Motor Data and Wire Size Specifications FW0016

0113
®
Single and Three Phase Jet/Centrifugal Supersedes
Motors 1109

Single Phase Motor Data 60 Hz 3450 RPM( ¹) Chart A


Service Factor Motor Locked Rotor Motor KVA
Motor Service AMPS AMPS Code
Motor Model No. HP Voltage Factor 115V 230V 115V 230V Letter
98J103 1/3 115/230 1.75 8.6 4.3 26.0 13.0 K
98L105 1/2 115/230 1.20 8.6 4.3 26.0 13.0 G
98J105, 98S105, 98U105 1/2 115/230 1.60 13.0 6.5 36.0 18.0 K
98L107 3/4 115/230 1.00 13.0 6.5 36.0 18.0 G
98J107, 98S107, 98U107 3/4 115/230 1.50 14.0 7.0 52.0 26.0 K
98H107 3/4 115/230 1.86 18.0 9.0 78.0 39.0 P
98L110 1 115/230 1.12 14.0 7.0 52.0 26.0 H
98J110, 98S110, 98U110 1 115/230 1.40 18.0 9.0 78.0 39.0 L
98H110 1 115/230 1.95 21.0 10.5 98.0 49.0 N
98J115, 98S115 1-1/2 115/230 1.30 21.0 10.5 98.0 49.0 J
98H115 1-1/2 115/230 1.66 25.0 12.5 116.0 58.0 K
98J120, 98S120 2 115/230 1.25 25.0 12.5 116.0 58.0 H
98J630, 98S630 3 230 1.00 - 13.5 - 53.0 D
(¹) Thermal Overload Protected - Automatic Reset

Single Phase Motor Data 50 Hz 2875 RPM(¹) Chart B


Service Factor Motor Locked Rotor Motor
Service AMPS AMPS KVA Code
Motor Model No. HP Motor Voltage Factor 110V 220V 110V 220V Letter
98J003 1/3 110/220 1.75 7.6 3.8 44.0 22.0 R
98J005, 98S005 1/2 110/220 1.60 10.0 5.0 48.0 24.0 M
98J007, 98S007 3/4 110/220 1.50 14.4 7.2 64.0 32.0 L
98J010, 98S010 1 110/220 1.40 16.4 8.2 72.0 36.0 K
98J015, 98S015 1-1/2 110/220 1.30 23.6 11.8 104.0 52.0 K
98J820, 98S820 2 220 1.00 - 13.2 - 55.0 H
(¹) Thermal Overload Protected - Automatic Reset

Three Phase Motor Data 60/50(¹ ²) Hz 3450/2875 RPM Chart C


Service Factor Motor Locked Rotor Motor
Service AMPS AMPS KVA Code
Motor Model No. HP Motor Voltage Factor 230V 460V 230V 460V Letter
98J305, 98S305 1/2 208-230/460 1.60 3.5 1.75 19.0 9.5 K
98J307, 98S307 3/4 208-230/460 1.50 3.5 1.75 19.0 9.5 K
98J310, 98S310 1 208-230/460 1.40 4.5 2.25 26.9 13.5 K
98J315, 98S315 1-1/2 208-230/460 1.30 5.7 2.85 33.5 16.8 K
98J320, 98S320 2 208-230/460 1.25 7.4 3.70 44.0 22.0 K
98J330, 98S330 3 208-230/460 1.00 9.8 4.90 48.0 24.0 D
(¹) 3 HP, 3 phase motors are operable on 60Hz only - 3450 RPM
(²) Thermal Overload Protector - Not Supplied
Three phase motors must be installed with a properly sized magnetic or manual starter, both with properly sized heaters.
Install starter following the instruction of the starter manufacturer.

Minimum Wire Size Chart (Gauge) - Copper Wire Chart D


Distance in Feet from Motor to Service Panel
Motor HP Volts Phase Breaker Size (Amps)
0-50 50-100 100-150 150-200 200-300
0.33 115/230 1 14/14 14/14 12/14 10/14 8/14 15/15
0.5 115/230 1 14/14 12/14 10/14 8/14 6/12 15/15
0.75 115/230 1 14/14 10/14 8/14 8/14 6/12 15/15
1 115/230 1 12/14 10/14 8/14 6/12 4/10 20/15
1.5 115/230 1 10/14 8/14 6/14 6/12 4/10 30/15
2 115/230 1 10/14 8/14 6/12 4/10 4/10 30/15
3 230 1 12 12 10 10 8 20
0.75 230/460 3 14/14 14/14 14/14 14/14 14/14 15/15
1 230/460 3 14/14 14/14 14/14 14/14 14/14 15/15
1.5 230/460 3 14/14 14/14 14/14 14/14 12/14 15/15
2 230/460 3 14/14 14/14 14/14 12/14 12/14 15/15
3 230/460 3 14/14 14/14 12/14 12/14 10/14 15/15
Maximum 5% voltage drop calculated by conductor resistance in NEC Table 8 and minimum ampacity rating as defined by NEC 430.22
WIRING DIAGRAMS
JET / CENTRIFUGAL MOTORS ®

115 VOLT 230 VOLT


SINGLE PHASE SINGLE PHASE
LINE LINE

L1 L1
A B L2 A B L2

YELLOW

WHITE

GRAY

RED

TAN

YELLOW

WHITE

GRAY

RED

TAN
NOTE: Dual voltage motor, change the red and gray wire to voltage
required.
Figure 2 - Wiring Diagram for Single Phase 1/3 - 2 HP Motors

230 VOLT
SINGLE PHASE
LINE

L1 L2
YELLOW
BLACK

RED
WHITE

GRAY

GRAY

IL1680

NOTE: Single voltage (230V) motor, and cannot be connected to 115V.

Figure 3 - Wiring Diagram for Single Phase 3 HP Motors

LOW VOLTAGE 230V 3-ø HIGH VOLTAGE 460 V

4 5 6 4 5 6

7 8 9 7 8 9

1 2 3 1 2 3
L1 L2 L3 L1 L2 L3
IL0770
1 - Tan 4 - Yellow 7 - Purple
2 - Red 5 - Black 8 - Gray
3 - Orange 6 - Blue 9 - White
CONNECTION FOR 3 PHASE, 9 LEADS. IF YOUR 3 PHASE LEADS ARE
COLOR CODED, MATCH NUMBER ABOVE TO THE CORRESPONDING COLOR.
NOTE: To reverse rotation, interchange any two incoming lines (Power) leads.
Figure 4 - Wiring Diagram for Three Phase Motors

Flint & Walling | 95 North Oak Street | Kendallville, IN 46755


800-345-9422 | flintandwalling.com
2 Copyright © 2012 Flint & Walling