Вы находитесь на странице: 1из 1

Connection Example

VLT® HVAC Drive Software: 3.4

Closed loop operation from 0 - 300kPa pressure transmitter with 0-10V output. If the transmitter output is 4-20mA,
change the DIP switch settings behind the LCP.

Relevant Parameters
Par. Function Settings
FC 102
202 0-02 Motor Speed Unit [1] Hz
+24 V 12 0-21 Display 1.2 small [1652] Feedback
+24 V 13 1-00 Configuration mode [3] Closed loop
D IN 18 Start / Stop 20-12 Unit [73] kPa
D IN 19 3-41 Ramp up time 20s
COM 20 3-42 Ramp down time 20s
D IN 27 Coast Inverse 3-02 Min reference 0
D IN 29 3-03 Max reference 300
D IN 32 315 Reference Source 1 [0] No function
D IN 33 6-24 Min feedback 0
D IN (S.Stopp)**37 Safety Stop 6-25 Max Feedback 300
20-13 Min reference 0
+10 V 50 Pressure transducer 20-14 Max refeerence 300
A IN (S201 U-I) 53 0-10V (or 4-20mA) 20-21 Setpoint 150
A IN (S202 U-I) 54 20-73 Min feedback 0
COM 55 20-74 Max Feedback 300
A OUT 42 20-81 Normal / Inverse [0] Normal
A OUT 39 20-83 PID start frequency 10
20-93 Proportional gain 2
01 20-94 Integral time 10
Relay 1

02
03

*04
Relay 2

*05
*06

NOTE: Erstellt von: Schulung


All settings are based on factory settings.
It is recommended to set all the motor parameters in Par. 1-20 to 1-26 and then perform Automatic Motor
Adaption (AMA) in Par. 1-29.

Вам также может понравиться