>> 1-2
>> 3-4
>> 180 fully adjustable air flow pattern by means of two air
deflections per slot.
>> Available with hit-and-miss damper which controls the air flow
rate without affecting the air flow pattern; can be used as an
equalizing grid.
>> For each slot the air deflector and hit-and-miss damper are
individually adjustable.
>> The deflector and the hit and miss damper are powder coated
with black color as standard.
Neck Size
78
5,5 9,7 5,5
Horizontal Left and
Horizontal Right Discharge
Hit-and-miss damper
9,1
55
27,3
18,1
Deflector
2,6
Flange Size
Neck Size
Neck Size
78
78
5,5 9,7 5,5
5,5 9,7 5,5
Horizontal Left and
Vertical Discharge
9,1
9,1
55
55
27,3
27,3
18,1
18,1 Deflector
Deflector
2,6
Plenum
Adjustable Screw
By Others
By Others
False Ceiling
By Others
Slot Diffuser
ORDERING SYSTEM
46 O
F5
r
ete
1m
different section
Ra
used as below
um
n im
drawing.
Mi
55
Type RLD 3S
without deflectors
with hit-and- miss dampers
PRODUCTS TESTING
The following tables include the results of tests conducted on three linear slot diffusers. The test results include Noise Criteria
(NC), static pressure versus air flow, throw and Ak. The diffusers were selected and supplied by Beta In October 1991. The
extrapolations and interpolation were made to cover a full range of sizes and parameters according to ETL testing laborato-
TEST METHOD
The air diffusers were tested in accordance with the Air diffusion council test code for grilles, registers and diffusers n o. ADC
The diffusers were installed in the ADC facility and supplied with measured volume of air. The static pressure was measured
Acoustical data was obtained employing Bruel and Kjaer digital frequency analyzer, and analyzed by computer. Sound power
levels were plotted on a graph of noise criteria curves which are in the ADC codes.
NOTES:
SYMBOLS CONDITIONS
L/S : Air volume in liter per second. * Supply
Ak : Effective face area in meter Square per 1000 mm. * Vertical discharge flow pattern.
Pt. : Total pressure in millimeters water gauge. * Noise Criteria values are based on(10 db) room attenuation.
Th. : Throw in meters. * Damper is fully open.
NC : Noise Criteria. * Throw values are based on terminal velocity of 0.50 m/s
SYMBOLS NOTES
L/S : Air volume in liter per second. * The large throw values are based on the minimum terminal velocity of 0.25m/Sec.
Ak : Effective face area in meter Square per 1000 mm. * The middle throw values are based on the middle terminal velocity of 0.50 m/Sec.
Pt. : Total pressure in millimeters water gauge. * The small throw values are based on the maximum terminal velocity of 0.75m/Sec.
Th. : Throw in meters.
NC : Noise Criteria.
CONDITIONS
* Supply
PERFORMANCE DATA
*S.I. UNITS
16mm 20mm 25mm
SLOTS L/S per meter Ps NC Ps NC Ps NC
35 3.38 24 2.16 19 1.38 15
47 5.95 31 3.81 25 2.44 20
1 59 9.13 40 5.84 32 3.74 26
71 13.81 49 8.84 39 5.66 31
83 18.66 55 11.94 44 7.64 35
71 3.97 24 2.54 19
19 1.63 15
83 5.80 31 3.71 25 2.37 20
2 94 7.19 36 4.60 29 2.94 23
118 11.11 45 7.11 36 4.55 29
142 15.88 53 10.16 42 6.50 34
94 3.97 25 2.54 20 1.63 16
118 6.19 33 3.96 26 2.53 21
3 142 8.94 39 5.72 31 3.66 25
165 12.14 46 7.77 37 4.97 30
212 20.16 54 12.90 43 8.26 34
142 6.34 28 4.06 22 2.60 18
165 8.61 35 5.51 28 3.53 22
4 189 11.11 40 7.11 32 4.55 26
236 16.78 48 10.74 38 6.87 30
283 24.92 55 15.95 44 10.21 35
142 4.44 26 2.84 21 1.82 17
189 7.86 35 5.03 28 3.22 22
5 236 12.30 43 7.87 34 5.04 27
283 17.66 48 11.30 38 7.23 30
330 24.02 55 15.37 44 9.84 35
189 6.19 29 3.96 23 2.53 18
236 9.64 36 6.17 29 3.95 23
6 283 13.89 44 8.89 35 5.69 28
330 18.86 49 12.07 39 7.72 31
378 24.69 55 15.80 44 10.11 35
SYMBOLS
L/S : Air volume in liter per second.
NC : Noise Criteria.
CONDITIONS
* Return
* Damper is full open.
* Noise Criteria values are based on(10 db) room attenuation
* The tested specimens were of 1000mm length
SLD/RLD - SUPPLY
VERTICAL DISCHARGE * IMPERIAL UNITS
3/5’’ 4/5’’ 1’’
SYMBOLS CONDITIONS
CFM : Air volume in cubic feet per minute. * Supply
Ak : Effective face area in meter Square feet per foot. * Vertical discharge flow pattern.
Pt. : Total pressure in inches water gauge. * Noise Criteria values are based on(10 db) room attenuation.
Th. : Throw in feets. * Damper is fully open.
NC : Noise Criteria. * Throw values are based on terminal velocity of 75 fpm
* The tested specimens were 3ft length
SYMBOLS NOTES
CFM : Air volume in cubic feet per minute. * The large throw values are based on the minimum terminal velocity of 50 fpm.
Ak : Effective face area in meter Square feet per feet. * The middle throw values are based on the middle terminal velocity of 75 fpm.
Pt. : Total pressure in inches water gauge. * The small throw values are based on the maximum terminal velocity of 150 fpm.
Th. : Throw in feet.
NC : Noise Criteria.
CONDITIONS
* Supply
SYMBOLS
CFM : Air volume in cubic feet per minute.
NC : Noise Criteria.
CONDITIONS
* Return
* Damper is full open.
* Noise Criteria values are based on(10 db) room attenuation
* The tested specimens were of 3ft length