Table of Contents

Job Title Page ................................................................................................................................................ 2


User Input Data.............................................................................................................................................. 3
Error Checker .LOG File .......................................................................................................................... 6
Solution Module .TXT File ...................................................................................................................... 7
Wind, Material, Thickness & Weights ............................................................................................ 13
Roof Evaluation/Design & Appendix F ............................................................................................ 15
Anchor Bolt Details .................................................................................................................................. 17
Nozzle Flexibility & Load Results................................................................................................. 19
Anchor Chair Calculations .................................................................................................................... 25
Fluid Height Calculations .................................................................................................................... 27
Wind Calculations ....................................................................................................................................... 29
Internal Pressure Calculations ........................................................................................................ 31
TANK 2016, API-650/653/620 Analysis 2
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm
TANK 2016, API-650/653/620 Analysis 3
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

API-650 12th Edition, Addendum 2, January 2016

API-620/650/653 General Tank Data:


------------------------------------------------------------------------------
API Design Code .................................... 650
Design Method (V, O, or A) ......................... One Foot
Run Objective ...................................... Design

Design Temperature ................................. 50.000 C


Design Pressure at Top ............................. 0.00000 kPa
Shell Material ..................................... A36,Mod
Internal Pressure Combination Factor ...........[Fp] 0.40000

Shell Design Stress .....................[Sd or Sts] 23200. lb./sq.in


Shell Hydro Test Stress ........................[St] 24900. lb./sq.in

Tank Nominal Diameter ...........................[D] 9000.0 mm.


Tank Shell Height .............................[HTK] 9000.0 mm.
Design Liquid Level .............................[H] 8100.0 mm.
Liquid Specific Gravity .........................[G] 1.0000
Weight of Attachments/Structures.................... 0.00000 lb.
Distance down to Top Wind Girder ................... 50.000 mm.
Joint Efficiency (App A or 653) .................[E] 1.0000
Wind Velocity ...................................... 55.000 m/sec

Insulation Thickness ............................... 0.00000 mm.


Insulation Density ................................. 0.00000 lb./cu.in

Include Annular Base Plate Details ................. No


Include Wind Moment in Appendix F_4_2 Calculations . Yes
Minimum Yield Strength of Bottom Plate: ............ 38000. lb./sq.in

Number of Shell Courses ............................ 5

Shell Course Height and Thickness:


| Course Height | Thickness | Corrosion Allowance |
# | mm. | mm. | mm. |
-----------------------------------------------------------------
1 | 1800.00 | 6.0000 | 3.0000 |
2 | 1800.00 | 5.0000 | 3.0000 |
3 | 1800.00 | 5.0000 | 3.0000 |
4 | 1800.00 | 5.0000 | 3.0000 |
5 | 1800.00 | 5.0000 | 3.0000 |

Shell Course Material Properties:


| | Sd| St| Fy| UTS| Max Thk |Grade|Group|
# | Material Name | lb./sq.in. | mm. | | |
-----------------------------------------------------------------------------
1 | A36,Mod | 23200| 24900| 36000| 58000| 19.050 | | 2 |
2 | A36,Mod | 23200| 24900| 36000| 58000| 19.050 | | 2 |
3 | A36,Mod | 23200| 24900| 36000| 58000| 19.050 | | 2 |
4 | A36,Mod | 23200| 24900| 36000| 58000| 19.050 | | 2 |
5 | A36,Mod | 23200| 24900| 36000| 58000| 19.050 | | 2 |

Anchor Bolt Input:


------------------------------------------------------------------------------
Anchor Bolt Diameter (optional) .................... 31.750 mm
Threads per Unit Length ............................ 0.27559 1/mm
Number of Anchor Bolts (optional) .................. 16.000
Bolt Yield Stress .................................. 36000. lb./sq.in
Bolt Offset from Mean Tank Diameter ................ 40.000 mm.
Anchor Bolt Corrosion Allowance (optional) ......... 0.25001 mm
TANK 2016, API-650/653/620 Analysis 4
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

Wind Data :
------------------------------------------------------------------------------
Kz parameter ....................................... 1.0400
Kzt parameter ...................................... 1.0000
Kd parameter ....................................... 0.95000
Importance Factor ... ...........................[I] 1.0000
Gust Factor ... .................................[G] 0.85000

Roof Data Input:


------------------------------------------------------------------------------
Roof Type .......................................... Rafter Sup
Angle Between Roof and Horizontal .................. 9.2000 deg
Net Area at Roof/Shell Junction ... .............[A] 500.00 sq.mm.
Thickness of Roof Plate ............................ 5.0000 mm.
Roof Plate Corrosion Allowance ..................... 3.0000 mm.
Ground Snow Load ................................... 0.00000 lb/ft2
Roof Live Load ..................................... 0.00000 lb/ft2
Roof Spherical Radius .............................. 0.00000 mm.
General Roof Data, No Design
Weight of Roof Plates .............................. 0.00000 lb.
Weight of Roof Framing ............................. 0.00000 lb.
Percent of Weights Supported by Shell .............. 100.00 %
Roof Joint Efficiency .............................. 0.70000

Nozzle Input Data:


------------------------------------------------------------------------------
Nozzle Designation / Number # 1..................... 1
Nozzle Height above bottom plate ................... 750.00 mm
Nozzle Outer Diameter .............................. 609.60 mm
delta Temperature .................................. 0.00000 C
Modulus of Elasticity .............................. 0.29500E+08 lb./sq.in
Expansion Coefficient .............................. 0.00000 mm./mm./d
Reinforcement on (S)hell or (N)ozzle ............... S
Nozzle RePad Thickness ............................. 6.0000 mm
Nozzle Weight ...................................... 0.00000 lb.
Applied External Radial Force ...................... 0.00000 lb.
Applied External Circumferential Moment ............ 0.00000 ft.lb.
Applied External Longitudinal Moment ............... 0.00000 ft.lb.
Apply PVP-1279 (Y)es or (N)o ....................... Y
Nozzle Thickness for PVP-1279 ...................... 0.00000 mm.
Repad Outer Diameter for PVP-1279 .................. 0.00000 mm

Nozzle Designation / Number # 1..................... 2


Nozzle Height above bottom plate ................... 9000.0 mm
Nozzle Outer Diameter .............................. 609.60 mm
delta Temperature .................................. 0.00000 C
Modulus of Elasticity .............................. 0.29500E+08 lb./sq.in
Expansion Coefficient .............................. 0.00000 mm./mm./d
Reinforcement on (S)hell or (N)ozzle ............... S
Nozzle RePad Thickness ............................. 6.0000 mm
Nozzle Weight ...................................... 0.00000 lb.
Applied External Radial Force ...................... 0.00000 lb.
Applied External Circumferential Moment ............ 0.00000 ft.lb.
Applied External Longitudinal Moment ............... 0.00000 ft.lb.
Apply PVP-1279 (Y)es or (N)o ....................... Y
Nozzle Thickness for PVP-1279 ...................... 0.00000 mm.
Repad Outer Diameter for PVP-1279 .................. 0.00000 mm

Computation Control Directives:


------------------------------------------------------------------------------
Roof Projection in Wind Moment = YES
Shell thick converg tolerance = 0.12699999 mm.
Generate Message File = YES
Cosine curve tolerance = 0.30000001
TANK 2016, API-650/653/620 Analysis 5
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

Cosine curve iteration limit = 100.00000


Wind girder shell thickness = MAX
Shell settlement method = FOURIER_SERIES
Corroded Nozzles = NO
653 Corroded hydrotest case = NO
Thickness roundup to nearest = 0.00000000 mm.
Plate material density = 0.28360000 lb./cu.in.
Modify fluid height by pressure = NO
Round anchor bolts by = 4.0000000
Wind moment in Appendix F = Sect_5.9.7.1
Full shell weight in Appendix F = YES
Use P from F.4.1 only in F.6 = YES
Use non corroded roof weight as dlr = YES

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016


TANK 2016, API-650/653/620 Analysis 6
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

NOTE #50 (General Tank Data)


The design pressure was not specified by the user.
This item will be assumed to be 0.0.

WARNING #51 (General Tank Data)


The shell plate nominal widths should normally be
at least 72 inches. (Refer to 5.6.1.2)

Note #149 - (Nozzle Data)


PVP-1279 has been activated. Nozzle flexibilities for this
nozzle will be determined using this PVP paper instead
of API-650 Appendix P.

Note #149 - (Nozzle Data)


PVP-1279 has been activated. Nozzle flexibilities for this
nozzle will be determined using this PVP paper instead
of API-650 Appendix P.

Error Check Summary Report

Fatal Errors 0

Warning Messages 1

Notes 3

Error Checking Completed

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016


TANK 2016, API-650/653/620 Analysis 7
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

Intergraph Corporation. Copyright @ 1994-2016


API-650/653/620 TANK Design/Analysis Program Message File
API-650 12th Edition, Addendum 2, January 2016
API-653 5th Edition, November 2014
API-620 12th Edition, Addendum 1, November 2014
API-2000 7th Edition, March 2014

Date: 6/21/18 Time: 13:29:13 Ver 2016

NOTE: This file is created by the solution module and is an


"internal" file. Most values shown in this file are presented in
the internal units (English) of the program. This file is for
data verification purposes only. This data should not be
included in any formal reports.

WIND DATA PER SECT 5.9.7.1


Wind Velocity in Miles/Hour: 123.03
Velocity Factor, (V/120)**2: 1.0512
Wind Pressure, including 10% + 5 psf: 37.542
Wind Profile Area in sq.ft.: 907.18
Horizontal Wind Moment (ft-lb): 0.52344E+06
Wind Shear Force (lb): 34058.

Thickness evaluation based on One Foot Method.

"One Foot" Shell Course Thicknesses before


Sect 5.6.1.1 check and round up.

Course, Design Thickness (in) 1 0.2027


Course, Test Thickness (in) 1 0.0789
Course, Design Thickness (in) 2 0.1832
Course, Test Thickness (in) 2 0.0606
Course, Design Thickness (in) 3 0.1637
Course, Test Thickness (in) 3 0.0424
Course, Design Thickness (in) 4 0.1441
Course, Test Thickness (in) 4 0.0242
Course, Design Thickness (in) 5 0.1246
Course, Test Thickness (in) 5 0.0060

Thickness(in) for each course.


# DESIGN TEST USER INPUT
1 0.23622 0.23622 0.23622
2 0.19685 0.19685 0.19685
3 0.19685 0.19685 0.19685
4 0.19685 0.19685 0.19685
5 0.19685 0.19685 0.19685

API-653 THICKNESS/CORROSION RESERVES


Retiring Thickness Remaining Corrosion
# Design Test Design Test
(in) (in) (in) (in)
1 0.00000 0.00000 0.23622 0.23622
2 0.00000 0.00000 0.19685 0.19685
3 0.00000 0.00000 0.19685 0.19685
4 0.00000 0.00000 0.19685 0.19685
5 0.00000 0.00000 0.19685 0.19685

Allowed Fluid Heights (ft) for each course.


# DESIGN TEST REQUIRED
TANK 2016, API-650/653/620 Analysis 8
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

1 36.692 77.615 26.575


2 24.795 64.846 20.669
3 24.795 64.846 14.764
4 24.795 64.846 8.8583
5 24.795 64.846 2.9528

Annular bottom plate mininum yield strength, Fy : 38000.


Annular bottom plate thickness (in) from Table 5-1 : 0.35433
Annular bot. plate width (in) per API650 5.5.2 : 31.021

SHELL WEIGHTS (with Nozzles)


Computed weight of shell (lb): 22900.
Computed corroded shell weight (lb): 9688.7
Insulation weight, in shell weight (lb 0.00000
Computed C.G. of shell (ft): 14.310
Weight of shell Used (lb): 22900.
C.G. of shell Used (ft): 14.310

WIND GIRDER COMPUTATIONS


Top Girder, required section modulus (in^3) 2.7062
Elastic Modulus Ratio: 1.0000
Distance from top to intermediate
wind girder, H1 (ft): 61.162
Intermediate girder section modulus (in^3): 5.6054

TRANSFORMED SHELL COMPUTATIONS, Girder #: 1


Trnsfrmd shell height below last girder(ft) 27.202
Individual transformed course & height (ft): 5 5.7415
Individual transformed course & height (ft): 4 5.9055
Individual transformed course & height (ft): 3 5.9055
Individual transformed course & height (ft): 2 5.9055
Individual transformed course & height (ft): 1 3.7437

THIS GIRDER IS NOT NECESSARY !!!

SEISMIC EVALUATION - FLUID WEIGHTS


Computed operating fluid weight (lb): 0.11342E+07
Computed test fluid weight (lb): 0.12603E+07
Computed empty fluid weight (lb): 0.00000

=====================================
TANK - Roof Design Data

Design Roof Load (psf): 8.0390

RAFTER SUPPORTED CONE ROOF

Total weight of Roof Plates (lb): 5576.6


Corroded weight of Roof Plates (lb): 5576.6
Roof load used (psi): 0.55827E-01
Computed "B" value: 193.60
B&Y spacing : 179.46

Rafter Spacing: t * SQRT( 2 * Sp / P )


Spacing according to B&Y Eq 4.25 (in): 179.46
Limiting spacing per API 5.10.4.4 (in): 84.000
Finalized outer rafter spacing (in): 84.000
Finalized inner rafter spacing (in): 66.000

Girder Ring Lengths & Quantities (from center ring)


According to B&Y Eq 4.26
L = 2 * R * SIN( 360 / 2N )
TANK 2016, API-650/653/620 Analysis 9
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

RING Number Length (ft)

RAFTER DETAILS FROM CENTER OF TANK

RING #, Initial Number Required : 1 13.252


Number after multiple/space check: 14
Outer edge # and spacing (in): 0 79.512 13.71
Inner edge # and spacing (in): 0 0.000

RAFTER SHAPE DETAILS FROM TANK CENTER

RING Number: 1

Rafter 1
Spacing 1 = 79.512 Spacing 2 = 0.000
Avg width = 39.756 Unit area load = 0.056 Allow Strs = 23200.000
Unit load, Moment, Required Sect Mod: 2.22 7508.94 0.32
Selected shape and Sect Modulus : ISMB100 3.14
Finalized shape and unit weight : ISMB100 7.70
Cumulative Rafter Weight : 1478.20

ROOF WEIGHT SUMMARY


Weight of Roof Plates (lb): 5576.634
Weight of Roof Rafters (lb): 1478.196
Weight of Roof Girders (lb): 0.0000000
Weight of Roof Columns (lb): 0.0000000
TOTAL Roof Weight (lb): 7054.830

Over-riding roof input parameters


Weight of Roof plates (lb) : 5576.6
Weight of Roof Framing (lb): 1478.2
Percent (fraction) supported by Shell : 1.0000

Roof Angle used: 9.2000


Fy value used (psi): 36000.
App M Factor used: 1.0000
Area used (sq.in.): 0.77500

Design Pressure, F.4.1


P (inches of Water): 6.9683
P (psi) : 0.25163

WIND OVERTURNING STABILITY CHECK


Wind uplift pressure (psi): 0.21899
Wind uplift area (sq.in.): 98607.
Velocity Factor: 1.0512
Weight for anchorage (lb): 16743.
MDL (ft-lb): 0.16487E+06
MF (ft-lb): 0.48360E+06
MPI (ft-lb): 0.00000
MW (ft-lb): 0.56237E+06
MWS (ft-lb): 0.24355E+06
wa (lb/ft): 353.11
Design tension load per bolt (lb): 4897.3
Estimated Number of anchors: 12
Anchors needed for Section 5.11

APPENDIX F CONSIDERATIONS
Uplift Pressure Force (lb): 0.00000
Resisting Weight (lb) : 29955.
Sections F.2 through F.6 can be used.

Roof Angle used: 9.2000


Fy value used (psi): 36000.
App M Factor used: 1.0000
TANK 2016, API-650/653/620 Analysis 10
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

Area used (sq.in.): 0.77500

Design Pressure, F.4.1


P (inches of Water): 6.9683
P (psi) : 0.25163

Required Roof Compression Area F.5


Compression Area (in^2) from F.5.1 : 0.00000
Participating Area (in^2) from 5.10.5: 0.25044

FRANGIBLE JUNCTION LIMIT (5.10.2.5.3)


Maximum Area at Junction (in^2): 0.66544

Failure Pressure f/ Compression Ring F.6


Failure Pressure (inches of water): 9.9599
Failure Pressure (psi) : 0.35965

Flexible Nozzle Data for Nozzle #: 1 1

Tank thickness for DESIGN case


Nozzle stiffnesses per PVP-1279
Tank diameter (ft): 29.528
Shell thickness (in): 0.47244
Nozzle Diameter (in): 24.000
Nozzle thickness (in): 0.00000
Repad outer diameter (in): 0.00000
Nozzle height from bottom (in): 29.528
Elastic Modulus of Shell (lb/sq.in): 0.29500E+08
Reinforcing location: Shell

The tank diameter is outside the range


procedure. (Valid range is 30-300 feet

BETA: 0.14046
Deflection, W (in): 0.23680E-01
Rotation, Theta (deg): 0.91840E-02
Coefficient Xa/SQRT(RT): 4.5391
Coefficient Xb/SQRT(RT): 1.9158
Coefficient Xc/SQRT(RT): 3.2275
Lambda: 1.3117
Interpolated Yf: 0.96000
Interpolated Yl: 2.3351
Interpolated Yc: 1.8880
Nomograph limit XBN: 0.10000
Nomograph limit XAN: 0.10000
Nomograph limit XCN: 0.10000
Pressure Force: 4727.2
Axis Force limit: 0.14451E-03
Axis Long Moment limit: 0.99021E-05
Axis Circum. Moment limit: 0.12247E-04
Max Force (lb): 691.97
Max Long. Moment (in-lb): 10099.
Max Long. Moment (in-lb): -10099.
Min Long. Moment (in-lb): 8165.2

Tank thickness for TEST case


Nozzle stiffnesses per PVP-1279
Tank diameter (ft): 29.528
Shell thickness (in): 0.47244
Nozzle Diameter (in): 24.000
Nozzle thickness (in): 0.00000
Repad outer diameter (in): 0.00000
Nozzle height from bottom (in): 29.528
Elastic Modulus of Shell (lb/sq.in): 0.29500E+08
Reinforcing location: Shell
TANK 2016, API-650/653/620 Analysis 11
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

The tank diameter is outside the range


procedure. (Valid range is 30-300 feet

BETA: 0.14046
Deflection, W (in): 0.23680E-01
Rotation, Theta (deg): 0.91840E-02
Coefficient Xa/SQRT(RT): 4.5391
Coefficient Xb/SQRT(RT): 1.9158
Coefficient Xc/SQRT(RT): 3.2275
Lambda: 1.3117
Interpolated Yf: 0.96000
Interpolated Yl: 2.3351
Interpolated Yc: 1.8880
Nomograph limit XBN: 0.10000
Nomograph limit XAN: 0.10000
Nomograph limit XCN: 0.10000
Pressure Force: 4727.2
Axis Force limit: 0.14451E-03
Axis Long Moment limit: 0.99021E-05
Axis Circum. Moment limit: 0.12247E-04
Max Force (lb): 691.97
Max Long. Moment (in-lb): 10099.
Max Long. Moment (in-lb): -10099.
Min Long. Moment (in-lb): 8165.2

Tank thickness for USER case


Nozzle stiffnesses per PVP-1279
Tank diameter (ft): 29.528
Shell thickness (in): 0.47244
Nozzle Diameter (in): 24.000
Nozzle thickness (in): 0.00000
Repad outer diameter (in): 0.00000
Nozzle height from bottom (in): 29.528
Elastic Modulus of Shell (lb/sq.in): 0.29500E+08
Reinforcing location: Shell

The tank diameter is outside the range


procedure. (Valid range is 30-300 feet

BETA: 0.14046
Deflection, W (in): 0.23680E-01
Rotation, Theta (deg): 0.91840E-02
Coefficient Xa/SQRT(RT): 4.5391
Coefficient Xb/SQRT(RT): 1.9158
Coefficient Xc/SQRT(RT): 3.2275
Lambda: 1.3117
Interpolated Yf: 0.96000
Interpolated Yl: 2.3351
Interpolated Yc: 1.8880
Nomograph limit XBN: 0.10000
Nomograph limit XAN: 0.10000
Nomograph limit XCN: 0.10000
Pressure Force: 4727.2
Axis Force limit: 0.14451E-03
Axis Long Moment limit: 0.99021E-05
Axis Circum. Moment limit: 0.12247E-04
Max Force (lb): 691.97
Max Long. Moment (in-lb): 10099.
Max Long. Moment (in-lb): -10099.
Min Long. Moment (in-lb): 8165.2

Each item below has 3 values for Design, Test, & Input Thck

Radial Stiffness (lb/in) 0.00000 0.00000 0.00000


TANK 2016, API-650/653/620 Analysis 12
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

Long. Stiffness (lb/in/deg) 0.00000 0.00000 0.00000


Circum. Stiffness (lb/in/deg) 0.00000 0.00000 0.00000
Radial Displacement (in) 0.23680E-01 0.23680E-01 0.23680E-01
Longitudinal Rotation (deg) 0.91840E-02 0.91840E-02 0.91840E-02
Max Allowed Radial Force (lb) 691.97 691.97 691.97
Max Allowed Long. Moment (in-lb) 10099. 10099. 10099.
Min Allowed Long. Moment (in-lb) -10099. -10099. -10099.
Max Allowed Circum. Moment (in-lb) 8165.2 8165.2 8165.2

Total weight of Roof Plates (lb): 5576.6


Corroded weight of Roof Plates (lb): 5576.6

W1 (lbs) .................... 15265.


W2 (lbs) .................... 16743.
W3 (lbs) .................... 28477.

Initial Number of Anchors: 16.000


Bolt Circle Circumference: 93.588
Maximum Allowed Bolt Spacing: 10.000

Case Uplift, Allowable, Load/Bolt


Design Pressure 0.0 15000.0 0.0
Test Pressure 0.0 20000.0 0.0
Failure Pressure 0.0 36000.0 0.0
Wind Loading 37823.3 28800.0 2364.0
Seismic OPE 0.0 28800.0 0.0
Seismic Test 0.0 28800.0 0.0
Design Press + Wind Load 0.0 20000.0 0.0
Design Press + Seismic OPE 0.0 28800.0 0.0
Design Press + Seismic Test 0.0 28800.0 0.0
Frangibility Pressure 0.0 36000.0 0.0

Anchor Bolt Initial Design


Case | Number | Diameter | Stre
Wind Loading | 16 | 1.250 | 2483.1 |

Anchor Bolt Final Design


Case | Number | Diameter | Stre
Wind Loading | 16 | 1.250 | 2483.1 |

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016


TANK 2016, API-650/653/620 Analysis 13
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

API-650 12th Edition, Addendum 2, January 2016

Wind Information:
------------------------------------------------------------------------------
Wind Velocity ...................................... 55.000 m/sec
Velocity Factor .................................... 1.0512
Wind Pressure ...................................... 1.7975 kPa
Area Exposed to Wind ............................... 0.84280E+08 mm.^2
Sect 5.9.7.1 Wind Moment on Tank ................... 0.52344E+06 ft.lb.
Wind Shear Force Acting on Tank .................... 34058. lb.
Wind Girder Height Reduction Factor ................ 1.0000

Material Property Information:


------------------------------------------------------------------------------

The following material properties have been modified in


accordance with API-650 (and API-653 where applicable).

Course | Material Name | Design Stress| Test Stress | App M |


Number | | (Sd or Sts) | (St) | Reduction |
| | (lb./sq.in.) | (lb./sq.in.) | |
--------------------------------------------------------------------
1 | A36,Mod | 23200. | 24900. | 1.0000 |
2 | A36,Mod | 23200. | 24900. | 1.0000 |
3 | A36,Mod | 23200. | 24900. | 1.0000 |
4 | A36,Mod | 23200. | 24900. | 1.0000 |
5 | A36,Mod | 23200. | 24900. | 1.0000 |

Shell Course Thickness Data - One Foot Method


------------------------------------------------------------------------------

| Thickness Values for Three Cases |Min. Temp| |


Course | Design | Test | User | (deg C )| Status |
# | (mm. ) | (mm. ) | (mm. ) | |Pass/Fail |
------------------------------------------------------------------------
1 | 6.0000 | 6.0000 | 6.0000 | -23.3 | NA |
2 | 5.0000 | 5.0000 | 5.0000 | -23.3 | NA |
3 | 5.0000 | 5.0000 | 5.0000 | -23.3 | NA |
4 | 5.0000 | 5.0000 | 5.0000 | -23.3 | NA |
5 | 5.0000 | 5.0000 | 5.0000 | -23.3 | NA |

Shell Course Allowed Fluid Heights:


------------------------------------------------------------------------------

| Fluid Heights for Three Cases |


Course | Design | Test | Required |
| (mm. ) | (mm. ) | (mm. ) |
-------------------------------------------------------
1| 11184. | 23657. | 8100.0 |
2| 7557.5 | 19765. | 6300.0 |
3| 7557.5 | 19765. | 4500.0 |
4| 7557.5 | 19765. | 2700.0 |
5| 7557.5 | 19765. | 900.00 |

Maximum Allowed Fluid Height of Entire Tank For:


Design Thickness Case ............................. 9357.5 mm.
Test Thickness Case ............................. 21565. mm.
Required fluid height ............................. 8100.0 mm.

Base Plate Details - Shell Weight & Center of Gravity:


------------------------------------------------------------------------------
Weight of Shell + Nozzles .......................... 22900. lb.
Total Weight of all Nozzles ........................ 0.00000 lb.
TANK 2016, API-650/653/620 Analysis 14
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

Center of Gravity (Shell+Nozzles) .................. 4361.5 mm.

Wind Overturning Stability Check:


------------------------------------------------------------------------------
Corroded Shell Weight + %Roof - Uplift ............. 16743. lb.
Line Load ......................................[wa] 29.426 lb./in.
Moment due to wind (hor+ver) press .............[Mw] 46864. ft.lb.
Moment due to wind (hor) press ................[Mws] 0.24355E+06 ft.lb.
Moment due to internal pressure ...............[Mpi] 0.00000 ft.lb.
Moment due to tank liquid ......................[Mf] 0.48360E+06 ft.lb.
Moment due to shell & roof ....................[Mdl] 0.16486E+06 ft.lb.

Wind Girder Information:


------------------------------------------------------------------------------
For "open top" tanks ...
Required Section Modulus, Top Girder ............... 44346. mm.^3
Table 5-20 Detail, B value ......................... b 0.00 mm.
Table 5-20 Shape name (if applicable)............... 3x3x.375

Maximum Height of Unstiffened Shell ................ 18642. mm.

Wind Girder - Transformed Section Method


Number of Intermediate Girders Reqd ................ 0

Weight Summary:
------------------------------------------------------------------------------
Shell (Corroded) ................................... 9689. lb.
Shell (Non-Corroded) ............................... 22900. lb.
Bottom Plate ....................................... 6756. lb.
Nozzles ............................................ 0. lb.
Roof Plates ........................................ 5577. lb.
Roof Framing/Structure ............................. 1478. lb.
Shell Attachments .................................. 0. lb.
Shell + Roof Insulation ............................ 0. lb.
Operating Fluid .................................... 1134212. lb.
Water Weight ....................................... 1260302. lb.

Operating Weight (Non-Corroded) .................... 1170923. lb.


Test Weight (Non-Corroded, Filled to Top)........... 1297013. lb.
Empty Weight (Non-Corroded) ........................ 36711. lb.

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016


TANK 2016, API-650/653/620 Analysis 15
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

API-650 12th Edition, Addendum 2, January 2016

TANK - Roof Design/Analysis Data

Rafter Supported Cone Roof Structural Library: INDIAN


Roof thickness per 5.10.2.2, Cone Roof ............. 5.0000 mm.

Total weight of Roof Plates ........................ 5576.6 lb.


Based on user input thickness
User Specified Design Roof Load .................... 0.38490 kPa
including user plate thickness
Computed Design Roof Load .......................... 0.38490 kPa
including user plate thickness

Computed Number of Rafter Rings: 1

Rafter Details from Tank Center


Ring |Number| Outer |NUM/| Inner |NUM/| Max Length |
| | Spacing|GRDR| Spacing|GRDR| (ft. ) |
| | (in. )| | (in. )| | |
-------------------------------------------------------------
1 | 14 | 2019.595 |( 0)| 0.000 |( 0)| 4178.755 |

Rafter Size Details from Tank Center


Ring| Rafter Load | Selected | --Section Modulus-- |
| (lb./in. ) | Shape | Required Actual |
| | | (mm.^3 ) (mm. **3) |
--------------------------------------------------------------
1 | 2.861 |ISMB100 | 6837.56| 51500.28|

ROOF WEIGHT SUMMARY


------------------------------------------------------------------------------
Weight of Roof Plates .............................. 5576.6 lb.
Weight of Roof Rafters ............................. 1478.2 lb.
TOTAL Roof Weight .................................. 7054.8 lb.

Roof Evaluations - Appendix F


------------------------------------------------------------------------------
Uplift force due to internal pressure............... 0.00000 lb.
Total weight resisting uplift ...................... 29955. lb.

Max Design Pressure, roof/shell joint.............. 6.9683 in of H2O


Max Design Pressure, roof/shell joint.............. 1.7349 kPa
(According to F.4.1)

Compression Ring Failure Pressure .................. 9.9599 in of H2O


Compression Ring Failure Pressure .................. 2.4797 kPa
(According to F.6)

Required Compression Areas, Roof/Shell Junction


Area as per Section F.5 ........................... 0.00000 mm.^2

Frangible Roof-to-Shell Junction Area Limit:


Area as per Section 5.10.2.6 ....................... 429.31 mm.^2

API 650 Appendix F Calculations:

Nominal Tank Weight


= Shell Weight + Roof Weight + Framing Weight + Attachment Weight
= 22900.4 + 5576.6 + 1478.2 + 0.0
= 29955.2 lb.
TANK 2016, API-650/653/620 Analysis 16
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

Note: The uplift was less than the total weight.

Appendix M Yield Stress reduction factor, M.3.6 [Mfact]:


= Yield Reduction Factor * Fy / Fyamb
= 1.000 * 36000.0/30000.0
= 1.000 Must be less than or equal to 1.0

Note: Using the new (uncorroded) roof weight in Appendix F calculations.

Note: The tank is considered anchored since anchor bolts are specified,
therefore Appendix F.4.2 calculations are not required.

Design Pressure per F.4.1 [P]:


= (0.962 * A * Fy * Mfact * tan(theta))/(D^2) + 0.245 * DLR/D^2
= (0.962*0.775*36000.0*1.000*tan(9.20))/(29.5^2)+0.245*7054/29.5^2
= 6.968 in. of water [176.996 mm. of water]
= 0.252 psi

Note: Design Pressure was less than maximum computed per F.4.1

Required Area of the Roof/Shell Junction per F.5.1 [A]:


= D^2(Pi-0.245*DLR/D^2)/(0.962*Fy*Mfact(tan(theta)))
= 29.5^2(0.000 -0.245*7054/29.5^2)/(0.962 *36000.0 *1.000 (tan(9.20 )))
= 0.000 in.^2

Maximum Frangible Roof Area 5.10.2.6 [A]:


= DLs/( 2 * pi * Fy * Mfact * tan(theta))
= 24378.6/( 2 * pi * 36000.0 * 1.000 * tan(9.20 ))
= 0.665 in.^2 [429.313 mm.^2]

Calculated failure Pressure from F.6 [Pf]:


= 1.6 * P - (0.147 * Dlr)/D^2
= 1.6 * 6.968 - (0.147 * 7054 )/29.5^2
= 9.960 in. of water [252.981 mm. of water]

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016


TANK 2016, API-650/653/620 Analysis 17
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

API-650 12th Edition, Addendum 2, January 2016

Anchor Bolt Results - Section 5.12


------------------------------------------------------------------------------

| Uplift | Allowable | Load/Bolt |


| (lb.) | Bolt Stress | (lb.) |
Load Case | | (lb./sq.in.) | |
------------------------------------------------------------------------
Wind Loading | 37823.3 | 28800. | 2363 |

Anchor Bolt Results - Section 5.12


------------------------------------------------------------------------------

| Number | Bolt | Bolt Stress |


| of Bolts | Diameter | (lb./sq.in.) |
Load Case | | (mm ) | |
-------------------------------------------------------------------------
Wind Loading | 16 | 31.750 | 2483 |

Final Anchor Bolt Spacing .............. (mm. ) 1782.85

Specified number of user bolts is sufficient.


Specified user bolt diameter is sufficient.

Bolt Load Calculations per API 650 Table 5.21b:

Compute weight per table 5.21b [W1]:


= Corr. Shell Wght + Attachment Wght + ( Corr. Roof Wght + Ins. ) * %
= 9688.7 + 0.0 + ( 5576.6 + 0.0 ) * 1.00
= 15265.3 lb.

Compute weight per table 5.21b [W2]:


= (Corr. Shell Wght + Ins. Wght)+Att. Wght+(Roof Wght + Fram Wght + Ins.)*%
= ( 9688.7 ) + 0.0 + ( 5576.6 + 1478.2 + 0.0 )*1.00
= 16743.5 lb.

Compute weight per table 5.21b [W3]:


= Nom. Shell Wght + Attachment Wght + (Nom. Roof Wght + Ins. Wght) * %
= 22900.4 + 0.0 + (7054.8 + 0.0 ) * 1.00
= 28477.1 lb.

Net Uplift due to Wind Pressure:


= PWR * D^2 * 4.08 + [4 * MWS/D] - W2
= 6.065 * 29.5^2 * 4.08 + [4 * 243554/29.5 ] - 16743.5
= 37823.3 lb.

Note:
The Frangibility case was not analyzed because the design
pressure was zero or the frangibilty requirements in
API 650 paragraph 5.10.2.6 were not met.

Initial Bolt Design for each Load Case (mm., lb./sq.in. & mm.^2):

Anchor Bolt Database: TEMA-Imperial

Case | Number | Diameter | Stress | Bolt Area |


-----------------------------------------------------------------------------
Wind Loading | 16 | 31.750 | 2483.1 | 614.1995 |

Final Bolt Design for each Load Case (mm., lb./sq.in. & mm.^2):
TANK 2016, API-650/653/620 Analysis 18
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

Case | Number | Diameter | Stress | Bolt Area |


-----------------------------------------------------------------------------
Wind Loading | 16 | 31.750 | 2483.1 | 614.1995 |

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016


TANK 2016, API-650/653/620 Analysis 19
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

API-650 12th Edition, Addendum 2, January 2016

Nozzle Flexibilities & Loads - Appendix P:

Load Condition | Design | Test | User |


Nozzle: 1 | | | |
---------------------------------------------------------------------------
Radial Stiffness (lb./in. ) | 0.00000| 0.00000| 0.00000|
Long. Bending Stiff(N.m./deg ) | 0.00000| 0.00000| 0.00000|
Circ. Bending Stiff(N.m./deg ) | 0.00000| 0.00000| 0.00000|
Radial Deflection (mm. ) | 0.60146 | 0.60146 | 0.60146 |
Long. Rotation (deg. ) | 0.91840E-02| 0.91840E-02| 0.91840E-02|
---------------------------------------------------------------------------
Radial Force Multp (1/lb. ) | 0.14451E-03| 0.14451E-03| 0.14451E-03|
Long. Moment Multp (1/ft.lb. ) | 0.11883E-03| 0.11883E-03| 0.11883E-03|
Circ. Moment Multp (1/ft.lb. ) | 0.14697E-03| 0.14697E-03| 0.14697E-03|
---------------------------------------------------------------------------
Radial Force Limit (lb. ) | 691.97 | 691.97 | 691.97 |
+Long. Moment Limit(ft.lb. ) | 841.57 | 841.57 | 841.57 |
-Long. Moment Limit(ft.lb. ) | -841.57 | -841.57 | -841.57 |
Circ. Moment Limit (ft.lb. ) | 680.43 | 680.43 | 680.43 |

Note: Nozzle 2 was on the roof. No flexibility calculations performed.

Nozzle Stiffness Calculations:

Design Case for Nozzle, 1 per PVP-1279:


------------------------------------------------------------------------------

Characteristic parameter per P.2.3 [beta]:


= 1.285 / (Rt)^0.5
= 1.285/(177.165 * 0.472 )^0.5
= 0.14046E+00 1/in. [0.55298E-02 1/mm.]

Unrestrained radial growth of the shell per P.2.5.1 [W]:


= (0.036*G*H*R^2)/Et
* [1-(e^-(beta*L)) * cos(beta*L) - (L/H)]
+ alpha * R * delta[T]
= (0.036*1.000 *318.898 *177.165^2)/29500000 *0.472
* [1-(e^-(0.140 *29.528 )) * cos(0.140 *29.528 ) - (29.528/318.90 )]
+ 0.000E+00 * 177.165 * 0.000
= 0.02368 in. [0.60146 mm.]

Unrestrained shell rotation of the shell per P.2.5.2 [theta]:


= (0.036*G*H*R^2)/E*t
* [(1/H)-(beta*e^-(beta*L))
* [cos(beta*L)+sin(beta*L)]]
= (0.036*1.000 *318.898 *177.165^2)/29500000 *0.472
* [(1/318.898 )-(0.140 *e^-(0.140 *29.528 ))
* [cos(0.140 *29.528 )+sin(0.140 *29.528 )]]
= 0.91840E-02 deg

Value of lamda per P.2.3 [lamda]:


= a/(Rt)^0.5
= 12.000/(177.165 * 0.472 )^0.5
= 1.312

Coefficient XA per P.2.3:


= L + a
= 29.528 + 12.000
= 41.528 in. [1054.800 mm.]

Coefficient XB per P.2.3:


TANK 2016, API-650/653/620 Analysis 20
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

= L - a
= 29.528 - 12.000
= 17.528 in. [445.200 mm.]

Coefficient XC per P.2.3:


= L
= 29.528 in. [750.000 mm.]

Coefficients YF and YL from figure P-4A based on lamda:


YF = 0.960
YL = 2.335

Coefficient YC from figure P-4B based on lamda:


YC = 1.888

Pressure end load on the opening per P.2.3:


= pi * a^2 * P
= 3.1415 * 12.000^2 * 10.449
= 4727.231 lbf.

Radial force nomogram limit values per figure P-3A:


= max[(1 - 0.75)(XA / (Rt)^0.5), 0.1]
= max[(1 - 0.75)(41.528/(177.165 *0.472 )^0.5), 0.1]
= 0.100

Longitudinal nomogram limit values per figure P-3A:


= max[(1 - 0.75)(XB / (Rt)^0.5), 0.1]
= max[(1 - 0.75)(17.528/(177.165 *0.472 )^0.5), 0.1]
= 0.100

Circumferential moment nomogram limit value per figure P-3B:


= max[(1 - 0.75)(XC / (Rt)^0.5), 0.1]
= max[(1 - 0.75)(29.528/(177.165 *0.472 )^0.5), 0.1]
= 0.100

Radial force multiplier per figure P-3A:


= lamda / (2 * YF * FP)
= 1.312/(2 * 0.960 * 4727.231 )
= 0.14451E-03 1/lbf.

Longitudinal moment multiplier per figure P-3A:


= lamda / (a / 12.0 * YL * FP)
= 1.312/(12.000/12.0 * 2.335 * 4727.231 )
= 0.11882E-03 1/ft.lb.

Circumferential moment multiplier per figure P-3B:


= lamda / (a * 12.0 * YC * FP)
= 1.312/(12.000 * 12.0 * 1.888 * 4727.231 )
= 0.14697E-03 1/ft.lb.

Radial force limit [ML = 0 and MC = 0] per figure P-3A [FRmax]:


= Radial force nomogram limit value / Radial force multp.
= 0.100/0.145E-03
= 0.69197E+03 lbf.

Positive Long. moment limit [MC = 0 and FR = 0] per figure P-3A [MLmax]:
= Long. moment nomogram limit value / Long. moment multiplier
= 0.100/0.119E-03
= 0.84158E+03 ft.lb.

Negative Long. moment limit [ML = 0 and MC = 0] per figure P-3A [MLmin]:
= - Radial Force nomogram limit value / Long. moment multiplier
= -0.100/0.119E-03
= -0.84158E+03 ft.lb.
TANK 2016, API-650/653/620 Analysis 21
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

Circ. moment limit [ML = 0 and FR = 0] per figure P-3B [MCmax]:


= Circ. moment nomogram limit value / Circ. moment multiplier
= 0.100/0.147E-03
= 0.68043E+03 ft.lb.

Test Case for Nozzle, 1 per PVP-1279:


------------------------------------------------------------------------------

Characteristic parameter per P.2.3 [beta]:


= 1.285 / (Rt)^0.5
= 1.285/(177.165 * 0.472 )^0.5
= 0.14046E+00 1/in. [0.55298E-02 1/mm.]

Unrestrained radial growth of the shell per P.2.5.1 [W]:


= (0.036*G*H*R^2)/Et
* [1-(e^-(beta*L)) * cos(beta*L) - (L/H)]
+ alpha * R * delta[T]
= (0.036*1.000 *318.898 *177.165^2)/29500000 *0.472
* [1-(e^-(0.140 *29.528 )) * cos(0.140 *29.528 ) - (29.528/318.90 )]
+ 0.000E+00 * 177.165 * 0.000
= 0.02368 in. [0.60146 mm.]

Unrestrained shell rotation of the shell per P.2.5.2 [theta]:


= (0.036*G*H*R^2)/E*t
* [(1/H)-(beta*e^-(beta*L))
* [cos(beta*L)+sin(beta*L)]]
= (0.036*1.000 *318.898 *177.165^2)/29500000 *0.472
* [(1/318.898 )-(0.140 *e^-(0.140 *29.528 ))
* [cos(0.140 *29.528 )+sin(0.140 *29.528 )]]
= 0.91840E-02 deg

Value of lamda per P.2.3 [lamda]:


= a/(Rt)^0.5
= 12.000/(177.165 * 0.472 )^0.5
= 1.312

Coefficient XA per P.2.3:


= L + a
= 29.528 + 12.000
= 41.528 in. [1054.800 mm.]

Coefficient XB per P.2.3:


= L - a
= 29.528 - 12.000
= 17.528 in. [445.200 mm.]

Coefficient XC per P.2.3:


= L
= 29.528 in. [750.000 mm.]

Coefficients YF and YL from figure P-4A based on lamda:


YF = 0.960
YL = 2.335

Coefficient YC from figure P-4B based on lamda:


YC = 1.888

Pressure end load on the opening per P.2.3:


= pi * a^2 * P
= 3.1415 * 12.000^2 * 10.449
= 4727.231 lbf.

Radial force nomogram limit values per figure P-3A:


= max[(1 - 0.75)(XA / (Rt)^0.5), 0.1]
= max[(1 - 0.75)(41.528/(177.165 *0.472 )^0.5), 0.1]
TANK 2016, API-650/653/620 Analysis 22
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

= 0.100

Longitudinal nomogram limit values per figure P-3A:


= max[(1 - 0.75)(XB / (Rt)^0.5), 0.1]
= max[(1 - 0.75)(17.528/(177.165 *0.472 )^0.5), 0.1]
= 0.100

Circumferential moment nomogram limit value per figure P-3B:


= max[(1 - 0.75)(XC / (Rt)^0.5), 0.1]
= max[(1 - 0.75)(29.528/(177.165 *0.472 )^0.5), 0.1]
= 0.100

Radial force multiplier per figure P-3A:


= lamda / (2 * YF * FP)
= 1.312/(2 * 0.960 * 4727.231 )
= 0.14451E-03 1/lbf.

Longitudinal moment multiplier per figure P-3A:


= lamda / (a / 12.0 * YL * FP)
= 1.312/(12.000/12.0 * 2.335 * 4727.231 )
= 0.11882E-03 1/ft.lb.

Circumferential moment multiplier per figure P-3B:


= lamda / (a * 12.0 * YC * FP)
= 1.312/(12.000 * 12.0 * 1.888 * 4727.231 )
= 0.14697E-03 1/ft.lb.

Radial force limit [ML = 0 and MC = 0] per figure P-3A [FRmax]:


= Radial force nomogram limit value / Radial force multp.
= 0.100/0.145E-03
= 0.69197E+03 lbf.

Positive Long. moment limit [MC = 0 and FR = 0] per figure P-3A [MLmax]:
= Long. moment nomogram limit value / Long. moment multiplier
= 0.100/0.119E-03
= 0.84158E+03 ft.lb.

Negative Long. moment limit [ML = 0 and MC = 0] per figure P-3A [MLmin]:
= - Radial Force nomogram limit value / Long. moment multiplier
= -0.100/0.119E-03
= -0.84158E+03 ft.lb.

Circ. moment limit [ML = 0 and FR = 0] per figure P-3B [MCmax]:


= Circ. moment nomogram limit value / Circ. moment multiplier
= 0.100/0.147E-03
= 0.68043E+03 ft.lb.

User Case for Nozzle, 1 per PVP-1279:


------------------------------------------------------------------------------

Characteristic parameter per P.2.3 [beta]:


= 1.285 / (Rt)^0.5
= 1.285/(177.165 * 0.472 )^0.5
= 0.14046E+00 1/in. [0.55298E-02 1/mm.]

Unrestrained radial growth of the shell per P.2.5.1 [W]:


= (0.036*G*H*R^2)/Et
* [1-(e^-(beta*L)) * cos(beta*L) - (L/H)]
+ alpha * R * delta[T]
= (0.036*1.000 *318.898 *177.165^2)/29500000 *0.472
* [1-(e^-(0.140 *29.528 )) * cos(0.140 *29.528 ) - (29.528/318.90 )]
+ 0.000E+00 * 177.165 * 0.000
= 0.02368 in. [0.60146 mm.]

Unrestrained shell rotation of the shell per P.2.5.2 [theta]:


TANK 2016, API-650/653/620 Analysis 23
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

= (0.036*G*H*R^2)/E*t
* [(1/H)-(beta*e^-(beta*L))
* [cos(beta*L)+sin(beta*L)]]
= (0.036*1.000 *318.898 *177.165^2)/29500000 *0.472
* [(1/318.898 )-(0.140 *e^-(0.140 *29.528 ))
* [cos(0.140 *29.528 )+sin(0.140 *29.528 )]]
= 0.91840E-02 deg

Value of lamda per P.2.3 [lamda]:


= a/(Rt)^0.5
= 12.000/(177.165 * 0.472 )^0.5
= 1.312

Coefficient XA per P.2.3:


= L + a
= 29.528 + 12.000
= 41.528 in. [1054.800 mm.]

Coefficient XB per P.2.3:


= L - a
= 29.528 - 12.000
= 17.528 in. [445.200 mm.]

Coefficient XC per P.2.3:


= L
= 29.528 in. [750.000 mm.]

Coefficients YF and YL from figure P-4A based on lamda:


YF = 0.960
YL = 2.335

Coefficient YC from figure P-4B based on lamda:


YC = 1.888

Pressure end load on the opening per P.2.3:


= pi * a^2 * P
= 3.1415 * 12.000^2 * 10.449
= 4727.231 lbf.

Radial force nomogram limit values per figure P-3A:


= max[(1 - 0.75)(XA / (Rt)^0.5), 0.1]
= max[(1 - 0.75)(41.528/(177.165 *0.472 )^0.5), 0.1]
= 0.100

Longitudinal nomogram limit values per figure P-3A:


= max[(1 - 0.75)(XB / (Rt)^0.5), 0.1]
= max[(1 - 0.75)(17.528/(177.165 *0.472 )^0.5), 0.1]
= 0.100

Circumferential moment nomogram limit value per figure P-3B:


= max[(1 - 0.75)(XC / (Rt)^0.5), 0.1]
= max[(1 - 0.75)(29.528/(177.165 *0.472 )^0.5), 0.1]
= 0.100

Radial force multiplier per figure P-3A:


= lamda / (2 * YF * FP)
= 1.312/(2 * 0.960 * 4727.231 )
= 0.14451E-03 1/lbf.

Longitudinal moment multiplier per figure P-3A:


= lamda / (a / 12.0 * YL * FP)
= 1.312/(12.000/12.0 * 2.335 * 4727.231 )
= 0.11882E-03 1/ft.lb.

Circumferential moment multiplier per figure P-3B:


TANK 2016, API-650/653/620 Analysis 24
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

= lamda / (a * 12.0 * YC * FP)


= 1.312/(12.000 * 12.0 * 1.888 * 4727.231 )
= 0.14697E-03 1/ft.lb.

Radial force limit [ML = 0 and MC = 0] per figure P-3A [FRmax]:


= Radial force nomogram limit value / Radial force multp.
= 0.100/0.145E-03
= 0.69197E+03 lbf.

Positive Long. moment limit [MC = 0 and FR = 0] per figure P-3A [MLmax]:
= Long. moment nomogram limit value / Long. moment multiplier
= 0.100/0.119E-03
= 0.84158E+03 ft.lb.

Negative Long. moment limit [ML = 0 and MC = 0] per figure P-3A [MLmin]:
= - Radial Force nomogram limit value / Long. moment multiplier
= -0.100/0.119E-03
= -0.84158E+03 ft.lb.

Circ. moment limit [ML = 0 and FR = 0] per figure P-3B [MCmax]:


= Circ. moment nomogram limit value / Circ. moment multiplier
= 0.100/0.147E-03
= 0.68043E+03 ft.lb.

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016


TANK 2016, API-650/653/620 Analysis 25
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

Anchor Chair Cap Input Values:

Thickness of Gusset Plates j 16.000 mm.


Width of Gussets at Top Plate twdt 120.000 mm.
Width of Gussets at Base Plate bwdt 120.000 mm.
Height of Gussets hg 150.000 mm.
Height of Gussets plus top Plate thickness h 166.000 mm.
Distance between Gussets g 75.000 mm.
Dist. from Bolt Center to Gusset (Rg/2) cg 37.500 mm.
External Corrosion Allowance Ca 1.5000 mm.
Top Plate allowable stress S 58000.0 lb./sq.in.
Number of Gussets per bolt ng 2
Bottom Shell Course Thickness 6.000 mm.
Shell Course Corrosion Allowance 3.0000 mm.
Thickness of Tank Baseplate m 6.000 mm.

Thickness of Top Plate c 16.000 mm.


Radial Width of the Top Plate b 120.000 mm.
Circumferential Width of the Top Plate a 100.000 mm.
Anchor Bolt Diameter d 31.750 mm.

Anchor Chair Cap and Gusset Plate Analysis Results:

Required Thickness of Top Chair Cap Plate per AISI:


P Bolt Load
e Bolt eccentricity (center of bolt to shell OD)
Sb Allowable Bending Stress ( 1.5 * S )
g Distance between Gussets
d Bolt Diameter

Top Chair Cap Plate Required Thickness per AISI [Tc]:


= ( P /( Sb * e ) * ( 0.375 * g - 0.22 * d ))½ + c
= (7091/(87000*37.000)*(0.375*75.00-0.22*31.750))½+1.500
= 6.9816 mm.

Stress in the Top Plate at given Thickness [Stpl]:


= P( 0.375 * b - 0.22 * d ) / e / ( c - Ca )²
= 7091 (0.375*75.000 - 0.22*31.750 )/37.000/(16.000 -1.500 )²
= 12433.5 lb./sq.in., must be less than 87000.0 lb./sq.in.

Required Gusset Thickness per AISI:


Gusset Plate Thickness is the greater of( 0.5 in (12mm), 0.04( hg ))
= max( 12.700, 0.04( 150.000 ) ) + Ca
= 14.200 mm.

For gusset plates the following must also be true [English Units]:
Gusset Thickness * Average Gusset Width >= (P/1000)/25
= ( 0.630 - 0.059 ) * 4.724 > ( 7091.862/1000)/25 ) Passed
= 2.697 > 0.284 Passed

Local Stress at the Top Plate per AISI, including axial Stress [S]:
= P*e/t²[1.32*Z/(1.43*a*h²/(R*t)
+ (4(a)(h)²).333 + 0.031 /(R*t)½
= 7091*37.00/3.00²[1.32*0.87/(1.43*100.00*(166.00)²/(4503.00*3.00)
+ (4*100.00 (166.00 )²)0.333 + 0.031/(4503.00 *3.00 )½
= 47226.1 lb./sq.in.

Intermediate Value [Z]:


= 1/[(0.177*a*m/(R*t)½)*(m/t)² + 1]
= 1/[(0.177*100.000*6.000/(4503.000*3.000)½)*(6.000/3.000)²+1]
= 0.874

Radial Distance [e]:


= ( Dc - Ds ) / 2
TANK 2016, API-650/653/620 Analysis 26
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

= ( 9074.001 - 9000.001 )/2


= 37.000 mm.

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016


TANK 2016, API-650/653/620 Analysis 27
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

Determine Maximum allowed Fluid Heights:

For Course # 1, Operating Case

Allowed fluid height above this course based on the 1ft method
= (Td - ca)Sd/(2.6 * D * G ) + X/12
= (0.2362 - 0.1181 )23200.00/(2.6 * 29.5 * 1.000 ) + 12.000/12
= 36.692 ft. [11183.837 mm.]

For Course # 1, Hydro Case, not corroded

Allowed fluid height above this course based on the 1ft method
= (Td - ca)Sd/(2.6 * D * G ) + X/12
= (0.2362 - 0.0000 )24900.00/(2.6 * 29.5 * 1.000 ) + 12.000/12
= 77.615 ft. [23657.170 mm.]

For Course # 2, Operating Case

Allowed fluid height above this course based on the 1ft method
= (Td - ca)Sd/(2.6 * D * G ) + X/12
= (0.1969 - 0.1181 )23200.00/(2.6 * 29.5 * 1.000 ) + 12.000/12
= 24.795 ft. [7557.497 mm.]

For Course # 2, Hydro Case, not corroded

Allowed fluid height above this course based on the 1ft method
= (Td - ca)Sd/(2.6 * D * G ) + X/12
= (0.1969 - 0.0000 )24900.00/(2.6 * 29.5 * 1.000 ) + 12.000/12
= 64.846 ft. [19765.104 mm.]

For Course # 3, Operating Case

Allowed fluid height above this course based on the 1ft method
= (Td - ca)Sd/(2.6 * D * G ) + X/12
= (0.1969 - 0.1181 )23200.00/(2.6 * 29.5 * 1.000 ) + 12.000/12
= 24.795 ft. [7557.497 mm.]

For Course # 3, Hydro Case, not corroded

Allowed fluid height above this course based on the 1ft method
= (Td - ca)Sd/(2.6 * D * G ) + X/12
= (0.1969 - 0.0000 )24900.00/(2.6 * 29.5 * 1.000 ) + 12.000/12
= 64.846 ft. [19765.104 mm.]

For Course # 4, Operating Case

Allowed fluid height above this course based on the 1ft method
= (Td - ca)Sd/(2.6 * D * G ) + X/12
= (0.1969 - 0.1181 )23200.00/(2.6 * 29.5 * 1.000 ) + 12.000/12
= 24.795 ft. [7557.497 mm.]

For Course # 4, Hydro Case, not corroded

Allowed fluid height above this course based on the 1ft method
= (Td - ca)Sd/(2.6 * D * G ) + X/12
= (0.1969 - 0.0000 )24900.00/(2.6 * 29.5 * 1.000 ) + 12.000/12
= 64.846 ft. [19765.104 mm.]

For Course # 5, Operating Case

Allowed fluid height above this course based on the 1ft method
= (Td - ca)Sd/(2.6 * D * G ) + X/12
= (0.1969 - 0.1181 )23200.00/(2.6 * 29.5 * 1.000 ) + 12.000/12
= 24.795 ft. [7557.497 mm.]
TANK 2016, API-650/653/620 Analysis 28
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

For Course # 5, Hydro Case, not corroded

Allowed fluid height above this course based on the 1ft method
= (Td - ca)Sd/(2.6 * D * G ) + X/12
= (0.1969 - 0.0000 )24900.00/(2.6 * 29.5 * 1.000 ) + 12.000/12
= 64.846 ft. [19765.104 mm.]

Appendix M Yield Stress reduction factor, M.3.6 [Mfact]:


= Yield Reduction Factor * Fy / Fyamb
= 1.000 * 36000.0/30000.0
= 1.000 Must be less than or equal to 1.0

Note:
Computing the roof weight not including the corrosion allowance
per user request.

Roof Analysis:

Total Design External Pressure Loading per V.7 [Pr]:


= max[ DL + (Lr or S) + Fpe*Pe, DL + Pe + 0.4(Lr or S)]
= max[8.039 + max[0.000, 0.000 ] + 0.400 * 0.000,
8.039 + 0.000 + 0.4 * max[0.000, 0.000 ]]
= max[ 8.039, 8.039 ]
= 8.039 psf

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016


TANK 2016, API-650/653/620 Analysis 29
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

Wind Load Calculations:

Wind velocity factor 5.2.1 [Vfact]:


= ( Wind Velocity / 120 )^2
= ( 123.0/120 )^2
= 1.051

Vertical projected wind area of tank [VArea]:


= Tank Height * Insulated Tank Diameter
= 29.53 * 29.53
= 871.877 ft^2 [81000016.000 mm.^2]

Velocity pressure per 5.9.7.1 [p]:


= 0.00256 * Kz * Kzt * kd * V^2 * I * G + 5.0
= 0.00256 * 1.040 * 1.000 * 0.950 * 123.032^2 * 1.000 * 0.850 + 5.0
= 37.542 psf

Wind moment on shell [Moment]:


= Wind Pressure * Wind Area * Tank Height/2
= 37.542 * 871.9 * 29.53/2
= 0.48325E+06 ft.lb.

Vertical projected wind area of Cone roof:


= Roof Height * Roof triangular base
= 2.39 * 14.76
= 35.303 ft^2 [3279785.000 mm.^2]

Area Exposed to Wind:


= Wind area of tank + Wind area of roof
= 871.877 + 35.303
= 907.180 ft.^2 [84279800.000 mm.^2]

Wind moment at the base including the cone roof [Total Moment]:
= Moment + ( Wind P * Roof Area( Tank Height + Roof Height/3))
= 0.483E+06 + ( 37.542 * 35.3 ( 29.5 + 2.39/3))
= 0.52344E+06 ft.lb.

Wind shear force acting on the tank:


= Wind Pressure * (tank area + roof area)
= 37.542 * 907.2
= 0.34058E+05 lbf.

Moment about shell-to-bottom joint [MDL]:


= ( Shell Weight + Attachement Weight + Framing Weight * % )D/2
= ( 9688.7 + 0.0 + 1478.2 * 1.00 )29.5/2
= 164865.1 ft.lb

Resisting Weight of Fluid [WL]:


= min( 5.6 * tb * sqrt( Fby * H * min( 0.7, G )), 0.45 * H * D )
= min(5.6*0.1181*sqrt(38000.0*26.57*min(0.7,1.000)),0.45*26.6*29.53)
= min( 556.1, 353.1 )
= 353.1 lbf/ft

Moment from Fluid Weight [MF]:


= WL * ( PI * D ) * ( D / 2 )
= 353.1 * ( 3.1416 * 29.53 ) * ( 29.53/2 )
= 483598.9 ft.lb

Moment from Design Internal Pressure [MPI]:


= Design Pressure * pi( Diameter in inches / 2 )^2 * ( D / 2 )
= 0.0000 * 3.1416 ( 354.33/2 )^2 * ( 29.53/2 )
= 0.0 ft.lb

Design Pressure per F.4.1 [P]:


TANK 2016, API-650/653/620 Analysis 30
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

= (0.962 * A * Fy * Mfact * tan(theta))/(D^2) + 0.245 * DLR/D^2


= (0.962*0.775*36000.0*1.000*tan(9.20))/(29.5^2)+0.245*7054/29.5^2
= 6.968 in. of water [176.996 mm. of water]
= 0.252 psi

Note: Design Pressure was less than maximum computed per F.4.1

Moment about shell-to-bottom joint [MWS]:


= Pws * D * H^2/2
= 18 * Vfact * (D + Insulation) * H^2/2
= 18 * 1.0512 (29.5 + 0.0 ) * 29.5^2/2
= 243554.1 ft.lb

Moment about shell-to-bottom joint [MW]:


= MWS + Wind Uplift * VArea * D / 2
= 243554.1 + 0.2190 * 98607.0 * 29.5/2
= 562365.7 ft.lb

Moment about shell-to-bottom joint [MDLR]:


= ( Roof Weight )D/2
= ( 5576.6 )29.5/2
= 82332.2 ft.lb

Warning: The following API 650 Section 5.11.2.1 criteria were not met:
1) 0.6MW + MPI < MDL/1.5 + MDLR
2) MW + FP(MPI) < (MDL + MF)/2 + MDLR
3) MWS + FP(MPI) < MDL/1.5 + MDLR

Note: Anchorage is required for this design.

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016


TANK 2016, API-650/653/620 Analysis 31
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

Determine required thickness per the selected Method:

Shell Course Thickness per the One Foot Method:

Required Thickness for Course # 1

Required thickness based on the 1ft method per 5.6.3.2, Operating [td]:
= 2.6D( H - 1 )G/Sd
= 2.6 * 29.528 ( 26.57 - 1 )1.000/23200.0
= 0.085 in. [2.150 mm.]

Minimum thickness per 5.6.1.1 : = 0.236 in. [6.000 mm.]

Final Selected Thickness including corrosion and other allowances:


= 0.23622 in. [6.00000 mm.]

Required thickness per 5.6.3.2, Hydrotest [tt]:


= 2.6D( H - 1 )/St
= 2.6 * 29.528 ( 26.57 - 1 )/24900.0
= 0.07885 in. [2.00285 mm.]

Minimum thickness per 5.6.1.1 : = 0.236 in. [6.000 mm.]

Final Selected Thickness including other Code allowances:


= 0.23622 in. [6.00000 mm.]

Required Thickness for Course # 2

Required thickness based on the 1ft method per 5.6.3.2, Operating [td]:
= 2.6D( H - 1 )G/Sd
= 2.6 * 29.528 ( 20.67 - 1 )1.000/23200.0
= 0.065 in. [1.653 mm.]

Minimum thickness per 5.6.1.1 : = 0.197 in. [5.000 mm.]

Final Selected Thickness including corrosion and other allowances:


= 0.19685 in. [5.00000 mm.]

Required thickness per 5.6.3.2, Hydrotest [tt]:


= 2.6D( H - 1 )/St
= 2.6 * 29.528 ( 20.67 - 1 )/24900.0
= 0.06064 in. [1.54037 mm.]

Minimum thickness per 5.6.1.1 : = 0.197 in. [5.000 mm.]

Final Selected Thickness including other Code allowances:


= 0.19685 in. [5.00000 mm.]

Required Thickness for Course # 3

Required thickness based on the 1ft method per 5.6.3.2, Operating [td]:
= 2.6D( H - 1 )G/Sd
= 2.6 * 29.528 ( 14.76 - 1 )1.000/23200.0
= 0.046 in. [1.157 mm.]

Minimum thickness per 5.6.1.1 : = 0.197 in. [5.000 mm.]

Final Selected Thickness including corrosion and other allowances:


= 0.19685 in. [5.00000 mm.]

Required thickness per 5.6.3.2, Hydrotest [tt]:


= 2.6D( H - 1 )/St
= 2.6 * 29.528 ( 14.76 - 1 )/24900.0
= 0.04244 in. [1.07789 mm.]
TANK 2016, API-650/653/620 Analysis 32
Licensee: SHRITARA ENGINEERS AND PROJECT CONSULTANTS
Job: STORAGE TANK Date: Jun 21,2018 Time: 1:29pm

Minimum thickness per 5.6.1.1 : = 0.197 in. [5.000 mm.]

Final Selected Thickness including other Code allowances:


= 0.19685 in. [5.00000 mm.]

Required Thickness for Course # 4

Required thickness based on the 1ft method per 5.6.3.2, Operating [td]:
= 2.6D( H - 1 )G/Sd
= 2.6 * 29.528 ( 8.86 - 1 )1.000/23200.0
= 0.026 in. [0.661 mm.]

Minimum thickness per 5.6.1.1 : = 0.197 in. [5.000 mm.]

Final Selected Thickness including corrosion and other allowances:


= 0.19685 in. [5.00000 mm.]

Required thickness per 5.6.3.2, Hydrotest [tt]:


= 2.6D( H - 1 )/St
= 2.6 * 29.528 ( 8.86 - 1 )/24900.0
= 0.02423 in. [0.61541 mm.]

Minimum thickness per 5.6.1.1 : = 0.197 in. [5.000 mm.]

Final Selected Thickness including other Code allowances:


= 0.19685 in. [5.00000 mm.]

Required Thickness for Course # 5

Required thickness based on the 1ft method per 5.6.3.2, Operating [td]:
= 2.6D( H - 1 )G/Sd
= 2.6 * 29.528 ( 2.95 - 1 )1.000/23200.0
= 0.006 in. [0.164 mm.]

Minimum thickness per 5.6.1.1 : = 0.197 in. [5.000 mm.]

Final Selected Thickness including corrosion and other allowances:


= 0.19685 in. [5.00000 mm.]

Required thickness per 5.6.3.2, Hydrotest [tt]:


= 2.6D( H - 1 )/St
= 2.6 * 29.528 ( 2.95 - 1 )/24900.0
= 0.00602 in. [0.15293 mm.]

Minimum thickness per 5.6.1.1 : = 0.197 in. [5.000 mm.]

Final Selected Thickness including other Code allowances:


= 0.19685 in. [5.00000 mm.]