Академический Документы
Профессиональный Документы
Культура Документы
ON
POWER SYSTEM PROTECTION
16th to 20th April 2018
Ho Chi Minh City
Vietnam
INTRODUCTION TO
PROTECTIVE RELAYING
By
Zulkarnain Ishak
TNB Grid Div.
Malaysia
Contents
1. Unit and Non-Unit Protection
3. Differential Protection
4. Distance Protection
1
Unit and Non-Unit Protection
2
Unit and Non-Unit Protection
Example of Unit Protection
1 1
2 3
3
Unit and Non-Unit Protection
Characteristics of Unit Protection
– Generally need identical CT parameters ( ratio, magnetizing
characteristic) to avoid mismatch differential current
• Sometime maybe use matching devices
– Interposing CT for ratio correction, phase shift correction .
– With numerical / computer relay, correction can be program inside the relay.
4
Unit and Non-Unit Protection
Example of Non-Unit Protection
Distance Protection
A B C
Rbc
Rab Zone 1
Zone 2
Zone 3
Rba Rcb
5
Unit and Non-Unit Protection
Attributes of Non-Unit Protection
6
Overcurrent Earth Fault Protection
DB
Application mcb1
s2
s12
– Can be found installed on almost all mcb2 F2
s3 F3
mcb3
power system equipment at all voltage F1 mcb4
levels.
– Basic and simplest protection s45
• Fuse
• MCB / ELCB
• Relay
– Main protection for domestic or low
voltage level
– Backup protection for HV system.
13
14
7
Overcurrent Earth Fault Protection
Pickup Setting
Phase overcurrent pick-up setting Iset normally is
set based on the equipment full load current
rating, e.g.
8
Differential Protection
Differential Protection
Application
– Mainly used as a Main protection,
• Instantaneous time operation
18
9
Unit and Non-Unit Protection
Example:
G
G
G
19
Differential Protection
Operating Principle
20
10
Differential Protection
Operating Principle
Differential Protection
Operating Principle
– The Differential Protection relay will operate if the
calculated differential current exceeded the given pick-up
I setting or within the operating area of the relay
characteristic.
I I
11
Differential Protection
Pickup Setting / Operating Characteristic
– Possible errors need to be considered for the Differential pickup
setting. Example,
• CT Ratio
• Current Phase Shift
• CT Saturation
• System Grounding (Solid / Impedance Grounded)
• Feeder charging current
23
Differential Protection
Pickup Setting / Operating Characteristic
24
12
Differential Protection
Un-Biased Differential Operating Characteristic
I
Operation Area
Iset
Restrain Area
Area
• Relay will operate if the measured differential current exceeded the differential current
setting, Iset.
• There is no Restrain/Bias element - the operation is not affected by restrain/ bias element.
Differential Protection
Bias Differential Operating Characteristic
I
Operation Area
Iset
Restrain Area
Bias Current IB
• Apply the restrain/ bias element – cater for current measurement mismatch during
normal load or through fault conditions.
• Relay will operate if the measured operating point is in the operating region of relay
characteristic.
• Bias Differential Characteristic – Normally apply by Medium and Low Impedance
Differential Protection Scheme e.g.
– Line Current Differential Protection
– Busbar Med / Low Imp. Protection
26
– Transformer Bias Differential Protection
13
Distance Protection
Distance Protection
Distance Protection Application
• Commonly used as Main and Backup protection for long overhead line
feeder (OHL).
• Can works independently without tele-protection or remote protection
relay (stand-alone)
• A stand-alone distance relay does not satisfy the conditions for a unit
protection system because the zone is not clearly defined.
• A stand-alone distance relay nominally responding only to faults within
their setting zone.
• For some conditions, the setting of a stand-alone distance relay may
extend outside of the protected zone. 28
14
Distance Protection
Operating Principle
Operation based on calculated impedance (from measured current and voltage)
Distance Protection
Operating Principle
Fault Loop Impedance Calculation
Distance relay continuously calculate/measure the loop impedance using the
input form Voltage (VT) and Current (CT) signals.
• Loop Impedance
– A-N
– B-N
– C-N
– A-B
– B-C
– C-A
• Distance relay will operate if calculated impedance is less than the set value
given to it.
– Z calculated < Z setting.
30
15
Distance Protection
Operating Principle
Impedance Directional
• Protecting a line with impedance measurement
only, may cause loss of discriminative operation.
Distance Protection
Rf
F1 F2
F4 A s/s F3 B s/s
Relay A C s/s
Relay B
xl
B s/s F2
• Distance should only operate for forward
Line impedance
F3 fault direction to protect the line AB.
F1
A s/s ϕ˚ • Without direction check, distance relay
Rl will operate at any fault direction within
F4
its reach setting.
16
Distance Protection
Impedance Directional
Simplified Distance Element Block Diag.
VT
Impedance + DC
Measuring
Element
&
Directional Distance
CT Element
Operation
(Foward)
jX
ZL
φ R
IMPEDANCE PLAN
Distance Protection
Pickup Setting
• Normally there are at least 3 zones provided by the Distance Protection
relay.
17
Distance Protection
Pickup Setting
A B C
Rbc
Rab Zone 1
Zone 2
Zone 3
jX Overlapping Zone.
D Z3A
C Z2A
B
Z1A
Distance Protection
Operating Time Setting
– Operating Time of individual zone is set based on the Main and
Backup functions. Following are typical time setting for Distance
Protection zones;
18
Zones of Protection
Time
T3 Z3A Z3C
1000ms –
3000ms
T2 Z2A Z2C
300ms –
450ms
T1 Z1A Z1C
<15ms –
<40ms
21ZA 21ZC
A C
21ZA
B 21ZD D
T1 Z1B
Z1D
<15ms –
<40ms
T2 Z2B
300ms – Z2D
450ms
T3 Z3B
Z3D
1000ms –
3000ms
Distance Protection
Operating Characteristic
19
Distance Protection
Operating Characteristic
MHO Characteristic
39
Distance Protection
Operating Characteristic
Lenticular Characteristic
The lenticular relay is similar to the mho
relay, except it is lens-shaped rather than
circular, thus providing less sensitivity to
load.
40
20
Distance Protection
Quadrilateral Characteristic
41
THANK YOU
21