Вы находитесь на странице: 1из 1

UNF PROJECT CALCULATION SHEET

DESIGN OF BLOCK FOUNDATION

1 DIMENSION DATA
xg
le
B = 5.00 m , footing width
L = 12.00 m , footing length
H
x zg he = 4.00 m , height of equipment
B
he be = 4.00 m , width of equipment
Q h le = 12.00 m , length of equipment
xg = 0.30 m
d1 z zg = 0.20 m
d2 L d1 = 0.40 m
d2 = 0.40 m
d3 d3 = 0.40 m
h = 3.00 m
Rubble/Lean Concrete
1. DESIGN LOAD 4) SEISMIC CALCULATION
1) EQUIPMENT LOADING DATA Seismic Point = 0.90
Empty Weight (Qe) = 400.0 KN Maximum Seismic Coefficien= 0.30
Operation Weight (Qo) = 700.0 KN Equipment Seismic Force, H= 210 kN

2) WEIGHT OF STRUCTURAL PROPER 5) WIND CALCULATION


Soil (γs) = 18.0 KN/m3 Wind Pressure (Wo) = 380 Pa
Reinforced concrete (γrc) = 23.5 KN/m3 Height Factor (K) = 0.60
Plain concrete (γpc) = 22.0 KN/m3 Aerodynamic Factor = 2.1
Ground water (γw) = 10.0 KN/m3 Height of Scaffolding = 4.6 m
*) assumed ground water level GL-0.0m shall be considered on design Equipment Wind Force (Hw)= 32 kN
Hw < 0.7He, L/C B is neglective
3) LOAD COMBINATION 6) FOUNDATION WEIGHT
For soil bearing capacity & stability check Footing Weight (Wf) = 1128 kN
Components A B C D Rubble Concrete (Wrc) = 564 kN
FDN Weight 1.0 1.0 1.0 1.0
Empty 1.0 7) BOUYANT FORCE
Operation 1.0 1.0 1.0 Bouyant Force (Bf) = 480 kN
Wind 1.0 1.0
Earthquake 0.7
*) see to 6464 C200-00100 Engineering Standard for
Civil & Buildings

2. SOIL BEARING CHECK 3. SLIDING CHECK


3.1 ALLOWABLE BEARING CAPACITY
For fixed load μ : Friction coefficient ( = 0.5 )
Qaf = 150.0 kN/m2 F : Actual safety ratio
For combined load N : Wf + Qo - Bf
Qac = 225.0 kN/m2 Due to Load Case C:
μ∑N 0.5 x 1048.00
F = = = 16.38 > 1.25 OK
3.2 ACTUAL BEARING PRESSURE Hw 32.0
qmax : P/Af + Mx/Sfx + Mz/Sfz, Maximum soil reaction, kN/m2 Due to Load Case D:
qmin : P/Af - Mx/Sfx - Mz/Sfz, Minimum soil reaction, kN/m2 μ∑N 0.5 x 1348.00
F = = = 4.59 > 1.25 OK
P : Q + Wf + Wrc, Total Vertical Load, kN 0.7*He 147.0
Mx : H * (h + d1 + d2 + d3) + Q * zg , Total Moment about X-Axis, kN-m
Mz : Q * xg , Total Moment about Z-Axis, kN-m 4. OVERTURNING CHECK
Af : 60 m2, B * L, Area of Footing ∑MR : Resisting moment
Sfx : 50 m3, (L * B2) / 6, Section Modulus of Footing about X-Axis ∑MO : Overturning moment
Sfz : 120 m3, (H * L2) / 6, Section Modulus of Footing about Z-Axis ∑N : Wf + Qo - Bf
Due to Load Case C:
CASE P (kN) Mx (kN) Mz (kN) qmax qmin Ratio Judge B 5.00
∑MR = ∑N = 1048.0 x = 2620.0 kNm
A 2392 0 0 40 40 0.27 OK! 2 2
C 2092 249 210 42 28 0.18 OK!
∑Mo = 121.6 kNm
D 2392 640 210 54 25 0.24 OK!
6 RE-BAR ARRANGEMENT ∑MR 2620.0
F = = = 21.55 > 1.25 OK
This foundation is a block foundation. ∑Moe 121.6
So, re-bar requirement is only shrinkage requirement.(BS 8110-1 3.12.11. Due to Load Case D:
Total reinforcement area is more than 0.25% of the concrete gross area. B 5.00
∑MR = ∑N = 1348.0 x = 3370.0 kNm
Top Bar D16 @ 250 2 2
Bottom Bar D16 @ 250
∑Mo = 558.6 kNm
Ast = 804.25 mm2
Asb = 804.25 mm2 ∑MR 3370.0
F = = = 6.03 > 1.25 OK
Ast + Asb ≧ 0.0025Ac ∑Moe 558.6
804 + 804 = 1608 < 2000 NG

Вам также может понравиться