A DS-Agile™ and PREDIX™ Grid APM ready device, the DGA 900’s wide range of communication • Designed for cyber security, with a range of
methods and protocols enables connection to those platforms and integration with GE’s Perception™ comms options and protocols
transformer fleet management software as well as other software, historian and SCADA systems.
Technical Specifications
MEASUREMENTS
Technology Frequency
Automated headspace gas extraction Configurable from once per hour to once every 4 weeks
Photo-acoustic spectroscopy (PAS) gas measurement Faster sampling automatically triggered upon alert level
reached
Thin film capacitive moisture sensor
"Rapid Mode" provides a rapid indication of the evolution
Immersed Fiber Optic Oxygen sensor of the gasses indicated below in ~30 minutes
Range
LDL UDL Accuracy* Repeatability Available in Rapid Mode
Hydrogen (H₂) 5- 5,000 ppm ± LDL or ±5% < 3% •
Carb. Monox. (CO) 1- 50,000 ppm ± LDL or ±3% < 2% • DGA 900 being tested in the factory
Methane (CH₄) 2- 50,000 ppm ± LDL or ±3% < 2%
Acetylene (C₂H₂) 0.5 - 50,000 ppm ± LDL or ±3% < 2% •
Ethylene (C₂H₄) 1- 50,000 ppm ± LDL or ±3% < 2%
Carb. Diox. (CO₂) 20 - 50,000 ppm ± LDL or ±3% < 3% •
Ethane (C₂H₆) 1- 50,000 ppm ± LDL or ±3% < 2%
Oxygen (O₂) 100 - 50,000 ppm ± LDL or ±5% < 2% •
Nitrogen (N₂) ** 10,000 - 100,000 ppm ± LDL or ±15%
Moisture (H₂O) 0- 100% RS (in ppm) ± 3% RH < 3% •
*whichever is greater. Accuracy quoted is the accuracy of the detectors during calibration. Gas-in-oil
measurement may be affected by oil type and condition. Repeatability as measured from final production
test data. DGA 900 gas levels displayed on the local LCD
screen
** N₂ value is calculated and available on free-breathing transformers only.
Kelman DGA900 E0 P0 M0 U0 S0 C0 CO X0 X0 X0 X0 X0 Base Unit 9 Gas DGA, Powder coated enclosure, 2m umbilical, Modbus TCP over Ethernet, Load CT, install kit, and Perception desktop.
Protocol Options P1 COMM90022 DNP3 over RS485
P2 COMM90012 DNP3 over Ethernet
P3 COMM90013 IEC 61850 Edition 1 over Ethernet
P4 COMM90014 IEC 61850 Edition 2 over Ethernet
Mounting Stand M1 24-0822-01 Mounting Stand
Umbilical Cable U1 CABL01054 5 Meter
U2 CABL01055 10 Meter
Sun Canopy S1 24-0973-01 Sun Canopy
Communication Options C1 COMM90016 Ethernet Converter - RJ45 to 10/100Mbps Multimode Fibre ST Connector
C2 COMM90017 Ethernet Converter - RJ45 to 10/100Mbps Multimode Fibre SC Connector
C3 COMM90018 Ethernet Converter - RJ45 to 10/100Mbps Multimode Fibre LC Connector
C4 COMM90019 Ethernet switch, 2 x 100BaseF - ST Multimode Fiber (2 Km max) + 4 x RJ45 10/100Mbps copper
C5 COMM90020 Ethernet switch, 2 x 100BaseF - SC Multimode Fiber (2 Km max) + 4 x RJ45 10/100Mbps copper
C6 COMM90021 Ethernet switch, 2 x 100BaseF - SC Singlemode Fiber (20 km max) + 4 x RJ45 10/100Mbps copper
C7 COMM90005 GSM / GPRS Modem
C10 COMM90015 Wireless Cell Modem for USA - internal
Analogue I/O Card (5 slots available) X1 X1 X1 X1 X1 13-0263-01 Analogue Input Card, 4-20mA
X2 X2 X2 X2 X2 13-0256-02 Analogue Input Card, for PT100 Temp Sensor (4 wire)
X3 X3 X3 X3 X3 13-0256-02-OPT1 Analogue Input Card, for PT100 Temp Sensor (3 wire)
Additional modules and configurations available. Please contact your sales representative or visit our online store
Grid Solutions
Lissue Industrial Estate East
Unit 1, 7 Lissue Walk
Lisburn BT28 2LU
United Kingdom
Tel: +44 (0) 2892 622915
GEGridSolutions.com
Modbus is a registered trademark of Schneider Automation Inc., IEC is a registered trademark of Commission
Electrotechnique Internationale. Voltesso is a registered trademark of Exxon Mobil Corporation. GE, the GE
monogram, Kelman, DS-Agile, PREDIX and Perception are trademarks of the General Electric Company.
GE reserves the right to make changes to specifications of products described at any time without notice
and without obligation to notify any person of such changes.