Let’s calculate voltage drop in transformer 1000KVA, 11/0.480 kV, impedance 5.75% due to
starting of 300 kW, 460V, 0.8 power factor, motor code D (kva/hp). Motor starts 2 times per
hour and the allowable voltage drop at transformer secondary terminal is 10%.
Calculation can be checked by using this MS Excel Spreadsheet dedicated especially to this kind
of problem.
Motor full load current = (Kw x 1000) / (1.732 x Volt (L-L) x P.F
Motor full load current = 300 × 1000 / 1.732 x 460 x 0.8 = 471 Amp.
Motor locked rotor current = Multiplier x Motor full load current
Transformer