Вы находитесь на странице: 1из 4
risro%8 Insulation Resistance Test - Open Electreal Insulation Resistance Test From Open Electrical The insulation resistance (IR) test (also commonly known as a Megget) is a spot insulation test which uses an applied DC voltage (typically either 250Vde, 500Vde or 1,000Vde for low voltage equipment <600V and 2,500Vde and 5,000Vde for high voltage equipment) to measure insulation resistance in either k2., MN or GO. ‘The measured resistance is intended to indicate the condition of the insulation or dieletric between two conductive parts, where the higher the resistance, the better the condition of the insulation. Ideally, the insulation resistance would be infinite, but as no insulators are perfect, leakage currents through the dielectric will ensure that a finite (though high) resistance value is measured Because IR testers are portable, the IR test is often used in the field as the final check of equipment insulation and. also to confirm the reliability of the circuit and that there are no leakage currents from unintended faults in the wiring (e.g. a shorted connection would be obvious from the test results). One of the advantages of the IR test is its non-destructive nature. DC voltages do not cause harmful and/or cumulative effects on insulation materials and provided the voltage is below the breakdown voltage of the insulation, does not deteriorate the insulation, IR test voltages are all well within the safe test voltage for most (if not all) insulation materials, Contents 1 Test Equipment 2 Test Procedure 3 Interpretation of Test Results 4 Factors Affecting Test Results = 4.1 Temperature = 4.2 Humidity * 5 Related Tests = 6 References Test Equipment ‘The Megger company (http:/Avww.megger.com/) were the original manufacturers of IR test equipment over 100 years ago and have become synonymous with insulation resistance testing. Most modern IR testers are digital, portable / handheld units and some have multi-functional capabilities (e.g. built-in continuity testing). Test Procedure Firstly ensure that the equipment to be tested and the work area is safe, e.g. equipment is de-energised and disconnected, all the relevant work permits IR test set (courtesy of Megger (ht have been approved and all locks / tags in place. ‘pilwwww.megger.com)) 7 risro%8 Insulation Resistance Test - Open Electreal Next, discharge capacitances on the equipment (especially for HV equipment) with static discharge sticks or an IR tester with automatic discharging capabilities. The leads on the IR tester can then be connected to the conductive parts of the equipment. For example, for a three- core and earth cable, the IR test would be applied between cores (Core | to Core 2, Core | to Core 3 and Core 2 to Core 3) and between each core and earth, Similarly for three-phase motors, circuit breakrs, switch-disconnectors, etc the IR test can be applied at the equipment terminals (and earth connection), Note that when applying an IR test to earth, itis good practice to connect the positive pole of the IR tester to earth in order to avoid any polarisation effects on the earth. Once connected, the IR tester is energised for a typical test duration of | minute. The IR test measurements are recorded after I minute When the IR testis finished, discharge capacitances again for a period of 4-5 times the test duration. Interpretation of Test Results The minimum values for IR tests vary depending on the type of equipment and the nominal voltage, They also vary according to international standards. Some standards will define the minimum IR test values for the general electrical installations. For example, for low voltage installations in the IEC world, IEC 60364-6 [1] Table 6A gives the minimum IR values and also suggests test voltage, i.e Aan Insulation moeae] Gireuit | Test Voltage | pesistance (ML ‘oltage (Vac) (Vdc) ® Extra low voltage 250 Dos Up to S00V 500 210 Above 500V 1,000 210 In the ANSI/NEC world, the standard ANSI/NETA ATS-2009 [2] provides test procedures and acceptance levels for most types of electrical equipment. Table 100.1 provides representative acceptance values for IR test measurements, which should be used in the absence of any other guidance (from the manufacturer or other standards): Min Nominal Equipment | Min Test Insulation Voltage (Vac) Voltage (Vde) | Resistance (M Q 250 500 25 600 1,000 100 1,000 1,000 100 2,500 1,000 500 5,000 2,500 1,000 216 risro%8 Insulation Resistance Test - Open Electreal 8,000 2,500 2,000 15,000 2,500 5,000 25,000 5,000 20,000 34,500 and above 15,000 100,000 NEPA 70B [3] also provides some guidance on insulation resistance testing for different types of equipment. Factors Affecting Test Results There are two main factors that will affect IR test results: Temperature Electrical resistance has an inverse exponential relationship with temperature, i.e. as temperature increases, resistance will decrease and vice versa. Since the minimum acceptable IR test values are based on a fixed reference temperature (usually 20°C), the measured IR test values must be corrected to the reference temperature in order to make sense of them. As arule of thumb, the resistance halves for every 10°C increase in temperature (and vice versa). So if the measured IR test value was 2MQ at 20°C, then it would be IMQ at 30°C or 4MQ at 10°C ANSI/NETA ATS-2009 Table 100.14 provides correction factors for IR (est measurements taken at temperatures other than 20°C or 40°C, which were in turn based on the correction factors in the freely available Megger book "A stitch in time..." [4]. Humidit The presence (or lack) of moisture can also affect the IR test measurements, the higher the moisture content in the air, the lower the IR test reading, If possible, IR tests should not be carried out in very humid atmospheres (below the dew point). While there are no standard correction factors or guidance for humid conditions, itis good practice to record the relative humidity of cach IR test so that they can be used for baseline comparisons in future tests. For example, having past data on the IR test values for dry and humid days will give you a foundation for evaluating future test values Related Tests For equipment maintenance, the Dielectric Absorption Test is normally performed in conjunction with the IR test using the same testing equipment. The results are either in the form of a Dielectric Absorption Ratio (DAR) or a Polarisation Index (PI). Refer to the Dielectric Absorption Test article for more details References = 1. IEC 60364-6, "Low voltage electrical installations - Part 6: Verification (https://webstore. ication/1887)", 2006 = 2. ANSI/NETA ATS, "Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems (http://www.netaworld.org/standards/ansi-neta-ats)", 2013 chipubl a6 Insulation Resistance Test- Open Electr = 3. NFPA 70B, "Recommended Practice for Electrical Equipment Maintenance (http://www.nfpa.org/co des-and-standards/document-information-pages?mode=code&code=70b)", 2013 = 4, Megger, "A stitch in time - The Complete Guide to Electrical Insulation Testing" (http://www.biddle megger.com/biddle/Stitch-new-pdf), a free book which is an excellent resource on IR testing, risro%8 Retrieved from http://wiki.openelectrical.org/index.php?title=Insulation_Resistance_Test&oldid=542" Category: Electrical Testing = This page was last edited on 18 February 2017, at 03:56, 46

Вам также может понравиться