EARTHING DESIGN CALCULATION

This drawing and design is the property of ALSTOM and must not be copied or lent without prior permission in writing

Name DM Name DM Name DM


01 REVISED AS PER CUSTOMER COMMENTS DATED 21.08.14
Date 27.08.14 Date 27.08.14 Date 27.08.14
Name DM Name DM Name DM
00 FIRST ISSUE
Date 21.08.14 Date 21.08.14 Date 21.08.14
SIGN.

SIGN.

SIGN.
REV. DESCRIPTION PREPARED CHECKED APPROVED

PROJECT:
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 400kV AIS S/S & 520 MVA, 420/235/33kV INTERCONNECTING
TRANSFORMER AT BIBIYANA, SYLHET ON TURNKEY BASIS
CONTRACTOR TITLE :
ALSTOM T&D INDIA LTD. EARTHING DESIGN CALCULATION
(Formerly Areva T&D) TOTAL SH. SH.
DLF IT PARK DOCUMENT No. No.
REV.
KOLKATA 700 156
16
5427PK089-BIB-E-SYD-SYS-0014-CN 1 01
Auto Grid Pro [Project: BIBIYANA; Scenario: ONLY400]
Page 1
Ground Grid Performance 27-August-2014 12:44:36 PM
Report #1:

*******************************************************************************
************************************************
AUTOGRID PRO USER INPUT DATA REPORT
Creation Date/Time: 27 Aug 2014/12:43:39
*******************************************************************************
************************************************

----------------------------------------------------------------
Input Data Summary Reports
----------------------------------------------------------------

System Data Summary


D:\PROJECTS\BIBIYANA EARTHING\BIBIYANA\ONLY400\Results\System Input.rep
Requested Computation Reports and Plots
D:\PROJECTS\BIBIYANA EARTHING\BIBIYANA\ONLY400\Results\User Input.rep

----------------------------------------------------------------
Graphics option chosen
----------------------------------------------------------------
Computation Plots
Touch Voltages
Show All Values
Show Unsafe Values Above Selected Safety Threshold

Step Voltages
Show All Values
Show Unsafe Values Above Selected Safety Threshold

Scalar Potential
Show All Values
Show Unsafe Values Above Selected Safety Threshold

Electric Network Configuration

Soil Resistivity Measurement Interpretation

Fault Current Distribution


Section Span Currents
Shunt Tower Currents
Shunt Tower Potentials
One Terminal Plot
Terminal Number ................... 1
All Sections Selected

Configuration Plots
Grounding System Configuration

----------------------------------------------------------------
Types of plot selected
----------------------------------------------------------------
Computation Plots
2D Spot
2D Curve
2D Contour
3D Perspective

Configuration Plots

File: C:\Program Files\SESSoftware


2006\GrarepWorkspace\session4\TempReport.txt
Auto Grid Pro [Project: BIBIYANA; Scenario: ONLY400]
Page 2

3D Perspective
Side View
Top View

End of Report #1

Report #2:

*******************************************************************************
************************************************
AUTOGRID PRO SYSTEM INPUT DATA REPORT
Creation Date/Time: 27 Aug 2014/12:43:39
*******************************************************************************
************************************************

-------------------------------------------------------------------------------
------------------------------------------------
Project Summary
-------------------------------------------------------------------------------
------------------------------------------------
Run Identification .......................... ONLY400
System of Units ............................. Metric
Radius Measured in .......................... Meters
Frequency ................................... 50 Hz

-------------------------------------------------------------------------------
------------------------------------------------
Soil Structure (use specified soil structure characteristics)
-------------------------------------------------------------------------------
------------------------------------------------
Soil type....................................Uniform

Layer Resistivity (Ohm-Meters)


------------------------------------------------------------
Air 1E+18
Soil 321.9
------------------------------------------------------------

-------------------------------------------------------------------------------
------------------------------------------------
Network Fault Current Distribution
-------------------------------------------------------------------------------
------------------------------------------------
Average soil characteristics along electric lines:
Resistivity(Ohm-m) .......................... 100
Relative Permeability (p.u.) ................ 1

Name ........................................
Ground Impedance (To be deduced from grounding computations)

File: C:\Program Files\SESSoftware


2006\GrarepWorkspace\session4\TempReport.txt
Auto Grid Pro [Project: BIBIYANA; Scenario: ONLY400]
Page 3

-------------------------------------------------------------------------------
------------------------------------------------
Safety
-------------------------------------------------------------------------------
------------------------------------------------
Determine Safety Limits for Touch and Step Voltages
Safety Threshold for Touch Voltages ......... 1055.6 V
Safety Threshold for Step Voltages .......... 3758.8 V
Automatic Generation of Observation Points.

----------------------------------------------------------------
The computation results are written in the following reports:
----------------------------------------------------------------
Ground Grid Perfomance
D:\PROJECTS\BIBIYANA EARTHING\BIBIYANA\ONLY400\Results\Ground Grid
Performance.rep
Safety Assessment
D:\PROJECTS\BIBIYANA EARTHING\BIBIYANA\ONLY400\Results\Safety.rep
List of Materials
D:\PROJECTS\BIBIYANA EARTHING\BIBIYANA\ONLY400\Results\Bill of
Materials.rep

End of Report #2

Report #3:

****************************************************************
List of Materials
Creation Date/Time: 27 Aug 2014/12:43:39
****************************************************************

Interconnection / Bonding Nodes ....................... 682


Extent of Grounding System ............................ 12636 (Square Meters)
Surface Layer Thickness ............................... 18 (Centimeters)
Volume of Insulating Layer ............................ 2274.48 (Cubic meters)
Wet Resistivity of Insulating Surface Layer ........... 4500 (Ohm-m)

Grounding System Data

Number of Rods Length (m) Diameter (m)


----------------------------------------------------------------
30 3 0.02

Number of Grid Conductors Length (m) Diameter (m)


----------------------------------------------------------------
14 234 0.02
48 54 0.02

Total Length of Grid Conductors (m) Diameter (m)


----------------------------------------------------------------
5958 0.02

End of Report #3

File: C:\Program Files\SESSoftware


2006\GrarepWorkspace\session4\TempReport.txt
Auto Grid Pro [Project: BIBIYANA; Scenario: ONLY400]
Page 4

Report #4:
Date of run (Start) = Wednesday,27 August 2014
Starting Time = 12:43:39 PM

>>Safety Calculation Table

System Frequency....................................: 50.000(Hertz)


System X/R..........................................: 20.000
Surface Layer Thickness.............................: 18.000(cm)
Number of Surface Layer Resistivities...............: 10
Starting Surface Layer Resistivity..................: NONE
Incremental Surface Layer Resistivity...............: 500.00(ohm-m)
Equivalent Sub-Surface Layer Resistivity........... .: 321.90(ohm-m)

Body Resistance Calculation.........................: IEEE Std.80-2000


Fibrillation Current Calculation....................: IEEE Std.80-2000 (50kg)
Foot Resistance Calculation.........................: IEEE Std.80-2000
User Defined Extra Foot Resistance..................: 0.0000 ohms

==============================================================================
Fault Clearing Time (sec) | 0.125 | 0.250 | 0.500 |
+----------------------------+---------------+---------------+---------------+
Decrement Factor | 1.224 | 1.120 | 1.062 |
Fibrillation Current (amps)| 0.328 | 0.232 | 0.164 |
Body Resistance (ohms)| 1000.00 | 1000.00 | 1000.00 |
==============================================================================

==========================================================================
| Fault Clearing Time | |
Surface |-----------------+-----------------+-----------------| Foot |
Layer | 0.125 sec. | 0.250 sec. | 0.500 sec. | Resist |
Resist |-----------------|-----------------|-----------------| ance |
ivity | Step | Touch | Step | Touch | Step | Touch | 1 Foot |
(ohm-m) |Voltage |Voltage |Voltage |Voltage |Voltage |Voltage | (ohms) |
|(Volts) |(Volts) |(Volts) |(Volts) |(Volts) |(Volts) | |
==========================================================================
NONE | 807.1| 402.7| 623.9| 311.3| 465.4| 232.2| 1005.9|
|---------+--------+--------+--------+--------+--------+--------+--------+
500.0| 1060.2| 466.0| 819.5| 360.2| 611.3| 268.7| 1478.3|
|---------+--------+--------+--------+--------+--------+--------+--------+
1000.0| 1752.6| 639.1| 1354.8| 494.0| 1010.6| 368.5| 2770.4|
|---------+--------+--------+--------+--------+--------+--------+--------+
1500.0| 2437.1| 810.2| 1883.9| 626.3| 1405.2| 467.2| 4047.5|
|---------+--------+--------+--------+--------+--------+--------+--------+
2000.0| 3119.0| 980.7| 2411.0| 758.1| 1798.4| 565.5| 5319.9|
|---------+--------+--------+--------+--------+--------+--------+--------+
2500.0| 3799.7| 1150.9| 2937.2| 889.6| 2191.0| 663.6| 6590.2|
|---------+--------+--------+--------+--------+--------+--------+--------+
3000.0| 4479.9| 1320.9| 3463.0| 1021.1| 2583.2| 761.7| 7859.4|
|---------+--------+--------+--------+--------+--------+--------+--------+
3500.0| 5159.7| 1490.9| 3988.5| 1152.5| 2975.2| 859.7| 9128.0|
|---------+--------+--------+--------+--------+--------+--------+--------+
4000.0| 5839.3| 1660.8| 4513.8| 1283.8| 3367.0| 957.6| 10396.1|
|---------+--------+--------+--------+--------+--------+--------+--------+
4500.0| 6518.8| 1830.7| 5039.0| 1415.1| 3758.8| 1055.6| 11663.9|
|---------+--------+--------+--------+--------+--------+--------+--------+
* Note * Listed values account for short duration asymmetric waveform
decrement factor listed at the top of each column.

File: C:\Program Files\SESSoftware


2006\GrarepWorkspace\session4\TempReport.txt
Auto Grid Pro [Project: BIBIYANA; Scenario: ONLY400]
Page 5

End of Report #4

Report #5:

DATE OF RUN (Start)= DAY 27 / Month 8 / Year 2014


STARTING TIME= 12:43:39:48

===========< G R O U N D I N G ( SYSTEM INFORMATION SUMMARY ) >===========

Run ID......................................: ONLY400


System of Units ............................: Metric
Earth Potential Calculations................: Single Electrode Case
Type of Electrodes Considered...............: Main Electrode ONLY
Soil Type Selected..........................: Uniform or Two-Layer Horizontal
SPLITS/FCDIST Scaling Factor................: 0.70000
1

EARTH PARAMETERS FOR HORIZONTALLY-LAYERED SOIL


----------------------------------------------

TOP LAYER RESISTIVITY = 321.90 ohm-meters


BOTTOM LAYER RESISTIVITY = 321.90 ohm-meters
REFLECTION COEFFICIENT = 0.000000 per unit
TOP LAYER HEIGHT = 10000. METERS

CONFIGURATION OF MAIN ELECTRODE


===============================

Original Electrical Current Flowing In Electrode..: 40000. amperes


Current Scaling Factor (SPLITS/FCDIST/specified)..: 0.70000
Adjusted Electrical Current Flowing In Electrode..: 28000. amperes
Number of Conductors in Electrode.................: 92
Resistance of Electrode System....................: 1.1143 ohms

SUBDIVISION
===========
Grand Total of Conductors After Subdivision.: 1664

Total Current Flowing In Main Electrode......: 28000. amperes


Total Buried Length of Main Electrode........: 5958.0 meters

EARTH POTENTIAL COMPUTATIONS


============================

Main Electrode Potential Rise (GPR).....: 31201. volts

End of Report #5

File: C:\Program Files\SESSoftware


2006\GrarepWorkspace\session4\TempReport.txt
Auto Grid Pro [Project: BIBIYANA; Scenario: ONLY400]
Page 6

File: C:\Program Files\SESSoftware


2006\GrarepWorkspace\session4\TempReport.txt
Grounding Grid (3D - View) [ID:ONLY400]

-60

0 SOIL SURFACE

60
Z AXIS (METERS)

120

180

240
150
Y
A

90
X
IS
(M

30
ET
ER

-30
S)

-90

-150
-150 -90 -30 30 90 150

X AXIS (METERS)

3-D View of Conductors


Grounding Grid (Side View) [ID:ONLY400]

-60

0 SOIL SURFACE

60
Z AXIS (METERS)

120

180

240
-150 -90 -30 30 90 150

X AXIS (METERS)

Side View of Conductors


Grounding Grid (Top View) [ID:ONLY400]

150

90

30
Y AXIS (METERS)

-30

-90

-150
-150 -90 -30 30 90 150

X AXIS (METERS)

Top View of Conductors


Touch Voltages (All - 2D Spot) [ID:ONLY400]
LEGEND
150
Maximum Value : 1053.555
Minimum Value : 231.627

100 1053.55

971.36

889.17
50
806.98
Y AXIS (METERS)

724.78
0 642.59

560.40

-50
478.21

396.01

313.82
-100
-125 -75 -25 25 75 125

X AXIS (METERS)
Touch Voltage Magn. (Volts) [Near]
Touch Voltages (Unsafe - 2D Spot) [ID:ONLY400]
LEGEND
150 Maximum Value : 1053.555
Minimum Threshold : 1055.600

100

50
Y AXIS (METERS)

-50

-100
-125 -75 -25 25 75 125

X AXIS (METERS)
Touch Voltage Magn. (Volts) [Near]
Step Voltages (All - 2D Spot) [ID:ONLY400]
LEGEND
150
Maximum Value : 1563.492
Minimum Value : 12.037

100 1563.49

1408.35

1253.20
50
1098.06
Y AXIS (METERS)

942.91
0 787.76

632.62

477.47
-50
322.33

167.18
-100
-125 -75 -25 25 75 125

X AXIS (METERS)
Step Voltage-Worst Magnitude (Volts)
Step Voltages (Unsafe - 2D Spot) [ID:ONLY400]
LEGEND
150 Maximum Value : 1563.492
Minimum Threshold : 3758.800

100

50
Y AXIS (METERS)

-50

-100
-125 -75 -25 25 75 125

X AXIS (METERS)
Step Voltage-Worst Magnitude (Volts)
Scalar Potential (All - 2D Spot) [ID:ONLY400]
SPOT LEVELS x 1.E+3
150
Maximum Value : 30.969
Minimum Value : 30.148

100 30.97

30.89

30.81
50
30.72
Y AXIS (METERS)

30.64
0 30.56

30.48

-50
30.39

30.31

30.23
-100
-125 -75 -25 25 75 125

X AXIS (METERS)
Potential Profile Magnitude (Volts)
Scalar Potential (Unsafe - 2D Spot) [ID:ONLY400]
SPOT LEVELS x 1.E+3
150
Maximum Value : 30.969
Minimum Value : 30.148

100 30.97

27.87

24.78
50
21.68
Y AXIS (METERS)

18.58
0 15.48

12.39

-50
9.29

6.19

3.10
-100
-125 -75 -25 25 75 125

X AXIS (METERS)
Potential Profile Magnitude (Volts)