S&C Manual Vista® Underground Distribution Switchgear

Outdoor Distribution (15.5 kV through 38 kV)

Specifications
and fault interrupters. The operating mechanisms operate
Conditions of Sale
independently of the speed of the manual handle and are
STANDARD: Seller’s standard conditions of sale set forth designed to prevent inadvertent operation from the closed
in Price Sheet 150 apply. position directly to the ground position and vice versa. Oper-
ating shafts are padlockable in any position and can also
SPECIAL TO THIS PRODUCT: be padlocked to prevent operation to the ground position.

INCLUSIONS: S&C Vista Underground Distribution Terminals are equipped with 200-ampere-rated bushing
Switchgear features load-interrupter switches for switch- wells or 600- or 900-ampere bushings (as specified). Bushing
ing 600- or 900-ampere main feeders, and microprocessor and bushing-well interfaces are in accordance with IEEE
controlled arc-spinners or vacuum fault interrupters for Standard 386 to accept all standard insulated connectors
switching and protection of 600- or 900-ampere main feeders and inserts.
and 200-, 600-, or 900-ampere taps, laterals, and subloops. In addition, Vista UDS has been certified as arc resistant
These elbow-connected components are enclosed in a SF6- per IEC 298 Appendix AA for fault currents up to 12.5 kA
insulated, welded-steel tank, completely protected from symmetrical for 15 cycles (25 kA symmetrical for units rated
the environment. The switchgear is available with up to six 25 kA short circuit). Arc resistance is standard for the Pad-
ways (bus terminals, switches and/or fault interrupters) in Mounted and UnderCover Styles. For the Vault-Mounted
ratings through 38 kV and 25 kA symmetrical. Styles, Catalog Number Suffix  “-N” must be specified, in
The three-position (closed-open-grounded) load- which case a flange will be welded to the pressure relief
interrupter switches are manually operated and provide device for connection of user-supplied piping to vent
three-pole live switching of 600- or 900-ampere three-phase exhaust gases out of the vault area.
circuits. These switches also provide a visible gap when When optional voltage indication is specified, all routine
open and internal grounding for all three phases—without operating tasks—switching, voltage testing, and ground-
exposure to medium voltage or the need to manipulate ing—can be accomplished by a single person without cable
elbows. The 200-ampere, 600-ampere, or 900-ampere fault handling or exposure to medium voltage. An optional fea-
interrupters feature either arc-spinning contacts (15.5-kV, ture that combines voltage indication with provisions for
12,500-symmetrical models) or vacuum interrupters in low-voltage phasing is also available. Cable testing for faults
series with manually operated three-position (closed-open- can be performed through the back of a user-supplied elbow
grounded) disconnects (15.5-kV, 25,000-symmetrical, and all or through a user-supplied feed thru insert eliminating the
29-kV and 38-kV models) for isolation and internal ground- need for difficult cable handling or parking stands.
ing of each phase. The programmable overcurrent control is programmed
Fault interrupters provide three-pole load switching and using a personal computer connected to the control through
fault interruption through 25  kA symmetrical, or single- an adapter cable (listed in the table of “ACCESSORIES” on
pole load switching and fault interruption through 12.5 kA page 11). Power and input signals are provided by current
symmetrical (for other possible ratings, refer to the near- transformers. The control features a variety of time-current
est S&C Sales Office). Fault interruption is initiated by a characteristic (TCC) curves—standard “E” and “K” speed
programmable overcurrent control. The total clearing time curves, innovative “coordinating” speed tap and main
(from initiation of the fault to total clearing) can be as fast curves, and relay curves per IEEE C37.112-1996.
as 40 milliseconds. For single-pole fault interrupters, the Coordinating-speed tap curves are used for fault inter-
overcurrent control can also be programmed to provide rupters feeding subloop taps and are specifically designed
three-pole fault interruption. to optimize coordination with load-side weak link/backup
Large windows provide a clear view of the open gap, current-limiting fuse combinations and source-side relays
ground position, and ground bus . . . allowing the operator to with low time-dial settings. The coordinating-speed
easily confirm the positions of the load-interrupter switches main curves are used for fault interrupters on main
and disconnects of the fault interrupters. Trip indicators, feeders and have a longer minimum response time and
which are readily visible through the windows, are provided different shape to coordinate with tap-interrupter curves.
for the fault interrupters. Each unit of gear is furnished Coordinating-speed curves have phase-overcurrent and
with a manual handle to charge the operating mechanisms ground-overcurrent settings. If desired, the ground-overcurrent
and open, close, and ground the load-interrupter switches

August 23, 2010© S&C Electric Company Specification Bulletin  681-31


S&C Manual Vista® Underground Distribution Switchgear

tion to the load-dropping ratings shown, the fault interrupter


Conditions of Sale—Continued
is capable of interrupting transformer magnetizing currents
setting can be turned off. (A ground-overcurrent setting is associated with the applicable loads, as well as line-charging
not available when the control is programmed for single- and cable-charging currents typical for distribution systems
pole tripping of the fault interrupters.) These curves can be of these voltage ratings. The duty-cycle fault-closing rating
tailored to the application using a variety of instantaneous shown for the fault interrupter defines the ability to close
and definite-time settings. the interrupter the designated number of times into the
Vista switchgear is considerably smaller than traditional closed position or ground position against a three-phase
air-insulated gear, and is available in several styles, so it can fault as follows:
be installed exactly where needed. The standard mounting • Main Contacts
styles of switchgear are as follows: The fault interrupter shall have the ability to close
the designated number of times into a three-phase
UnderCover Style fault equal to rated value and interrupt the resulting
When the UnderCover style is specified, the gear is provided short-circuit current. The fault interrupter shall remain
with a stainless-steel tank and submersible wiring. operable and able to carry and interrupt its rated con-
Vault-Mounted Style tinuous current.
Two versions of this style are available: Wet-Vault-Mounted • Ground Contacts
Style is intended for vaults that are subject to periodic The fault interrupter ground switch shall have the abil-
flooding and includes submersible wiring and electrical ity to close the designated number of times against
components. Dry-Vault-Mounted Style is intended for vaults a three-phase fault equal to the rated value with the
that are not subject to periodic flooding and does not include ground switch remaining operable and able to carry its
submersible wiring and electrical components. rated fault-closing current.
When the Wet-Vault-Mounted Style is specified, a stain- A Note on Single-Pole Switching
less-steel tank is furnished, suitable for mounting on the In single-pole switching of ungrounded-primary three-phase
floor or wall of a vault. When the Dry-Vault-Mounted Style transformers or banks (or single-phase transformers con-
is specified, a mild-steel tank is furnished. nected line-to-line), circuit connections or parameters may,
Pad-Mounted Style in some cases, produce excessive overvoltages. In particu-
lar, for the following applications above 22 kV, single-pole
When the pad-mounted style is specified, a mild-steel or,
switching by any means should be performed only under
optionally, stainless-steel enclosure and tank are provided.
the conditions stated in italics:
Pad-mounted enclosures meet the requirements of ANSI
C57.12.28 (enclosure integrity). The top of the pad-mounted • Switching unloaded or lightly loaded delta-connected
enclosure is hinged on both sides for convenient access or ungrounded-primary wye-wye connected three-
to the operating and termination compartments. A remov- phase transformers or banks (or line-to-line connected
able panel provides access to the elbows and cables and single-phase transformers), rated 150 kVA or less three-
is secured by the overlapping padlockable top. A resilient phase, or 50  kVA or less single-phase—or of any kVA
closed-cell gasket on the enclosure bottom flange protects rating when combined with unloaded cables or lines—
the finish from being scratched during installation and where maximum system operating voltage exceeds
isolates it from the alkalinity of a concrete foundation. 22 kV. Single-pole switching should be performed only
Enclosures are protected from corrosion by S&C’s Ultra- if each phase is carrying 5% load or more, or if the
dur® Finishing System. transformer or bank is temporarily grounded at the
primary neutral during switching.
APPLICATION NOTES: • Switching loaded or unloaded ungrounded-primary
Fault Interrupter wye-delta connected three-phase transformers or
S&C Vista Underground Distribution Switchgear features banks—alone or combined with unloaded cables or
either arc-spinning contacts (15.5 kV, 12.5 kA symmetrical), lines—where maximum system operating voltage
vacuum fault interrupters for three-pole load switching and exceeds 22  kV. Single-pole switching should be per-
fault interruption through 25  kA symmetrical, or single- formed only if each phase is carrying 5% load or more
pole load switching and fault interruption through 12.5 kA and if the lighting-load phase is always switched open
symmetrical. first (or switched closed last); or if the transformer or
bank is temporarily grounded at the primary neutral
Complete ratings for the fault interrupter, as applied in
during switching.
Vista switchgear, are shown in the table on page 3. In addi-

2   S&C Specification Bulletin 681-31


S&C Manual Vista® Underground Distribution Switchgear

Load-Interrupter Switch How to Order


S&C Vista Underground Distribution Switchgear features
load-interrupter switches for three-pole live switching of 1. Obtain the catalog number of the desired unit from the
three-phase circuits. table on pages 4 through 6.
Complete ratings for the load-interrupter switch, as 2. Specify the desired switchgear style from the table on
applied in Vista Switchgear, are shown in the table below. page  7 and add the appropriate suffix to the catalog
In addition to the load-dropping ratings shown, the switch number.
is capable of interrupting transformer magnetizing currents 3. For 12.5-kA-rated models with one or more fault
associated with the applicable loads, as well as line-charging interrupters, add a suffix designation to the catalog
and cable-charging currents typical for distribution systems number indicating the desired number of three-pole
of these voltage ratings. For applications involving load and single-pole fault interrupters, selected from the
current with high harmonic content (such as rectifier load table on page 7. This step is not applicable to models
currents), refer to the nearest S&C Sales Office. The duty- rated 25 kA short circuit.
cycle fault-closing rating shown for the switch defines the
ability to close the switch into the closed or ground position 4. Add suffix designations to the catalog number indicat-
the designated number of times against a three-phase fault ing the optional features desired, selected from the
equal to the rated value, with the switch remaining operable table on pages 8 through 10.
and able to carry and interrupt rated current. 5. Obtain the catalog number of the accessories from the
table on page 11 and touch-up kit components from the
EXCLUSIONS: Three-phase units listed on pages 4 through table on page 11.
6 do not include the switchgear style, optional features, or
accessories listed in the tables on pages 7 through 11. For example, the catalog number of a Vista Underground
Distribution Switchgear unit, UnderCover style, Model 422
with all single-pole fault interrupters, rated 12.5 kA short
circuit and 15.5 kV maximum at 60 hertz, and equipped with
voltage indication with provisions for low-voltage phasing
is 934222R1-UT0L2.

50/60-Hz ANSI Ratings—IEC Ratings in Parentheses12


kV Amperes, RMS

Fault Interrupter Load-Interrupter Switch

Main Bus Short- Ten-Time Duty-Cycle


System Cont., Load Fault-Closing, Sym. Ten-Time Cont., Load Ten-Time
Max BIL Cont. Circuit, Mom. and
Class Dropping, Duty-Cycle Dropping, Duty-Cycle
Current Sym. Into Into One-Second,
and Load Fault-Interr., and Load Fault-Closing,
Closed Grounded Sym.
Splitting3 Sym. Splitting3 Sym.4
Position Position
12 500 200 12 500 12 500 12 500 600 12 500 12 500
15.5 15.5 95 600 (12 500) (200)d (12 500) (12 500) (12 500) (630)a (12 500) (12 500)
(12) (15.5) (95) (630)f 25 000 600 25 000 25 000 600 25 000
(25 000) (630)l (25 000) • (25 000) (630)k • (25 000)
12 500 200 12 500 12 500 12 500 600 16 000 12 500
27 29 125 600 (12 500) (200)d (12 500) (12 500) (12 500) (630)a (16 000) (12 500)
(24) (29) (125) (630)f 25 000 600 25 000 25 000 600 25 000
(25 000) (630)l (25 000) • (25 000) (630)k • (25 000)
12 500 200 12 500 12 500 12 500 600 16 000 12 500
38 38 150 600 (12 500) (200)d (12 500) (12 500) (12 500) (630)a (16 000) (12 500)
(36) (38) (150) (630)f 25 000 600 25 000 25 000 600 25 000
(25 000) (630)l (25 000) • (25 000) (630)k • (25 000)
1 ANSI ratings have been assigned in accordance with the applicable l 900 (900) amperes when switchgear is furnished with optional
portions of IEEE C37.71, C37.72, and C37.73. IEC Ratings have been 900-ampere fault interrupters, Catalog Number Suffix “-Q1” through
assigned in accordance with the applicable portions of IEC 265-1 for a “-Q6,” plus optional copper bus, Catalog Number Suffix “-Z5.”
Class A switch. • 25 000 (25 000) amperes symmetrical three-time duty-cycle fault-
2 Refer to the nearest S&C Sales Office for other possible ratings. closing rating; 16 000 (16 000) amperes symmetrical ten-time duty-cycle
3 Parallel or loop switching. Fault interrupters and load-interrupter fault-closing rating.
switches can switch the magnetizing current of transformers associ- a 200 (200) amperes when switchgear is furnished with optional
ated with the load-dropping rating. Unloaded cable switching rating: 200-ampere bushing wells at load-interrupter switch terminals, Catalog
10 amperes at 15.5 kV, 20 amperes at 29 kV and 38 kV. Number Suffix “-M4.”
4 Applicable to fault closing into closed or grounded position. k 900 (900) amperes when switchgear is furnished with optional
f 1200 (1200) amperes when switchgear is furnished with optional 900-ampere load-interrupter switches, Catalog Number Suffix “-K1” through
copper bus, Catalog Number Suffix “-Z5.” “-K6,” plus optional copper bus, Catalog Number Suffix “-Z5.”
d 600 (630) amperes when switchgear is furnished with optional
600-ampere bushings at fault interrupter terminals, Catalog Number
Suffix “-M2” or “-M3.”
S&C Specification Bulletin 681-31   3
S&C Manual Vista® Underground Distribution Switchgear

THREE-PHASE UNITS
Ratings3
Page Reference
Short-Circuit Catalog Net Wt.,
Model1 One-Line Diagram2 kV for Dimensional
Amperes, Number Lbs.4
Information
Max BIL RMS, Sym.
12 500 932012R1 550
15.5 95
25 000 852012d 550
12 500 932013 550
201 29 125
25 000 852013d 800
12 500 932014d 800
38 150
25 000 852014d 800
12 500 932102R1 550
15.5 95
25 000 852102d 550
12 500 932103 550
210 29 125
25 000 852013d 800
12 500 932104d 800
38 150
25 000 852104d 800
12 500 932112R1 550
15.5 95
25 000 852112d 550
12 500 932113 550
211 29 125
25 000 852113d 800
12 500 932114d 800
38 150
25 000 852114d 800
12 through 19
12 500 933202R1 825
15.5 95
25 000 853202 825
12 500 933203 825
320 29 125
25 000 853203 1075
12 500 933204 1075
38 150
25 000 853204 1075
12 500 933212R1 825
15.5 95
25 000 853212 825
12 500 933213 825
321 29 125
25 000 853213 1075
12 500 933214 1075
38 150
25 000 853214 1075
12 500 933302R1 825
15.5 95
25 000 853302 825
12 500 933303 825
330 29 125
25 000 853303 1075
12 500 933304 1075
38 150
25 000 853304 1075
1 The model number defines the total number of ways, the number of 3 Refer to the ratings table on page 3 for continuous, load-dropping,
load-interrupter switch ways, and the number of fault-interrupter ways. interrupting, and momentary ratings.
For example, a Model 431 has “4” ways in total of which “3” are load- 4 Welded-steel tank including components and SF6 gas.
interrupter switch ways and “1” is a fault-interrupter way.
d These models have not been certified as arc resistant for unrestricted
2 Refer to the nearest S&C Sales Office for other possible configurations. access. Refer to the nearest S&C Sales Office.

TABLE CONTINUED v

4   S&C Specification Bulletin 681-31


S&C Manual Vista® Underground Distribution Switchgear

THREE-PHASE UNITS—Continued
Ratings3
Page Reference
Short-Circuit Catalog Net Wt.,
Model1 One-Line Diagram2 kV for Dimensional
Amperes, Number Lbs.4
Information
Max BIL RMS, Sym.
12 500 934132R1 1100
15.5 95
25 000 854132 1100
12 500 934133 1100
413 29 125
25 000 854133 1350
12 500 934134 1350
38 150
25 000 854134 1350
12 500 934222R1 1100
15.5 95
25 000 854222 1100
12 500 934223 1100
422 29 125
25 000 854223 1350
12 500 934224 1350
38 150
25 000 854224 1350
12 500 934312R1 1100
15.5 95
25 000 854312 1100
12 500 934313 1100
431 29 125 12 through 19
25 000 854313 1350
12 500 934314 1350
38 150
25 000 854314 1350
12 500 934402R1 1100
15.5 95
25 000 854402 1100
12 500 934403 1100
440 29 125
25 000 854403 1350
12 500 934404 1350
38 150
25 000 854404 1350
12 500 935142R1 1375
15.5 95
25 000 855142 1375
12 500 935143 1375
514 29 125
25 000 855143 1625
12 500 935144 1625
38 150
25 000 855144 1625
1 The model number defines the total number of ways, the number of 2 Refer to the nearest S&C Sales Office for other configurations.
load-interrupter switch ways, and the number of fault-interrupter ways. 3 Refer to the ratings table on page 3 for continuous, load-dropping,
For example, a Model 431 has “4” ways in total of which “3” are load- interrupting, and momentary ratings.
interrupter switch ways and “1” is a fault-interrupter way.
4 Welded-steel tank including components and SF6 gas.

TABLE CONTINUED v

S&C Specification Bulletin 681-31   5


S&C Manual Vista® Underground Distribution Switchgear

THREE-PHASE UNITS—Continued
Ratings3
Page Reference
Short-Circuit Catalog Net Wt.,
Model1 One-Line Diagram2 kV for Dimensional
Amperes, Number Lbs.4
Information
Max BIL RMS, Sym.
12 500 935232R1 1375
15.5 95
25 000 855232 1375
12 500 935233 1375
523 29 125
25 000 855233 1625
12 500 935234 1625
38 150
25 000 855234 1625
12 500 936242R1 1650
15.5 95
25 000 856242 1650
12 500 936243 1650
624 29 125 12 through 19
25 000 856243 1900
12 500 936244 1900
38 150
25 000 856244 1900
12 500 936332R1 1650
15.5 95
25 000 856332 1650
12 500 936333 1650
633 29 125
25 000 856333 1900
12 500 936334 1900
38 150
25 000 856334 1900
1 The model number defines the total number of ways, the number of 2 Refer to the nearest S&C Sales Office for other configurations.
load-interrupter switch ways, and the number of fault-interrupter ways. 3 Refer to the ratings table on page 3 for continuous, load-dropping,
For example, a Model 431 has “4” ways in total of which “3” are load- interrupting, and momentary ratings.
interrupter switch ways and “1” is a fault-interrupter way.
4 Welded-steel tank including components and SF6 gas.

6   S&C Specification Bulletin 681-31


S&C Manual Vista® Underground Distribution Switchgear

SWITCHGEAR STYLES
Suffix to be Added
Applicable
Item to Switchgear
to Models
Catalog Number

UnderCover Style. Includes stainless-steel tank and submersible wiring and control housings -U All models
Dry-Vault-Mounted Style. Includes mild-steel tank. Does not include submersible wiring and
-V3 All models
control housings
Wet-Vault-Mounted Style. Includes stainless-steel tank and submersible wiring and control
-V4 All models
housings

Mild-steel outer Olive green finish -P2 201, 210, 211


closure Light gray finish -P7 201, 210, 211
Two-way unit
Stainless-steel outer Olive green finish -P12 201, 210, 211
closure Light gray finish -P17 201, 210, 211

Pad-Mounted Style. 320, 321, 330, 413,


Olive green finish -P4
Includes mild-steel Mild-steel outer 422, 431, 440
tank and mild-steel or closure 320, 321, 330, 413,
stainless-steel pad- Light gray finish -P9
Three- or four-way 422, 431, 440
mounted enclosure for
unit 320, 321, 330, 413,
mounting switchgear on Olive green finish -P14
a pad. Does not include Stainless-steel outer 422, 431, 440
submersible wiring and closure 320, 321, 330, 413,
control housings Light gray finish -P19
422, 431, 440

Mild-steel outer Olive green finish -P6 514, 523, 624, 633
closure Light gray finish -P11 514, 523, 624, 633
Five- or six-way
unit Olive green finish -P16 514, 523, 624, 633
Stainless-steel outer
closure Light gray finish -P21 514, 523, 624, 633

SINGLE-POLE OR THREE-POLE FAULT INTERRUPTING123


Suffix to be Added
Applicable
Item to Switchgear
to Models
Catalog Number

12.5-kA-rated models
Single-Pole Manual Fault Interrupter on all fault-interrupting ways -T0 with 1 or more fault
interrupters
12.5-kA-rated models
Three-Pole Manual Fault Interrupter on one fault-interrupting way (single-pole manual fault
-T1 with 1 or more fault
interrupter on all other fault-interrupting ways)
interrupters
12.5-kA-rated models
Three-Pole Manual Fault Interrupter on two fault-interrupting ways (single-pole manual fault
-T2 with 2 or more fault
interrupter on all other fault-interrupting ways)
interrupters
12.5-kA-rated models
Three-Pole Manual Fault Interrupter on three fault-interrupting ways (single-pole manual fault
-T3 with 3 or more fault
interrupter on all other fault-interrupting ways)
interrupters
12.5-kA-rated models
Three-Pole Manual Fault Interrupter on four fault-interrupting ways (single-pole manual fault
-T4 with 4 or more fault
interrupter on all other fault-interrupting ways)
interrupters
12.5-kA-rated models
Three-Pole Manual Fault Interrupter on five fault-interrupting ways (single-pole manual fault
-T5 with 5 or more fault
interrupter on all other fault-interrupting ways)
interrupters
12.5-kA-rated models
Three-Pole Manual Fault Interrupter on six fault-interrupting ways -T6 with 6 or more fault
interrupters
1 Not applicable to models rated 25 kA short circuit. All 25-kA-rated 3 For standard models, components are in the following order (from left
models include three-pole manual fault interrupters. to right) when facing the operating side of the gear: load switches, bus
2 Refer to the nearest S&C Sales Office for other possible configurations. taps, three-pole fault interrupters, single-pole fault interrupters.

S&C Specification Bulletin 681-31   7


S&C Manual Vista® Underground Distribution Switchgear

OPTIONAL FEATURES
Suffix to be Added
Applicable
Item to Switchgear
to Models
Catalog Number

Stainless-Steel Tank for Dry-Vault-Mounted Style, Wet-Vault-Mounted Style, or Pad-Mounted Style


-S All models
Switchgear

Without viewing window in pad-


Mounting Provisions for Fault Indicator for each Load- -F1
mounted enclosure
Interrupter Switch in Pad-Mounted Style Switchgear. All models except
Accommodates three-phase indicator with single-phase Model 201
sensors With viewing window in pad-mounted
-F2d
enclosure

Potential Indication with Test Feature. Includes LCD Without provisions for low-voltage
display to indicate presence of voltage on each phase, -L1
phasing
and solar panel to supply power for testing of complete
All models
voltage-indication circuit and phasing circuit (if furnished).
One potential indicator is provided for each bus-terminal, With provisions for low-voltage phasing -L2
load-interrupter switch, and fault-interrupter way

Spanish Labels -L51 All models

International Crating1 -L71 All models


Way 1 -K1
Way 2 -K2
Way 3 -K3
900-Ampere Load-Interrupter Switch234 on
Way 4 -K4
Way 5 -K5
Way 6 -K6
All models rated 25 kA
Way 1 -Q1
Way 2 -Q2
Way 3 -Q3
900-Ampere Fault Interrupter234 on
Way 4 -Q4
Way 5 -Q5
Way 6 -Q6

1 Wood products used in packaging are either hardwood or certified by 4 Copper bus, Catalog Number Suffix “-Z5,” must be specified if
the wood supplier as being “heat treated” (kiln dried) to a core tempera- 900-ampere load-interrupter switches and/or 900-ampere fault interrupt-
ture of 133° F (56° C) for a minimum of 30 minutes. ers are specified.
2 900-ampere cable connectors must be used. d Specify Suffix “-F12” for Pad-Mounted Style switchgear with stainless-
3 If piggybacked cable connectors are desired, refer to the nearest S&C steel outer enclosure, Catalog Number Suffix “-P12,” “-P14,” “-P16,”
Sales Office. “-P17,” “-P19,” or “-P21.”

TABLE CONTINUED v

8   S&C Specification Bulletin 681-31


S&C Manual Vista® Underground Distribution Switchgear

OPTIONAL FEATURES—Continued
Suffix to be Added
Applicable
Item to Switchgear
to Models
Catalog Number

600-A Bushings Without Studs, at load-interrupter switch and bus terminals (in lieu of
-M1 All models rated 12.5 kA
standard 600-A bushings with studs)

600-A1 Bushings Without Studs, at load-interrupter switch, fault interrupter, and bus
-M1 All models rated 25 kA
terminals (in lieu of standard 600-A1 bushings with studs)

600-A Bushings at fault interrupter terminals (in lieu of Without studs -M2 All models rated 12.5 kA except
200-A bushing wells) With studs -M3 Models 210, 320, 330, and 440

200-A Bushing Wells at load-interrupter switch and bus terminals (in lieu of 600-A bushings All models rated 12.5 kA except
-M4
with studs) Model 2012
Arc Resistance for Vault-Mounted Style (arc resistance is standard for Pad-Mounted and
UnderCover Styles), per IEC 298 Appendix AA, for arcs occurring internal to the tank All models with Catalog Number
-N
(15 cycles, 12 kA symmetrical for 12.5-kA-rated models and 15 cycles, 25 kA symmetrical Suffix “-V3” or “-V4”
for 25-kA-rated models)
Two-Hole Ground Pad, one per way, located below bushings or bushing wells (in lieu of
-O All models
standard one ground pad per tank)
All Pad-Mounted and Dry-Vault-
-R11
With wires routed on tank for Mounted Styles
future customer connections All UnderCover and Wet-Vault-
Remote Low-Pressure Alarm3—includes internal contact -R12
Mounted Styles
for remote low-pressure indication, with wiring to outside
of tank With wires terminated in an
enclosure furnished with a All Pad-Mounted and Dry-Vault-
-R2
terminal block for customer Mounted Styles
connections

1 Bushings are rated 900 amperes on ways furnished with 900-ampere 2 Model 201 is furnished with 200-ampere bushing wells at bus termi-
load-interrupter switches (Catalog Number Suffix “-K1” through “-K6”) nals as standard.
and/or 900-ampere fault interrupters (Catalog Number Suffix “-Q1” 3 Must be specified if remote supervisory features such as remote low-
through “-Q6”). pressure indication are planned.

TABLE CONTINUED v

S&C Specification Bulletin 681-31   9


S&C Manual Vista® Underground Distribution Switchgear

OPTIONAL FEATURES—Continued
Suffix to be
Added to
Item Applicable to Models
Switchgear
Catalog Number

All Pad-Mounted and Dry-Vault-


-R31
In addition to standard overcurrent Mounted Styles
External Trip Provisions. Allows three-pole tripping control for all fault interrupters All UnderCover and Wet-Vault-
of single-pole or three-pole fault interrupters via a -R32
Mounted Styles
trip signal from a remote location or an external
relay. Requires a 110/ 120-Vac 50/60-Hz control All Pad-Mounted and Dry-Vault-
In lieu of standard overcurrent control -R41
power source1 Mounted Styles
and current transformers for all fault
interrupters All UnderCover and Wet-Vault-
-R42
Mounted Styles
All Pad-Mounted and Dry-Vault-
-R33
In addition to standard overcurrent Mounted Styles
External Trip Provisions. Allows three-pole tripping control for all fault interrupters All UnderCover and Wet-Vault-
of single-pole or three-pole fault interrupters via a -R34
Mounted Styles
trip signal from a remote location or an external
relay. Requires a 220/ 240-Vac 50/60-Hz control All Pad-Mounted and Dry-Vault-
In lieu of standard overcurrent control -R43
power source1 Mounted Styles
and current transformers for all fault
interrupters All UnderCover and Wet-Vault-
-R44
Mounted Styles
Any in which Way 1 is a load-
Way 1 -X1 interrupter switch or three-pole
fault interrupter
Any in which Way 2 is a load-
Way 2 -X2 interrupter switch or three-pole
fault interrupter
Any in which Way 3 is a load-
Way 3 -X3 interrupter switch or three-pole
Key Interlocks. Locks load-interrupter switch or fault interrupter
three-pole fault interrupter (Catalog Number
Suffix “-T1” through “-T6”) in the open position2 Any in which Way 4 is a load-
Way 4 -X4 interrupter switch or three-pole
fault interrupter
Any in which Way 5 is a load-
Way 5 -X5 interrupter switch or three-pole
fault interrupter
Any in which Way 6 is a load-
Way 6 -X6 interrupter switch or three-pole
fault interrupter

Copper Bus3 -Z5 All models


1 The user-supplied trip-initiating signal must be a momentary contact. 2 Motor operators can not be retrofitted onto ways with key interlocks.
Refer to the nearest S&C Sales Office if an application requires the use 3 Main bus can be rated up to 1200 amperes when Catalog Number
of a latching contact. Suffix “-Z5” is specified.

10   S&C Specification Bulletin 681-31


S&C Manual Vista® Underground Distribution Switchgear

accessories
Item Catalog Number

69-5Z\x0 length 9933-150


Shotgun Clamp Sticks for use with separable connectors
89-5Z\x0 length 9933-151
69-60 length 9933-152
Storage Bag for Shotgun Clamp Sticks, heavy canvas
89-60 length 9933-153
For personal computers having 25-pin
TA-2366
For connecting control to user-furnished serial communication port
personal computer in the field For personal computers having 9-pin serial
Overcurrent-Control Adapter TA-2367
communication port
Cable. Required for programming
overcurrent control For personal computers having 25-pin
For connecting control (removed TA-2368
serial communication port
from its enclosure) to user-furnished
personal computer in the shop For personal computers having 9-pin serial
TA-2369
communication port
User-furnished 24-volt battery and battery
38320R1
charger
Portable Motor Operator for operation of load-interrupter switches and single-
or three-pole fault interrupters from a remote location. Includes carrying case, S&C-furnished 24-volt battery and battery
38322R1
and 50-foot cable with remote controls. Power supplied by charger
S&C-furnished AC input power supply 38323R1
Pentahead Socket, for Z\x-inch drive 9931-074

usb cable kit


Item Catalog Number

USB Cable Kit for connecting a personal computer to the Vista Overcurrent Control. Includes USB cable, adapter cable,
TA-3153
driver CD-ROM, and installation instructions

firmware upgrade
Item Catalog Number

Firmware Upgrade Kit for Vista Overcurrent Control. Includes CD-ROM and instructions CUA-6895

touch-up kit components—Aerosol Coatings in 12-ounce cans


Item Catalog Number

S&C Light Gray Outdoor Finish 9999-080


S&C Olive Green (Munsell 7GY3.29/1.5) Outdoor Finish 9999-058
S&C Red-Oxide Primer 9999-061

S&C Specification Bulletin 681-31   11


S&C Manual Vista® Underground Distribution Switchgear

Vista UDS Tank—Applicable to All Models Rated 15.5 kV, 12.5 kA Symmetrical
(Model 422 shown)

Dimensions in inches (mm)

3¹⁵⁄₁₆ (100) 5 (127) TYPICAL

26⁵⁄₈d
(676)
25³⁄₈d
(645)
17¹⁄₂d
(445)

TERMINATION VIEW

⁵⁄₈ (16) DIAMETER


8 PLACES

34¹³⁄₁₆
(884)
33⁷⁄₁₆
(849)

1³⁄₄ (44) 5¹⁄₄ (133) 8 (203)


3 (76)

5 (127)  3¹⁵⁄₁₆ (100)


APPROXIMATE PROJECTED TYPICAL
CABLE CENTER LINES
D E G

ANCHOR BOLT PLAN

d Measured to bottom of mounting feet.

12   S&C Specification Bulletin 681-31


S&C Manual Vista® Underground Distribution Switchgear

32³⁄₁₆ 5¹⁄₄
(817) (133)

SIDE VIEW

Ratings

Model Short-Circuit, Da Ea Ga W
kV, Max Amperes,
RMS, Sym.

201, 210, 211 NA NA NA 32ZC\zn (833)

320, 321, 330 NA NA NA 47ZC\zn (1214)

413, 422, 431, 440 15.5f 12 500 28ZB\zn (735) 7B\, (194) 28ZB\zn (735) 65M\zn (1662)

514, 523 28ZB\zn (735) 7B\, (194) 43ZB\zn (1116) 80M\zn (2043)

624, 633 43ZB\zn (1116) 7B\, (194) 43ZB\zn (1116) 95M\zn (2424)

a All four-, five-, and six-way units include an extra 2B\,-inch (67-mm) f See pages 14 and 15 for 15.5-kV, 25-kA symmetrical models.
gap between Ways Two and Three (four-way units) or between Ways
Three and Four (five- and six-way units).

S&C Specification Bulletin 681-31   13


S&C Manual Vista® Underground Distribution Switchgear

Vista UDS Tank—Applicable to All Models Except Those Rated 15.5 kV, 12.5 kA Symmetrical
(Model 422, 29 kV, 12.5 kA symmetrical shown)

Dimensions in inches (mm)

B C C

33
(838)
28³⁄₄
(730)

W 35 5¹⁄₄
(889) (133)

TERMINATION VIEW SIDE VIEW

EIGHT ⁵₈ (16) DIAMETER


1¹⁄₂ (38) TYPICAL
W

3 (76) TYPICAL

35 26
(889) (660)

8
(203) 1¹⁄₁₆ (27) TYPICAL

B C F
D E G

APPROXIMATE PROJECTED
CABLE CENTER LINES

ANCHOR BOLT PLAN

14   S&C Specification Bulletin 681-31


S&C Manual Vista® Underground Distribution Switchgear

Ratings

Model Short-Circuit, B C Dd Ed F Gd W
kV, Max Amperes,
RMS, Sym.

15.5f 25 000 26ZZ\zn (678) 5 (127) NA NA 3ZB\zn (100) NA 55>\zn (1411)

12 500 3ZB\zn (100) 5 (127) NA NA 3ZB\zn (100) NA 32M\zn (824)


201 29
210 25 000 22Z\zn (560) 5C\v (146) NA NA 4ZC\zn (122) NA 55>\zn (1411)
211
12 500 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 38B\zn (973)
38
25 000 22Z\zn (560) 5C\v (146) NA NA 4ZC\zn (122) NA 55>\zn (1411)

15.5f 25 000 11ZZ\zn (297) 5 (127) NA NA 3ZB\zn (100) NA 55>\zn (1411)

12 500 3ZB\zn (100) 5 (127) NA NA 3ZB\zn (100) NA 47ZC\zn (1214)


320 29
321 25 000 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 55>\zn (1411)
330
12 500 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 55>\zn (1411)
38
25 000 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 55>\zn (1411)

15.5f 25 000 3ZB\zn (100) 5 (127) 28ZB\zn (735) 7B\, (194) 3ZB\zn (100) 28ZB\zn (735) 65M\zn (1662)

12 500 3ZB\zn (100) 5 (127) 28ZB\zn (735) 7B\, (194) 3ZB\zn (100) 28ZB\zn (735) 65M\zn (1662)
413
29
422
25 000 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 72ZC\zn (1849)
431
440
12 500 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 72ZC\zn (1849)
38
25 000 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 72ZC\zn (1849)

15.5f 25 000 3ZB\zn (100) 5 (127) 28ZB\zn (735) 7B\, (194) 3ZB\zn (100) 43ZB\zn (1116) 80M\zn (2043)

12 500 3ZB\zn (100) 5 (127) 28ZB\zn (735) 7B\, (194) 3ZB\zn (100) 43ZB\zn (1116) 80M\zn (2043)
29
514
25 000 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 90Z\zn (2288)
523
12 500 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 90Z\zn (2288)
38
25 000 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 90Z\zn (2288)

15.5f 25 000 3ZB\zn (100) 5 (127) 43ZB\zn (1116) 7B\, (194) 3ZB\zn (100) 43ZB\zn (1116) 95M\zn (2424)

12 500 3ZB\zn (100) 5 (127) 43ZB\zn (1116) 7B\, (194) 3ZB\zn (100) 43ZB\zn (1116) 95M\zn (2424)
29
624
25 000 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 107B\zn (2726)
633
12 500 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 107B\zn (2726)
38
25 000 4ZC\zn (122) 5C\v (146) NA NA 4ZC\zn (122) NA 107B\zn (2726)

d All four-, five-, and six-way units rated 15.5 kV, 25 kA symmetrical or f See pages 12 and 13 for 15.5-kV, 12.5-kA symmetrical models.
29 kV, 12.5 kA symmetrical include an extra 2B\,-inch (67-mm) gap
between Ways Two and Three (four-way units) or between Ways Three
and Four (five- and six-way units).

S&C Specification Bulletin 681-31   15


S&C Manual Vista® Underground Distribution Switchgear

Pad-Mounted Style Switchgear—Models 201, 210, 211, 320, 321, 330, 413, 422, 431, 440a
(Model 422, 29 kV, 12.5 kA symmetrical shown)

Dimensions in inches (mm)

2³⁄₄ (70) TYPICAL N TYPICAL


I
OPERATION SIDE

L TYPICAL ⁵⁄₈ (16) DIAMETER


ANCHOR BOLT BY USER
ANCHOR BRACKET BY S&C
M 37
TANK (940)
A D
K

APPROXIMATE PROJECTED
8 CABLE CENTERLINES
C (203)
B
H TYPICAL TERMINATION
SIDE
J TYPICAL
G F
W
W
TERMINATION VIEW ANCHOR BOLT PLAN

Ratings

Model Short- A B C D Fd Gd H
kV, Max Circuit, A,
RMS, Sym.

12 500 55 (1397) 17Z\x (445) 29Z\x (749) 61 (1549) NA NA 5 (127)


15.5
25 000 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5 (127)
201 12 500 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5 (127)
210 29
211 25 000 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5C\v (146)
12 500 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5C\v (146)
38
25 000 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5C\v (146)
12 500 55 (1397) 17Z\x (445) 29Z\x (749) 61 (1549) NA NA 5 (127)
15.5
25 000 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5 (127)
320 12 500 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5 (127)
321 29
330 25 000 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5C\v (146)
12 500 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5C\v (146)
38
25 000 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5C\v (146)
12 500 55 (1397) 17Z\x (445) 29Z\x (749) 61 (1549) 7B\, (194) 32C\zn (818) 5 (127)
15.5
25 000 65 (1651) 28 (711) 38 (965) 65 (1651) 7B\, (194) 32C\zn (818) 5 (127)
413
422 12 500 65 (1651) 28 (711) 38 (965) 65 (1651) 7B\, (194) 32C\zn (818) 5 (127)
29
431 25 000 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5C\v (146)
440
12 500 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5C\v (146)
38
25 000 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5C\v (146)
d All four-, five, and six-way units rated 15.5 kV or 29 kV, 12.5 kA sym- Three (four-way units) or between Ways Three and Four (five- and six-
metrical include an extra 2B\,-inch (67-mm) gap between Ways Two and way units).

a See pages 18 and 19 for Models 514, 523, 624, and 633.

16   S&C Specification Bulletin 681-31


S&C Manual Vista® Underground Distribution Switchgear

80° COVER
OPENING

8  ⁵⁄₈ (16) DIA. ANCHOR BOLTS


BY USER
P ANCHOR BRACKET
BY S&C

TANK OR CABINET

GASKET
BY S&C
1¹⁄₂ (38) MIN.
5 CONCRETE PAD
(127)
D

SIDE VIEW ANCHOR BOLT DETAIL

Ratings

Model Short- I J K L M N P W
kV, Max Circuit, A,
RMS, Sym.

12 500 3 (76) 7 (178) 32ZC\zn (833) 7Z\, (181) 32C\zn (818) 10Z\x (267) 23ZC\zn (605) 39 (991)
15.5
25 000 4 (102) 38C\, (975) 55>\zn (1411) 13Z\, (333) 35 (889) 7Z\x (191) 23Z\x (597) 79 (2007)
201 12 500 4 (102) 7 (178) 32ZC\zn (833) 4Z\x (114) 35 (889) 7Z\x (191) 23Z\x (597) 39 (991)
210 29
211 25 000 4 (102) 33C\v (857) 55>\zn (1411) 13Z\, (333) 35 (889) 7Z\x (191) 23Z\x (597) 79 (2007)
12 500 4 (102) 7B\, (194) 38ZB\zn (989) 4Z\v (107) 35 (889) 7Z\x (191) 23Z\x (597) 44 (1118)
38
25 000 4 (102) 33C\v (857) 55>\zn (1411) 13Z\, (333) 35 (889) 7Z\x (191) 23Z\x (597) 79 (2007)
12 500 3 (76) 16 (406) 47ZC\zn (1214) 16Z\, (409) 32C\zn (818) 7Z\x (191) 23ZC\zn (605) 72 (1829)
15.5
25 000 4 (102) 23C\, (594) 55>\zn (1411) 13Z\, (333) 35 (889) 7Z\x (191) 23Z\x (597) 79 (2007)
320 12 500 4 (102) 16 (406) 47ZC\zn (1214) 13Z\x (342) 35 (889) 7Z\x (191) 23Z\x (597) 72 (1829)
321 29
330 25 000 4 (102) 16Z\x (419) 55B\, (1413) 13Z\, (333) 35 (889) 7Z\x (191) 23Z\x (597) 79 (2007)
12 500 4 (102) 16Z\x (419) 55B\, (1413) 13Z\, (333) 35 (889) 7Z\x (191) 23Z\x (597) 79 (2007)
38
25 000 4 (102) 16Z\x (419) 55B\, (1413) 13Z\, (333) 35 (889) 7Z\x (191) 23Z\x (597) 79 (2007)
12 500 3 (76) 7C\zn (183) 65M\zn (1662) 7Z\, (181) 32C\zn (818) 10Z\x (267) 23ZC\zn (605) 72 (1829)
15.5
25 000 4 (102) 10ZZ\zn (271) 65M\zn (1662) 8Z\, (206) 35 (889) 11 (279) 23Z\x (597) 79 (2007)
413
422 12 500 4 (102) 7C\zn (183) 65M\zn (1662) 4B\, (117) 35 (889) 7Z\x (191) 23Z\x (597) 72 (1829)
29
431 25 000 4 (102) 7M\, (200) 72ZC\zn (1849) 4Z\x (114) 35 (889) 7Z\x (191) 23Z\x (597) 79 (2007)
440
12 500 4 (102) 7M\, (200) 72ZC\zn (1849) 4Z\x (114) 35 (889) 7Z\x (191) 23Z\x (597) 79 (2007)
38
25 000 4 (102) 7M\, (200) 72ZC\zn (1849) 4Z\x (114) 35 (889) 7Z\x (181) 23Z\x (597) 79 (2007)

S&C Specification Bulletin 681-31   17


S&C Manual Vista® Underground Distribution Switchgear

Pad-Mounted Style Switchgear—Models 514, 523, 624, and 633a


(Model 523, 29 kV, 12.5 kA symmetrical shown)

Dimensions in inches (mm)


⁵⁄₈ (16)
2³⁄₄ (70) N ANCHOR BOLT BY USER
TYPICAL TYPICAL ANCHOR BRACKET BY S&C I
OPERATION SIDE

K
37
M (940)

L D
TANK
A
8
(203)

TERMINATION SIDE
C J TYPICAL H TYPICAL
G F
B APPROXIMATE PROJECTED
CABLE CENTER LINES
W

TERMINATION VIEW ANCHOR BOLT PLAN

Ratings

Model Short- A B C D Fd Gd H
kV, Max Circuit, A,
RMS, Sym.

12 500 55 (1397) 17Z\x (445) 29Z\x (749) 61 (1549) 7B\, (194) 39ZZ\zn (1008) 5 (127)
15.5
25 000 65 (1651) 28 (711) 38 (965) 65 (1651) 7B\, (194) 39ZZ\zn (1008) 5 (127)

12 500 65 (1651) 28 (711) 38 (965) 65 (1651) 7B\, (194) 39ZZ\zn (1008) 5 (127)
514
29
523
25 000 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5C\v (146)

12 500 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5C\v (146)


38
25 000 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5C\v (146)

12 500 55 (1397) 17Z\x (445) 29Z\x (749) 61 (1549) 7B\, (194) 47C\zn (1199) 5 (127)
15.5
25 000 65 (1651) 28 (711) 38 (965) 65 (1651) 7B\, (194) 47C\zn (1199) 5 (127)

12 500 65 (1651) 28 (711) 38 (965) 65 (1651) 7B\, (194) 47C\zn (1199) 5 (127)
624
29
633
25 000 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5C\v (146)

12 500 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5C\v (146)


38
25 000 65 (1651) 28 (711) 38 (965) 65 (1651) NA NA 5C\v (146)

d All four-, five, and six-way units rated 15.5 kV or 29 kV, 12.5 kA
symmetrical include an extra 2B\,-inch (67-mm) gap between Ways Two
and Three (four-way units) or between Ways Three and Four (five- and
six-way units).

a See pages 16 and 17 for Models 201, 210, 211, 320, 321, 330, 413, 422, 431, and 440.

18   S&C Specification Bulletin 681-31


S&C Manual Vista® Underground Distribution Switchgear

80° COVER 8  ⁵⁄₈ (16) DIA. ANCHOR BOLTS


OPENING BY USER
ANCHOR BRACKET
BY S&C

P TANK OR CABINET

GASKET
BY S&C
1¹⁄₂ (38) MIN.
5 CONCRETE PAD
D (127)

SIDE VIEW ANCHOR BOLT DETAIL

Ratings

Model Short- I J K L M N P W
kV, Max Circuit, A,
RMS, Sym.

12 500 3 (76) 14ZZ\zn (373) 80M\zn (2043) 14M\, (377) 32C\zn (818) 7Z\x (191) 23ZC\zn (605) 102 (2591)
15.5
25 000 4 (102) 14ZZ\zn (373) 80M\zn (2043) 12Z\, (308) 35 (889) 7Z\x (191) 23Z\x (597) 102 (2591)

12 500 4 (102) 14ZZ\zn (373) 80M\zn (2043) 12Z\, (308) 35 (889) 7Z\x (191) 23Z\x (597) 102 (2591)
514
29
523
25 000 4 (102) 16Z\v (413) 90Z\zn (2288) 12M\, (327) 35 (889) 7Z\x (191) 23Z\x (597) 113 (2870)

12 500 4 (102) 16Z\v (413) 90Z\zn (2288) 12M\, (327) 35 (889) 7Z\x (191) 23Z\x (597) 113 (2870)
38
25 000 4 (102) 16Z\v (413) 90Z\zn (2288) 12M\, (327) 35 (889) 7Z\x (191) 23Z\x (597) 113 (2870)

12 500 3 (76) 7C\zn (183) 95M\zn (2424) 7C\, (187) 32C\zn (818) 10Z\x (267) 23ZC\zn (605) 102 (2591)
15.5
25 000 4 (102) 7C\zn (183) 95M\zn (2424) 4B\, (117) 35 (889) 7Z\x (191) 23Z\x (597) 102 (2591)

12 500 4 (102) 7C\zn (183) 95M\zn (2424) 4B\, (117) 35 (889) 7Z\x (191) 23Z\x (597) 102 (2591)
624
29
633
25 000 4 (102) 7B\, (194) 107B\zn (2726) 4Z\v (107) 35 (889) 7Z\x (191) 23Z\x (597) 113 (2870)

12 500 4 (102) 7B\, (194) 107B\zn (2726) 4Z\v (107) 35 (889) 7Z\x (191) 23Z\x (597) 113 (2870)
38
25 000 4 (102) 7B\, (194) 107B\zn (2726) 4Z\v (107) 35 (889) 7Z\x (191) 23Z\x (597) 113 (2870)

S&C Specification Bulletin 681-31   19