7.1.11.2 b) Lightning impulse withstand voltage kV peak Refer to Chpt 2, Section 1 1300
7.1.11.3 c) Switching impulse withstand voltage kV peak Refer to Chpt 2, Section 1 950
7.1.11.4 One minute power frequency withstand vkV rms Bidder to Supply 3
7.3.11.3 c) Switching impulse withstand voltage kV peak Refer to Chpt 2, Sect 1 Not Applicable
7.5.13.2 b) Lightning impulse withstand voltage kV peak Refer to Chpt 2, Sect 1 650
7.5.13.2 c) Switching impulse withstand voltage kV peak Refer to Chpt 2, Sect 1 NA
7.5.13.4 d) One minute power frequency withstand kV rms Refer to Chpt 2, Sect 1 3
voltage-
secondary
7.5.14 Min. Creepage distance mm/kV 31 31
7.5.15 Instrument security factor Bidder to Supply </=5
7.5.16 Maximum secondary resistance Bidder to Supply </=5
7.5.17 Radio interference voltage Bidder to Supply < 2500µV
7.5.18 Rated Voltage Factor 1.2 1.2
7.5.19 Number of cores 1 1
7.5.20 Core Details
7.5.20.1 Metering Class 1, 50/100 VA Class 1, 50/100 VA
7.5.4 Enclosure protection for the secondary terminal IP 56 IP 56
box
7.5.5 Secondary terminal box Cast aluminium or Mild Mild Steel
steel
Technical Data Sheet for Instrument transformers
VOLTAGE TRANSFORMERS – 33 KV (ORANGE GROVE)
Item Particulars Unit Minimum Guaranteed
Requirements Particulars
7.6.1 Service conditions Outdoor Outdoor
7.6.2 Type Oil filled, metallic top tank type Oil filled, metallic top tank type
with silicone bushing. with silicone bushing.
7.6.3 Standards IEC 61869-3 IEC 61869-3
7.6.4 Rated frequency Hz 50 50
7.6.5 Nominal System Voltage kV rms 33/√3 33/√3
7.6.6 Highest System Voltage kV rms 36/√3 36/√3
7.6.7 Ratio 33/√3 kV : 33/√3 kV : 110/√3kV
110/√3 V
7.6.8 Rated primary voltage 33/√3 kV 33/√3
7.6.9 Rated secondary voltage 110/√3 V 110/√3kV
7.6.1 System Neutral - Solid
7.6.11 Rated short time thermal current I (3 sec) kA 25 NA
7.6.12 Rated peak current kA peak 65 NA
7.6.13 Insulation level – primary winding
7.6.13.1 a) Power frequency withstand voltage kV rms Refer to Chpt 2, Sect 1 70
- one min
7.6.13.2 b) Lightning impulse withstand voltage kV peak Refer to Chpt 2, Sect 1 170
7.6.13.3 c) Switching impulse withstand voltage kV peak Refer to Chpt 2, Sect 1 NA
7.6.14 One minute power frequency withstand kV rms Refer to Chpt 2, Sect 1 3
voltage- secondary
7.6.15 Min. Creepage distance mm/kV 31 31
7.6.16 Instrument security factor 10 Bidder to Supply </= 5
7.6.17 Radio interference voltage Bidder to Supply </= 5
7.6.18 Rated Voltage Factor 1.9 1.9
7.6.19 Number of cores 2 1
7.6.20 Core Details
7.6.20.1 Protection (star configuration) Class 1, 100 VA Class 1, 100 VA
7.6.20.2 Protection (open delta configuration) Class 1, 100 VA Class 1, 100 VA
7.6.21 Enclosure protection for the secondary IP 56 IP 55
terminal box
7.6.22 Secondary terminal box Cast aluminium or Mild Steel
Mild steel