General Data

Project Name CDA VERIFY CAR


CLASE D
Upper layer resistivity (Ohm_m) 62.66
Lower layer resistivity (Ohm_m) 1
Upper layer thickness (m) 2.14
Crushed rock resistivity (Ohm_m) 3000
Thickness of crushed rock surfacing (m) 0.5
Fault duration (s) 0.15
Maximum ground fault current (A) 2406
Remote Current Contribution (%) 60
System Frequency (Hz) 60

Horizontal Conductors

Name X1(m) Y1(m) X2(m) Y2(m) h(m) R(m)


A 4 0 0 0 0.5 0.004
B 0 4 0 0 0.5 0.004
C 0 4 4 4 0.5 0.004
D 4 0 4 4 0.5 0.004
E 2 0 2 4 0.5 0.004
F 4 2 0 2 0.5 0.004

Rods
Name X(m) Y(m) L(m) h(m) R(m)
VARILLA1 0 0 2.44 0.5 0.008
VARILLA2 4 4 2.44 0.5 0.008
VARILLA3 4 0 2.44 0.5 0.008
VARILLA4 0 4 2.44 0.5 0.008

Results
Grounding grid resistance (Ohm) 0.252
Ground Potenctial Rise GPR (V) 364.156
Grid Current (A) 1443.600
Fault Current Division Factor Sf 0.600
Tolerable Touch Voltage - 70 kg person (V) 2082.073
Tolerable Touch Voltage - 50 kg person (V) 1538.347
Report
Page 2 of 11

Touch Voltage (V) 135.870


Tolerable Step Voltage - 70 kg person (V) 7112.177
Tolerable Step Voltage - 50 kg person (V) 5254.857
Step Voltage (V)) 96.677
Total length of the conductor (m) 24.000
Total number of rods 4
Report
Page 3 of 11

Grid
Report
Page 4 of 11

Grid Profiles
Report
Page 5 of 11

Grid 3D
Report
Page 6 of 11

Touch voltage
Report
Page 7 of 11

Step voltage
Report
Page 8 of 11

Touch2D voltage
Report
Page 9 of 11

Step2D voltage
Report
Page 10 of 11

Touch voltage profiles


Report
Page 11 of 11

Step voltage profiles

Вам также может понравиться