Specifications
and fault interrupters. The operating mechanisms operate
Conditions of Sale
independently of the speed of the manual handle and are
STANDARD: Seller’s standard conditions of sale set forth designed to prevent inadvertent operation from the closed
in Price Sheet 150 apply. position directly to the ground position and vice versa. Oper-
ating shafts are padlockable in any position and can also
SPECIAL TO THIS PRODUCT: be padlocked to prevent operation to the ground position.
INCLUSIONS: S&C Vista Underground Distribution Terminals are equipped with 200-ampere-rated bushing
Switchgear features load-interrupter switches for switch- wells or 600- or 900-ampere bushings (as specified). Bushing
ing 600- or 900-ampere main feeders, and microprocessor and bushing-well interfaces are in accordance with IEEE
controlled arc-spinners or vacuum fault interrupters for Standard 386 to accept all standard insulated connectors
switching and protection of 600- or 900-ampere main feeders and inserts.
and 200-, 600-, or 900-ampere taps, laterals, and subloops. In addition, Vista UDS has been certified as arc resistant
These elbow-connected components are enclosed in a SF6- per IEC 298 Appendix AA for fault currents up to 12.5 kA
insulated, welded-steel tank, completely protected from symmetrical for 15 cycles (25 kA symmetrical for units rated
the environment. The switchgear is available with up to six 25 kA short circuit). Arc resistance is standard for the Pad-
ways (bus terminals, switches and/or fault interrupters) in Mounted and UnderCover Styles. For the Vault-Mounted
ratings through 38 kV and 25 kA symmetrical. Styles, Catalog Number Suffix “-N” must be specified, in
The three-position (closed-open-grounded) load- which case a flange will be welded to the pressure relief
interrupter switches are manually operated and provide device for connection of user-supplied piping to vent
three-pole live switching of 600- or 900-ampere three-phase exhaust gases out of the vault area.
circuits. These switches also provide a visible gap when When optional voltage indication is specified, all routine
open and internal grounding for all three phases—without operating tasks—switching, voltage testing, and ground-
exposure to medium voltage or the need to manipulate ing—can be accomplished by a single person without cable
elbows. The 200-ampere, 600-ampere, or 900-ampere fault handling or exposure to medium voltage. An optional fea-
interrupters feature either arc-spinning contacts (15.5-kV, ture that combines voltage indication with provisions for
12,500-symmetrical models) or vacuum interrupters in low-voltage phasing is also available. Cable testing for faults
series with manually operated three-position (closed-open- can be performed through the back of a user-supplied elbow
grounded) disconnects (15.5-kV, 25,000-symmetrical, and all or through a user-supplied feed thru insert eliminating the
29-kV and 38-kV models) for isolation and internal ground- need for difficult cable handling or parking stands.
ing of each phase. The programmable overcurrent control is programmed
Fault interrupters provide three-pole load switching and using a personal computer connected to the control through
fault interruption through 25 kA symmetrical, or single- an adapter cable (listed in the table of “ACCESSORIES” on
pole load switching and fault interruption through 12.5 kA page 11). Power and input signals are provided by current
symmetrical (for other possible ratings, refer to the near- transformers. The control features a variety of time-current
est S&C Sales Office). Fault interruption is initiated by a characteristic (TCC) curves—standard “E” and “K” speed
programmable overcurrent control. The total clearing time curves, innovative “coordinating” speed tap and main
(from initiation of the fault to total clearing) can be as fast curves, and relay curves per IEEE C37.112-1996.
as 40 milliseconds. For single-pole fault interrupters, the Coordinating-speed tap curves are used for fault inter-
overcurrent control can also be programmed to provide rupters feeding subloop taps and are specifically designed
three-pole fault interruption. to optimize coordination with load-side weak link/backup
Large windows provide a clear view of the open gap, current-limiting fuse combinations and source-side relays
ground position, and ground bus . . . allowing the operator to with low time-dial settings. The coordinating-speed
easily confirm the positions of the load-interrupter switches main curves are used for fault interrupters on main
and disconnects of the fault interrupters. Trip indicators, feeders and have a longer minimum response time and
which are readily visible through the windows, are provided different shape to coordinate with tap-interrupter curves.
for the fault interrupters. Each unit of gear is furnished Coordinating-speed curves have phase-overcurrent and
with a manual handle to charge the operating mechanisms ground-overcurrent settings. If desired, the ground-overcurrent
and open, close, and ground the load-interrupter switches
THREE-PHASE UNITS
Ratings3
Page Reference
Short-Circuit Catalog Net Wt.,
Model1 One-Line Diagram2 kV for Dimensional
Amperes, Number Lbs.4
Information
Max BIL RMS, Sym.
12 500 932012R1 550
15.5 95
25 000 852012d 550
12 500 932013 550
201 29 125
25 000 852013d 800
12 500 932014d 800
38 150
25 000 852014d 800
12 500 932102R1 550
15.5 95
25 000 852102d 550
12 500 932103 550
210 29 125
25 000 852013d 800
12 500 932104d 800
38 150
25 000 852104d 800
12 500 932112R1 550
15.5 95
25 000 852112d 550
12 500 932113 550
211 29 125
25 000 852113d 800
12 500 932114d 800
38 150
25 000 852114d 800
12 through 19
12 500 933202R1 825
15.5 95
25 000 853202 825
12 500 933203 825
320 29 125
25 000 853203 1075
12 500 933204 1075
38 150
25 000 853204 1075
12 500 933212R1 825
15.5 95
25 000 853212 825
12 500 933213 825
321 29 125
25 000 853213 1075
12 500 933214 1075
38 150
25 000 853214 1075
12 500 933302R1 825
15.5 95
25 000 853302 825
12 500 933303 825
330 29 125
25 000 853303 1075
12 500 933304 1075
38 150
25 000 853304 1075
1 The model number defines the total number of ways, the number of 3 Refer to the ratings table on page 3 for continuous, load-dropping,
load-interrupter switch ways, and the number of fault-interrupter ways. interrupting, and momentary ratings.
For example, a Model 431 has “4” ways in total of which “3” are load- 4 Welded-steel tank including components and SF6 gas.
interrupter switch ways and “1” is a fault-interrupter way.
d These models have not been certified as arc resistant for unrestricted
2 Refer to the nearest S&C Sales Office for other possible configurations. access. Refer to the nearest S&C Sales Office.
TABLE CONTINUED v
THREE-PHASE UNITS—Continued
Ratings3
Page Reference
Short-Circuit Catalog Net Wt.,
Model1 One-Line Diagram2 kV for Dimensional
Amperes, Number Lbs.4
Information
Max BIL RMS, Sym.
12 500 934132R1 1100
15.5 95
25 000 854132 1100
12 500 934133 1100
413 29 125
25 000 854133 1350
12 500 934134 1350
38 150
25 000 854134 1350
12 500 934222R1 1100
15.5 95
25 000 854222 1100
12 500 934223 1100
422 29 125
25 000 854223 1350
12 500 934224 1350
38 150
25 000 854224 1350
12 500 934312R1 1100
15.5 95
25 000 854312 1100
12 500 934313 1100
431 29 125 12 through 19
25 000 854313 1350
12 500 934314 1350
38 150
25 000 854314 1350
12 500 934402R1 1100
15.5 95
25 000 854402 1100
12 500 934403 1100
440 29 125
25 000 854403 1350
12 500 934404 1350
38 150
25 000 854404 1350
12 500 935142R1 1375
15.5 95
25 000 855142 1375
12 500 935143 1375
514 29 125
25 000 855143 1625
12 500 935144 1625
38 150
25 000 855144 1625
1 The model number defines the total number of ways, the number of 2 Refer to the nearest S&C Sales Office for other configurations.
load-interrupter switch ways, and the number of fault-interrupter ways. 3 Refer to the ratings table on page 3 for continuous, load-dropping,
For example, a Model 431 has “4” ways in total of which “3” are load- interrupting, and momentary ratings.
interrupter switch ways and “1” is a fault-interrupter way.
4 Welded-steel tank including components and SF6 gas.
TABLE CONTINUED v
THREE-PHASE UNITS—Continued
Ratings3
Page Reference
Short-Circuit Catalog Net Wt.,
Model1 One-Line Diagram2 kV for Dimensional
Amperes, Number Lbs.4
Information
Max BIL RMS, Sym.
12 500 935232R1 1375
15.5 95
25 000 855232 1375
12 500 935233 1375
523 29 125
25 000 855233 1625
12 500 935234 1625
38 150
25 000 855234 1625
12 500 936242R1 1650
15.5 95
25 000 856242 1650
12 500 936243 1650
624 29 125 12 through 19
25 000 856243 1900
12 500 936244 1900
38 150
25 000 856244 1900
12 500 936332R1 1650
15.5 95
25 000 856332 1650
12 500 936333 1650
633 29 125
25 000 856333 1900
12 500 936334 1900
38 150
25 000 856334 1900
1 The model number defines the total number of ways, the number of 2 Refer to the nearest S&C Sales Office for other configurations.
load-interrupter switch ways, and the number of fault-interrupter ways. 3 Refer to the ratings table on page 3 for continuous, load-dropping,
For example, a Model 431 has “4” ways in total of which “3” are load- interrupting, and momentary ratings.
interrupter switch ways and “1” is a fault-interrupter way.
4 Welded-steel tank including components and SF6 gas.
SWITCHGEAR STYLES
Suffix to be Added
Applicable
Item to Switchgear
to Models
Catalog Number
UnderCover Style. Includes stainless-steel tank and submersible wiring and control housings -U All models
Dry-Vault-Mounted Style. Includes mild-steel tank. Does not include submersible wiring and
-V3 All models
control housings
Wet-Vault-Mounted Style. Includes stainless-steel tank and submersible wiring and control
-V4 All models
housings
Mild-steel outer Olive green finish -P6 514, 523, 624, 633
closure Light gray finish -P11 514, 523, 624, 633
Five- or six-way
unit Olive green finish -P16 514, 523, 624, 633
Stainless-steel outer
closure Light gray finish -P21 514, 523, 624, 633
12.5-kA-rated models
Single-Pole Manual Fault Interrupter on all fault-interrupting ways -T0 with 1 or more fault
interrupters
12.5-kA-rated models
Three-Pole Manual Fault Interrupter on one fault-interrupting way (single-pole manual fault
-T1 with 1 or more fault
interrupter on all other fault-interrupting ways)
interrupters
12.5-kA-rated models
Three-Pole Manual Fault Interrupter on two fault-interrupting ways (single-pole manual fault
-T2 with 2 or more fault
interrupter on all other fault-interrupting ways)
interrupters
12.5-kA-rated models
Three-Pole Manual Fault Interrupter on three fault-interrupting ways (single-pole manual fault
-T3 with 3 or more fault
interrupter on all other fault-interrupting ways)
interrupters
12.5-kA-rated models
Three-Pole Manual Fault Interrupter on four fault-interrupting ways (single-pole manual fault
-T4 with 4 or more fault
interrupter on all other fault-interrupting ways)
interrupters
12.5-kA-rated models
Three-Pole Manual Fault Interrupter on five fault-interrupting ways (single-pole manual fault
-T5 with 5 or more fault
interrupter on all other fault-interrupting ways)
interrupters
12.5-kA-rated models
Three-Pole Manual Fault Interrupter on six fault-interrupting ways -T6 with 6 or more fault
interrupters
1 Not applicable to models rated 25 kA short circuit. All 25-kA-rated 3 For standard models, components are in the following order (from left
models include three-pole manual fault interrupters. to right) when facing the operating side of the gear: load switches, bus
2 Refer to the nearest S&C Sales Office for other possible configurations. taps, three-pole fault interrupters, single-pole fault interrupters.
OPTIONAL FEATURES
Suffix to be Added
Applicable
Item to Switchgear
to Models
Catalog Number
Potential Indication with Test Feature. Includes LCD Without provisions for low-voltage
display to indicate presence of voltage on each phase, -L1
phasing
and solar panel to supply power for testing of complete
All models
voltage-indication circuit and phasing circuit (if furnished).
One potential indicator is provided for each bus-terminal, With provisions for low-voltage phasing -L2
load-interrupter switch, and fault-interrupter way
1 Wood products used in packaging are either hardwood or certified by 4 Copper bus, Catalog Number Suffix “-Z5,” must be specified if
the wood supplier as being “heat treated” (kiln dried) to a core tempera- 900-ampere load-interrupter switches and/or 900-ampere fault interrupt-
ture of 133° F (56° C) for a minimum of 30 minutes. ers are specified.
2 900-ampere cable connectors must be used. d Specify Suffix “-F12” for Pad-Mounted Style switchgear with stainless-
3 If piggybacked cable connectors are desired, refer to the nearest S&C steel outer enclosure, Catalog Number Suffix “-P12,” “-P14,” “-P16,”
Sales Office. “-P17,” “-P19,” or “-P21.”
TABLE CONTINUED v
OPTIONAL FEATURES—Continued
Suffix to be Added
Applicable
Item to Switchgear
to Models
Catalog Number
600-A Bushings Without Studs, at load-interrupter switch and bus terminals (in lieu of
-M1 All models rated 12.5 kA
standard 600-A bushings with studs)
600-A1 Bushings Without Studs, at load-interrupter switch, fault interrupter, and bus
-M1 All models rated 25 kA
terminals (in lieu of standard 600-A1 bushings with studs)
600-A Bushings at fault interrupter terminals (in lieu of Without studs -M2 All models rated 12.5 kA except
200-A bushing wells) With studs -M3 Models 210, 320, 330, and 440
200-A Bushing Wells at load-interrupter switch and bus terminals (in lieu of 600-A bushings All models rated 12.5 kA except
-M4
with studs) Model 2012
Arc Resistance for Vault-Mounted Style (arc resistance is standard for Pad-Mounted and
UnderCover Styles), per IEC 298 Appendix AA, for arcs occurring internal to the tank All models with Catalog Number
-N
(15 cycles, 12 kA symmetrical for 12.5-kA-rated models and 15 cycles, 25 kA symmetrical Suffix “-V3” or “-V4”
for 25-kA-rated models)
Two-Hole Ground Pad, one per way, located below bushings or bushing wells (in lieu of
-O All models
standard one ground pad per tank)
All Pad-Mounted and Dry-Vault-
-R11
With wires routed on tank for Mounted Styles
future customer connections All UnderCover and Wet-Vault-
Remote Low-Pressure Alarm3—includes internal contact -R12
Mounted Styles
for remote low-pressure indication, with wiring to outside
of tank With wires terminated in an
enclosure furnished with a All Pad-Mounted and Dry-Vault-
-R2
terminal block for customer Mounted Styles
connections
1 Bushings are rated 900 amperes on ways furnished with 900-ampere 2 Model 201 is furnished with 200-ampere bushing wells at bus termi-
load-interrupter switches (Catalog Number Suffix “-K1” through “-K6”) nals as standard.
and/or 900-ampere fault interrupters (Catalog Number Suffix “-Q1” 3 Must be specified if remote supervisory features such as remote low-
through “-Q6”). pressure indication are planned.
TABLE CONTINUED v
OPTIONAL FEATURES—Continued
Suffix to be
Added to
Item Applicable to Models
Switchgear
Catalog Number
accessories
Item Catalog Number
USB Cable Kit for connecting a personal computer to the Vista Overcurrent Control. Includes USB cable, adapter cable,
TA-3153
driver CD-ROM, and installation instructions
firmware upgrade
Item Catalog Number
Firmware Upgrade Kit for Vista Overcurrent Control. Includes CD-ROM and instructions CUA-6895
Vista UDS Tank—Applicable to All Models Rated 15.5 kV, 12.5 kA Symmetrical
(Model 422 shown)
26⁵⁄₈d
(676)
25³⁄₈d
(645)
17¹⁄₂d
(445)
TERMINATION VIEW
34¹³⁄₁₆
(884)
33⁷⁄₁₆
(849)
32³⁄₁₆ 5¹⁄₄
(817) (133)
SIDE VIEW
Ratings
Model Short-Circuit, Da Ea Ga W
kV, Max Amperes,
RMS, Sym.
413, 422, 431, 440 15.5f 12 500 28ZB\zn (735) 7B\, (194) 28ZB\zn (735) 65M\zn (1662)
514, 523 28ZB\zn (735) 7B\, (194) 43ZB\zn (1116) 80M\zn (2043)
624, 633 43ZB\zn (1116) 7B\, (194) 43ZB\zn (1116) 95M\zn (2424)
a All four-, five-, and six-way units include an extra 2B\,-inch (67-mm) f See pages 14 and 15 for 15.5-kV, 25-kA symmetrical models.
gap between Ways Two and Three (four-way units) or between Ways
Three and Four (five- and six-way units).
Vista UDS Tank—Applicable to All Models Except Those Rated 15.5 kV, 12.5 kA Symmetrical
(Model 422, 29 kV, 12.5 kA symmetrical shown)
B C C
33
(838)
28³⁄₄
(730)
W 35 5¹⁄₄
(889) (133)
3 (76) TYPICAL
35 26
(889) (660)
8
(203) 1¹⁄₁₆ (27) TYPICAL
B C F
D E G
APPROXIMATE PROJECTED
CABLE CENTER LINES
Ratings
Model Short-Circuit, B C Dd Ed F Gd W
kV, Max Amperes,
RMS, Sym.
15.5f 25 000 3ZB\zn (100) 5 (127) 28ZB\zn (735) 7B\, (194) 3ZB\zn (100) 28ZB\zn (735) 65M\zn (1662)
12 500 3ZB\zn (100) 5 (127) 28ZB\zn (735) 7B\, (194) 3ZB\zn (100) 28ZB\zn (735) 65M\zn (1662)
413
29
422
25 000 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 72ZC\zn (1849)
431
440
12 500 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 72ZC\zn (1849)
38
25 000 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 72ZC\zn (1849)
15.5f 25 000 3ZB\zn (100) 5 (127) 28ZB\zn (735) 7B\, (194) 3ZB\zn (100) 43ZB\zn (1116) 80M\zn (2043)
12 500 3ZB\zn (100) 5 (127) 28ZB\zn (735) 7B\, (194) 3ZB\zn (100) 43ZB\zn (1116) 80M\zn (2043)
29
514
25 000 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 90Z\zn (2288)
523
12 500 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 90Z\zn (2288)
38
25 000 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 90Z\zn (2288)
15.5f 25 000 3ZB\zn (100) 5 (127) 43ZB\zn (1116) 7B\, (194) 3ZB\zn (100) 43ZB\zn (1116) 95M\zn (2424)
12 500 3ZB\zn (100) 5 (127) 43ZB\zn (1116) 7B\, (194) 3ZB\zn (100) 43ZB\zn (1116) 95M\zn (2424)
29
624
25 000 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 107B\zn (2726)
633
12 500 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 107B\zn (2726)
38
25 000 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 107B\zn (2726)
d All four-, five-, and six-way units rated 15.5 kV, 25 kA symmetrical or f See pages 12 and 13 for 15.5-kV, 12.5-kA symmetrical models.
29 kV, 12.5 kA symmetrical include an extra 2B\,-inch (67-mm) gap
between Ways Two and Three (four-way units) or between Ways Three
and Four (five- and six-way units).
Pad-Mounted Style Switchgear—Models 201, 210, 211, 320, 321, 330, 413, 422, 431, 440a
(Model 422, 29 kV, 12.5 kA symmetrical shown)
APPROXIMATE PROJECTED
8 CABLE CENTERLINES
C (203)
B
H TYPICAL TERMINATION
SIDE
J TYPICAL
G F
W
W
TERMINATION VIEW ANCHOR BOLT PLAN
Ratings
Model Short- A B C D Fd Gd H
kV, Max Circuit, A,
RMS, Sym.
a See pages 18 and 19 for Models 514, 523, 624, and 633.
80° COVER
OPENING
TANK OR CABINET
GASKET
BY S&C
1¹⁄₂ (38) MIN.
5 CONCRETE PAD
(127)
D
Ratings
Model Short- I J K L M N P W
kV, Max Circuit, A,
RMS, Sym.
12 500 3 (76) 7 (178) 32ZC\zn (833) 7Z\, (181) 32C\zn (818) 10Z\x (267) 23ZC\zn (605) 39 (991)
15.5
25 000 4 (102) 38C\, (975) 55>\zn (1411) 13Z\, (333) 35 (889) 7Z\x (191) 23Z\x (597) 79 (2007)
201 12 500 4 (102) 7 (178) 32ZC\zn (833) 4Z\x (114) 35 (889) 7Z\x (191) 23Z\x (597) 39 (991)
210 29
211 25 000 4 (102) 33C\v (857) 55>\zn (1411) 13Z\, (333) 35 (889) 7Z\x (191) 23Z\x (597) 79 (2007)
12 500 4 (102) 7B\, (194) 38ZB\zn (989) 4Z\v (107) 35 (889) 7Z\x (191) 23Z\x (597) 44 (1118)
38
25 000 4 (102) 33C\v (857) 55>\zn (1411) 13Z\, (333) 35 (889) 7Z\x (191) 23Z\x (597) 79 (2007)
12 500 3 (76) 16 (406) 47ZC\zn (1214) 16Z\, (409) 32C\zn (818) 7Z\x (191) 23ZC\zn (605) 72 (1829)
15.5
25 000 4 (102) 23C\, (594) 55>\zn (1411) 13Z\, (333) 35 (889) 7Z\x (191) 23Z\x (597) 79 (2007)
320 12 500 4 (102) 16 (406) 47ZC\zn (1214) 13Z\x (342) 35 (889) 7Z\x (191) 23Z\x (597) 72 (1829)
321 29
330 25 000 4 (102) 16Z\x (419) 55B\, (1413) 13Z\, (333) 35 (889) 7Z\x (191) 23Z\x (597) 79 (2007)
12 500 4 (102) 16Z\x (419) 55B\, (1413) 13Z\, (333) 35 (889) 7Z\x (191) 23Z\x (597) 79 (2007)
38
25 000 4 (102) 16Z\x (419) 55B\, (1413) 13Z\, (333) 35 (889) 7Z\x (191) 23Z\x (597) 79 (2007)
12 500 3 (76) 7C\zn (183) 65M\zn (1662) 7Z\, (181) 32C\zn (818) 10Z\x (267) 23ZC\zn (605) 72 (1829)
15.5
25 000 4 (102) 10ZZ\zn (271) 65M\zn (1662) 8Z\, (206) 35 (889) 11 (279) 23Z\x (597) 79 (2007)
413
422 12 500 4 (102) 7C\zn (183) 65M\zn (1662) 4B\, (117) 35 (889) 7Z\x (191) 23Z\x (597) 72 (1829)
29
431 25 000 4 (102) 7M\, (200) 72ZC\zn (1849) 4Z\x (114) 35 (889) 7Z\x (191) 23Z\x (597) 79 (2007)
440
12 500 4 (102) 7M\, (200) 72ZC\zn (1849) 4Z\x (114) 35 (889) 7Z\x (191) 23Z\x (597) 79 (2007)
38
25 000 4 (102) 7M\, (200) 72ZC\zn (1849) 4Z\x (114) 35 (889) 7Z\x (181) 23Z\x (597) 79 (2007)
K
37
M (940)
L D
TANK
A
8
(203)
TERMINATION SIDE
C J TYPICAL H TYPICAL
G F
B APPROXIMATE PROJECTED
CABLE CENTER LINES
W
Ratings
Model Short- A B C D Fd Gd H
kV, Max Circuit, A,
RMS, Sym.
12 500 55 (1397) 17Z\x (445) 29Z\x (749) 61 (1549) 7B\, (194) 39ZZ\zn (1008) 5 (127)
15.5
25 000 65 (1651) 28 (711) 38 (965) 65 (1651) 7B\, (194) 39ZZ\zn (1008) 5 (127)
12 500 65 (1651) 28 (711) 38 (965) 65 (1651) 7B\, (194) 39ZZ\zn (1008) 5 (127)
514
29
523
25 000 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5C\v (146)
12 500 55 (1397) 17Z\x (445) 29Z\x (749) 61 (1549) 7B\, (194) 47C\zn (1199) 5 (127)
15.5
25 000 65 (1651) 28 (711) 38 (965) 65 (1651) 7B\, (194) 47C\zn (1199) 5 (127)
12 500 65 (1651) 28 (711) 38 (965) 65 (1651) 7B\, (194) 47C\zn (1199) 5 (127)
624
29
633
25 000 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5C\v (146)
d All four-, five, and six-way units rated 15.5 kV or 29 kV, 12.5 kA
symmetrical include an extra 2B\,-inch (67-mm) gap between Ways Two
and Three (four-way units) or between Ways Three and Four (five- and
six-way units).
a See pages 16 and 17 for Models 201, 210, 211, 320, 321, 330, 413, 422, 431, and 440.
P TANK OR CABINET
GASKET
BY S&C
1¹⁄₂ (38) MIN.
5 CONCRETE PAD
D (127)
Ratings
Model Short- I J K L M N P W
kV, Max Circuit, A,
RMS, Sym.
12 500 3 (76) 14ZZ\zn (373) 80M\zn (2043) 14M\, (377) 32C\zn (818) 7Z\x (191) 23ZC\zn (605) 102 (2591)
15.5
25 000 4 (102) 14ZZ\zn (373) 80M\zn (2043) 12Z\, (308) 35 (889) 7Z\x (191) 23Z\x (597) 102 (2591)
12 500 4 (102) 14ZZ\zn (373) 80M\zn (2043) 12Z\, (308) 35 (889) 7Z\x (191) 23Z\x (597) 102 (2591)
514
29
523
25 000 4 (102) 16Z\v (413) 90Z\zn (2288) 12M\, (327) 35 (889) 7Z\x (191) 23Z\x (597) 113 (2870)
12 500 4 (102) 16Z\v (413) 90Z\zn (2288) 12M\, (327) 35 (889) 7Z\x (191) 23Z\x (597) 113 (2870)
38
25 000 4 (102) 16Z\v (413) 90Z\zn (2288) 12M\, (327) 35 (889) 7Z\x (191) 23Z\x (597) 113 (2870)
12 500 3 (76) 7C\zn (183) 95M\zn (2424) 7C\, (187) 32C\zn (818) 10Z\x (267) 23ZC\zn (605) 102 (2591)
15.5
25 000 4 (102) 7C\zn (183) 95M\zn (2424) 4B\, (117) 35 (889) 7Z\x (191) 23Z\x (597) 102 (2591)
12 500 4 (102) 7C\zn (183) 95M\zn (2424) 4B\, (117) 35 (889) 7Z\x (191) 23Z\x (597) 102 (2591)
624
29
633
25 000 4 (102) 7B\, (194) 107B\zn (2726) 4Z\v (107) 35 (889) 7Z\x (191) 23Z\x (597) 113 (2870)
12 500 4 (102) 7B\, (194) 107B\zn (2726) 4Z\v (107) 35 (889) 7Z\x (191) 23Z\x (597) 113 (2870)
38
25 000 4 (102) 7B\, (194) 107B\zn (2726) 4Z\v (107) 35 (889) 7Z\x (191) 23Z\x (597) 113 (2870)