ENGINEERING SPECIFICATION
PDVSA N° TITULO
APPD. Alexis Arévalo DATE OCT.00 APPD. Enrique Carmona DATE OCT.00
E1994 ESPECIALISTAS
ENGINEERING SPECIFICATION PDVSA N–250
REVISION FECHA
PDVSA TECHNICAL SPECIFICATION FOR FORM–
WOUND SQUIRREL CAGE INDUCTION 0 OCT.00
MOTORS–250 HORSEPOWER AND LARGER Página 1
.Menú Principal Indice manual Indice volumen Indice norma
Index
SECTION 1 – GENERAL
1 OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.1 Scope (Exception) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2 Alternative Designs (Exceptions ) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.4 Coordination Responsibility (Addition – New Subclause) . . . . . . . . . . . . . 3
1.6 Referenced Publications (Addition) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SECTION 3 – ACCESSORIES
3.1 Terminal Boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.2 Winding temperature Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.3 Bearing Temperature Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.4 Space Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.6 Alarms and Control Devices for Motor Protection . . . . . . . . . . . . . . . . . . . . 7
SECTION 1 – GENERAL
1 OVERVIEW
This specification covers Particular Requirements for the design, manufacture,
testing and shipment of Form–Wound Squirrel Cage Induction Motors – 250
Horsepower and Larger – as detailed in API Standard 541, for use in oil refineries,
gas plants, chemical plants, exploration and production facilities, and
supply/marketing installations owned by PDVSA.
This specification along with the Owner’s Induction Motor Data Sheet (Appendix
“A”) and the requirements of API Std 541 shall be considered complementary.
Any conflict among them shall be referred to the Owner for clarification before
proceeding with design and manufacture.
The following clauses are exceptions, additions or new clauses (sub–clauses) to
API Std 541. Clauses that are not mentioned herein shall remain applicable as
written. When the word “should” appears in the API Std 541, it must be substituted
by “shall” and, therefore, considered mandatory.
The additional requirements or clarifications specified herein are required in order
to:
a. Make selections from options given in the API Std 541.
b. Specify additional and more stringent requirements, as necessary, to
operate and maintain motors according to PDVSA practices.
The following paragraph numbers refer to those used in API Std 541 or added in
this specification.
2.1 General
2.1.3 (Exception)
In order to comply with Venezuelan requirements concerning exposure of plant
personnel to noise (COVENIN 1565), individual noise sources shall be limited,
where possible, to the following sound levels:
– 85 dBA at 1 meter from the source of the noise. The Manufacturer shall achieve
this condition as a contractual requirement for the equipment in its basic state
(i.e. no special sound treatment provisions).
– Noise levels of up to 88 and 91 dBA are considered acceptable where exposure
levels are less than 4 and 2 hours, respectively.
2.1.15 (New)
Interchangeability of same rating motors shall be pursued.
2.2.1.2 (Exception)
Unless otherwise specified in Appendix “A”, motors rated 250 hp and larger shall
be medium voltage. System voltage ratings and characteristics will be designed
for single voltage service according to ANSI C84–1.
2.2.2.3 (New)
Medium voltage coils shall have corona suppression coatings.
2.2.3.3 (New)
Motors shall comply with the driven speed–torque requirements over their entire
starting range, at 80 percent rated voltage, unless a lower voltage is specified in
Appendix “A”. Motors shall be capable of accelerating during start–up as well as
(where applicable) reaccelerating the driven equipment after a momentary power
interruption with a minimum of 20% margin, including inertia and load torque and
with the voltage at the motor terminals mentioned above.
When the driven equipment load inertia values are not known, the NEMA load
inertia values shall be used.
For motors supplied as part of rotating equipment packages, inertia of the driven
equipment shall be as identified by the Bidder having unit responsibility.
2.2.4 (Addition)
For very critical applications where instantaneous restarting is required (as
specified in appendix “A”), motors shall be capable of withstanding automatic
reacceleration with full opposite residual voltage, under full load conditions.
2.2.5.3 (Exception)
When the motor speed/torque curve, at the conditions specified in 2.2.5.2.a or b,
is plotted over the load speed/torque curve, the motor torque shall exceed the load
torque by a minimum of 20 percent at all locations throughout the speed range,
up to the motor breakdown torque point.
2.2.5.5 (New)
For motors driving reciprocating or other machinery having a pulsating load, the
Motor Manufacturer shall ensure that the rotating equipment train will have
sufficient rotational inertia:
– to keep the irregularity factor within the values specified by the Driven
Equipment Manufacturer.
– to limit the variations of the current to values not exceeding 66% of the peak
value of the rated full load current, unless a lower figure is specified in Appendix
“A”.
ENGINEERING SPECIFICATION PDVSA N–250
REVISION FECHA
PDVSA TECHNICAL SPECIFICATION FOR FORM–
WOUND SQUIRREL CAGE INDUCTION 0 OCT.00
MOTORS–250 HORSEPOWER AND LARGER Página 5
.Menú Principal Indice manual Indice volumen Indice norma
2.2.6 (Addition)
Motors connected to captive transformers shall be capable of overcoming the
inertia of the load and accelerate the load to rated speed with 70 percent of the
rated voltage at the motor terminals, without damages from overheating. The
Bidder shall be responsible for checking the starting time for critical situations,
such as starting at reduced voltage of driven equipment with high inertia and/or
high brake torque. Bidder shall submit the calculations to Owner.
2.2.6.1 (Exception)
At any voltage between 80% and 100% of rated voltage, motors, including their
unit transformer, shall be capable of:
1. Three successive starts with the motor initially at maximum ambient
temperature
2. Two successive starts with the motor initially at full load operating
temperature
3. One start every hour after (1) and (2) but not exceeding four starts in a 24
hour period.
2.2.7.d (Addition)
Motor losses will be evaluated at $2000/kW, unless otherwise specified in
Appendix “A”.
2.4.5.1.5 Exception
For motors rated over 3700 kW (5000 hp), the shaft shall be provided with an
integral shaft hub flange.
2.4.5.2.2 Exception
Cast or fabricated aluminum cage designs are not acceptable.
2.4.5.2.11 New
When nonmagnetic retainer rings are used, the ring material shall be either 18
Mn–18 Cr or 18 Mn–13 Cr.
2.4.6.1.5 New
For special–purpose motors rated 7500 kW (10,000 hp) and below, the first critical
speed shall be at least 20 percent above the motor no–load speed.
2.4.6.2.2 Addition
Grinding shall not be permitted.
2.4.7.17 Addition
Access for the measurement of shaft vibration by a portable probe adjacent to the
drive–end bearing shall be provided.
2.4.10.8 Heat Exchanger (Exception)
Aluminum is not acceptable
2.4.11.4 New
All equipment items shall be provided with corrosion resistant tags with the
purchaser item number.
SECTION 3 – ACCESSORIES
3.1 Terminal Boxes
3.1.1 Addition
Terminal boxes shall be extra–large and sized to accomodate cables and
accessories as stated in Appendix “A”.
3.1.4 Addition
Terminal boxes shall be NEMA type 4X. A motor lead seal and separator shall be
provided betwen the motor frame and the terminal box.
Stator windings shall be equipped with 12 (three per phase) 100–ohm platinum
RTDs, wired to a terminal strip in a NEMA 4X terminal box. Six of the RTDs shall
be used for local temperature indication and six RTDs shall be used for protective
relaying.
APPENDIX “A”
OWNER’S INDUCTION MOTOR DATA PROJECT No. ITEM No.
PAGE 1 OF 4 BY
SHEET
DATE REVISION
APPLICABLE TO: PROPOSAL PURCHASE AS BUILT
MODEL
PLANT UNIT
SITE DRIVEN EQUIPMENT
SERVICE NO. REQUIRED
SERIAL NO.
TYPE OF MOTOR (1.1.2) GENERAL PURPOSE SPECIAL PURPOSE LOAD CURVE 2.2.3.2, ITEM a
VOLTS PHASE (1.2) HERTZ VOLTAGE AT LOCKED ROTOR (2.2.5.2, ITEM a) (MIN % OF RATED)
NAMEPLATE HP (2.2.1.1) SERVICE FACTOR (2.2.1.3) NUMBER OF FULL–VOLTAGE STARTS, IF NOT 5000 (2.4.5.1.1)
SYNCHRONOUS RPM CAPABILITY IN EXCESS OF TABLE 2 (2.2.6.2)
UNUSUAL CONDITIONS:
FLOW SENSOR LOCAL INDICATOR (2.4.1.2.4, ITEM f)
ABRASIVE DUST (2.4.1.2.2, ITEM c)
OUTER TUB ON DOUBLE TUBE COOLERS LEAK DETECTION
EXTERNAL FORCES AND MOMENTS (2.4.4) 2.4.1.2.4, ITEM b) TYPE
SEISMIC LOADING (2.4.2.2) DRIVE SYSTEM:
CORROSIVE AGENTS (2.4.10.1.2) DIRECT CONNECTED GEAR 2.2.3.2, ITEM c)
OTHER TYPE OF COUPLING (2.4.9.4)
ELECTRIC SYSTEM CONDITIONS: FURNISHED BY
MAX S.C. KVA AT MOTOR BUS (3.1.2) ROTATION REQ’D BY DRIVEN EQUIPMENT WHEN FACING MOTOR
l2t LET–THROUGH ENERGY (3.1.2) OPPOSITE DRIVE END: CLOCKWISE COUNTERCLOCKWISE
MIN S.C. KVA AT MOTOR BUS (2.2.5.2 ITEM b) DRIVEN–EQUIPMENT Wk2 (2.2.3.2 ITEM c) LB–FT2@ RPM
X/R RATIO (2.2.5.2 ITEM b)
LOAD REACCELERATION REQUIRED (2.2.3.2, ITEM b)? YES NO
TYPE OF SYSTEM GROUNDING RESISTENCE REACTANCE
IF YES PROVIDE:
UNGROUNDED SOLID
MAX VOLTAGE INTERRUPTION, (CYCLES)
GROUND FAULT AMPERES
VOLTAGE AT MOTOR TERMINALS ON RECLOSURE
STARTING (2.2.3, 2.2.5.2):
TORQUES IN EXCESS OF NEMA MG 1–20.41 (2.2.7 ITEM C) LOAD SPEED–TORQUE REFERENCE CURVE NO.
APPENDIX “A”
OWNER’S INDUCTION MOTOR DATA PROJECT No. ITEM No.
PAGE 2 OF 4 BY
SHEET
DATE REVISION
ACCESSORY EQUIPMENT
APPENDIX “A”
OWNER’S INDUCTION MOTOR DATA PROJECT No. ITEM No.
PAGE 3 OF 4 BY
SHEET
DATE REVISION
OTHER
COMMENTS:
ENGINEERING SPECIFICATION PDVSA N–250
REVISION FECHA
PDVSA TECHNICAL SPECIFICATION FOR FORM–
WOUND SQUIRREL CAGE INDUCTION 0 OCT.00
MOTORS–250 HORSEPOWER AND LARGER Página 12
.Menú Principal Indice manual Indice volumen Indice norma
APPENDIX “A”
OWNER’S INDUCTION MOTOR DATA PROJECT No. ITEM No.
PAGE 4 OF 4 BY
SHEET
DATE REVISION
OTHER
ENGINEERING SPECIFICATION PDVSA N–250
REVISION FECHA
PDVSA TECHNICAL SPECIFICATION FOR FORM–
WOUND SQUIRREL CAGE INDUCTION 0 OCT.00
MOTORS–250 HORSEPOWER AND LARGER Página 13
.Menú Principal Indice manual Indice volumen Indice norma
APPENDIX “B”
PROJECT No. ITEM No.
DATE REVISION
MOTOR PROPOSAL DATA PROPOSAL NO.
LOCKED ROTOR:
EFFICIENCY
POWER FACTOR
GUAR. EFFICIENCY
(6.1.4, ITEM g) LIST OF OPTIONAL ASTM TEST PROPOSED BY VENDOR (2.4.10.1.4)
IEEE METHOD
BEARING TYPE
ROTOR/SHAFT DETAIL (6.1.9)
COMMENTS:
ENGINEERING SPECIFICATION PDVSA N–250
REVISION FECHA
PDVSA TECHNICAL SPECIFICATION FOR FORM–
WOUND SQUIRREL CAGE INDUCTION 0 OCT.00
MOTORS–250 HORSEPOWER AND LARGER Página 14
.Menú Principal Indice manual Indice volumen Indice norma
APPENDIX “C”
PROJECT No. ITEM No.
PAGE 1 OF 2 BY
AS DESIGNED AS BUILT
GENERAL INFORMATION
FOR MODEL
SITE UNIT
SERVICE DRIVEN EQUIPMENT
VENDOR NO. REQUIRED
SERIAL NO.
MOTOR DATA
NAMEPLATE HP (2.2.1.1) SERVICE FACTOR (2.2.1.3) PHASE–TO–PHASE RESISTANCE OHM, @ °C
VOLTS PHASE HERTZ SUBTRANSIENT REACTANCE X”d
ACCESSORIES
WINDING TEMPERATURE DETECTOR : WINDING TEMPERATURE DETECTOR :
RISISTANCE RATING, OHM/MATERIAL RTD OHMS MATERIAL OTHER
2–WIRE SYSTEM 3–WIRE SYSTEM RECOMMENDED ALARM SETTING, °C
RECOMMENDED ALARM SETTING, °C RECOMMENDED TRIP SETTING, °C
RECOMMENDED TRIP SETTING, °C
VIBRATOR DETECTORS:
THERMAL TEMPERATURE SWITCH CONTACTS: PROVISIONS ONLY (3.8.1) INSTALLED
NORMALLY OPEN NORMALLY CLOSED PROBE TYPE MODEL
OPENING SETTING, °C CLOSED SETTING, °C
OSCILATOR/DEMODULATOR MODEL
NO. PER BEARING TWO (3.8.1) FOUR (3.8.2)
ENGINEERING SPECIFICATION PDVSA N–250
REVISION FECHA
PDVSA TECHNICAL SPECIFICATION FOR FORM–
WOUND SQUIRREL CAGE INDUCTION 0 OCT.00
MOTORS–250 HORSEPOWER AND LARGER Página 15
.Menú Principal Indice manual Indice volumen Indice norma
APPENDIX “C”
PROJECT No. ITEM No.
PAGE 2 OF 2 BY
AS DESIGNED AS BUILT
ACCESSORIES (CONTINUED)
BEARING SEISMIC SENSORS (3.8.3) DIFFERENTIAL PRESSURE SWITCH
PROVISIONS ONLY INSTALLED TYPE SETTING
SENSOR TYPE MODEL CURRENT TRANSFORMERS:
OUTPUT TRANSDUCER MODEL DIFFERENTIAL CLASS RATIO NO. MOUNTED
NO. PER BEARING LOCATION (H, V, A)
PHASE CLASS RATIO NO. MOUNTED
VIBRATION SWITCH (3.8.3) MANUAL RESET ELECTRIC RESET
POTENTIAL TRANSFORMERS:
SWITCH TYPE MODEL
CONNECTION RATIO NO. MOUNTED
SPACE HEATER FOR MAIN CONDUIT BOX:
VOLTAGE, V 1–PHASE 3–PHASE FUSES SIZE NO. MOUNTED
WATTAGE, kW MAX SURFACE TEMPERATURE , °C SURGE PROTECTION:
LIGHTNING ARRESTER TYPE VOLTAGE
AIR FILTERS: MANUFACTURER
TYPE CAPACITOR TYPE CAPACITANCE
AIR COOLERS
NUMBER OF SECTION LOCATION WATER FLOW, GPM: MAX MIN
SECTION RATING % OF FULL LOAD
FLOW SENSING DEVICE TYPE VOLTAGE
CONSTRUCTION MATERIAL DATA SHEET REFERENCED:
AUXILIARY RELAY CONTACTS:
AIR/AIR AIR/WATER
NORMALLY OPEN NORMALLY CLOSED
LEAK DETECTOR TYPE
AIR FLOW SCFM PSIG HIGH–FLOW ALARM SETTING, GPM
OTHER INFORMATION
SHAFT MATERIAL
GRADE OF CASTINGS
ENGINEERING SPECIFICATION PDVSA N–250
REVISION FECHA
PDVSA TECHNICAL SPECIFICATION FOR FORM–
WOUND SQUIRREL CAGE CONDUCTION 0 OCT.00
MOTORS–250 HORSEPOWER AND LARGER Página 16
.Menú Principal Indice manual Indice volumen Indice norma
APPENDIX “D”
DEVIATIONS AND EXCEPTIONS TAKEN BY BIDDER
BIDDER:
BIDDER’S AUTHORIZED SIGNATURE
DATE: