Академический Документы
Профессиональный Документы
Культура Документы
CM 579
Coupler Profinet
© ABB Group
October 22, 2010 | Slide 1
AC500 PROFINET
Description
© ABB Group
October 22, 2010 | Slide 2
PROFINET IO RT
(Processed Fieldbus Ethernet)
PROFINET IO RT Features
Standardization organization IEC 61158
Nomenclature: Controller (Master) / Device (Slave)
Bus Topologies: Bus, Star, Tree
No direct Slave to Slave communication possible
Limitation is 65536 Slots with 65536 subslots (if supported by stack)
Ethernet over PROFINET IO RT possible
Device description (GSDML) based on xml standard
PROFINET IO RT Hardware Components
Controller can be a standard Ethernet Controller (but not IRT!)
Device needs special hardware
Standard switch components possible for RT
PROFINET IO IRT
Solution only available from Siemens at present
© ABB Group
October 22, 2010 | Slide 3
AC500 PROFINET
Topologies (1)
© ABB Group
October 22, 2010 | Slide 4
AC500 PROFINET
Topologies (2)
© ABB Group
October 22, 2010 | Slide 5
AC500 PROFINET
AC500 PROFINET Devices (1)
IO Controller
CM579-PNIO communication module
Internal Ethernet switch with 2 ports
Transfer rate 10/100 MBit/s, full duplex
Protocol PROFINET IO
Maximal 128 IO Devices
5 status LEDs, some bicolored
2 rotary switches for address setting (not used)
© ABB Group
October 22, 2010 | Slide 6
AC500 PROFINET
AC500 PROFINET Devices (2)
IO Device CI 501-PNIO
Decentralized IO Device with own I/O channels
4 analog inputs 12 Bit + sign
2 analog outputs 12 Bit + sign
8 digital inputs
8 digital outputs
Extension with up to 10 IO Modules
Electrical connection with S500 Terminal Units TU507-RT-ETH
or TU 808-RT-ETH
© ABB Group
October 22, 2010 | Slide 7
AC500 PROFINET
AC500 PROFINET Devices (3)
IO Device CI 502-PNIO
Decentralized IO Device with own I/O channels
8 digital configurable inputs/outputs
8 digital inputs
8 digital outputs
Extension with up to 10 IO Modules
Electrical connection with S500 Terminal Units TU507-RT-ETH
or TU 808-RT-ETH
© ABB Group
October 22, 2010 | Slide 8
AC500 PROFINET
PROFINET RT
Data Exchange, Diagnosis
Data exchange is provided by automatically
created operands
Diagnosis is provided by Function Blocks
VE name Function
PNIO_DEV_ALARM Provide arising diagnostic information about a certain device
PNIO_DEV_DIAG Provide diagnostic information of a certain PROFINET IO Device
PNIO_DEV_INFO Provide general information of a certain PROFINET IO Device
PNIO_DEV_SPECIFIER Display the PNIO_DEV_ALARM SPECIFIER in plain text
PNIO_IM0 Provide access to the identification and maintenance information of
a certain device
PNIO_STATE Provide general information about the condition of a certain
PROFINET bus
PNIO_SYS_DIAG Provide in detail information about the condition of a certain
PROFINET bus
© ABB Group
October 22, 2010 | Slide 9
AC500 PROFINET
Configuration
Configuration in ABB Configurator
2. Choose “CM579-PNIO”
© ABB Group
October 22, 2010 | Slide 10
AC500 PROFINET
Configuration
© ABB Group
October 22, 2010 | Slide 11
AC500 PROFINET
Configuration
© ABB Group
October 22, 2010 | Slide 12
AC500 PROFINET
Configuration
Configuration in ABB Configuration
4. Choose Your slave in list
Insert different I/O or slave module.
© ABB Group
October 22, 2010 | Slide 14
AC500 PROFINET
Configuration
Implement Standard I/O module
8. Choose Your I/O extension in list
© ABB Group
October 22, 2010 | Slide 15
AC500 PROFINET
Configuration
Configure Slave module
9. Double click on you slave and configure
the signal.
© ABB Group
October 22, 2010 | Slide 17
© ABB Group