No DESCRIPTION UNIT QTY


A ELECTRICAL HIGH SIDE WORKS
Erection,Testing & Commissioning of Outdoor type No 1
1 11KV/415V, 2500KVA Transformer with OLTC, RTCC
Panel.
4Cx2.5sqmm YWY UG Cable including Termination and Mtrs 100
2 JBs (Make:Havells/Polycab/Universal/FortuneArt)
6Cx2.5sqmm YWY UG Cable including Termination and
3 Mtrs 100
JBs (Make:Havells/Polycab/Universal/FortuneArt)
16Cx2.5sqmm YWY UG Cable including Termination and
4 Mtrs 100
JBs (Make:Havells/Polycab/Universal/FortuneArt)
Laying of 25 x6 mm Copper Flat on DMC Insulator Mtrs 60
5 supports for LA's earthing.
Providing of Pipe electrode Earth pits with 100mm Nos 12
6 dia .C.I Pipe of length 2.5m long including suppiying of
alternate layers of salt&Charcoal etc
Providing of Plate Earth pits with 100mm dia .C.I Pipe of Nos 2
length 2.5m long, 600'x 600 x3.15mm Copper Plate with
50 x 6mm cu Flat including suppiying of alternate
7 layers of salt&Charcoal etc

Laying of 100x16mm Hot dip galvanised Flat for body Mtrs 60


8 earthing of the Equipments
Laying of 75x6mm Hot dip galvanised Flat for body Mtrs 80
9 earthing of the Equipments
Laying of 50x6mm Hot dip galvanised Flat for body Mtrs 100
10 earthing of the Equipments
Laying of 100x10mm COPPER Flat for body Neutral Mtrs 25
11 earthing of the transformer
B BUS DUCT

Installation, testing and comissioning of following TPN


busducts in sandwich construction of aluminium bus
bars with expansion joints, fire barriers including
necessary supports and ventilation arrangement ,
fabricated from GI sheet and with approved paint shade
1 as per technical specification including Al earthing
conductor throughout the length of the bus duct based
on bus duct. (Quoted rates shall be inclusive of all
necessary arrangement for Horizontal/ Vertical bends,
flang end provision, adpt box, expention joints, rub blw,
ph change over, fixing & bends etc.)

Page 1
RATE (Rs) AMOUNT(Rs)

Page 2
S.No DESCRIPTION UNIT QTY
4000 Amps TPN Al bus duct (65 KA) as described above
a and as per technical specification.(from transformer to Rmt 35
LT kiosk & LT Kioskto main panel)

3200 Amps TPN Al bus duct (50 KA) as described above


b and as per technical specification.(from syncronizing Rmt 50
panel to main panel

4000 Amps copper flexible end connection as per


c technical specification for Transformer, LT kiosk & Main Nos 4
Panel.

3200 Amps copper flexible end connection as per


4 technical specification for Syuchronization Panel & Nos 2
Main Panel.

2 SANDWICH CONSTRUCTION RISING MAINS

Installation, testing and commissioning of following


rising mains in sandwich construction of aluminium bus
bars with tap-off connection points at every 1000 mm
intervals, expansion joints, fire barriers including
necessary support and louvers for ventilation, fabricated
out of GI sheet painted with approved paint shade
including 2 Nos. of suitable size of Aluminium earthing
conductor throughout the length of the rising mains as
per technical specification. (Thrust pad shall be
provided for each rising main for necessary support to
rising main and to prevent the bus bar expansion in
downward direction, also provide end cover to close
the end of rising main and to provide extra end
supports to the bus bars. (Quoted rates shall be
inclusive of all necessary arrangement for Horizontal/
Vertical bends, flang end provision, end cover, fixing,
bends etc.) Item to include necessary Rising mains
supports one coat primer & two coats painting

2000 Amps TPN(50 KA) Rising mains for Raw Power of


a Rmt 130
phase-1 floors. ( 2 runs)

Page 3
RATE (Rs) AMOUNT(Rs)

Page 4
S.No DESCRIPTION UNIT QTY
1000 Amps TPN(50 KA) Rising mains for UPS Power of
b Rmt 70
phase-1 floors.( 1 run)

3 TAP OFF BOX


Installation, testing and commissioning of tap off boxes
made out of 14 gauge GI sheet duly painted for
mounting on the rising mains including providing and
fixing of following MCCB’s.

630 Amps TPN MCCB (36 KA) (for raw power of


a Nos 3
Basemnet-1 2Nos & second floor 1No)

400 Amps TPN MCCB (36 KA) (for raw power of


b Nos 3
basement-2 1 No, Ground floor 1No & First floor 1 No)

160 TPN Amps MCCB (36 KA) (for raw power of Third
c Nos 1
floor 1no)

125 TPN Amps MCCB (36 KA) ( (for raw power of Fourth
d Nos 2
floor 1no & for fifth fllor 1 no)

400 Amps TPN MCCB (36 KA) (for ups power of Second
e Nos 1
floor 1 No)

f 200 TPN Amps MCCB (36 KA) (for ups power of First Nos 1
floor 1no)

160 TPN Amps MCCB (36 KA) ( (for ups power of


g Nos 2
Basement-1 1no & for ground floor 1 no)

100 TPN Amps MCCB (36 KA) ( (for ups power of each 1
h no of tap off box of Basement-2, third, Fourth & fifth Nos 4
floors 1 no)
C ELECTRICAL PANELS

Page 5
RATE (Rs) AMOUNT(Rs)

Page 6
S.No DESCRIPTION UNIT QTY

Installation, Testing and Commissioning of 3 phase and


Neutral 415V, 4 wire , Free Standing Floor mounted MV
Panel made out of 14 SWG MS sheet after seven tank
process and painting with Epoxy powder coating. The
panel shall consist of suitable rating TPN Aluminium
busbar supported with DMC/ SMC barriers and color
coded with Heat shrinkable sleeves. The Metering shall
be provided as specified. The panel shall have Short
circuit withstanding capacity consist of the switchgear
as mentioned below. The panel shall be got fabricated
from manufacturers with CPRI Test certificate only. . The
size of all Panel Mounting Meters shall be 96X96mm.
The Panels shall be mounted on U channels including
supply and fixing of the same. Every ACB/ MCCB shall be
provided with ON/OFF/TRIP, Indication lamps of LED
type. For all Electrically operated Breakers, Local
Remote Selector switches shall be provided for
controlling the Breakers remotely. The Panel is to be
installed in Indoor.

1 MAIN PANEL Nos 1


EB Incoming :
3200A,65KA 4P EDO, ACB with O/C, S/C,U/V,E/L
Thermal Magnetic Based Release – 2 no
DG Incoming :
3200A,65KA 4P EDO, ACB with O/C, S/C,U/V,E/L
Thermal Magnetic Based Release – 2 no
2 HVAC PANEL-1 Nos 1
1600A,50KA 3P MDO, ACB with O/C, S/C,U/V,E/L
Thermal Magnetic Based Release– 1 Nos
3 FLOOR PANEL Nos 1
2000A,50KA 3P MDO, ACB with O/C, S/C,U/V,E/L
Thermal Magnetic Based Release– 1 Nos
4 UTILITY PANEL Nos 1
Incoming: 630A,50KA 4P MCCB with O/C, S/T Thermal
Magnetic Based Release-1 No
5 APFC PANEL(700 KVAR) Nos 1
1600A,50KA 3P MDO, ACB with O/C, S/C,U/V,E/L
Thermal Magnetic Based Release– 1 Nos

Page 7
RATE (Rs) AMOUNT(Rs)

Page 8
S.No DESCRIPTION UNIT QTY
6 LIFT PANEL Nos 1
Incoming: 320 A,50KA 3P MCCB with O/C,S/C,E/L
Thermal Magnetic Based Release - 1 No
7 UPS PANEL Nos 1
800A,50KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos
8 GROUND FLOOR LEFT WING PANEL Nos 1
400A,36KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos
9 GROUND FLOOR RIGHT WING PANEL Nos 1
100A,25KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos
10 GROUND FLOOR UPS LEFT WING PANEL Nos 1
160A,25KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos
11 GROUND FLOOR UPS RIGHT WING PANEL Nos 1
100A,25KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos
12 FIRST FLOOR LEFT WING PANEL Nos 1
400A,36KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
13 FIRST FLOOR RIGHT WING PANEL Nos 1
200A,25KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
14 FIRST FLOOR UPS LEFT WING PANEL Nos 1
200A,25KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
15 FIRST FLOOR UPS RIGHT WING PANEL Nos 1
100A,25KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
16 SECOND FLOOR LEFT WING PANEL Nos 1
630A,36KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
17 SECOND FLOOR RIGHT WING PANEL Nos 1
160A,25KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
18 SECOND FLOOR UPS LEFT WING PANEL Nos 1
400A,36KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
19 SECOND FLOOR UPS RIGHT WING PANEL Nos 1

Page 9
RATE (Rs) AMOUNT(Rs)

Page 10
S.No DESCRIPTION UNIT QTY
200A,25KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
20 THIRD FLOOR LEFT WING PANEL Nos 1
160A,36KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
21 THIRD FLOOR RIGHT WING PANEL Nos 1
100A,25KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
22 THIRD FLOOR UPS LEFT WING PANEL Nos 1
100A,36KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
23 THIRD FLOOR UPS RIGHT WING PANEL Nos 1
100A,25KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
24 FOURTH FLOOR PANEL Nos 1
125A,36KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
25 FOURTH FLOOR UPS PANEL Nos 1
100A,25KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
26 FIFTH FLOOR PANEL Nos 1
125A,36KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
27 FIFTH FLOOR UPS PANEL Nos 1
100A,25KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
28 BASEMENT-1 FLOOR LEFT WING PANEL Nos 1
1000A,36KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
29 BASEMENT-1 FLOOR RIGHT WING PANEL Nos 1
630A,25KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
30 BASEMENT-1 FLOOR UPS LEFT WING PANEL Nos 1
160A,36KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
31 BASEMENT-1 FLOOR UPS RIGHT WING PANEL Nos 1
100A,25KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
32 BASEMENT-2 FLOOR LEFT WING PANEL Nos 1
400A,36KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.

Page 11
RATE (Rs) AMOUNT(Rs)

Page 12
S.No DESCRIPTION UNIT QTY
33 BASEMENT-2 FLOOR RIGHT WING PANEL Nos 1
200A,25KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
34 BASEMENT-2 FLOOR UPS LEFT WING PANEL Nos 1
100A,36KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
35 BASEMENT-2 FLOOR UPS RIGHT WING PANEL Nos 1
100A,25KA 3P MCCB with O/C, S/C,U/V,E/L Thermal
Magnetic Based Release– 1 Nos.
D MV CABLES:
Laying and commissioning of following size 1.1KVgrade
XLPE PVC insulated armoured Aluminium conductor
a
cable, neatly dressed & clamped to existing cable
trays/Trench.
1 3.5CX300 SQMM XLPE AL.AR.CABLE Rmt 490
2 3.5CX240 SQMM XLPE AL.AR.CABLE Rmt 300
3 3.5CX185 SQMM XLPE AL.AR.CABLE Rmt 220
4 3.5CX150 SQMM XLPE AL.AR.CABLE Rmt 210
5 3.5CX120 SQMM XLPE AL.AR.CABLE Rmt 110
6 3.5CX95 SQMM XLPE AL.AR.CABLE Rmt 480
7 3.5CX70 SQMM XLPE AL.AR.CABLE Rmt 220
8 3.5CX50 SQMM XLPE AL.AR.CABLE Rmt 170
9 3.5CX35 SQMM XLPE AL.AR.CABLE Rmt 770
10 3.5CX25 SQMM XLPE AL.AR.CABLE Rmt 80
11 4CX16 SQMM XLPE AL.AR.CABLE Rmt 3000
12 3CX 95SQMM XLPE AL.AR.CABLE Rmt 50
13 3CX 70SQMM XLPE AL.AR.CABLE Rmt 170
14 3CX 50SQMM XLPE AL.AR.CABLE Rmt 50
15 3CX 35SQMM XLPE AL.AR.CABLE Rmt 320
16 3CX 25SQMM XLPE AL.AR.CABLE Rmt 220
17 3C X 2.5 Sq.mm PVC AL.AR.CABLE Rmt 4200

Laying and commissioning of following size 1.1KVgrade


PVC insulated armoured copper conductor cable, in
b built up cable trench/ / on cable tray with all installation
materials.
1 4C X 10 Sq.mm PVC CU.AR.CABLE Rmt 780
2 4C X 6 Sq.mm PVC CU.AR.CABLE Rmt 320
3 4C X 4 Sq.mm PVC CU.AR.CABLE Rmt 180
4 4C X 2.5 Sq.mm PVC CU.AR.CABLE Rmt 2870
c MV CABLE TERMINATIONS:

Page 13
RATE (Rs) AMOUNT(Rs)

Page 14
S.No DESCRIPTION UNIT QTY

Providing Indoor ordinary end terminations for the


cable specified above with compression type steel
gland,Bi-metallic lugs using crimping tool,Insulation
tape,Identification tags etc., including end termination
and Earthing of Gland with 8SWG 'GI Wire

1 3.5CX300 SQMM XLPE AL.AR.CABLE Nos 36


2 3.5CX240 SQMM XLPE AL.AR.CABLE Nos 12
3 3.5CX185 SQMM XLPE AL.AR.CABLE Nos 14
4 3.5CX150 SQMM XLPE AL.AR.CABLE Nos 12
5 3.5CX120 SQMM XLPE AL.AR.CABLE Nos 8
6 3.5CX95 SQMM XLPE AL.AR.CABLE Nos 26
7 3.5CX70 SQMM XLPE AL.AR.CABLE Nos 10
8 3.5CX50 SQMM XLPE AL.AR.CABLE Nos 8
9 3.5CX35 SQMM XLPE AL.AR.CABLE Nos 34
10 3.5CX25 SQMM XLPE AL.AR.CABLE Nos 4
11 4CX16 SQMM XLPE AL.AR.CABLE Nos 210
12 3CX 95SQMM XLPE AL.AR.CABLE Nos 4
13 3CX 70SQMM XLPE AL.AR.CABLE Nos 16
14 3CX 50SQMM XLPE AL.AR.CABLE Nos 4
15 3CX 35SQMM XLPE AL.AR.CABLE Nos 28
16 3CX 25SQMM XLPE AL.AR.CABLE Nos 8
17 3C X 2.5 Sq.mm PVC AL.AR.CABLE Nos 352
18 4C X 10 Sq.mm PVC CU.AR.CABLE Nos 48
19 4C X 6 Sq.mm PVC CU.AR.CABLE Nos 16
20 4C X 4 Sq.mm PVC CU.AR.CABLE Nos 10
21 4C X 2.5 Sq.mm PVC CU.AR.CABLE Nos 188

E CABLE TRAY

Installation of following size 2mm thick GI Perforated


type cable tray with coupler plates, bends, elbows, tees
etc as required. The scope also includes suitable cable
tray supports arrangements on walls/Ceiling/Trench
with M.S.Structrual steel / Threaded rods, anchor bolts
& nuts wherever required as per site conditions.

1000 mm wide x 50 mm deep x 2 mm thick Rmt 180


600 mm wide x 50 mm deep x 2 mm thick Rmt 550
300 mm wide x 50 mm deep x 2 mm thick Rmt 950
150 mm wide x 50 mm deep x 2 mm thick Rmt 350
F EARTHING

Page 15
RATE (Rs) AMOUNT(Rs)

Page 16
S.No DESCRIPTION UNIT QTY

Installation of G.I. Earth station, with 40mm dia


2500mm long GI pipe including construction of brick
pedestal, providing meshed funnel,CI cover and other
1 No 48
civil Engineering works,spreading a homogenous
mixture of salt, charcoal aroundthe pipe etc, completely
as per IS 3043, 1987 or latest revision.

Installation of Copper Earth station, with


600X600X3.15mm Copper plate at 2500mm depth
including construction ofbrick pedestal, providing
2 meshed funnel,CI cover and other civil Engineering No 48
works, spreading a homogenous mixture ofsalt,charcoal
around the pipe etc,completely as per IS3043,1987 or
latest revision.

3 Laying of following earth strips/ conductors.


50 x 6 MM GI Flat Rmt 1200
25 x 6 MM GI Flat Rmt 3800
25 x 6 MM Cu Flat Rmt 3300
1C x 10Sqmm PVC Insulated Flexible Copper Rmt 850
Cable(Green)
G STREET POLE

Supply and Installation of Swaged tublar steel pole 7


meter long with base plate, 1 meter reach
bracket,earthing studs, 3 phase and neutral loop-in and
loop-out box as per specifications, and The pole inside Nos 40
shall be consisting of 6A MCB with 4 ploe 16A
connector. The wiring from Junction box to Light fixture
shall be carried out with 3 core 1sq.mm flexible copper
cable.

H SAFETY ITEMS
Installation,Testing and commissioning of the Following
Safety and Fire fighting accessories as per standards and
specification
Fire Extinguishers - 4.5 KG CAPACITY CO 2 Confirming to
1 IS 2878 fitted with discharge bend pipe and horn fitted Nos 20
on wall
2 Rubber Mats 11 KV, 2 m x 1 m Nos 4
3 Rubber Mats 415 V, 2 m x 1 m Nos 40
4 Shock treatment Chart with wooden frame and glass Nos 4
5 First Aid Box Nos 16

Page 17
RATE (Rs) AMOUNT(Rs)

Page 18
S.No DESCRIPTION UNIT QTY
Sand Bucket with stand with 3 Nos of buckets with
6 set 2
canopy
7 415 V Danger Boards Nos 40
8 11 KV Hand Gloves set 8

I LIGHTING PROTECTION

Installation of Early Streamer Emission Lighting


Protection Device and Strike Counter with protection
radius of 72 Mtrs at level-3 Suitable to mount on the
1 Nos 2
terrace of the Building with 75NB GI tubular structure of
3m/4m Height, complete with masonary pedestal and
other installation items for structural requiements.

Laying under ground/above ground of following size


strips including all necessary interconnections between
2 earth station and equipments including earth
excavation, back filling, intermediate supports for strips
as applicable and directed by engineer in charge.

Laying of 1C x 70 Sq.mm PVC flexible copper conductor


3 Rmt 200
cable.(Green).

Installation of maintenance free earthing which consists


of 50 mm Dia ,Standard length (as per Equipment
Supplier ) electrode capsule,filled with earth enhancing
4 compound,sealed at both ends and brazed lead for Nos 4
connection at one end .Bentonite compound up to a
depth of 2.0 mtr around the electrode capsule and also
wih brick chamber and cast Iron cover etc complete.

Page 19
RATE (Rs) AMOUNT(Rs)

Page 20