Introduction
4
Introduction to the construction and the types of materials specified by BS6883 which deals with cables suitable for offshore
installations, ships and hazardous areas.
5
6 Cable Range
Instrumentation Cable
1. 150/250 V pairs and triples 0.75-1.5mm2 through to 37pr and 1-12 triples
7 Individually Screened
Collectively Screened
8 Unbraided
Steel or Phosphor Bronze Braided
N.B. 1.5mm2 BS6883: 1991 only
9
Power & Control Cables
10 2. 600/1000 V single-core to thirty seven core.
Unarmoured or steel, phosphor bronze or copper wire braided.
3. 1.9/3.3 kV, 3.3/3.3 kV, 3.8/6.6 kV, 6.6/6.6 kV and 6.35/11 kV un-screened, single and three core Steel or Phosphor
11 bronze braided.
4. 3.8/6.6 kV, 6.35/11 kV and 8.7/15 kV.
12 Screened, single and three core.
Unarmoured or steel, or phosphor bronze wire braided.
13 Construction
Conductors
14 Stranded metal coated copper conductors complying with BS EN 60228 for Class 2 or Class 5. Anixter can also supply Class 2
flexible on sizes of 6sqmm and above.
15 Insulation
Material shall comply with the requirements of BS7655 for type GP4 and shall have Halogen Acid Gas Emission levels equal to,
16 or lower than, that of the sheath material where specified.
Sheath
17 Where a cable has both an inner and outer sheath, the class of sheathing material shall be identical (except on FS types).
18
19
20
Armour
3
Single-cores - phosphor bronze wire braid or tinned copper wire braid.
Multicore - galvanised steel wire braid.
The braid on single-core cables intended for use on a.c. circuits shall consist of tinned annealed copper wires or tinned 4
phosphor bronze wires.
Bronze wires to BS EN 12166.
5
Copper wires to BS EN 13602.
Steel wires to BS EN 10257-1.
6
Cable Legend
The following information shall be printed or embossed on the outer surface of all cables.
7
a) The number of the B.S. (where applicable).
b) Sheath class i.e. Type SW4 (where applicable). 8
c) No and c.s.a. of conductors.
d) Voltage rating.
9
e) Manufacturers name.
f) IEC rating (i.e. IEC 60332-3A).
g) UKOOA Code (where applicable). 10
11
12
13
14
15
16
17
18
19
20
16
17
18
19
20
Armour
3
Material for wire braid shall consist of galvanised mild steel, tinned bronze or tinned annealed copper wires. The steel wires
shall comply with BS EN 10257-1, the bronze wires with BS EN 12166, and the copper wires with BS EN 13602.
4
Cable Marking
A means of identifying the manufacturer shall be provided throughout the length of all cables.This may be done by coloured
5
threads, printed tapes, printing or embossing of the outer surface. If coloured threads are used, the colours shall comply with
manufacturers name. The printing or embossing on the outer sheath must include as a minimum the manufacturers name
and voltage grade. 6
Cable Characteristics
7
Insulation Bedding & Sheath
EPR SW1 SW2 SW3 SW4
8
Oxygen index (minimum) 23 32 32 30 30
3m cube smoke emission test N/A N/A N/A Pass Pass
9
HCL emission at 800°C <0.5% N/A <5% <0.5% <0.5%
10
11
12
13
14
15
16
17
18
19
20
15
16
17
18
19
20
These products are common in the manufacture of cables used on oil rigs, oil platforms, ships, etc. With the high risk of fire in
3
these environments, the behaviour of cables is of prime importance.
When most standard cables are subjected to flames, the basic effects are no different to any other products manufactured of 4
similar materials.
5
Generally the following happens:
The flames will gradually spread, smoke and gases will be generated and eventually the cable will breakdown electrically
and be severely damaged or destroyed. The resultant effects of these hazards endanger life and hinder rescue and fire 6
fighting services.
7
The main fire performance requirements are:
Flame Retardancy 8
The ability to slow down the spread of flames along the cable.
9
Low Smoke Emission
The importance of personnel being able to see, in order to evacuate an area, and the fire-fighters having access to get to the
seat of the fire. 10
14
15
16
17
18
19
20
6
Application
7
Unarmoured cable for use where mechanical protection is not required for fixed wiring in ships and in mobile and fixed
offshore units (e.g. drilling rigs, oil platforms, etc.).
8
9 Specifications
• In accordance with BS6883 • Oxygen index >32% Temperature index 250°C, HCL
10 • Conductor: Tinned annealed copper conductor. emission <0.5% of weight of compound @ 800°C
Stranded to BS EN 60228 Class 2 • Flame retardant to IEC60332-3-22 Category A
11 • Insulation: EPR complying with BS7655 GP4 (reduced propagation)
• Sheath: LSZH to BSS7655 section 2.6 Type SW4. • Temperature Rating: 90°C maximum conductor
Enhanced oil resistance, low smoke zero halogen, operating temperature
12
minimum tear resistance • Voltage Rating: 600/1000 V
• Identification: Legend will include manufacturers name,
13 voltage, BS6883, number of cores and c.s.a., cable sheath
class (e.g. SW4), UK00A code where applicable
14
15
16
17
18
19
20
Part numbers refer to cables with green/yellow outer sheaths for earthing purposes.
Other colours available, details upon request.
13
For further technical information refer to page 6:27.
14
15
16
17
18
19
20
6
Application
7
Unarmoured cables, for use where the mechanical protection is not required, for fixed wiring in ships and in mobile and fixed
offshore units (e.g. drilling rigs, oil platforms, etc.).
8
9 Specifications
• In accordance with BS6883 • Standard sheath colours black. Other colours available
10 • Conductor: Tinned annealed copper conductor. Stranded on request
to BS EN 60228 Class 2 • Oxygen index >32% Temperature index 250°C, HCL
11 • Insulation: EPR complying with BS7655 GP4 emission <0.5% of weight of compound at 800°C
• Core Identification: The cores will be identified by • Flame retardant to IEC 60332-3-22 Category A
either colours or numbers (reduced propagation)
12
• Outer Sheath: LSZH to BSS7655 section 2.6 Type SW4. • Temperature Rating: 90°C maximum conductor
Enhanced oil resistance, low smoke zero halogen, operating temperature
13
minimum tear resistance • Voltage Rating: 600/1000 V
• Identification: Legend will include manufacturers name,
14 voltage, BS6883, number of cores and c.s.a., cable sheath * denotes number of cores.
class (e.g. SW4)
15
16
17
18
19
20
14
15
16
17
18
19
20
7
Application
8
Armoured cables for fixed wiring in ships and in mobile and fixed offshore units (e.g. drilling rigs, oil platforms, etc.). For use in
regularly occupied areas such as accommodation facilities, control rooms and computer suites. Any application where life may
9 be endangered by smoke and noxious fumes and where vital, sensitive equipment may be damaged by acid forming gases.
10
Specifications
11 • In accordance with BS6883 • Outer Sheath: As inner sheath. Identification legend will
• Conductor: Tinned annealed copper. Stranded to include manufacturers name, voltage, BS6883, number of
BS EN 60228 Class 2 or flexible to BS EN 60228 Class 5. cores and c.s.a. cable sheath class (e.g. SW4), IEC 60332
12 and UK00A code where applicable
Class 2 flexible can be supplied where required on
6sqmm and above • Standard sheath colour is black. Other colours available
13 • Insulation: EPR complying with BS7655 GP4 on request
• Core Identification: The cores shall be identified by • Oxygen index >32%. Temperature index 250°C, HCL
14 numbers unless requested otherwise emission <0.5% of weight of compound at 800°C
• Inner Sheath: Will be the same material as the outer • Flame retardant to IEC60332-3-22 Category A
sheath, based generally on the requirements of BS7655 (reduced propagation)
15
section 2.6 Type SW4. Enhanced oil resistance, low smoke • Temperature Rating: 90°C maximum conductor
zero halogen, minimum tear resistance operating temperature
16
• Armour: wire braid in the following optional materials: • Voltage Rating: 600/1000 V
- Galvanised mild steel to BS EN 10257-1
17 - Tinned phosphor bronze to BS EN 12166
- Copper to BS EN 13602
18 N.B. Galvanised mild steel should not be used on single-core
cables where used for a.c. circuits.
19
20
Continued overleaf... 20
13
14
15
16
17
18
19
20
14
15
16
17
18
19
20
7
Application
8 Armoured control and instrumentation cables for fixed wiring on ships and in mobile offshore units (e.g. drilling rigs, oil
platforms, etc.). For use in regularly occupied areas such as accommodation facilities, control rooms and computer suites.
Any application where life may be endangered by smoke and noxious fumes and where vital, sensitive equipment may be
9 damaged by acid forming gases.
10
Specifications
11 • In accordance with BS6883 • Outer Sheath: As inner sheath. Identification legend will
• Conductor: Tinned annealed copper. Stranded Class 2 or include manufacturers name, voltage, BS6883, number of
flexible Class 5 to BS EN 60228 pairs/triples and c.s.a, cable sheath class (e.g. SW4) and
12
IEC 60332 and UK00A code where applicable
• Insulation: EPR complying with BS7655 GP4
• Standard sheath colours are grey, blue or black.
13 • Core Identification: Black and white pairs. Triples black,
Other colours available on request
white and red
• Oxygen index >32%, temperature index 250°C, HCL
• Screening: Aluminium mylar tape in contact with tinned
14 emission <0.5% of weight of compound at 800°C
copper drain wire
• Flame retardant to IEC60332-3-22 Category A
• Inner Sheath: Will be the same material as the outer
15 (reduced propagation)
sheath, based on the requirements of BS7655 section
2.6 Type SW4 with improved characteristics. Enhanced • Temperature Rating: 90°C maximum conductor
oil resistance, low smoke zero halogen, minimum operating temperature
16
tear resistance • Voltage Rating: 150/250 V
• Armour: Galvanised steel wire braid to BS EN 10257-1
17
18
19
20
Anixter Number UK00A Nominal Nominal Number of Diameter Over Min Max Approx Anixter No Anixter
Code Cond Cond Pairs/ Inner Sheath O/D O/D Weight Prysmian Number 4
Area Stranding Triples Min Max E1XF Hawke
mm2 #/mm mm mm mm mm kg/km Gland Gland
Multipair E1BP-E1XF E1DZ-UNI
5
A10FK-03075F-D-06 KGH00 0.75 24/0.2 3PR 12.0 13.7 16.1 18.4 468 -20 -20
A10FK-03075F-D-09 KJH00 0.75 24/0.2 3PR 12.0 13.7 16.1 18.4 468 -20 -20 6
A10FK-07075F-D-06 KGJ00 0.75 24/0.2 7PR 16.0 17.9 20.3 23.1 706 -25 -25
A10FK-07075F-D-09 KJJ00 0.75 24/0.2 7PR 16.0 17.9 20.3 23.1 706 -25 -25 7
A10FK-12075F-D-06 KGK00 0.75 24/0.2 12PR 21.3 23.8 26.0 29.1 1030 -32 -32
A10FK-12075F-D-09 KJK00 0.75 24/0.2 12PR 21.3 23.8 26.0 29.1 1030 -32 -32
8
A10FK-20075F-D-06 KGL00 0.75 24/0.2 20PR 26.8 29.5 32.8 36.5 1662 -40 -40
A10FK-20075F-D-09 KJL00 0.75 24/0.2 20PR 26.8 29.5 32.8 36.5 1662 -40 -40
9
A10FK-01015-D-## - 1.5 7/0.53 1PR 8.7 9.8 12.7 14.3 297 -20S -20S
A10FK-02015-D-## - 1.5 7/0.53 2PR 13.4 14.8 17.8 19.7 505 -25 -25 10
A10FK-03015-D-## - 1.5 7/0.53 3PR 14.4 16.0 18.8 20.8 593 -25 -25
A10FK-05015-D-## - 1.5 7/0.53 5PR 17.5 19.1 22.2 24.6 826 -25 -25 11
A10FK-07015-D-## - 1.5 7/0.53 7PR 19.0 23.7 23.7 26.2 929 -25 -25
A10FK-10015-D-## - 1.5 7/0.53 10PR 24.2 26.4 29.5 32.6 1343 -32 -32 12
A10FK-12015-D-## - 1.5 7/0.53 12PR 25.0 27.2 31.0 34.2 1510 -40 -40
A10FK-20015-D-## - 1.5 7/0.53 20PR 31.5 34.2 38.1 41.7 2287 -50S -40
13
Multitriple
A10FK-01015T-B-## - 1.5 7/0.53 1TR 9.2 10.3 13.2 14.8 304 -20S -20S
14
A10FK-03015T-B-## - 1.5 7/0.53 3TR 17.9 19.6 22.4 24.9 760 -25 -25
A10FK-07015T-B-## - 1.5 7/0.53 7TR 24.1 26.3 29.0 32.0 1262 -32 -32 15
A10FK-12015T-B-## - 1.5 7/0.53 12TR 32.6 35.4 38.9 42.5 2148 -50S -40
16
## For black outer sheath insert suffix -02, for blue outer sheath insert suffix -06, for grey outer sheath insert suffix -09.
18
19
20
7
Application
8 Armoured control and instrumentation cables for fixed wiring on ships and in mobile offshore units (e.g. drilling rigs, oil
platforms, etc.). For use in regularly occupied areas such as accommodation facilities, control rooms and computer suites.
Any application where life may be endangered by smoke and noxious fumes and where vital, sensitive equipment may be
9 damaged by acid forming gases.
10
Specifications
11 • In accordance with BS6883 • Outer Sheath: As inner sheath. Identification legend will
• Conductor: Tinned annealed copper. Stranded Class 2 or include manufacturers name, voltage, BS6883, number of
flexible Class 5 to BS EN 60228 pairs/triples and c.s.a., cable sheath class (e.g. SW4),
12
IEC 60332 and UK00A code where applicable
• Insulation: EPR complying with BS7655 GP4
• Standard sheath colours are grey, blue or black.
13 • Core Identification: Black and white pairs. Triples -
Other colours available on request
black, white and red. Quads - black, white, red, blue
• Oxygen index >32%. Temperature index 250°C, HCL
• Screening: Aluminium mylar tape wrapped round each
14 emission <0.5% of weight of compound at 800°C
pair/triple/quad in contact with tinned copper drain wire
• Flame retardant to IEC 60332-3-22 Category A
• Inner Sheath: Will be the same material as the outer
15 (reduced propagation)
sheath based on the requirements of BS7655 Section
2.6 Type SW4 with improved characteristics. Enhanced • Temperature Rating: 90°C maximum conductor
oil resistance, low smoke zero halogen, minimum operating temperature
16
tear resistance • Voltage Rating: 150/250 V
• Armour: Galvanised steel wire braid to BS EN 10257-1
17
18
19
20
Anixter Number UK00A Nominal Nominal Number of Diameter Over Min Max Approx Anixter No Anixter
Code Cond Cond Pairs/ Inner Sheath O/D O/D Weight Prysmian Number 4
Area Stranding Triples Min Max E1XF Hawke
mm2 #/mm mm mm mm mm kg/km Gland Gland
Multipairs E1BP-E1XF E1DZ-UNI 5
A10FK-02075-C-## - 0.75 7/0.37 2PR 12.6 14.1 17.0 19.0 480 -20 -20
A10FK-03075-C-## - 0.75 7/0.37 3PR 13.2 14.7 17.6 19.6 549 -20 -20
6
A10FK-05075-C-## - 0.75 7/0.37 5PR 16.3 18.0 20.8 23.3 777 -25 -25
A10FK-10075-C-## - 0.75 7/0.37 10PR 22.3 24.5 27.4 30.2 1273 -32 -32
7
A10FK-02075F-D-06 KHX00 0.75 24/0.2 2PR(QD) 9.1 10.3 13.2 14.6 287 -20S -20S
A10FK-02075F-D-09 KKX00 0.75 24/0.2 2PR(QD) 9.1 10.3 13.2 14.6 287 -20S -20S
A10FK-03075F-C-06 KHH00 0.75 24/0.2 3PR 13.2 14.7 17.6 19.6 549 N/A -25 8
A10FK-03075F-C-09 KKH00 0.75 24/0.2 3PR 13.2 14.7 17.6 19.6 549 N/A -25
A10FK-07075F-C-06 KHJ00 0.75 24/0.2 7PR 18.2 20.0 22.9 25.5 919 -25 -25
A10FK-07075F-C-09 KKJ00 0.75 24/0.2 7PR 18.2 20.0 22.9 25.5 919 -25 -25
9
A10FK-12075F-C-06 KHK00 0.75 24/0.2 12PR 23.4 25.6 28.6 31.5 1380 -32 -32
A10FK-12075F-C-09 KKK00 0.75 24/0.2 12PR 23.4 25.6 28.6 31.5 1380 -32 -32 10
A10FK-01010F-D-06 KHF01 1.0 32/0.2 1PR 7.9 9.1 11.9 13.6 262 -20S -20S
A10FK-01010F-D-09 KKF01 1.0 32/0.2 1PR 7.9 9.1 11.9 13.6 262 -20S -20S 11
A10FK-02015-C-## - 1.5 7/0.53 2PR 14.6 16.1 19.0 21.1 591 -25 -25
A10FK-03015-C-## - 1.5 7/0.53 3PR 15.2 16.8 19.7 22.1 697 -25 -25 12
A10FK-05015-C-## - 1.5 7/0.53 5PR 18.8 20.5 23.5 26.0 983 -25 -25
A10FK-07015-C-## - 1.5 7/0.53 7PR 20.9 23.0 25.9 28.5 1181 -32 -32
13
A10FK-10015-C-## - 1.5 7/0.53 10PR 25.6 27.8 31.8 35.0 1323 -32 -32
A10FK-12015-C-## - 1.5 7/0.53 12PR 27.2 29.4 33.4 36.5 1907 -40 -40
A10FK-20015-C-## - 1.5 7/0.53 20PR 36.2 39.0 42.9 46.8 3052 -50 -50 14
Multitriple
A10FK-03075TF-A-06 KHS00 0.75 24/0.2 3TR 16.0 17.6 20.5 22.9 699 -25 -25 15
A10FK-03075TF-A-09 KKS00 0.75 24/0.2 3TR 16.0 17.6 20.5 22.9 699 -25 -25
A10FK-07075TF-A-06 KHT00 0.75 24/0.2 7TR 24.0 26.2 28.9 31.9 1172 -32 -32
A10FK-07075TF-A-09 KKT00 0.75 24/0.2 7TR 24.0 26.2 28.9 31.9 1172 -32 -32
16
A10FK-12075TF-A-06 KHU00 0.75 24/0.2 12TR 29.2 31.8 35.4 38.8 1982 -40 -40
A10FK-12075TF-A-09 KKU00 0.75 24/0.2 12TR 29.2 31.8 35.4 38.8 1982 -40 -40 17
A10FK-01010TF-B-06 KHR01 1.0 32/0.2 1TR 8.6 9.7 12.6 14.2 273 -20S -20S
A10FK-01010TF-B-09 KKR01 1.0 32/0.2 1TR 8.6 9.7 12.6 14.2 273 -20S -20S 18
## For black outer sheath insert suffix -02, for blue outer sheath insert suffix -06, for grey outer sheath insert suffix -09.
19
(QD) = Quad.
7
Application
8 Armoured cables for fixed wiring in ships and offshore units where circuit integrity is essential under fire conditions, e.g: safety
and emergency lighting, fire pumps, shut down systems, communications systems, gas detectors, alarms, etc. For use in
regularly occupied areas such as accommodation facilities, control rooms and computer suites. Any application where life may
9 be endangered by smoke and noxious fumes and where vital, sensitive equipment may be damaged by acid forming gases.
10
Specifications
11 • In accordance with BS7917. Fire resisting properties, • Outer Sheath: Low smoke zero halogen type SW4 to
relevant to the internationally recognised test of IEC60331 BS7655 Section 2.6. Enhanced oil resistance, low smoke
• Conductor: Tinned annealed copper conductor. zero halogen, minimum tear resistance
12
Stranded to BS EN 60228 Class 2 or flexible to • Identification: Legend will include manufacturers name,
BS EN 60228 Class 5 voltage, number of cores and c.s.a, cable sheath class
13 (e.g. SW4), IEC 60331 and UK00A reference where
• Insulation: Mica Glass Tape, EPR complying with
BS7655 GP4 applicable
14 • Core Identification: The cores shall be identified by • Standard sheath colour black. Other colours available
numbers unless specified otherwise on request
15 • Inner Sheath: Zero halogen rubber complying generally • Oxygen index >32%. Temp index 250°C, HCL emission
with BS7655 <0.5% of weight of compound at 800°C
• Armour: Wire braid in the following optional materials: • Flame retardant to IEC 60332-3-22 Category A
16
- Galvanised mild steel to BS EN 10257-1. (reduced propagation)
- Tinned phosphor bronze to BS EN 12166. • Fire resistant to IEC 60331 (enhanced to 1000°C for
17 - Copper to BS4109. 3 hours)
N.B. Galvanised mild steel should not be used on single-core • Temperature Rating: 90°C maximum conductor
18 cables where used for a.c. circuits. operating temperature
• Voltage Rating: 600/1000 V
19
20
7
Application
8 Armoured cables for fixed wiring in ships and offshore units where circuit integrity is essential under fire conditions, e.g: safety
and emergency lighting, fire pumps, shut down systems, communications systems, gas detectors, alarms, etc. For use in
regularly occupied areas such as accommodation facilities, control rooms and computer suites. Any application where life may
9 be endangered by smoke and noxious fumes and where vital, sensitive equipment may be damaged by acid forming gases.
10
Specifications
11 • In accordance with BS7917. Fire resisting properties, • Outer Sheath: Low smoke zero halogen type SW4 to
relevant to the internationally recognised test of IEC60331 BS7655 Section 2.6. Enhanced oil resistance, low smoke
• Conductor: Tinned annealed copper conductor. zero halogen, minimum tear resistance
12
Stranded to BS EN 60228 Class 2 or flexible to • Identification: Legend will include manufacturers name,
BS EN 60228 Class 5 voltage, number of cores and c.s.a, cable sheath class
13 (e.g. SW4), IEC 60331 and UK00A reference where
• Insulation: Mica Glass Tape, EPR complying with
BS7655 GP4 applicable
14 • Core Identification: The cores shall be identified by • Standard sheath colour black. Other colours available
numbers unless specified otherwise on request
15 • Inner Sheath: Zero halogen rubber complying generally • Oxygen index >32%. Temp index 250°C, HCL emission
with BS7655 <0.5% of weight of compound at 800°C
• Armour: Wire braid in the following optional materials: • Flame retardant to IEC 60332-3-22 Category A
16
- Galvanised mild steel to BS EN 10257-1. (reduced propagation)
- Tinned phosphor bronze to BS EN 12166. • Fire resistant to IEC 60331 (enhanced to 1000°C for
17 - Copper to BS4109. 3 hours)
N.B. Galvanised mild steel should not be used on single-core • Temperature Rating: 90°C maximum conductor
18 cables where used for a.c. circuits. operating temperature
• Voltage Rating: 600/1000 V
19
20
7
Application
8 Control and instrumentation cable for use in fixed installations in ships and offshore units where fire resistance and circuit
integrity is essential. For use in regularly occupied areas such as accommodation facilities, control rooms and computer suites.
Any application where life may be endangered by smoke and noxious fumes and where vital, sensitive equipment may be
9 damaged by acid forming gases.
10
Specifications
11 • In accordance with BS7917. Fire resistant properties • Identification: Legend will include manufacturers name,
relevant to IEC60331 voltage, number of pairs/triples c.s.a, cable sheath type
• Conductor: Tinned annealed copper. Stranded to (e.g. SW4), IEC 60331 and UK00A code where applicable
12
BS EN 60228 Class 2 or flexible to BS EN 60228 Class 5 • Standard sheath colours are grey, blue or black.
• Insulation: Mica Glass Tape, EPR complying with Other colours available on request
13 BS7655 GP4 • Oxygen index >32%. Temperatures index 250°C, HCL
• Core Identification: Black and white pairs. Triples black, emission <0.5% of weight of compound at 800°C
14 white and red • Flame retardant to IEC 60332-3-22 Category A
• Screening: Aluminium mylar tape in contact with tinned (reduced propagation)
15 copper drain wire • Fire resistant to IEC60331 (enhanced to 1000°C for
• Inner Sheath: Zero halogen rubber complying generally 3 hours)
16 with BS7655 • Temperature Rating: 90°C maximum conductor
• Armour: Galvanised steel wire braid to BS EN 10257-1 operating temperature
• Outer Sheath: Low smoke zero halogen Type SW4 to • Voltage Rating: 150/250 V
17
BS7655 section 2.6. Enhanced oil resistance, low smoke
zero halogen, minimum tear resistance
18
19
20
Anixter Number UK00A Nominal Nominal Number of Diameter Over Min Max Approx Anixter No Anixter
Code Cond Cond Pairs/ Inner Sheath O/D O/D Weight Prysmian Number 4
Area Stranding Triples Min Max E1XF Hawke
mm2 #/mm mm mm mm mm kg/km Gland Gland
Multipairs E1BP-E1XF E1DZ-UNI
5
A10BZ-03075F-D-06 GLH00 0.75 24/0.2 3PR 13.4 15.1 17.5 19.8 629 -25 -25
A10BZ-03075F-D-09 GNH00 0.75 24/0.2 3PR 13.4 15.1 17.5 19.8 629 -25 -25 6
A10BZ-07075F-D-06 GLJ00 0.75 24/0.2 7PR 17.9 19.9 22.2 25.1 936 -25 -25
A10BZ-07075F-D-09 GNJ00 0.75 24/0.2 7PR 17.9 19.9 22.2 25.1 936 -25 -25 7
A10BZ-12075F-D-06 GLK00 0.75 24/0.2 12PR 23.9 26.5 28.6 30.8 1350 -32 -32
A10BZ-12075F-D-09 GNK00 0.75 24/0.2 12PR 23.9 26.5 28.6 30.8 1350 -32 -32
8
A10BZ-20075F-D-06 GLL00 0.75 24/0.2 20PR 30.1 33.3 36.1 40.0 2124 -40 -40
A10BZ-20075F-D-09 GNL00 0.75 24/0.2 20PR 30.1 33.3 36.1 40.0 2124 -40 -40
9
A10BZ-01015-D-## - 1.5 7/0.53 1PR 9.6 10.8 13.6 15.2 320 -20S -20S
A10BZ-02015-D-## - 1.5 7/0.53 2PR 14.7 16.2 19.1 25.5 666 -25 -25 10
A10BZ-03015-D-## - 1.5 7/0.53 3PR 15.8 17.4 20.1 26.6 771 -25 -25
A10BZ-05015-D-## - 1.5 7/0.53 5PR 19.3 21.1 24.0 30.5 1045 -32 -32 11
A10BZ-07015-D-## - 1.5 7/0.53 7PR 21.0 23.0 25.7 32.6 1189 -32 -32
A10BZ-10015-D-## - 1.5 7/0.53 10PR 26.8 29.0 32.0 39.2 1678 -40 -40 12
A10BZ-12015-D-## - 1.5 7/0.53 12PR 27.7 29.9 33.7 40.8 1869 -50S -50
A10BZ-20015-D-## - 1.5 7/0.53 20PR 34.9 37.6 41.4 45.3 2860 -50S -50
13
A10BZ-24015-D-## - 1.5 7/0.53 24PR 39.0 42.0 45.8 49.7 3225 -50 -50
Multitriples
A10BZ-01015T-B-## - 1.5 7/0.53 1TR 10.1 11.4 14.2 15.8 336 -20 -20
14
A10BZ-03015T-B-## - 1.5 7/0.53 3TR 19.8 21.8 24.3 31.0 979 -32 -32
A10BZ-07015T-B-## - 1.5 7/0.53 7TR 26.7 28.8 31.5 38.7 1594 -40 -40 15
A10BZ-12015T-B-## - 1.5 7/0.53 12TR 36.2 39.0 42.4 50.1 2647 -50 -50
16
## For black outer sheath insert suffix -02, for blue outer sheath insert suffix -06, for grey outer sheath insert suffix -09.
18
19
20
7
Application
8
Control and instrumentation cable for use in fixed installations in ships and offshore units where fire resistance and circuit
integrity is essential.
9
10 Specifications
• In accordance with BS7917. Fire resistant properties • Identification: Legend will include manufacturers name,
11 relevant to IEC60331 voltage, number of pairs/triples/quads, c.s.a., IEC 60331,
• Conductor: Tinned annealed copper. Stranded to and UKOOA code where applicable
BS EN 60228 Class 2 or flexible to BS EN 60228 Class 5 • Standard sheath colours are grey, blue or black. Other
12 colours available on request
• Insulation: Mica Glass Tape, EPR complying with
BS7655 GP4 • Oxygen index >32%. Temperature index 250°C, HCL
13 • Core Identification: Black and white pairs. Triples black, emission <0.5% of weight of compound at 800°C
white and red. Quads, black, white, red, blue • Flame retardant to IEC 60332-3-22 Category A
14 • Screening: Aluminium mylar tape wrapped over each (reduced propagation)
pair/triple/quad in contact with tinned copper drain wire • Fire resistant to IEC60331 (enhanced to 1000°C
15 • Inner Sheath: Zero halogen rubber complying generally for 3 hours)
with BS7655 • Temperature Rating: 90°C maximum conductor
• Armour: Galvanised steel wire braid to BS EN 10257-1 operating temperature
16
• Outer Sheath: Low smoke zero halogen Type SW4 to • Voltage Rating: 150/250 V
BS7655 section 2.6. Enhanced oil resistance, low smoke
17
zero halogen
18
19
20
A10BZ-02015-C-## - 1.5 7/0.53 2PR 14.9 16.5 19.3 21.5 602 -25 -25
11
A10BZ-03015-C-## - 1.5 7/0.53 3PR 15.9 17.5 20.4 22.8 732 -25 -25
A10BZ-05015-C-## - 1.5 7/0.53 5PR 19.5 21.4 24.2 26.7 1031 -32 -25
A10BZ-07015-C-## - 1.5 7/0.53 7PR 21.5 23.6 26.5 29.1 1242 -32 -32 12
A10BZ-10015-C-## - 1.5 7/0.53 10PR 27.4 29.6 33.6 36.7 1877 -40 -40
A10BZ-12015-C-## - 1.5 7/0.53 12PR 28.6 30.8 34.8 37.9 2039 -40 -40
13
A10BZ-20015-C-## - 1.5 7/0.53 20PR 36.1 38.4 42.9 46.7 3232 -50 -50
Multitriple 14
A10BZ-03075TF-A-06 GMS00 0.75 24/0.2 3TR 15.0 17.0 19.2 21.6 783 -25 -25
A10BZ-03075TF-A-09 GPS00 0.75 24/0.2 3TR 15.0 17.0 19.2 21.6 783 -25 -25 15
A10BZ-07075TF-A-06 GMT00 0.75 24/0.2 7TR 19.9 22.3 24.4 27.4 1329 -32 -32
A10BZ-07075TF-A-09 GPT00 0.75 24/0.2 7TR 19.9 22.3 24.4 27.4 1329 -32 -32
A10BZ-12075TF-A-06 GMU00 0.75 24/0.2 12TR 26.9 29.7 32.0 35.8 2258 -50S -50 16
A10BZ-12075TF-A-09 GPU00 0.75 24/0.2 12TR 26.9 29.7 32.0 35.8 2258 -50S -50
17
A10BZ-01010TF-B-06 GMR01 1.0 32/0.2 1TR 8.9 10.2 12.6 14.5 305 -20S -20S
A10BZ-01010TF-B-09 GPR01 1.0 32/0.2 1TR 8.9 10.2 12.6 14.5 305 -20S -20S
18
## For black outer sheath insert suffix -02, for blue outer sheath insert suffix -06, for grey outer sheath insert suffix -09.
19
(QD) = Quad.
6
Application
7
Anixter armoured cables are designed for use where mechanical protection is required on offshore platforms, drilling rigs and
onshore petrochemical plants. This range of cables can be exposed to fluids such as diesel, petrol, glycol, ethanol, white spirit
8 and ASTM oil 2. The resistance to these fluids is in accordance with DOD-STD-1678 method 8030.
9
Specifications
10 • Fibre Type: 0.9mm tight buffered coded fibres • Inner Sheath: Flame retardant and halogen free
• Fibre Colours: Blue, orange, green, brown, grey, white, inner sheath
11 red, black, yellow, violet, pink, turquoise, blue/black, • Armour: Galvanised steel wire braid armour
orange/black, green/black, brown, black, grey/black, • Outer Sheath: Halogen free weather resistant material
white/black, red/black, brown(tan)/black, yellow/black,
12 • Fire Characteristics: Flame retardant to IEC60332-3-24
violet/black, pink/black, turquoise/black
Category C
13
Anixter Fibre Core/ Maximum Bandwidth M.B.R. Maximum Weight Temperature
Number Count Cladding Attenuation Tensile Rating
14 370-403- 850/1300 Installed * Load
µm dB/km MHz/km mm N Kg/km ºC
20
Where more than six cables are bunched, a rating factor of 0.85 should be applied to the current rating. 18
For ambient temperatures other than 45°C, the following rating factors should be applied:
19
Ambient air temp °C 35 40 45 50 55 60 65 70 75 80
Rating factor 1.11 1.05 1.0 0.94 0.88 0.82 0.75 0.67 0.58 0.47 20
14
Where more than six cables are bunched, a rating factor of 0.85 should be applied to the current rating.
15 For ambient temperatures other than 45°C, the following rating factors should be applied:
17
18
19
20
17
18
19
20
ELECTRICAL CHARACTERISTICS
5 Conductor Maximum d.c. Maximum a.c. Reactance Impedance
Size Conductor Conductor @ 60 Hz @ 90ºC,
Resistance Resistance 60 Hz
6 @ 20ºC @ 90ºC
mm2 ohms/km ohms/km ohms/km ohms/km
7 1.5 12.2 15.6 0.142 15.6
1.5* 13.7 17.5 0.142 17.5
8 2.5 7.56 9.64 0.133 9.64
4.0 4.70 5.99 0.133 5.99
9
6.0 3.11 3.97 0.126 3.97
10 1.84 2.35 0.118 2.35
10
16 1.16 1.48 0.112 1.48
25 0.734 0.936 0.107 0.941
11
35 0.529 0.674 0.104 0.684
50 0.391 0.499 0.103 0.510
12
70 0.270 0.344 0.102 0.358
17
18
19
20
ELECTRICAL CHARACTERISTICS
5
Conductor Maximum d.c. Maximum a.c. Reactance Impedance
Size Conductor Conductor @ 60 Hz @ 90ºC, 60 Hz
Resistance Resistance 6
@ 20ºC @ 90ºC
mm2 ohms/km ohms/km ohms/km ohms/km
7
1.5 12.2 15.6 0.152 15.6
1.5* 13.7 17.5 0.152 17.5
8
2.5 7.56 9.64 0.142 9.64
4.0 4.70 5.99 0.139 5.99 9
6.0 3.11 3.97 0.131 3.97
10 1.84 2.35 0.123 2.35 10
16 1.16 1.48 0.116 1.48
25 0.734 0.936 0.111 0.943 11
35 0.529 0.674 0.108 0.683
50 0.391 0.499 0.107 0.510 12
70 0.270 0.344 0.103 0.359
95 0.195 0.271 0.101 0.289
13
120 0.154 0.214 0.099 0.236
14
150 0.126 0.175 0.099 0.201
185 0.100 0.140 0.099 0.171
15
240 0.0762 0.108 0.097 0.145
300 0.0607 0.087 0.097 0.130
16
* Class 5 (30/0.25mm) flexible conductors.
17
18
19
20
ELECTRICAL CHARACTERISTICS
5
Electrical Characteristic Unit Cable
8 Maximum d.c. conductor resistance @ 20°C ohms/km 25.3 18.6 12.4 25.3 18.6 12.4
Maximum a.c. conductor resistance @ 90°C ohms/km 32.3 23.7 15.9 32.3 23.7 15.9
9 Maximum LOOP self-inductance (up to 1kHz) mH/km 0.860 0.819 0.778 0.912 0.867 0.823
Maximum L/R ratio µH/ohm 21.0 27.0 38.0 22.0 29.0 40.0
10 Maximum mutual capacitance:
Cables with collective screen only
11 (except one-pair, one triple & one quad) pF/m 88 96 105 80 86 94
One-pair collectively screened and all
cables with individually screened pairs pF/m 104 115 128 93 102 114
12
One triple/quad collectively screened and all
cables with individually screened triples/quads pF/m 92 101 111 83 91 100
13
Resistances for 0.75mm2 (24/0.2mm) and 1.0mm2 (32/0.2mm) Class 5 conductors will be as follows:
14
0.75mm2 1.0mm2
15 Maximum d.c. conductor resistance @ 20°C ohms/km 27.2 20.4
Maximum a.c. conductor resistance @ 90°C ohms/km 34.7 26.0
16
17
18
19
20
12
13
14
15
16
17
18
19
20
7
MINIMUM BENDING RADIUS
8 Ideally cables should be bent as little as possible and never to radii less than the following:
15 * All fire survival (FS) cables - 8 x diameter. ** 4 x diameter Class 2 flexible cables.
16
17
18
19
20
6
Application
7
These cables are designed for use where mechanical protection is not required for fixed wiring in ships, and in mobile and fixed
offshore units such as drilling rigs and oil platforms.
8
Specifications 9
• In accordance with IEC60092-353 • Sheath Characteristics:
• Conductor: Class 2 tinned or plain compacted copper Oxygen index: >37% 10
conductor to BS EN 60228 Temperature index: 250°C
HCL emission: <0.5% of weight of compound
• Insulation: XLPE complying with IEC60092-351 11
@ 800°C (typically <0.1%)
• Core Identification:
• Fire Performance: Flame retardant to IEC60332-3-22
Single-core is black 12
Category A (reduced propagation)
2 cores are black and light blue
3 cores are black, brown and light blue • Temperature Rating: 90°C maximum conductor
4 cores are black, blue, brown and white operating temperature 13
5 cores and above are white and numbered • Voltage Rating: 600/1000 V
Earthing core (on request) is green/yellow 14
• Outer Sheath: Zero halogen type SHF1 to IEC60092-359
• Identification: The legend will include the manufacturers 15
name, voltage, number of cores and cross sectional
area, and IEC60332-3A reference where applicable.
The standard sheath colour is black 16
17
18
19
20
20
Anixter Number Nominal Cond Nominal Cond Approximate Approximate Flame Proof Stuffing Gland
3
Area Stranding Overall Diameter Weight PRYSMIAN CMP
mm2 #/mm mm kg/km EIAT-A2EX EIAT-A2F
4
3 Core
A10FU-030015-02 1.5 7/0.53 8.5 100 -20S -20SC
5
A10FU-030025-02 2.5 7/0.67 10.0 140 -20S -20SC
A10FU-030040-02 4 19/0.53 11.5 195 -20 -20C
A10FU-030060-02 6 19/0.64 12.5 265 -20 -20C
6
A10FU-030100-02 10 56/0.52 14.5 395 -25 -25C
A10FU-030160-02 16 80/0.52 17.0 585 -25 -25C
7
A10FU-030250-02 25 128/0.52 22.1 1023 -32 -32C
A10FU-030350-02 35 176/0.52 23.5 1200 -32 -32C 8
A10FU-030500-02 50 240/0.52 26.0 1660 -40 -40C
A10FU-030700-02 70 360/0.52 31.0 2310 -40 -40C 9
A10FU-030950-02 95 496/0.52 33.5 3040 -50 -50SC
A10FU-031200-02 120 624/0.52 38.0 3815 -50 -50C 10
A10FU-031500-02 150 768/0.52 42.0 4740 -50 -50C
A10FU-031850-02 185 960/0.52 47.5 5840 -63 -63SC 11
A10FU-032400-02 240 1280/0.52 53.5 7505 - -63C
A10FU-033000-02 300 1504/0.52 59.5 9350 - -75SC 12
4 Core
A10FU-040015-02 1.5 7/0.53 10.0 125 -20S -20SC 13
A10FU-040025-02 2.5 7/0.67 11.0 175 -20S -20C
A10FU-040040-02 4 19/0.53 12.5 250 -20 -20C 14
A10FU-040060-02 6 19/0.64 14.0 345 -25 -25C
A10FU-040100-02 10 56/0.52 16.0 510 -25 -25C
15
A10FU-040160-02 16 80/0.52 19.0 780 -25 -32C
A10FU-040250-02 25 128/0.52 23.0 1170 -32 -32C
16
A10FU-040350-02 35 176/0.52 26.0 1590 -40 -40C
A10FU-040500-02 50 240/0.52 29.5 2220 -40 -40C
17
A10FU-040700-02 70 360/0.52 35.5 3055 -50 -50SC
A10FU-040950-02 95 496/0.52 38.5 4045 -50 -50C
18
A10FU-041200-02 120 624/0.52 42.5 5075 -50 -50C
A10FU-041500-02 150 768/0.52 47.5 6330 -63 -63SC
19
A10FU-041850-02 185 960/0.52 53.0 7780 - -63C
A10FU-042400-02 240 1280/0.52 59.5 9985 - -75SC
A10FU-043000-02 300 1504/0.52 66.0 11880 - -75C
20
6 7 Core
A10FU-070015-02 1.5 7/0.53 12.0 195 -20 -20C
14 24 Core
A10FU-240015-02 1.5 7/0.53 22.0 610 -32 -32C
15 27 Core
A10FU-270015-02 1.5 7/0.53 22.5 670 -32 -32C
16 A10FU-270025-02 2.5 7/0.67 25.0 970 -32 -32C
30 Core
17 A10FU-300015-02 1.5 7/0.53 23.0 730 -32 -32C
37 Core
18 A10FU-370015-02 1.5 7/0.53 25.0 885 -32 -32C
A10FU-370025-02 2.5 7/0.67 28.5 1335 -40 -40C
19
For further technical information please refer to page 6:51.
20
6
Application
7
Suitable for drilling rigs and oil platforms, this cable is designed for fixed wiring in ships, and in mobile and fixed offshore
units such as drilling rigs and oil platforms. This cable is particularly designed for use in areas regularly occupied by people,
such as accommodation facilities, control rooms and computer suites, which assists in reducing smoke and noxious fumes and 8
where vital, sensitive equipment may be damaged by acid forming gases.
9
Specifications
10
• In accordance with IEC60092-353 • Sheath Characteristics:
• Conductor: Class 2 tinned or plain compacted copper Oxygen index: >37%
Temperature index: 250°C 11
conductor to BS EN 60228
HCL emission: <0.5% of weight of compound
• Insulation: XLPE complying with IEC60092-351
@ 800°C (typically <0.1%) 12
• Core Identification:
• Fire Performance: Flame retardant to IEC60332-3-22
Single-core is black
Category A (reduced propagation) 13
2 cores are black and light blue
3 cores are black, brown and light blue • Temperature Rating: 90°C maximum conductor
4 cores are black, blue, brown and white operating temperature
14
5 cores and above are white and numbered • Voltage Rating: 600/1000 V
Earthing core (on request) is green/yellow
• Armour: Tinned or plain copper wire braid
15
• Outer Sheath: Zero halogen type SHF1 to IEC60092-359
16
• Identification: The legend will include the manufacturers
name, voltage, number of cores and cross sectional
area, and IEC60332-3A reference where applicable. 17
The standard sheath colour is black
18
19
20
20
Anixter Number Nominal Cond Nominal Cond Overall Diameter Approximate Flame Proof Stuffing Gland
3
Area Stranding mm Weight PRYSMIAN CMP
mm2 #/mm min max kg/km EIAT-A2EX EIAT-A2F
4
3 Core
A10FU1-030015-02 1.5 7/0.53 9.7 10.0 145 -20S -20SC
5
A10FU1-030025-02 2.5 7/0.67 10.67 11.0 190 -20S -20SC
A10FU1-030040-02 4 19/0.53 11.64 12.0 250 -20 -20C
A10FU1-030060-02 6 19/0.64 13.09 13.5 360 -20 -20C
6
A10FU1-030100-02 10 56/0.52 16.00 16.5 545 -25S -25C
A10FU1-030160-02 16 80/0.52 17.94 18.5 785 -25 -25C
7
A10FU1-030250-02 25 128/0.52 21.38 22.5 1170 -32 -32C
A10FU1-030350-02 35 176/0.52 24.25 25.0 1530 -32 -32C 8
A10FU1-030500-02 50 240/0.52 27.16 28.0 2080 -40 -40C
A10FU1-030700-02 70 360/0.52 32.01 33.0 2830 -50S -50SC 9
A10FU1-030950-02 95 496/0.52 34.43 35.5 3740 -50S -50SC
A10FU1-031200-02 120 624/0.52 38.8 40.0 4630 -50 -50C 10
A10FU1-031500-02 150 768/0.52 42.68 44.0 5700 -50 -63SC
A10FU1-031850-02 185 960/0.52 48.5 50.0 6990 -63 -63SC 11
A10FU1-032400-02 240 1280/0.52 53.83 55.5 8880 -63 -
A10FU1-033000-02 300 1504/0.52 59.65 61.5 10950 -75S - 12
4 Core
A10FU1-040015-02 1.5 7/0.53 10.18 10.5 175 -20S -20SC 13
A10FU1-040025-02 2.5 7/0.67 11.64 12.0 230 -20 -20C
A10FU1-040040-02 4 19/0.53 12.61 13.0 300 -20 -20C 14
A10FU1-040060-02 6 19/0.64 14.55 15.0 475 -25 -25C
A10FU1-040100-02 10 56/0.52 16.97 17.5 685 -25 -25C
15
A10FU1-040160-02 16 80/0.52 19.88 20.5 980 -32 -32C
A10FU1-040250-02 25 128/0.52 23.76 24.5 1460 -32 -32C
16
A10FU1-040350-02 35 176/0.52 26.67 27.5 1940 -40 -40C
A10FU1-040500-02 50 240/0.52 30.07 31.0 2640 -40 -40C
17
A10FU1-040700-02 70 360/0.52 36.37 37.5 3710 -50S -50C
A10FU1-040950-02 95 496/0.52 39.28 40.5 4810 -50 -50C
18
A10FU1-041200-02 120 624/0.52 43.65 45.0 5960 -63S -63SC
A10FU1-041500-02 150 768/0.52 48.01 49.5 7370 -63S -63SC
19
A10FU1-041850-02 185 960/0.52 53.35 55.0 9040 -63 -
A10FU1-042400-02 240 1280/0.52 59.65 61.5 11510 -75S -
A10FU1-043000-02 300 1504/0.52 65.98 68.0 14270 -75 -
20
6 7 Core
A10FU1-070015-02 1.5 7/0.53 12.12 12.5 250 -20 -20C
16
17
18
19
20
6
Application
7
Anixter armoured cables are designed for use where mechanical protection is required for fixed wiring in ships, and in mobile
and fixed offshore units such as drilling rigs and oil platforms. These cables are particularly designed for regularly occupied
areas such as accommodation facilities, control rooms and computer suites. This is essential in reducing smoke and 8
noxious fumes, and helps during evacuation procedures and fire fighting duties, and also helps to protect vital and
sensitive equipment. 9
Specifications 10
18
19
20
14 Individual Screen
A10FU2-02075-A-09 0.75 2PR 13.0 180 -20 -20C
20
6
Application
7
Anixter armoured fire resistant cables are designed for use where additional mechanical protection (armour) is required for
fixed wiring in ships, and in mobile and fixed offshore units such as drilling rigs and oil platforms. These cables are
particularly designed for regularly occupied areas such as accommodation facilities, control rooms and computer suites. 8
This is essential in reducing smoke and noxious fumes, and helps during evacuation procedures and fire fighting duties,
and also helps to protect vital and sensitive equipment. These cables are also used where circuit integrity is essential under 9
fire conditions e.g. safety and emergency lighting, fire pumps, shut down systems, communications systems, gas detectors,
alarms etc.
10
Specifications 11
• In accordance with IEC60092-353 and with fire resistant • Sheath Characteristics:
properties relevant to the internationally recognised test Oxygen index: >37% 12
of IEC60331 Temperature index: 250°C
• Conductor: Class 2 tinned or plain copper compacted HCL emission: <0.5% of weight of compound
@ 800°C (typically <0.1%) 13
conductor to BS EN 60228
• Insulation: Mica Glass Tape, XLPE complying with • Fire Performance: Flame retardant to IEC60332-3-22
IEC60092-351 Category A (reduced propagation). 14
Fire resistant to IEC60331 (750°C for three hours)
• Core Identification:
2 cores are black and light blue • Temperature Rating: 90°C maximum conductor 15
3 cores are black, brown and light blue operating temperature
4 cores black, blue, brown and white • Voltage Rating: 600/1000 V 16
5 cores and above are white and numbered
Earthing core (on request) is green/yellow
• Armour: Tinned or plain copper wire braid 17
• Outer Sheath: Zero halogen type SHF1 to IEC60092-359
• Identification: The legend will include the manufacturers
18
name, voltage, number of cores and cross sectional area,
and IEC60331 and IEC60332-3A reference where 19
applicable. The standard sheath colour is black
20
3 Core
15
16
17
18
19
20
7
Application
Anixter armoured fire resistant cables are designed for use where mechanical protection is required for fixed wiring in ships, 8
and in mobile and fixed offshore units such as drilling rigs and oil platforms. These cables are particularly designed for
regularly occupied areas such as accommodation facilities, control rooms and computer suites. This is essential in reducing 9
smoke and noxious fumes, and helps during evacuation procedures and fire fighting duties, and also helps to protect vital and
sensitive equipment. These cables are also used where circuit integrity is essential under fire conditions e.g. safety and
emergency lighting, fire pumps, shut down systems, communications systems, gas detectors, alarms etc. 10
11
Specifications
• In accordance with IEC60092-375, 60092-350 with fire • Sheath Characteristics: 12
resistant properties relevant to the internationally Oxygen index: >37%
recognised test of IEC60331 Temperature index: 250°C
HCL emission: <0.5% of weight of compound 13
• Conductor: Class 2 tinned or plain copper conductor to
BS EN 60228 @ 800°C (typically <0.1%)
• Insulation: Mica Glass Tape, XLPE complying with • Fire Performance: Flame retardant to IEC60332-3-22 14
IEC60092-351 Category A (reduced propagation)
Fire resistant to IEC60331 (750°C for three hours)
• Core Identification: 15
Pairs are light blue, black and numbered. • Temperature Rating: 90°C maximum conductor
Triples are light blue, black, brown and numbered operating temperature
16
• Screening: Aluminium mylar tape in contact with tinned • Voltage Rating: 250 V
copper drain wire
17
• Inner Sheath: Zero halogen type SHF1 to IEC60092-359
• Armour: Tinned or plain copper wire braid
18
• Outer Sheath: Zero halogen type SHF1 to IEC60092-359
• Identification: The legend will include the manufacturers
name, voltage, number of cores and cross sectional area, 19
and IEC60331 and IEC60332-3A reference where
applicable. The standard sheath colour is grey 20
15
16
17
18
19
20
6
Application
7
Anixter unarmoured fire resistant cables are designed for use where mechanical protection is not required for fixed wiring in
ships, and in mobile and fixed offshore units such as drilling rigs and oil platforms. These cables are particularly designed for
regularly occupied areas such as accommodation facilities, control rooms and computer suites. This is essential in reducing 8
smoke and noxious fumes, and helps during evacuation procedures and fire fighting duties, and also helps to protect vital and
sensitive equipment. These cables are also used where circuit integrity is essential under fire conditions e.g. safety and 9
emergency lighting, fire pumps, shut down systems, communications systems, gas detectors, alarms etc.
10
Specifications
• In accordance with IEC60092-353 with fire resistant • Sheath Characteristics: 11
properties relevant to the internationally recognised test Oxygen index: >37%
of IEC60331 Temperature index: 250°C 12
• Conductor: Class 2 tinned or plain copper compacted HCL emission: <0.5% of weight of compound
conductor to BS EN 60228 @ 800°C (typically <0.1%)
13
• Insulation: Mica Glass Tape, XLPE complying with • Fire Performance: Flame retardant to IEC60332-3-22
IEC60092-351 Category A (reduced propagation)
Fire resistant to IEC60331 (750°C for three hours) 14
• Core Identification:
2 cores are black and light blue • Temperature Rating: 90°C maximum conductor
3 cores are black, brown and light blue operating temperature 15
4 cores black, blue, brown and white • Voltage Rating: 600/1000 V
5 cores and above are white and numbered 16
Earthing core (on request) is green/yellow
• Outer Sheath: Zero halogen type SHF1 to IEC60092-359
17
• Identification: The legend will include the manufacturers
name, voltage, number of cores and cross sectional area,
and IEC60331 and IEC60332-3A reference where 18
applicable. The standard sheath colour is black
19
20
3 Core
15
16
17
18
19
20
Where more than six cables are bunched, a rating factor of 0.85 should be applied to the current rating. 18
For ambient temperatures other than 45°C, the following rating factors should be applied:
19
Ambient air temp °C 35 40 45 50 55 60 65 70 75 80
Rating factor 1.11 1.05 1.0 0.94 0.88 0.82 0.75 0.67 0.58 0.47 20
14
Where more than six cables are bunched, a rating factor of 0.85 should be applied to the current rating.
15 For ambient temperatures other than 45°C, the following rating factors should be applied:
17
18
19
20
Cables to IEC60092 9
13
14
15
16
17
18
19
20