risro%8 Insulation Resistance Test - Open Electreal
Insulation Resistance Test
From Open Electrical
The insulation resistance (IR) test (also commonly known as a Megget) is a spot insulation test which uses an
applied DC voltage (typically either 250Vde, 500Vde or 1,000Vde for low voltage equipment <600V and
2,500Vde and 5,000Vde for high voltage equipment) to measure insulation resistance in either k2., MN or GO.
‘The measured resistance is intended to indicate the condition of the insulation or dieletric between two conductive
parts, where the higher the resistance, the better the condition of the insulation. Ideally, the insulation resistance
would be infinite, but as no insulators are perfect, leakage currents through the dielectric will ensure that a finite
(though high) resistance value is measured
Because IR testers are portable, the IR test is often used in the field as the final check of equipment insulation and.
also to confirm the reliability of the circuit and that there are no leakage currents from unintended faults in the
wiring (e.g. a shorted connection would be obvious from the test results).
One of the advantages of the IR test is its non-destructive nature. DC voltages do not cause harmful and/or
cumulative effects on insulation materials and provided the voltage is below the breakdown voltage of the
insulation, does not deteriorate the insulation, IR test voltages are all well within the safe test voltage for most (if
not all) insulation materials,
Contents
1 Test Equipment
2 Test Procedure
3 Interpretation of Test Results
4 Factors Affecting Test Results
= 4.1 Temperature
= 4.2 Humidity
* 5 Related Tests
= 6 References
Test Equipment
‘The Megger company (http:/Avww.megger.com/) were the original
manufacturers of IR test equipment over 100 years ago and have become
synonymous with insulation resistance testing. Most modern IR testers are
digital, portable / handheld units and some have multi-functional capabilities
(e.g. built-in continuity testing).
Test Procedure
Firstly ensure that the equipment to be tested and the work area is safe, e.g.
equipment is de-energised and disconnected, all the relevant work permits IR test set (courtesy of Megger (ht
have been approved and all locks / tags in place. ‘pilwwww.megger.com))
7risro%8 Insulation Resistance Test - Open Electreal
Next, discharge capacitances on the equipment (especially for HV equipment) with static discharge sticks or an IR
tester with automatic discharging capabilities.
The leads on the IR tester can then be connected to the conductive parts of the equipment. For example, for a three-
core and earth cable, the IR test would be applied between cores (Core | to Core 2, Core | to Core 3 and Core 2 to
Core 3) and between each core and earth, Similarly for three-phase motors, circuit breakrs, switch-disconnectors,
etc the IR test can be applied at the equipment terminals (and earth connection),
Note that when applying an IR test to earth, itis good practice to connect the positive pole of the IR tester to earth
in order to avoid any polarisation effects on the earth.
Once connected, the IR tester is energised for a typical test duration of | minute. The IR test measurements are
recorded after I minute
When the IR testis finished, discharge capacitances again for a period of 4-5 times the test duration.
Interpretation of Test Results
The minimum values for IR tests vary depending on the type of equipment and the nominal voltage, They also vary
according to international standards. Some standards will define the minimum IR test values for the general
electrical installations.
For example, for low voltage installations in the IEC world, IEC 60364-6 [1] Table 6A gives the minimum IR
values and also suggests test voltage, i.e
Aan Insulation
moeae] Gireuit | Test Voltage | pesistance (ML
‘oltage (Vac) (Vdc) ®
Extra low voltage 250 Dos
Up to S00V 500 210
Above 500V 1,000 210
In the ANSI/NEC world, the standard ANSI/NETA ATS-2009 [2] provides test procedures and acceptance levels
for most types of electrical equipment. Table 100.1 provides representative acceptance values for IR test
measurements, which should be used in the absence of any other guidance (from the manufacturer or other
standards):
Min
Nominal Equipment | Min Test Insulation
Voltage (Vac) Voltage (Vde) | Resistance (M
Q
250 500 25
600 1,000 100
1,000 1,000 100
2,500 1,000 500
5,000 2,500 1,000
216risro%8 Insulation Resistance Test - Open Electreal
8,000 2,500 2,000
15,000 2,500 5,000
25,000 5,000 20,000
34,500 and above 15,000 100,000
NEPA 70B [3] also provides some guidance on insulation resistance testing for different types of equipment.
Factors Affecting Test Results
There are two main factors that will affect IR test results:
Temperature
Electrical resistance has an inverse exponential relationship with temperature, i.e. as temperature increases,
resistance will decrease and vice versa. Since the minimum acceptable IR test values are based on a fixed reference
temperature (usually 20°C), the measured IR test values must be corrected to the reference temperature in order to
make sense of them.
As arule of thumb, the resistance halves for every 10°C increase in temperature (and vice versa). So if the
measured IR test value was 2MQ at 20°C, then it would be IMQ at 30°C or 4MQ at 10°C
ANSI/NETA ATS-2009 Table 100.14 provides correction factors for IR (est measurements taken at temperatures
other than 20°C or 40°C, which were in turn based on the correction factors in the freely available Megger book
"A stitch in time..." [4].
Humidit
The presence (or lack) of moisture can also affect the IR test measurements, the higher the moisture content in the
air, the lower the IR test reading, If possible, IR tests should not be carried out in very humid atmospheres (below
the dew point). While there are no standard correction factors or guidance for humid conditions, itis good practice
to record the relative humidity of cach IR test so that they can be used for baseline comparisons in future tests. For
example, having past data on the IR test values for dry and humid days will give you a foundation for evaluating
future test values
Related Tests
For equipment maintenance, the Dielectric Absorption Test is normally performed in conjunction with the IR test
using the same testing equipment. The results are either in the form of a Dielectric Absorption Ratio (DAR) or a
Polarisation Index (PI). Refer to the Dielectric Absorption Test article for more details
References
= 1. IEC 60364-6, "Low voltage electrical installations - Part 6: Verification (https://webstore.
ication/1887)", 2006
= 2. ANSI/NETA ATS, "Standard for Acceptance Testing Specifications for Electrical Power Equipment
and Systems (http://www.netaworld.org/standards/ansi-neta-ats)", 2013
chipubl
a6Insulation Resistance Test- Open Electr
= 3. NFPA 70B, "Recommended Practice for Electrical Equipment Maintenance (http://www.nfpa.org/co
des-and-standards/document-information-pages?mode=code&code=70b)", 2013
= 4, Megger, "A stitch in time - The Complete Guide to Electrical Insulation Testing" (http://www.biddle
megger.com/biddle/Stitch-new-pdf), a free book which is an excellent resource on IR testing,
risro%8
Retrieved from http://wiki.openelectrical.org/index.php?title=Insulation_Resistance_Test&oldid=542"
Category: Electrical Testing
= This page was last edited on 18 February 2017, at 03:56,
46