TRANSFORMER DAILY CHECKLIST

DESCRIPTION OF THE EQU


LOCATION
CAPACITY
Sl.No ACTIVITY SPECIFICATION 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

Technical Inspection

1 Check the oil level 1/2 of conservator

2 Check the oil Temperature 30deg to 90deg

Check the winding Temperature 30deg to 80deg

3 Check any leakage in the transformer No Leakage

4 Check the silica gel colour Blue

Sign of Operator:
Month:
HE EQUIPMENT

20 21 22 23 24 25 26 27 28 29 30 31

Signature of E.I.C.
WEEKLY PREVENTIVE MAINTENANCE CHECK LIST

Eqpt.Name : TRANSFORMER
Sl.no Location : Date :
DESCRIPTION Observation/Remarks
1 Check tightness for all bots & nuts
2 Check the oil level in the conservator
3 Check Transformer winding temperature
4 Check oil temperature
5 Check the condition of silica gel
6 Check condition of explosion vent (Diaphragm)
Check the condition of body earthing & neutral
7 earthing

8 Check the sealant condition of the cable entry points


9 Check for local over heating

10 Check all insulator and bushes for crake or damage


Check for the water proofing in the Transformer Bus-
11 duct
12 Check for humming noise of Transformer
13 Check for any oil leakage
14 Check the tap changer mechanism & panel light
15 Note & record all parameters

16 Check for sufficient quantity of floor jelly in the yard


Clean the transformer, tap changing motor
17 mechanism & bus duct
Remarks:

Signature Of Operator. Signature Of E.I.C


MONTHLY PREVENTIVE MAINTENANCE CHECK LIST

Eqpt.Name : TRANSFORMER
Sl.no
Location :
DESCRIPTION Observation/Remarks
1 Check tightness for all bots & nuts
2 Check the oil level in the conservator
3 Check Transformer winding temperature
4 Check oil temperature
5 Check the condition of silica gel
6 Check condition of explosion vent (Diaphragm)
7 Check the condition of body earthing & neutral earthing
8 Check the sealant condition of the cable entry points
9 Check for local over heating
10 Check all insulator and bushes for crake or damage
11 Check for the water proofing in the Transformer Bus-duct
12 Check for humming noise of Transformer
13 Check for any oil leakage
14 Check the tap changer mechanism & panel light
15 Check for sufficient quantity of floor jelly in the yard
16 Visual inspection of neutral bushing
17 Check for proper ventilation of Transformer
18 Check for I/C cable termination for loose connection & over heating
19 Check the Bucholz relay for normal operation
20 Visual inspection of Transformer body for any leakage & damages
21 Check the LV Bus Bar for loose connection & over heating
22 Check the Transformer Earth plates, tight if necessary
23 Check the conservator oil level & add if it’s necessary
24 Check the safety device are working normal
25 Clean the transformer, tap changing motor mechanism & bus duct
Remarks:

Signature Of Operator. Signature Of E.I.C


CE CHECK LIST

Date :
Observation/Remarks

ature Of E.I.C
QUATERLY PREVENTIVE MAINTENANCE CHECK LIST

Eqpt.Name : TRANSFORMER
Sl.no
Location :
DESCRIPTION Observation/Remarks
1 Check tightness for all bots & nuts
2 Check the oil level in the conservator
3 Check Transformer winding temperature
4 Check oil temperature
5 Check the condition of silica gel
6 Check condition of explosion vent (Diaphragm)
7 Check the condition of body earthing & neutral earthing
8 Check the sealant condition of the cable entry points
9 Check for local over heating
10 Check all insulator and bushes for crake or damage

11 Check for the water proofing in the Transformer Bus-duct

12 Check for humming noise of Transformer


13 Check for any oil leakage
14 Check the tap changer mechanism & panel light
15 Visual inspection of neutral bushing
16 Check for proper ventilation of Transformer
Check for I/C cable termination for loose connection & over
17
heating
18 Check the Bucholz relay for normal operation
Visual inspection of Transformer body for any leakage &
19
damages
Check the function of on load tap changer driving
20
mechanism
21 Check the LV Bus Bar for loose connection & over heating

22 Check the Transformer Earth plates, tight if necessary


23 Check the conservator oil level & add if it’s necessary
24 Check the safety device are working normal
Check & Record the earth resistance ,add water if
25
necessary
26 Check gasket joints and retight as necessary
Clean the transformer, tap changing motor mechanism &
27
bus duct
Remarks:
Signature Of Operator. Signature Of E.I.C
NTENANCE CHECK LIST

Date :
Observation/Remarks
Signature Of E.I.C
HALF YEARLY CHECK LIST - TRANSFORMER

Eqpt.Name : TRANSFORMER
Sl.no
Location :
DESCRIPTION Observation/Remarks
1 Check tightness for all bots & nuts
2 Check Transformer winding temperature
3 Check oil temperature
4 Check the condition of silica gel
5 Check condition of explosion vent (Diaphragm)
6 Check the condition of body earthing & neutral earthing
7 Check the sealant condition of the cable entry points
8 Check for local over heating
9 Check all insulator and bushes for crake or damage
10 Check for the water proofing in the Transformer Bus-duct
11 Check for humming noise of Transformer
12 Check for any oil leakage
13 Check the tap changer mechanism & panel light
14 Check for sufficient quantity of floor jelly in the yard
15 Visual inspection of neutral bushing
16 Check for proper ventilation of Transformer
17 Check for I/C cable termination for loose connection & over heating
18 Check the Bucholz relay for normal operation
19 Visual inspection of Transformer body for any leakage & damages
20 Check the function of on load tap changer driving mechanism
21 Check the LV Bus Bar for loose connection & over heating
22 Check the Transformer Earth plates, tight if necessary
23 Check the conservator oil level & add if it’s necessary
24 Check the safety device are working normal
25 Check & Record the earth resistance ,Recondition the pits
26 Check gasket joints and retight as necessary
27 Surge relay operation of Winding temperature indication
28 Surge relay operation of oil temperature indication
29 Carry out break down voltage test of transformer oil
30 Carry out acidity test of transformer oil
31 Activate & check winding temperature limit switch
32 Activate & check oil temperature limit switch
33 Clean the transformer, tap changing motor mechanism & bus duct
Remarks.

Signature of Operator. Signature of E.I.C.