H

 Acoustic cladding  Actuator 2


No entry: none No entry: none
D With acoustic cladding B50 Min/Max switching, 24 V AC/DC
supply voltage
 Material B52 Min/Max switching, 24 V AC/DC
No entry: galvanised sheet steel supply voltage, with auxiliary switch
P1 Powder-coated, silver grey (RAL 7001) B60 Min/Max switching, 230 V AC
supply voltage
B62 Min/Max switching, 230 V AC
supply voltage, with auxiliary switch
B70 Variable adjustment, 24 V AC/DC
supply voltage
B72 Variable adjustment, 24 V AC/DC
supply voltage, with auxiliary switch

 Volume flow rates [m3/h or l/s]


only actuators 
min – max for factory setting

Order example EN-D/200×100

Acoustic cladding................with acoustic cladding


Material .............................. galvanised sheet steel
Nominal size ................................... 200 × 100 mm

04/2013 – DE/en K5 – 2.1 – 39


CAV controllers
TOC

Aerodynamic data EN

Volume flow rate Volume flow rate ranges and minimum differential pressure values
ranges
① ②
Nominal 
The minimum differential ∆pst min ∆
size
pressure of CAV
l/s m³/h Pa Pa ±%
controllers is an important
factor in designing the 40 144 50 60 13
ductwork and in rating the 80 288 50 80 9
fan including speed 200 × 100
120 432 50 115 6
control.
160 576 50 160 5

2 Sufficient duct pressure


must be ensured for all
65
130
234
468
50
50
60
85
13
9
operating conditions and 300 × 100
for all terminal units. The 195 702 50 125 6
measurement points for 250 900 50 170 5
the speed control must be 105 378 50 60 13
selected accordingly.
210 756 50 80 9
300 × 150
315 1134 50 115 6
420 1512 50 160 5
130 468 50 60 13
260 936 50 80 9
300 × 200
390 1404 50 110 6
520 1872 50 160 5
210 756 50 60 13
420 1512 50 80 9
400 × 200
630 2268 50 115 6
840 3024 50 160 5
230 828 50 60 13
460 1656 50 80 9
500 × 200
690 2484 50 115 6
920 3312 50 160 5
255 918 50 60 13
510 1836 50 80 9
600 × 200
765 2754 50 115 6
1020 3672 50 160 5
220 792 50 60 13
440 1584 50 80 9
400 × 250
660 2376 50 115 6
880 3168 50 160 5
300 1080 50 60 13
600 2160 50 80 9
500 × 250
900 3240 50 115 6
1200 4320 50 160 5
320 1152 50 60 13
640 2304 50 80 9
600 × 250
960 3456 50 115 6
1280 4608 50 160 5
315 1134 50 60 13
630 2268 50 80 9
400 × 300
945 3402 50 115 6
1260 4536 50 160 5
375 1350 50 60 13
750 2700 50 80 9
500 × 300
1125 4050 50 115 6
1500 5400 50 160 5
① EN
② EN with secondary silencer TX

K5 – 2.1 – 40 04/2013 – DE/en


CAV controllers
TOC

Aerodynamic data EN

Volume flow rate ranges Volume flow rate ranges and minimum differential pressure values
① ②
Nominal 
The minimum differential ∆pst min ∆
size
pressure of CAV
l/s m³/h Pa Pa ±%
controllers is an important
factor in designing the 420 1512 50 60 13
ductwork and in rating the 840 3024 50 75 9
fan including speed 600 × 300
1260 4536 50 110 6
control.
1680 6048 50 150 5
Sufficient duct pressure
must be ensured for all
420
840
1512
3024
50
50
60
85
13
9
2
operating conditions and 400 × 400
for all terminal units. The 1260 4536 50 120 6
measurement points for 1680 6048 50 175 5
the speed control must be 460 1656 50 60 13
selected accordingly.
920 3312 50 80 9
500 × 400
1380 4968 50 115 6
1840 6624 50 160 5
510 1836 50 60 13
1020 3672 50 80 9
600 × 400
1530 5508 50 115 6
2040 7344 50 160 5
600 2160 50 60 13
1200 4320 50 80 9
500 × 500
1800 6480 50 115 6
2400 8640 50 160 5
640 2304 50 55 13
1280 4608 50 70 9
600 × 500
1920 6912 50 95 6
2560 9216 50 130 5
840 3024 50 60 13
1680 6048 50 75 9
600 × 600
2520 9072 50 105 6
3360 12096 50 145 5
① EN
② EN with secondary silencer TX

Upstream conditions Bend Junction

The volume flow rate


accuracy Δ applies to a
straight upstream section
of the duct. Bends,
junctions or a narrowing
or widening of the duct
cause turbulences that
may affect measurement.
Duct connections, e.g.
branches off the main 1.5B 0.5B
1.5B 0.5B
duct, must comply with
EN 1505. Some
installation situations The stated volume flow rate accuracy Δ can only be A junction causes strong turbulences. The stated volume
require straight duct achieved with a straight duct section of at least 1.5B flow rate accuracy Δ can only be achieved with a
sections upstream. upstream between any bend and the controller, and a straight duct section of at least 1.5B upstream between
straight duct section of at least 0.5B downstream any bend and the controller, and a straight duct section
Free air intake only with a between the controller and any bend. of at least 0.5B downstream between the controller and
straight duct section of 1B any bend. Shorter upstream sections require a
upstream. perforated plate in the branch and before the CAV
controller. If there is no straight upstream section at all,
the control will not be stable, even with a perforated
plate.

04/2013 – DE/en K5 – 2.1 – 41


CAV controllers
TOC

Quick sizing EN

Air-regenerated noise Quick sizing: Sound pressure level at differential pressure 150 Pa

Quick sizing tables Air-regenerated noise Case-radiated noise


provide a good overview Nominal  ① ② ① ③
of the room sound size LPA LPA1 LPA2 LPA3
pressure levels that can
be expected. Approximate l/s m³/h dB(A)
intermediate values can 40 144 35 19 21 <15
be interpolated. Precise
80 288 41 28 28 21
intermediate values and 200 × 100
spectral data can be 120 432 44 34 33 26

2 calculated with our Easy


Product Finder design
160
65
576
234
46
38
38
22
35
24
30
16
programme.
130 468 44 30 32 24
300 × 100
195 702 45 35 36 29
The first selection criteria 260 936 47 38 39 32
for the nominal size are
the actual volume flow 105 378 41 24 28 19
rates min and max. The 210 756 44 31 34 26
300 × 150
quick sizing tables are 315 1134 46 35 39 32
based on normally
420 1512 47 38 41 35
accepted attenuation
levels. If the sound 130 468 45 24 31 21
pressure level exceeds 260 936 46 29 35 26
the required level, a larger 300 × 200
390 1404 46 33 38 29
VAV terminal unit and/or a
silencer is required. 520 1872 47 35 40 32
210 756 42 23 30 20
420 1512 43 27 35 26
400 × 200
630 2268 44 31 38 30
840 3024 44 33 40 33
230 828 40 21 28 18
460 1656 40 26 33 24
500 × 200
690 2484 41 29 36 28
920 3312 42 31 38 31
255 918 38 20 27 17
510 1836 39 24 31 23
600 × 200
765 2754 39 28 35 27
1020 3672 40 31 37 31
220 792 44 23 32 22
440 1584 45 28 37 27
400 × 250
660 2376 45 31 39 30
880 3168 45 34 41 33
300 1080 41 21 31 21
600 2160 42 26 36 27
500 × 250
900 3240 43 30 39 30
1200 4320 43 33 41 33
320 1152 40 20 30 20
640 2304 40 25 34 25
600 × 250
960 3456 41 28 37 29
1280 4608 42 31 39 32
315 1134 45 25 53 25
630 2268 46 29 40 30
400 × 300
945 3402 47 34 43 34
1260 4536 47 36 45 36
375 1350 43 22 34 23
750 2700 44 28 38 29
500 × 300
1125 4050 44 31 41 32
1500 5400 45 33 43 35
① EN
② EN with secondary silencer TX
③ EN-D

K5 – 2.1 – 42 04/2013 – DE/en


CAV controllers
TOC

Quick sizing EN

Air-regenerated noise Quick sizing: Sound pressure level at differential pressure 150 Pa

Quick sizing tables Air-regenerated noise Case-radiated noise


provide a good overview Nominal  ① ② ① ③
of the room sound size LPA LPA1 LPA2 LPA3
pressure levels that can
be expected. Approximate l/s m³/h dB(A)
intermediate values can 420 1512 41 21 33 22
be interpolated. Precise
840 3024 42 26 37 28
intermediate values and 600 × 300
spectral data can be 1260 4536 42 30 40 31
calculated with our Easy
Product Finder design
1680
420
6048
1512
43
47
32
27
42
39
34
29
2
programme.
840 3024 49 32 44 34
400 × 400
1260 4536 49 36 47 37
The first selection criteria 1680 6048 50 38 49 40
for the nominal size are
the actual volume flow 460 1656 45 24 37 27
rates min and max. The 920 3312 46 29 42 32
500 × 400
quick sizing tables are 1380 4968 47 33 44 35
based on normally
1840 6624 47 35 46 37
accepted attenuation
levels. If the sound 510 1836 43 22 36 25
pressure level exceeds 1020 3672 44 27 40 30
the required level, a larger 600 × 400
1530 5508 44 31 43 33
VAV terminal unit and/or a
silencer is required. 2040 7344 45 33 45 36
600 2160 47 26 40 30
1200 4320 48 31 45 35
500 × 500
1800 6480 49 35 48 39
2400 8640 49 37 50 41
640 2304 45 24 39 28
1280 4608 46 29 43 33
600 × 500
1920 6912 46 32 46 36
2560 9216 46 35 48 39
840 3024 46 26 41 31
1680 6048 47 30 46 36
600 × 600
2520 9072 48 35 49 39
3360 12096 48 37 51 42
① EN
② EN with secondary silencer TX
③ EN-D

04/2013 – DE/en K5 – 2.1 – 43


CAV controllers
TOC

Dimensions and weight – EN EN

Description – Volume flow controller for constant air volume


flow control

Volume flow controller


Type EN

2 Dimensions Dimensional drawing of EN

ˤ ̔ʹʷʷ
400 

‫ݢ‬

m³/h

l/s
900

̔ʹʷʷ
1200
360
1500
480

1800

H
600
2100
720
2400

2700

300
0

/h

EN 400 x 200

̔350 ˣ Øʸʺ̍ʹʷ

① Keep clear to provide access for operation

Dimensions and weight


Nominal Nominal
Nominal B1 B2 H1 H2 m
width height
size
mm mm mm mm mm mm kg
200 × 100 200 100 234 276 134 176 5
300 × 100 300 100 334 376 134 176 6
300 × 150 300 150 334 376 184 226 7
300 × 200 300 200 334 376 234 276 7
400 × 200 400 200 434 476 234 276 9
400 × 250 400 250 434 476 284 326 10
400 × 300 400 300 434 476 334 376 12
400 × 400 400 400 434 476 434 476 18
500 × 200 500 200 534 576 234 276 11
500 × 250 500 250 534 576 284 326 12
500 × 300 500 300 534 576 334 376 13
500 × 400 500 400 534 576 434 476 18
500 × 500 500 500 534 576 534 576 19
600 × 200 600 200 634 676 234 276 13
600 × 250 600 250 634 676 284 326 14
600 × 300 600 300 634 676 334 376 15
600 × 400 600 400 634 676 434 476 18
600 × 500 600 500 634 676 534 576 19
600 × 600 600 600 634 676 634 676 20

K5 – 2.1 – 44 04/2013 – DE/en


CAV controllers
TOC

Dimensions and weight – EN-D EN

Description – Volume flow controller with acoustic cladding


for constant air volume flow control
– For rooms where the case-radiated noise of the
unit is not sufficiently reduced by a false ceiling
– The rectangular ducts for the room under
consideration must have adequate acoustic
insulation (provided by others) on the fan and
room ends
CAV controller Type EN-D – Acoustic cladding cannot be retrofitted

Dimensions Dimensional drawing of EN-D 2


ˤ ̔ʹʷʷ

400 

‫ݢ‬

m³/h

l/s
900

̔ʹʷʷ
1200
360
1500
480


1800

H
600
2100
720
2400

2700

3000

/h

EN 400 x 200

M8
̔350 ˣ

① Keep clear to provide access for operation

Dimensions and weight


Nominal Nominal
Nominal B1 B2 H1 H2 m
width height
size
mm mm mm mm mm mm kg
200 × 100 200 100 234 280 134 180 8
300 × 100 300 100 334 380 134 180 10
300 × 150 300 150 334 380 184 230 11
300 × 200 300 200 334 380 234 280 12
400 × 200 400 200 434 480 234 280 15
400 × 250 400 250 434 480 284 330 17
400 × 300 400 300 434 480 334 380 18
400 × 400 400 400 434 480 434 480 26
500 × 200 500 200 534 580 234 280 17
500 × 250 500 250 534 580 284 330 18
500 × 300 500 300 534 580 334 380 19
500 × 400 500 400 534 580 434 480 26
500 × 500 500 500 534 580 534 580 28
600 × 200 600 200 634 680 234 280 20
600 × 250 600 250 634 680 284 330 22
600 × 300 600 300 634 680 334 380 22
600 × 400 600 400 634 680 434 480 26
600 × 500 600 500 634 680 534 580 29
600 × 600 600 600 634 680 634 680 30

04/2013 – DE/en K5 – 2.1 – 45


CAV controllers
TOC

Specification text EN

Standard text Rectangular volume flow controllers for constant Mineral wool
air volume systems, mechanical self-powered, – To EN 13501, fire rating class A2,
This specification text without external power supply, suitable for supply non-combustible
describes the general or extract air, available in 19 nominal sizes. – RAL quality mark RAL-GZ 388
properties of the product.
Texts for individual
Ready-to-commission unit consists of the casing – Biosoluble and hence hygienically safe
variants can be generated containing a damper blade with low-friction according to the German TRGS 905 (Technical
with our Easy Product bearings, bellows, external cam plate and leaf Rules for Hazardous Substances) and
Finder design spring. EU directive 97/69/EG
programme. Volume flow controllers without actuators are
factory set to a reference volume flow rate Construction
2 (customers can set the required volume flow rate
on site).
– Galvanised sheet steel
– P1: Powder-coated, silver grey (RAL 7001)
Both ends suitable for the connection of air duct
Technical data
profiles.
– Nominal sizes: 200 × 100 to 600 × 600 mm
Casing air leakage to EN 1751, class C
– Volume flow rate range: 40 – 3360 l/s or
(B + H ≤400, class B)
144 – 12096 m³/h
Special features – Volume flow rate control range:
– Volume flow rate can be set using an external approx. 25 – 100 % of the nominal volume flow
scale; no tools required rate
– High volume flow rate control accuracy – Differential pressure: 50 – 1000 Pa
– Any installation orientation
Sizing data
– Correct operation even under unfavourable
–  ______________________________ [m³/h]
upstream or downstream conditions (1.5 B
– Δpst ______________________________ [Pa]
straight section required upstream and 0.5 B
– LPA Air-regenerated noise __________ [dB(A)]
required downstream)
– LPA Case-radiated noise ___________ [dB(A)]
Materials and surfaces
– Casing and damper blade made of galvanised
sheet steel
– Leaf spring made of stainless steel
– Polyurethane bellows
– Plain bearings with PTFE coating

EN-D
– Acoustic cladding made of galvanised sheet
steel
– Rubber profile for the insulation of structure-
borne noise
– Lining is made of mineral wool

Order options  Type  Actuator


EN Volume flow controller No entry: none
B50 Min/Max switching, 24 V AC/DC
 Acoustic cladding supply voltage
No entry: none B52 Min/Max switching, 24 V AC/DC
D With acoustic cladding supply voltage, with auxiliary switch
B60 Min/Max switching, 230 V AC
 Material supply voltage
No entry: galvanised sheet steel B62 Min/Max switching, 230 V AC
P1 Powder-coated, silver grey (RAL 7001) supply voltage, with auxiliary switch
B70 Variable adjustment, 24 V AC/DC
 Nominal size [mm]
supply voltage
B×H
B72 Variable adjustment, 24 V AC/DC
supply voltage, with auxiliary switch

 Volume flow rates [m3/h or l/s]


only actuators 
min – max for factory setting

K5 – 2.1 – 46 04/2013 – DE/en


2.3 –
TOC

X XBasic information and nomenclature testregistrierung

Basic information and


nomenclature
2

Constant volume flow control – CONSTANTFLOW


Product selection
Principal dimensions
Nomenclature
Correction values for system attenuation
Measurements
Sizing and sizing example

04/2013 – DE/en K5 – 2.3 – 1


Constant volume flow control – CONSTANTFLOW
TOC

Basic information and nomenclature

Product selection
Type

RN EN VFL VFC RN-Ex EN-Ex

Type of system
Supply air Ѐ Ѐ Ѐ Ѐ Ѐ Ѐ

Extract air Ѐ Ѐ Ѐ Ѐ Ѐ Ѐ

Duct connection,
fan end
2 Circular Ѐ Ѐ Ѐ Ѐ

Rectangular Ѐ Ѐ

Volume flow rate range


Up to [m³/h] 5040 12100 900 1330 5040 12100
Up to [l/s] 1400 3360 250 370 1400 3360
Air quality
Filtered Ѐ Ѐ Ѐ Ѐ Ѐ Ѐ

Office extract air Ѐ Ѐ Ѐ Ѐ Ѐ Ѐ

Polluted Ͽ Ͽ Ͽ Ͽ Ͽ Ͽ
Contaminated Ͽ Ͽ Ͽ Ͽ Ͽ Ͽ
Control function
Constant Ѐ Ѐ Ѐ Ѐ Ѐ Ѐ

Variable Ͽ Ͽ Ͽ
Min/Max Ͽ Ͽ Ͽ
Acoustic requirements
High < 40 dB (A) Ͽ Ͽ Ͽ Ͽ Ͽ
Low < 50 dB (A) Ѐ Ѐ Ѐ Ѐ Ѐ Ѐ

Special areas
Potentially explosive
Ѐ Ѐ
atmospheres
Ѐ Possible
Ͽ Possible under certain conditions: Robust unit variant and/or specific actuator
or useful additional product
Not possible

K5 – 2.3 – 2 04/2013 – DE/en


Constant volume flow control – CONSTANTFLOW
TOC

Basic information and nomenclature

Principal dimensions ØD [mm] B₃ [mm]


Outside diameter of the connecting spigot Unit width

ØD₁ [mm] H [mm]


Pitch circle diameter of flanges Duct height

ØD₂ [mm] H₁ [mm]


Outside diameter of flanges Screw hole pitch of air duct profile (vertical)

ØD₄ [mm] H₂ [mm]

2
Inside diameter of the flange screw holes Outside dimension of air duct profile (height)

L [mm] H₃ [mm]
Length of unit including spigot Unit height

L₁ [mm] n[]
Length of casing or acoustic cladding Number of flange screw holes

W [mm] T [mm]
Width of the duct Flange thickness

B₁ [mm] m [kg]
Screw hole pitch of air duct profile (horizontal) Unit weight including the minimum required
attachments (e.g. Compact controller)
B₂ [mm]
Outside dimension of air duct profile (width)

Nomenclature fm [Hz] nom [m³/h] and [l/s]


Octave band centre frequency Nominal volume flow rate (100 %)

LPA [dB(A)]  [m³/h] and [l/s]


A-weighted sound pressure level of Volume flow rate
air-regenerated noise of the CAV controller,
system attenuation taken into account Δ [± %]
Volume flow rate accuracy
LPA1 [dB(A)]
A-weighted sound pressure level of Δpst [Pa]
air-regenerated noise of the CAV controller with Static differential pressure
secondary silencer, system attenuation taken into
Δpst min [Pa]
account
Minimum static differential pressure
LPA2 [dB(A)]
A-weighted sound pressure level of case- All sound pressure levels are based on 20 μPa.
regenerated noise of the CAV controller, system
attenuation taken into account

LPA3 [dB(A)]
A-weighted sound pressure level of
case-regenerated noise of the CAV controller with
acoustic cladding, system attenuation taken into
account

Definition of noise Static differential pressure

‫ݑ‬

‫ݣ‬ ‫ݢ‬

͍Æst
LPA

① Air-regenerated noise
② Case-radiated noise

04/2013 – DE/en K5 – 2.3 – 3


Constant volume flow control – CONSTANTFLOW
TOC

Basic information and nomenclature

The quick sizing tables Reducing the sound pressure level of the air-regenerated noise
show the sound pressure
levels that can be
expected in a room both
for the air-regenerated
noise and for the case-
radiated noise. The sound
pressure level in a room
results from the sound
power level of the
products – for a given

2 volume flow rate and


differential pressure – and
the attenuation and
insulation on site. This is
why generally accepted
attenuation and insulation
values have been taken
into account for the tables. ‫ݢ‬

The distribution of air ‫ݣ‬


across the ductwork, ‫ݤ‬
‫ݦ‬ ‫ݥ‬
changes of direction, end
reflection, and room
attenuation all affect the
sound pressure level of
the air-regenerated noise.
① VAV terminal unit ④ End reflection
Ceiling insulation and
② Distribution in the ducting ⑤ Ceiling insulation
room attenuation
influence the sound ③ Change of direction
pressure level of the case-
radiated noise.

Correction values for Octave correction for the distribution in the ducting,
acoustic quick sizing used to calculate the air-regenerated noise
The correction values for  [m³/h] 500 1000 1500 2000 2500 3000 4000 5000 6000
the distribution in the [l/s] 140 280 420 550 700 840 1100 1400 1700
ducting are based on the
number of diffusers [dB] 0 3 5 6 7 8 9 10 11
assigned to any one air
terminal unit. If there is
just one diffuser
(assumption: 140 l/s or
500 m³/h), no correction
is necessary.

One change of direction, System attenuation per octave to VDI 2081 for the calculation of the air-regenerated noise
e.g. at the horizontal
connection of the diffuser Centre 63 125 250 500 1000 2000 4000 8000
plenum box, has been frequency ΔL ΔL
taken into consideration [Hz] dB dB dB dB dB dB dB dB
for the system attenuation
values. Vertical Change of
0 0 1 2 3 3 3 3
connection of the plenum direction
box does not result in a End reflection 10 5 2 0 0 0 0 0
system attenuation.
Room
Additional changes of 5 5 5 5 5 5 5 5
attenuation
direction result in lower
sound pressure levels.
Octave correction for the calculation of case-radiated noise

Centre 63 125 250 500 1000 2000 4000 8000


frequency ΔL
[Hz] dB dB dB dB dB dB dB dB
Ceiling
4 4 4 4 4 4 4 4
insulation
Room
5 5 5 5 5 5 5 5
attenuation

K5 – 2.3 – 4 04/2013 – DE/en


Constant volume flow control – CONSTANTFLOW
TOC

Basic information and nomenclature

Measurements Measuring the air-regenerated noise

The acoustic data for the


air-regenerated noise and
case-radiated noise are
determined according to
EN ISO 5135. All
measurements are
carried out in a ‫ݢ‬
reverberation chamber to
EN ISO 3741.

2
‫ݥ‬ ‫ݦ‬ ‫ݣ‬ ‫ݦ‬

‫ݑ‬ ǎÆst
‫ ݤ‬LPA

① Reverberation chamber ④ Fan


② VAV terminal unit ⑤ Sound attenuator
③ Microphone

Measuring the case-radiated noise

‫ݢ‬

‫ݥ‬ ‫ݦ‬

‫ݣ‬

‫ݑ‬ ǎÆst
‫ ݤ‬LPA2

① Reverberation chamber ④ Fan


② VAV terminal unit ⑤ Sound attenuator
③ Microphone

04/2013 – DE/en K5 – 2.3 – 5


Constant volume flow control – CONSTANTFLOW
TOC

Basic information and nomenclature

Sizing with the help of This catalogue provides convenient quick sizing
this catalogue tables for CAV controllers.
The sound pressure levels for air-regenerated
noise and for case-radiated noise are provided for
all nominal sizes. In addition, generally accepted
attenuation and insulation values have been taken
into account.
Sizing data for other volume flow rates and
differential pressures can be determined quickly
and precisely using the Easy Product Finder
2 design programme.

Sizing example Given data


max = 280 l/s (1010 m3/h)
Δpst = 150 Pa
Required sound pressure level in the room 30
dB(A)

Quick sizing
RN/200
Air-regenerated noise LPA = 47 dB(A)
Case-radiated noise LPA = 39 dB(A)

Sound pressure level in the room = 27 dB(A)


(logarithmic addition since the terminal unit is
installed in the suspended ceiling of the room)

Easy Product Finder

The Easy Product Finder


allows you to size
products using your
specific data.

You will find the Easy


Product Finder on our
website.