Вы находитесь на странице: 1из 7

Job21-08: getting ing sábado, 30 de junio de 2018

Job Details: FX-350/1/3-126 Series

Section Name Value


Job Info: Job Info: Job 21: "getting ing"
Current Version: Version 8:
Comments: get 0005
Created on: 2018-06-30
by: admin
Language Show system messages in English
Options: Manual Signal Silence Yes
Fire Drill Yes
Waterflow Retard Operation No
Auxiliary Disconnect Alm&Spv No
Alarm Transmit Silence No
Common Supervisory Relay No
Signal Isolator Used No
Strobes Type Normal
Evacuation Code Continuous
Two Stage Operation No
Second Stage Alarm Relay Op. N/A
Monitor alert No
Polled Device Flashes Yes
Class A Loop No
Agency Selection ULC Standard
Positive Alarm Sequence No
Timers: Signal Silence Inhibit Disabled
Auto Signal Silence Disabled
General Alarm N/A
Power Fail Delay None
Date and Time: Enable Daylight Saving Yes
Clock Daily Compensation (sec) 0
Enable Auto After Hours No
Day Start Time: N/A
Night Start Time: N/A
Weekend Start: N/A
Weekend End: N/A
Holidays Reprogram Holiday Trouble: N/A
N/A
Holidays Defined xxxx-01-01
xxxx-12-25 - xxxx-12-26

Job21-08: getting ing Page 1 of 7


Job21-08: getting ing sábado, 30 de junio de 2018
Job Details: FX-350/1/3-126 Series / Base I/O / Loop 0 (Hardwired)

Addr Device Type F1 F3 Tag (Line1) Tag (Line2) Delay


1 Supv Opt Ckt Strobe 0
2 Supv Opt Ckt Strobe 0
3 Supv Opt Ckt Signal 0
4 Supv Opt Ckt Signal 0

Job21-08: getting ing Page 2 of 7


Job21-08: getting ing sábado, 30 de junio de 2018
Job Details: FX-350/1/3-126 Series / Base I/O / Loop 1

Addr Device Type F1 F3 Sens Tag (Line1) Tag (Line2) Delay


1 Photo Det Alarm Input 3.20% Sensor de Humo Garita 1CCTV
2 Photo Det Alarm Input 3.20% Sensor de Humo Ofic. Admin 2 Piso
3 Photo Det Alarm Input 3.20% Sensor de Humo Mant 1 Piso
4 Photo Det Alarm Input 3.20% Sensor de Humo Comedor
5 Photo Det Alarm Input 3.20% Sensor de Humo Ofic. Recepcion
6 Photo Det Alarm Input 3.20% Sensor de Humo Gerencia
7 Photo Det Alarm Input 3.20% Sensor de Humo Sala de Reuniones
8 Photo Det Alarm Input 3.20% Sensor de Humo Subestacion
9 Photo Det Alarm Input 3.20% Sensor de Humo Garita 2
10 Photo Det Alarm Input 3.20% Sensor de Humo Almacen 2
11 Photo Det Alarm Input 3.20% Sensor de Humo Electrobomba
101 Contact Mini Module Alarm Input Estacion Manual Tango 1
102 Contact Mini Module Alarm Input Estacion Manual Comedor
103 Contact Mini Module Alarm Input Estacion Manual Tango 2
104 Contact Mini Module Alarm Input Estacion Manual Pati 2 Nave 2
105 Contact Mini Module Alarm Input Estacion Manual Pati 4 Nave 5 6
106 Contact Mini Module Alarm Input Estacion Manual Pati 3 Nave 6
107 Contact Mini Module Alarm Input Estacion Manual Pati 3 Nave 5
108 Contact Mini Module Alarm Input Estacion Manual Pati 1 Nave 2

Job21-08: getting ing Page 3 of 7


Job21-08: getting ing sábado, 30 de junio de 2018
Job Details: FX-350/1/3-126 Series / Main Display

Section Name Value


System Messages System Normal Sistema sin Problema
Pass Codes Level 1 1111
Level 2 2222
Level 3 3333
Access Levels Reports 0
Aux Bypass 0
Dev Bypass 1
Group Bypass 1
Loop Bypass 1
Walk Test 1
Set After Hours 0
Set Time/Date 1
Daylight Saving and Clock 1
Clear Event Logs 2
Clear Verif Cntrs 2
Dialer Test 1
Dialer Configuration 2
Panel Configuration 2

Job21-08: getting ing Page 4 of 7


Job21-08: getting ing sábado, 30 de junio de 2018
Job Details: FX-350/1/3-126 Series / Dialer

Section Name Value


Account 1 Account ID 123456
Telephone 101
Report Format Contact ID
Account 2 Account ID 654321
Telephone 101
Report Format Contact ID
Line 1 Dial using tone Yes
Wait for dial tone Yes
Line 2 Dial using tone Yes
Wait for dial tone Yes
Report Priority Alarm Account 1
Supervisory Account 1
Trouble Account 1
Timers: AC loss delay 0
Line 2 cellular test No
Day of month N/A
Auto test at 12:30 a. m.
Dialer Line retries 6
Rings 5
Mode UDACT
Enable No
Aux Disconnect No

Job21-08: getting ing Page 5 of 7


Job21-08: getting ing sábado, 30 de junio de 2018
Input Summary

CktNo Loop Addr UDACT Ref Tag


0 1 1 001 Sensor de Humo Garita 1CCTV
1 1 2 002 Sensor de Humo Ofic.Admin 2 Piso
2 1 3 003 Sensor de Humo Mant1 Piso
3 1 4 004 Sensor de Humo Comedor
4 1 5 005 Sensor de Humo Ofic.Recepcion
5 1 6 006 Sensor de Humo Gerencia
6 1 7 007 Sensor de Humo Sala de Reuniones
7 1 8 008 Sensor de Humo Subestacion
8 1 9 009 Sensor de Humo Garita 2
9 1 10 010 Sensor de Humo Almacen 2
10 1 11 011 Sensor de Humo Electrobomba
11 1 101 012 Estacion Manual Tango 1
12 1 102 013 Estacion Manual Comedor
13 1 103 014 Estacion Manual Tango 2
14 1 104 015 Estacion Manual Pati2 Nave 2
15 1 105 016 Estacion Manual Pati4 Nave 5 6
16 1 106 017 Estacion Manual Pati3 Nave 6
17 1 107 018 Estacion Manual Pati3 Nave 5
18 1 108 019 Estacion Manual Pati1 Nave 2

Job21-08: getting ing Page 6 of 7


Job21-08: getting ing sábado, 30 de junio de 2018
Output Summary

CktNo Loop Addr UDACT Ref Tag


0 0 1 001
1 0 2 002
2 0 3 003
3 0 4 004

Job21-08: getting ing Page 7 of 7