Вы находитесь на странице: 1из 2

Flowing

Diff Head Density Diff Head


GPM (psi) (#/cuft) (ft) For Differential Heads from 50-300 ft
50 180 40.87 634.0 Out of Range
Pump Eff (%) for Flow between 100-1000 gpm
Out of Range 114.4 D4 formula from Brannan, Eq 2.2

Pump Eff (%) for Flow between 25-99 gpm


95.1 112.5658 D1 is adjustment of D4 value per Brannan
D7 is D4 @ 100gpm
Pump BHP for Flow between 100-1000 gpm
Out of Range

Pump BHP for Flow between 25-99 gpm


5.5

Driver Eff (%) From Brannan, Table 2.1, pg 26


87
Driver BHP kw
6.3 4.7
Flowing
Diff Head Density Diff Head
GPM (psi) (#/cuft) (ft) For Differential Heads from 50-300 ft
290 60 61 141.6
Pump Eff (%) for Flow between 100-1000 gpm
59.4 59.4 D4 formula from Brannan, Eq 2.2

Pump Eff (%) for Flow between 25-99 gpm


Out of Range 54.12447 D1 is adjustment of D4 value per Brannan
D7 is D4 @ 100gpm
Pump BHP for Flow between 100-1000 gpm
40.3

Pump BHP for Flow between 25-99 gpm


Out of Range

Driver Eff (%) From Brannan, Table 2.1, pg 26


89
Driver BHP kw
45.3 33.8