BUS BAR –II PROTECTION RELAY

Pick Up (Volts) Operated (Volts) CT Operated Flag


Indication
Red Phase to Neutral
26.64 28.25 28.25 Volts
Yellow Phase to Neutral
25.88 27.99 27.99 Volts
Blue Phase to Neutral
26.12 28.67 28.67 Volts
Red – Yellow Phase
50.15 53.8 54 Volts
Yellow – Blue Phase
50.18 53.79 54 Volts
Blue – Red Phase
52 53 54 Volts

Remarks:

1. Bus Bar – II protection type RADHA make ABB tested through injection from Test Plug for
Phase to Neutral and Phase to Phase .Results are shown in the above Table.
2. Bus Bar – II Master Relay tested and found healthy but while injecting fault from terminal
block for Phase to Neutral, Master relay operated with healthy indications but lockout relay
86-3,86-4 (MVAJ GE make) and LOR BBII did not operate means all concern Circuit Breakers
of Bus Bar- II did not trip.
3. While through temporary positive pulse loop between positive DC from terminal block to
coil of the MVAJ, all Bus Bar-II circuit breakers tripped.

Indications Noted:

1. It was physically checked on the field that all the concern circuit breakers related to Bus Bar-
II protection was tripped which are as follows,
D1Q2 OPEN, D2Q2 OPEN, D3Q2 OPEN, D4Q3 open
BUS BAR –I PROTECTION RELAY

Pick Up (Volts) Operated (Volts) CT Operated Flag At Terminal Block


Indication P/U Operated Flag
Indication
Red Phase to Neutral
24.9 30 Did not drop 24.3 26.3 Did not drop
Yellow Phase to Neutral
23.88 28.99 Did not drop 24.1 26.8 Did not drop
Blue Phase to Neutral
26.6 30 Did not drop 26 28 Did not drop
Red – Yellow Phase
47.5 51.15 Did not drop 47 48 Did not drop
Yellow – Blue Phase
47.45 51.6 Did not drop 47 48 Did not drop
Blue – Red Phase
48.67 51.25 Did not drop 49 50.5 Did not drop

Indications Noted:

1. It was physically checked on the field that all the concern circuit breakers related to Bus Bar-I
protection was tripped which are as follows,
D1Q1 OPEN, D2Q1 OPEN, D3Q1 OPEN, D4Q1 open
2. D3Q3 also tripped (Indiscriminate tripping).