Вы находитесь на странице: 1из 6

Application of Battery Energy Storage in Wind

Penetrated Two Area Power System


S Zahid Nabi Dar Mairaj-ud-Din Mufti
Department of Electrical Engineering, Department of Electrical Engineering,
NIT Srinagar, J&K, India NIT Srinagar, J&K, India
Email: zahidnabi21@gmail.com Email: muftimd@yahoo.com

Abstract: In this paper, a Battery Energy Storage System (BESS) Different strategies and schemes are discussed in the literature
having a rating of 1 % of total plant capacity of 75 MW is utilized
based upon the availability of wind. Delta type of wind reserve
with a linearized two area power system infiltrated with 20% wind.
A linear DFIG model is constructed based on set point. A voltage
is established by deloading the power available from wind
source converter (VSC) is configured with IGBT and a two when abundant supply of wind is available. Normally the wind
quadrant chopper is employed for bidirectional power interface. farms operate at Maximum power point tracking (MPPT), but
The participation of wind turbines into automatic generation a wind power transfer from wind farm to grid during the state
control (AGC) system is made possible by addition of inertial of power imbalance might lead to voltage or frequency
control loop in wind turbine generators (WTGs). The inclusion of oscillations. This scenario suggests for a constrained operation
compact sized BESS helps in diminishing the peak overshoot in of wind farm, rather tracking MPPT, a fixed point called as set
frequency and tie power oscillations. Studies carried out in Matlab – point would be more economical and beneficial (1).The role
Simulink Environment, shows about 79 % decrease in frequency
of compact rated Flexible alternating current transmission
oscillations and the tie - power deviations get completely vanished.
system (FACTS) based energy storage system battery energy
storage system (BESS) is considered.
Keywords: wind power plants (WPPs), load frequency control
(LFC), doubly fed induction generator (DFIG), wind Turbine Among the various types of wind turbines our focus is on
generators (WTGs), battery energy storage system (BESS) doubly-fed induction generator (DFIG) based configuration,
being power house of wind industry as almost 50% wind
penetration into conventional system are DFIG based. In this
I. Introduction paper, a linearized power system without incorporation of any
nonlinearity such as governor dead band and steam reheat
For participating in primary, secondary and tertiary frequency constraints is considered. The focus is to integrate a BESS
control, a variable source wind turbine (VSWT) requires to be with this two area power system infiltrated with 20% wind.
made functional in suboptimal mode, in order to reserve During an event of contingency the balance of power amidst
certain amount of active power for supplying in the event of supply and demand is disturbed, the governing factor happens
frequency contingency. This is possible through wind turbine to be the total system inertia and the size of power imbalance
deloaded control. Primarily two types of control based on the measured by the rate of change of frequency (ROCOF).
reserve capacity inside the pitch and inertial kinetic energy
stored in the wind turbine blades is utilized. The pitch control The DFIG model utilized in this paper is constructed on the
employs derating of wind turbine to add the additional power, basis of model developed in (2). The system data is given in
whereas the inertial control is applied over short period by Appendix ‘A’ and the DFIG data is presented in Appendix ‘B’
generator torque control mechanism to replicate the For properly utilizing BESS in the power system the
conventional synchronous system behavior. application of simultaneous control is needed, wherein the
fundamental (inner) control loop targets at interchanging the
To counter a frequency dip due to any event, inertial control requisite power between the BESS and the network for
employing discharge of KE stacked in the rotating parts in enhanced dynamic power system operation. Analyzing the
wind turbine generators (WTGs) is divided into two groups response of the suggested scheme, a two area power system is
viz; frequency based inertial control (FBIC) and stepwise considered (2). The schematic diagram of DFIG is
inertial control (SIC). The performance of inertial response represented in figure 1 and of BESS in figure 2. Specifications
characteristics are governed by wind power penetration level that are utilized in integrating the BESS with an electrical
and the number of WTGs capable of providing inertial utility system are presented in Appendix ‘C’. The
support.
mathematical modeling for BESS and its complete design is
based on (3).
FIG 1. Inertial block diagram with frequency regulation incorporating wind turbine.

FIG 2. Configuration of BESS in Power System

II. Modeling of DFIG Pm is the mechanical power of prime mover in p.u;

A considerable amount of energy is available in fast rotating Pe is electrical power in p.u.


electrical generators and majority of this energy is present ΔP is the load generation mismatch
within the rotor blades as discussed in (4-5). The frequency The hidden inertia controller is `simply based on a control
mismatch condition can be depicted by the classical frequency loop which is added in the power converter controller. This
version of swing equation:- controller increases the WTGs electrical power output
significantly on occurrence of a frequency dip during the
2H df initial stages of disturbance, by generation of active power
 p m  p e  Δp control signal as represented by the below given equations:-
f 0 dt
df sys
Δp emu  2H emu f sys
Wherein, dt
H represents the inertia constant of generator, given in seconds (Wherein Hemu is the emulated inertia and fsys is represents the
is the rated value of frequency, system frequency
fo is the rate of change of frequency (ROCOF)
ΔPEmu depicts the additional control loop injected to the
reference signal Pref present within the back to back converters
of the WT. This virtual inertia is present in the closed loop
controllers in form gain, represented by a proportional transfer
function that can take any value. H emu is below the total WT
inertia and allows for a greater KE contribution with raising
values.
In scenarios of not requiring inertial support from wind farms
the inertial control loops incorporate a dead- band that enables
in stopping initializing of inertial response ,this further
enhances the machine lifetime by lessening the effects of
friction by constant wear and tear.(6-8)

III. SIMULATION STUDIUES


It can be seen from figures 3 and 4 there is about 79%
reduction in peak overshoot with incorporation of DFIG based
WTGs when a step load disturbance of 0.01 and –0.01 is
applied at interval of 20 and 80 seconds.From figure 5 it is
Observed with incorporation of BESS there is no deviation in
tie power oscillations. Figure 6 represents the area control error
(ACE).Figure 7 represents the deviation in battery voltage
when it is introduced to a load disturbance profile as given in
Figure 8.
Fi
Fig. 4. Area 2 with and without WTG and BESS

.
Fig 5. Tie- power deviation with and without DFIG
Fig. 3. Area 1 with and without WTG and BESS
Fig 6. ACE with and without DFIG Fig 8. Load disturbance

VI. CONCLUSION

A linear DFIG Model based upon set point was developed. The
integration of the WTGs based on these plans was introduced to a
two area linear model of load frequency controller. An additional
integration of a compact sized battery whose Power Conditioning
System (PCS) is rated just 1% of the total plant capacity of 75MW
delivered about 79% reduction in LFC characteristics and the
deviation in tie-power is completely eliminated. The role of BESS is
seen from figure 7 when there is 300 volts change in BESS voltage
on occurrence of perturbation. Further incorporation of this compact
rated system to a pragmatic power system with Wind penetration
would lead to reliable and improved sustainable power.

Appendix ‘A’: System Data

He1=He2=3.5 p.u.MW.sec

KP1= KP2=62 Hz / (p.u.)

TP1= 10S
Fig 7. Battery Voltage

TP2=15S

TT1=TT2=1
Thi=Th2=0.1
1. Chang-Chien L R, Sun CC and Yeh Y J (2014) ‘”.Modeling
of Wind- Farm participation in AGC” IEEE Transactions
R1=R2= 3Hz/ (p.u.MW) on Power Systems.Vol.29,No.2 ,pp.1204-1211

2. Dar, S.Z.N. and Mufti, M. D. (2017a) “Enhanced load


B1=B2=0.05(p.u.MW/radian) frequency control response with integration of Supervisory
controlled superconducting magnetic energy storage system
T12=0.07(p.u..MW/Hz) in wind penetrated two- area power systems “ International
Journal of Wind Engineering” Vol. 41, No. 5 ,pp.330-342.
Appendix ‘B’: DFIG data
3. Dar, S.Z.N. and Mufti, M. D. (2017b) ‘Analysis of two
Kwi1=0.1 area power system with battery energy storage, “2nd
International Conference for Convergence in Technology
(I2CT)” ,pp.915-919.
Kwp1=1.58
4. Fischer, M., Engelken, S., Mihov, N., et al.(2014):
Kwi2=0.1 “Operational Experiences with Inertial Response Provided
by Type 4 Wind Turbines” IET Renewable Power
Generation, 2016, Vol. 10, No 1, pp. 17 –24
Kwp2=1.61
5. Rutledge L, Flynn D (2015) “ Emulated inertial
Ta1= Ta2=0.2 Sec
response from wind turbines: gain scheduling
Tr1= Tr2=0.1 Sec and resource co-ordination” IEEE Transactions on
Power Systems Vol 31 No 5 pp 31(5):3747–3755
Th1= Th2=0.1 Sec

Tt1= Tt2=1 Sec 6. Tarnow ski C. “Coordinated frequency control of wind


turbines in power systems with high wind power
penetration,” PhD thesis, Technical University of Denmark,
Tw1= Tw2=6 Sec 2012

Appendix ‘C’: Battery Data


7. Van de Jan V, Jeroen DMD, Bart M et al (2016) “Droop
Maximum Battery voltage = 4800 V dc control as an alternative inertial response strategy for the
synthetic inertia on wind turbines”. IEEE Trans Power
Initial Battery Voltage = 2200 V dc System Vol 31 No 12 pp 1129-1138

BESS unit rating= (750KW (1% of 75MW)


8. 8 F. Teng and G. Strbac (2016), “Assessment of the role
C BP  52597 and value of frequency response support from wind plants”
IEEE Trans. Sustain. Energy,Vol.7,No. 2, pp. 586–595,
C B1  1F
R BAT  0.0167
TBP  0.005sec
R BP  10KΩ
R B1  0.001Ω
R BS  0.013
L  (1/1000)
K P  0.1254(proporitional  gain)
K I  4.98745(integral  gain)

References

Вам также может понравиться