TGB & TMGB Ground Busbars

Meets Specifications of TIA/EIA 607 and


Conforms to BICSI Recommendations
Applications:
With the increasing demand for computer network installations, the TMGB and the TGB should be continuous and run in the
proper telecommunications grounding and bonding is critical most direct path possible. Often, the TGB is installed to the
to ensure proper systems operation. The sensitivity of the side of the panelboard. When the buildingÕs structural steel
electronic equipment requires that the telecommunications is effectively grounded, each TGB should be bonded to the
cabling and power be effectively equalized to prevent loops steel within the same room with a No. 6 AWG conductor.
or transients that can damage the equipment. This requires Exothermic welding is recommended for these connections.
designing a complete grounding and bonding system that Always use the shortest distance possible in the grounding
goes beyond the basic Ògreen wireÓ methodology. system.
In general, a telecommunications grounding system contains Features:
the following components: telecommunications bonding ¥ Complete offering of Telecommunications Main
conductor, telecommunications main grounding busbar Grounding Busbar (TMGB) & Telecommunications
(TMGB), telecommunications bonding backbone (TBB), Grounding Busbar (TGB) for central bonding of
telecommunications grounding busbar (TGB), and the telecommunications equipment
telecommunications bonding backbone interconnecting
¥ Electro-tin plated busbar provides superior connections by
bonding conductor (TBBIBC).
lowering contact resistance and minimizes requirements
The TMGB is the dedicated extension of the building for cleaning
grounding electrode system for the telecommunications ¥ UL & cUL Listed to UL467 & C22.2 respectively
infrastructure. Because it is the central attachment point for ¥ Stainless steel brackets and fasteners provide superior
TBBs and equipment, the TMGB should provide easy corrosion resistance
access for telecommunications personnel. The TGB centrally
connects systems and equipment served by a telecommuni- ¥ Insulated standoffs provide busbar isolation
cations closet. Both the TMGB and the TGB are electro-tin ¥ Splice plates for both TGB and TMGB busbars allow
plated to ensure low resistance corrosion free contact between for future expansion or the use of multiple smaller
the lugs and the busbars. The bonding conductor between lengths to be used to meet system requirements

www.erico.com
TGB Ground Busbars
SPECIFICATIONS PART NUMBER

TGB-A29L18PT

TGB-A25L14PT

TGB-A20L12PT

TGB-A18L10PT

TGB-A16L08PT

TGB-A14L06PT

ERICO’S coordinated approach to facility protection - CADWELD, CRITEC, ERITECH


TMGB Ground Busbars
SPECIFICATIONS PART NUMBER

TMGB-A29L41PT

TMGB-A25L33PT

TMGB-A20L27PT

TMGB-A18L23PT

TMGB-A16L19PT

TMGB-A14L15PT

ERICO’S coordinated approach to facility protection - CADWELD, CRITEC, ERITECH


ERITECH TGB & TMGB Ground Busbars
SPECIFICATIONS PART NUMBERING SYSTEM
Materials T G B

Busbars: ERICO
TELECOMMUNICATION
- 6mm (1/4Ó) thick Copper GROUND BAR
L P
DESIGNATION
- ASTM B187-C11000 T M G B
PIG TAIL LENGTH FT. (BLANK IF NONE)
- Electro-tin plated ERICO A=1 E=5 J=9 N = 16 S = 24 W = 32
TELECOMMUNICATION B=2 F=6 K = 10 P = 18 T = 26 X = 34
Insulators: MAIN GROUND BAR
DESIGNATION
C=3
D=4
G=7
H=8
L = 12
M = 14
Q = 20
R = 22
U = 28
V = 30
Y = 36
Z = 38
- Manufactured of rugged polyamide, an
environmentally friendly, halogen-free CONFIGURATION ERICO CABLE CODE (BLANK IF NONE)
A = INSULATOR & BRACKET
nylon material which is reinforced with C = NONE (BAR ONLY) 1K = #4 SOL 2Q = 4/0 CONC
glass fiber LENGTH
(ROUND UP TO
1T = #2 SOL TIN
2C = 1/0 CONC
2V = 250KCM CONC
3D = 350KCM CONC
- 51mm (2Ó) standoff height NEAREST INCH) NUMBER
OF PAIRS OF
2G = 2/0 CONC
2L = 3/0 CONC
3Q = 500KCM CONC
4L = 750KCM CONC
- Meet the requirements of UL 94 VO 5/16" HOLES
T = TINNED
for self-extinguishing materials (BLANK IF NONE)

Brackets:
- Type 304 Stainless Steel
- 3mm (1/8Ó) thick
Fasteners:
- Type 304 Stainless Steel

ORDERING INFORMATION
Part Number Size (in) Length (in) Pairs of Pairs of
5/16” Holes 7/16” Holes
TGB - A29L18PT 1/4 x 2 29 18 5
TGB - A25L14PT 1/4 x 2 24-1/2 14 5
TGB - A20L12PT 1/4 x 2 20 12 3
TGB - A18L10PT 1/4 x 2 17-3/4 10 3
TGB - A16L08PT 1/4 x 2 15-1/ 2 8 3
TGB - A14L06PT 1/4 x 2 13-1/4 6 3

TMGB - A29L41PT 1/4 x 4 29 41 5


TMGB - A25L33PT 1/4 x 4 24-1/2 33 5
TMGB - A20L27PT 1/4 x 4 20 27 3
TMGB - A18L23PT 1/4 x 4 17-3/4 23 3
TMGB - A16L19PT 1/4 x 4 15-1/2 19 3
TMGB - A14L15PT 1/4 x 4 13-1/2 15 3

TGB - SPLICEKIT Includes plates and fasteners for splicing two TGB busbars
TMGB - SPLICEKIT Includes plates and fasteners for splicing two TMGB busbars
Due to the ERICO philosophy of continuous product development,
specifications are subject to change without notice.

USA/Canada ph: 1-800-677-9089 or 1-440-248-0100 fax: 1-800-677-8131 Chile ph: 56-2-624-4004 fax: 56-2-624-4006
Mexico ph: 52-5-260-5991 fax: 52-5-260-3310
www.erico.com
G280S G551LT00 01215M0 ©2000 ERICO, Inc. Printed in U.S.A