Вы находитесь на странице: 1из 8

Project Name: Sondu (Therdibuoro)- Homa

Bay (Ndhiwa)- Awendo Electrification Project


Customer: Republic of Kenya- Ministry of
Energy
PO number:

Commissioning Nr: COMS307

Switchgear Identification: RH02


F650 Feeder Protection
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.895.301
Functions Tested: 51P-50P-51G Type : Multifunctional Protection
Comments:

INSPECTION TEST

1. VISUAL INSPECTION
 Ok

2. USB/ETHERNET PORT COMMUNICATION


 OK

3. CONFIGURATION FILE UPLOAD


 OK. Ndhiwa_BCU_33kV_RH03_rev01.650

4. POWER SUPPLY
 107.0Vdc

5. CONTACT INPUTS
 Verified

6. CONTACT OUTPUTS
 Verified

7. LOGIC
 Verified

8. VOLTAGE AND CURRENT INPUTS METERING TESTS


 Verified

9. PROTECTION AND FUNCTIONAL TESTS


 Verified
Switchgear Identification: RH01
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.896.102
Functions Tested: 51P-50P-51G Type : Multifunctional Protection

SUMMARY OF WIRED CONTACT OUTPUTS


Contact
Description State Tested
ID

F3 CB TC1 NO OK

F4 CB TC2 NO OK

F5 TRP CB T02 CBF Stag NO OK

F7 CB remote open NO OK

F8 CB remote close NO OK

G3 AR Init to D30 NO OK

G4 BLCK Autoreclose NO OK

G5 CB_MAN_CLOSE_COMND NO OK

H3 Open DS NO OK

H4 Close DS NO OK

H6 POS REPT DS & CB in NO OK

H7 POS REPT DS & CB in NO OK

J4 Line DS Open NO OK

J5 Line DS Close NO OK

2
Switchgear Identification: RH01
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.896.102
Functions Tested: 51P-50P-51G Type : Multifunctional Protection

SUMMARY OF WIRED CONTACT INPUTS


Contact ID Description Tested Remarks

F_CC2 (F2) DC suply fail P1 OK

F_CC4 (F4) Distance IntFAUL OK

F_CC6 (F6) CBF INI distance OK


F_CC9 (F9)
Heat Suply fail OK
F_CC10 (F10)
VT BCPU fai OK
F_CC11 (F11)
BCPU IL Ovrd/sw OK
F_CC12 (F12)
CB CLS BLCK Dis OK

G_CC2 (G2) CB OPEN pos OK

3
Switchgear Identification: RH01
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.896.102
Functions Tested: 51P-50P-51G Type : Multifunctional Protection

G_CC3 (G3) CB CLOSE pos OK

G_CC6 (G6) CB SF6 AL OK

G_CC7 (G7) CB SF6 Block OK

G_CC9 (G9) CB CLS LOCK DRIV OK


G_CC10
CB EXC MOT RUN OK
(G10)
G_CC11 (G11) CB MOT PROT TRP OK
G_CC12
CB HEAT FAIL OK
(G12)
G_CC13
CB In Remote OK
(G13)
G_CC14
CB In Local OK
(G14)
H_CC1(H01) DS Mot Prot TRP OK

H_CC2 (H02) DS In Remote OK

H_CC3 (H03) DS In Local OK

H_CC4 (H04) DS Closed OK

H_CC5 (H05) DS Open OK

H_CC6 (H06) DS MCB Heat FA OK

H_CC9 (H09) DSES mot Prt TRP OK

H_CC10 (H10) DSES in remote OK

H_CC11 (H11) DSES in local OK

H_CC12 (H12) Line DS closed OK

H_CC13 (H13) Line DS open OK

H_CC14 (H14) ES open OK

H_CC15 (H15) ES closed OK

H_CC16 (H16) DSES MCB heat F OK

J_CC1 (J01) DC DS/DSES FAIL OK

J_CC3 (J03) VT meter FAIL OK

J_CC5 (J05) TC 1 FAIL OK

4
Switchgear Identification: RH01
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.896.102
Functions Tested: 51P-50P-51G Type : Multifunctional Protection

J_CC6 (J06) TC 2 FAIL OK

5
Switchgear Identification: RH01
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.896.102
Functions Tested: 51P-50P-51G Type : Multifunctional Protection

UNBALANCED SYSTEM TO IDENTIFY PHASES (Read values on Primary values)

VOLTAGE CURRENT
Phase ACTUAL VALUE ACTUAL VALUE
INJECTION INJECTION
V Mag V Angle V Mag V Angle I Mag I Angle I Mag I Angle
359.93
A 20 V 0º 6.002KV 0.0º 1A 0º 0.249KA

11.974K 119.750 119.70
B 40 V -120º 2A -120º 0.499KA
V º 4º
17.962K 239.497 239.29
C 60 V -240º 3A 120º 0.750KA
V º 6º

CURRENT
ACTUAL VALUE
INJECTION (G)
I Mag I Angle I Mag I Angle
0.249K
1A
A

BALANCED V&I SYSTEM (Read values on Primary values)

VOLTAGE CURRENT
Phase ACTUAL VALUE ACTUAL VALUE
INJECTION INJECTION
V Mag V Angle V Mag V Angle I Mag I Angle I Mag I Angle
19.048K 359.74
A 63,5 V 0º 0.0º 1A 0º 0.249KA
V 0º
19.012K 119.454 119.33
B 63,5 V -120º 1A -120º 0.249KA
V º 3º
19.007K 239.264 238.77
C 63,5 V -240º 1A 120º 0.249KA
V º 5º

6
Switchgear Identification: RH01
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.896.102
Functions Tested: 51P-50P-51G Type : Multifunctional Protection

51P – PHASE TIME OVERCURRENT-


CURRENT INJECTION SETTING VALUE TESTED VALUE CONCLUSION

I Mag I Angle PKP TIME PKP TIME RESULT DATE


(OK/NOT OK)

A 1.5A 0º 1.06A 1.022ms OK


IEC CURVE A
B 1.5A -120º 1.05A TDM:0.05 1.06A 1.012ms OK 21/3/17
(0.97s)
C 1.5A 120º 1.06A 1.007s OK

CONTACT
OUTPUTS F03, F04, G03 OK 21/03/17
ACTIVATED

LED LED 1 OK 21/03/17

50P – PHASE INSTANTANEOUS OVERCURRENT-


CURRENT INJECTION SETTING VALUE TESTED VALUE CONCLUSION

I Mag I Angle PKP TIME PKP TIME RESULT DATE


(OK/NOT OK)

A 7.1A 0º 7.1A 35.3ms OK

B 7.1A -120º 7A 0s 7.1A 41.0ms OK 21/03/17

C 7.1A 120º 7.1A 36.4ms OK

CONTACT
OUTPUTS F03, F04, G03 OK 21/03/17
ACTIVATED

LED LED 2 OK 21/03/17

7
Switchgear Identification: RH01
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.896.102
Functions Tested: 51P-50P-51G Type : Multifunctional Protection

51G– GROUND TIME OVERCURRENT-


CURRENT INJECTION SETTING VALUE TESTED VALUE CONCLUSION

I Mag I Angle PKP TIME PKP TIME RESULT DATE


(OK/NOT OK)

G 0.19A 0º NO PKP - OK
0.2A 0.3s 21/03/17
G 0.21A 0º 0.21 334.3ms OK

CONTACT
OUTPUTS F03, F04, G03 OK 21/03/17
ACTIVATED

LED LED 2 OK 21/03/17

REMARKS:

GE Digital Energy Customer


INSPECTORS Representati Representati
ve ve
NAME

SIGNATURE

DATE