DIgSI/info - DPL Program 'Create' started

DIgSI/info - DPL program 'Create' successfully executed


DIgSI/info - DPL Program 'Create' started
DIgSI/info - DPL program 'Create' successfully executed
DIgSI/info - DPL Program 'Create' started
DIgSI/info - DPL program 'Create' successfully executed
DIgSI/info - DPL Program 'Create' started
DIgSI/info - DPL program 'Create' : 'exit'
DIgSILENT Project:
PowerFactory
15.1.7 Date: 4/19/2018

Load Flow Calculation Complete System Report: Substations, Voltage Profiles, Grid Interchange
AC Load Flow, balanced, positive sequence Automatic Model Adaptation for Convergence No
Automatic Tap Adjust of Transformers No Max. Acceptable Load Flow Error for
Consider Reactive Power Limits No Nodes 1.00 kVA
Model Equations 0.10 %

Grid: CIPJ2017 System Stage: CIPJ2017 Study Case: Study Case Annex: / 1
rated Active Reactive Power
Voltage Bus-voltage Power Power Factor Current Loading Additional Data
[kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%]
A
13.80 1.03 14.26 -31.45
Cub_1 /Tr2 T-1 -4.32 -2.04 -0.90 0.19 31.15 Tap: 0.00 Min: -10 Max: 10
Cub_2 /Lne L-AB 4.32 2.04 0.90 0.19 48.79 Pv: 71.63 kW cLod: 0.10 Mvar L: 5.00 km
AT60
60.00 1.05 63.00 0.00
Cub_1 /Xnet SEIN 4.35 2.26 0.89 0.04 Sk": 519.62 MVA
Cub_2 /Tr2 T-1 4.35 2.26 0.89 0.04 31.15 Tap: 0.00 Min: -10 Max: 10
B
13.80 1.01 14.00 -31.70
Cub_3 /Lod LoadB 2.43 1.18 0.90 0.11 Pl0: 2.43 MW Ql0: 1.18 Mvar
Cub_1 /Lne L-AB -4.25 -2.08 -0.90 0.20 48.79 Pv: 71.63 kW cLod: 0.10 Mvar L: 5.00 km
Cub_2 /Lne L-BC 1.82 0.90 0.90 0.08 31.06 Pv: 45.45 kW cLod: 0.00 Mvar L: 4.50 km
C
13.80 0.99 13.60 -32.08
Cub_3 /Lod LoadC 1.35 0.65 0.90 0.06 Pl0: 1.35 MW Ql0: 0.65 Mvar
Cub_1 /Lne L-BC -1.77 -0.87 -0.90 0.08 31.06 Pv: 45.45 kW cLod: 0.00 Mvar L: 4.50 km
Cub_2 /Tr2 T-2 0.42 0.22 0.89 0.02 48.35 Tap: 0.00 Min: -3 Max: 3
Grid: CIPJ2017 System Stage: CIPJ2017 Study Case: Study Case Annex: / 2
rated Active Reactive Power
Voltage Bus-voltage Power Power Factor Current Loading Additional Data
[kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%]
D
0.44 0.97 0.43 -63.55
Cub_2 /Lod Load1 0.13 0.07 0.90 0.20 Pl0: 0.14 MW Ql0: 0.07 Mvar
Cub_3 /Lod General Load 0.15 0.06 0.93 0.22 Pl0: 0.15 MW Ql0: 0.06 Mvar
Cub_4 /Lod Load2 0.13 0.07 0.90 0.20 Pl0: 0.14 MW Ql0: 0.07 Mvar
Cub_5 /Lodmv MV Load 0.00 -0.00 1.00 0.00
Cub_1 /Tr2 T-2 -0.42 -0.19 -0.91 0.63 48.35 Tap: 0.00 Min: -3 Max: 3
Total
Load: 0.42 0.19
DIgSILENT Project:
PowerFactory
15.1.7 Date: 4/19/2018

Load Flow Calculation Complete System Report: Substations, Voltage Profiles, Grid Interchange
AC Load Flow, balanced, positive sequence Automatic Model Adaptation for Convergence No
Automatic Tap Adjust of Transformers No Max. Acceptable Load Flow Error for
Consider Reactive Power Limits No Nodes 1.00 kVA
Model Equations 0.10 %

Grid: CIPJ2017 System Stage: CIPJ2017 Study Case: Study Case Annex: / 3
rtd.V Bus - voltage Voltage - Deviation [%]
[kV] [p.u.] [kV] [deg] -10 -5 0 +5 +10
A
13.80 1.034 14.26 -31.45
AT60
60.00 1.050 63.00 0.00
B
13.80 1.014 14.00 -31.70
C
13.80 0.986 13.60 -32.08
D
0.44 0.967 0.43 -63.55
DIgSILENT Project:
PowerFactory
15.1.7 Date: 4/19/2018

Load Flow Calculation Complete System Report: Substations, Voltage Profiles, Grid Interchange
AC Load Flow, balanced, positive sequence Automatic Model Adaptation for Convergence No
Automatic Tap Adjust of Transformers No Max. Acceptable Load Flow Error for
Consider Reactive Power Limits No Nodes 1.00 kVA
Model Equations 0.10 %

Grid: CIPJ2017 System Stage: CIPJ2017 Study Case: Study Case Annex: / 4
Volt. Generation Motor Load Compen- External Power Total Load Noload
Level Load sation Infeed Interchange Interchange Losses Losses Losses
[MW]/ [MW]/ [MW]/ [MW]/ [MW]/ to [MW]/ [MW]/ [MW]/ [MW]/
[kV] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar]
0.44 0.00 0.00 0.42 0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.19 0.00 0.00 0.00 0.00 0.00
13.80 kV -0.42 0.00 0.00 0.00
-0.19 0.03 0.01 0.01
13.80 0.00 0.00 3.78 0.00 0.00 0.12 0.12 0.00
0.00 0.00 1.83 0.00 0.00 -0.01 0.09 -0.10
0.44 kV 0.42 0.00 0.00 0.00
0.22 0.03 0.01 0.01
60.00 kV -4.32 0.03 0.01 0.02
-2.04 0.22 0.14 0.08
60.00 0.00 0.00 0.00 0.00 4.35 0.00 0.00 0.00
0.00 0.00 0.00 0.00 2.26 0.00 0.00 0.00
13.80 kV 4.35 0.03 0.01 0.02
2.26 0.22 0.14 0.08
Total: 0.00 0.00 4.20 0.00 4.35 0.00 0.15 0.13 0.02
0.00 0.00 2.02 0.00 2.26 0.00 0.24 0.25 -0.01
DIgSILENT Project:
PowerFactory
15.1.7 Date: 4/19/2018

Load Flow Calculation Complete System Report: Substations, Voltage Profiles, Grid Interchange
AC Load Flow, balanced, positive sequence Automatic Model Adaptation for Convergence No
Automatic Tap Adjust of Transformers No Max. Acceptable Load Flow Error for
Consider Reactive Power Limits No Nodes 1.00 kVA
Model Equations 0.10 %

Total System Summary Study Case: Study Case Annex: / 5


Generation Motor Load Compen- External Inter Area Total Load Noload
Load sation Infeed Flow Losses Losses Losses
[MW]/ [MW]/ [MW]/ [MW]/ [MW]/ [MW]/ [MW]/ [MW]/ [MW]/
[Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar]
\CURSO HYO\Curso_Protecciones2018 SEM 1\Network Model\Network Data\CIPJ2017
0.00 0.00 4.20 0.00 4.35 0.00 0.15 0.13 0.02
0.00 0.00 2.02 0.00 2.26 0.00 0.24 0.25 -0.01
Total:
0.00 0.00 4.20 0.00 4.35 0.15 0.13 0.02
0.00 0.00 2.02 0.00 2.26 0.24 0.25 -0.01