Академический Документы
Профессиональный Документы
Культура Документы
Many power distribution systems use selective coordination strategies to minimize the amount of equipment impacted
when faults open overcurrent protection (OCP) devices. Although selective coordination is achieved using fuses and
circuit breakers, ATSs placed in these systems must support the selective coordination strategy. This document describes
selective coordination concepts and provides guidance on specifying appropriate automatic transfer switches.
In a power distribution system equipped with multiple levels of OCP, circuit breakers or fuses are located in primary,
secondary, and perhaps tertiary circuits. If a fault were to occur far from the primary distribution panel in an uncoordinated
system, it is possible that an OCP device could open far upstream of the fault location, as shown in Figure 1. The tripped
breaker would disconnect power to an unnecessarily large portion of a facility.
0.1 sec
ATS
x
0.1 sec
ATS
0.1 sec
ATS
FAULT
0.1 sec
2
SELECTIVE COORDINATION DEFINED
Selective Coordination is an approach where OCP opening times are adjusted to allow fuses or breakers located closest
to faults to open first. Article 100 of the 2017 National Electrical Code® (NEC®) provides a more formal definition:1
Localization of an overcurrent condition to restrict outages to the circuit or equipment affected, accomplished by the selection and
installation of overcurrent protective devices and their ratings or settings for the full range of available overcurrents, from overload to the
maximum available fault current, and for the full range of overcurrent protective device opening times associated with those overcurrents.
By installing OCP devices with sequential trip times, designers can ensure that the device located nearest to a fault will
trip first. This arrangement results in the power interruption to fewer loads and less disruption to the facility served by
the power distribution system. Figure 2 shows the isolation of a fault in a system where OCP opening times have been
selectively coordinated.
0.2 sec
ATS
0.15 sec
ATS
x
FAULT
0.05 sec
1 National Fire Protection Association, “NFPA 70 – National Electrical Code,” Quincy, Massachusetts. 2017. p 70-35.
3
DIFFERENCES BETWEEN OVERCURRENT PROTECTION DEVICES AND ATSs
Selective coordination definitions and requirements are set forth in the NEC, which addresses installation standards for
electrical systems and equipment. Specific requirements exist for healthcare facilities, elevator and escalator systems,
emergency and life safety systems, and more. Table 1 below lists commonly referenced NEC provisions regarding selective
coordination. NFPA 99 – Health Care Code and NFPA 110 - Standard for Emergency and Standby Power Systems also
set forth performance requirements for selectively coordinated systems.
As noted, large fault currents generate magnetic forces that attempt to open switch Older UL 1008 editions described time ratings
in cycles, while later editions describe them in
contacts. If an ATS were to transfer load to an alternate power source during a seconds. The following table specifies converts
common time ratings.
fault, it must be able to close on and hold that current to avoid power interruption. Cycle/Seconds Conversion
In addition, large fault currents passing across ATS switching contacts generate Cycles Seconds
heat that can degrade contact materials and surfaces. To become UL 1008 Listed, 1.5 0.025
3 0.05
ATSs must undergo testing by Underwriters Laboratories or a UL-approved lab to 6 0.1
evaluate the amounts of fault current they can withstand and close on for time- 9 0.15
12 0.2
based ratings specified in the standard or any optional ratings specified on the 18 0.3
manufacturer’s label. The resulting ratings are known as Withstand and Close-On 30 0.5
Ratings, or WCRs.
There is an inverse relationship between the amount of fault current that a transfer switch can handle and the duration it
can be held, as shown in Figure 4. Different types of OCP devices offer differing clearing times. Consequently, an ATS will
typically be assigned multiple ratings according to the types of upstream OCP that can be used. Example ratings from
ASCO transfer switches are shown in Table 2.
Mechanical Limit
I2 t
Amps
Time
H 800-1200 800-1200 200kA 200kA 1600 L 65kA 65kA 65kA 0.05 50kA 50kA 50kA 36kA -- 36kA --
Q 600-1600 600-1600 200kA 200kA 2000 L 65kA 65kA 65kA 0.05 65kA 65kA 65kA 50kA 50kA
S 800-1200 800-1200 200kA 200kA 2500 L 100kA 100kA 65kA 0.05 100kA 100kA 65kA 65kA 65kA
G 1000-1200 1000-1200 200kA 200kA 2000 L 85kA 85kA 85kA 0.05 85kA 85kA 85kA -- --
Because current-limiting fuses open most quickly and also limit the peak fault current, their use results in the highest WCR
ratings. Manufacturers also list maximum test values for use with specific circuit breakers. Because these open less quickly,
the associated values are usually lower than those for fuses. In addition, manufacturers specify values for coordinating
the ATS with circuit breakers other than those on an ATS’ specific list. Because these optional ratings are associated with
a 0.025 or 0.05-second test time interval, they are known as Time Based Ratings. Finally, manufacturers have the option
of testing switches for longer intervals, and UL 1008 suggests durations of 0.1, 0.13, 0.3, and 0.5 seconds. The resulting
values are known as Short Time Ratings. Each type of rating is shown for select ASCO ATSs in Table 2 above.
5
REQUIRED INFORMATION
6
SUMMARY
Selective coordination strategies are used to minimize the quantity of loads that will be de-energized if an OCP device
opens. These strategies enable OCP devices located closest to the fault to trip first, avoiding power disruption to a larger
area of a facility.
Selective coordination is accomplished by using OCP devices that have longer trip times near the power source and
shorter times near load equipment. Automatic transfer switches are not used to selectively coordinate power protection.
Instead they must support selective coordination schemes by closing on and holding greater fault currents than nearby
OCP devices, and must remain closed until OCP devices clear the circuit.
Specifying OCP devices that open later than necessary offers several disadvantages. A resulting selective coordination
strategy could require devices, including ATSs, that are larger and more costly. In addition, using long opening times could
increase incident energies at downstream locations. This effect could affect personnel safety and equipment serviceability.
7
ASCO Power Technologies - Global Headquarters
160 Park Avenue
Florham Park, NJ 07932
Tel: 800 800 ASCO
customercare@ascopower.com
www.ascopower.com whitepapers.ascopower.com
www.ascoapu.com