ANNEXURE - II

0 FOR APPROVAL 23.04.2014

REV. DESCRIPTION DATE STATUS

CUSTOMER:

ZESCO LIMITED, ZAMBIA

CONSULTANT:
SWECO INTERNATIONAL AB
GJORWELLSGATAN 22, BOX 34044,
100 26 STOCKHOLM, SWEDEN
CONTRACTOR:
NATIONAL CONTRACTING CO. LTD.
TRANSMISSION & DISTRIBUTION DIVISION,
POST BOX No. 90, AL-KHOBAR - 31952,
KINGDOM OF SAUDI ARABIA.
NAME OF PROJECT:
THE PROCUREMENT OF CONSTRUCTION WORKS FOR POWER GRID EXTENSION IN THE
CENTRAL REGION (MUKONCHI FARM BLOCK AND MANGANGO)
CONTRACT No.: ZESCO/IAES/W/006/12
TITLE:
SHORT CIRCUIT FORCE CALCULATION FOR EQUIPMENT STRUCTURES

SH. No/TOTAL SHTS.


PREPARED BY KDN SIZE A4

CHECKED BY KDN SCALE -

APPROVED BY RSM DATE 15.04.2014

REV No.
DOC./DWG No.: NCC-ZES-MD-ELE-DRG-XXX 0

297 X 210 - A4
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 33KV BUS & 33KV DOF KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 33 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 0.8 m

1.12 Length of Jumper (Maximum length considered) LT = 1.5 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 75 N/m
2π x 0.8

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 75 * 1.5 = 112.5 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 11.47 kG

3.02 The Short Circuit Tensile Force of 11.47kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 33KV BUS & 33KV DOF KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 33KV DOF & 33KV PI KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 33 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 0.8 m

1.12 Length of Jumper (Maximum length considered) LT = 1.5 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 75 N/m
2π x 0.8

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 75 * 1.5 = 112.5 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 11.47 kG

3.02 The Short Circuit Tensile Force of 11.47kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 33KV DOF & 33KV PI KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 33KV PI & 33KV LA KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 33 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 0.8 m

1.12 Length of Jumper (Maximum length considered) LT = 1.5 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 75 N/m
2π x 0.8

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 75 * 1.5 = 112.5 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 11.47 kG

3.02 The Short Circuit Tensile Force of 11.47kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 33KV PI & 33KV LA KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 33KV OHL & 33KV LA KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 33 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 1.25 m

1.12 Length of Jumper (Maximum length considered) LT = 1.5 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 48 N/m
2π x 1.25

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 48 * 1.5 = 72 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 7.34 kG

3.02 The Short Circuit Tensile Force of 7.34kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 33KV OHL & 33KV LA KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV SA & 33KV VT KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 33 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Number of sub conductors n = 1

1.07 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.08 Cross sectional area of the conductor As = 0.000597 m2

1.09 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.10 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.11 = 490.5 N (50x9.81x1)
(=Tension per sub conductor x 9.81 x No. of Conductors)

1.12 Resultant spring constant of both supports of one span S = 100000 N/m

1.13 Phase to Phase spacing of the conductor a = 1.25 m

1.14 Chord length of main conductor in the span Lc = 3 m

1.15 Absolute permeability of vacuum μo = 4 π x 10-7 H/m

1.16 Acceleration due to gravity gn = 9.81 m/sec2

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV SA & 33KV VT KDN RSM 0

2.00 METHODOLGY AND ASSUMPTIONS

2.01 The Effect of short circuit force has been considered to be on the gantries having strung bus within the
substation to cater for the extreme operational situations.

2.02 Temperature rise due to short circuit and the subsequent reduction in tension to this effect is neglected.

3.00 TENSILE FORCE DURING SHORT CIRCUIT

3.01 Electromagnetic force per unit length (F' )

μo x 0.75 x Isc2 x Lc
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L
Where,
Lc = L

4πx 10-7 x 0.75 x (20000^2)


F' =
2π x 1.25

F' = 48 N/m

3.02 The Parameter ' r '


F' 48
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (20))
r = =
n x m's x gn 1 x 2.002 x 9.81

r = 2.444

3.03 Stiffness Norms (N) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (25))


1 1
N = +
SxL n x E s x As

Where,
Fst x 90
Es = E x 0.3+ 0.7sin For (Fst/nAs ≤ σfin)
(n x As x σfin)

Es = E For (Fst/nAs > σfin)

σfin = 5.00E+07 N/m2 Lowest value of s when Young's Modulus becomes constant.

490.5 x 90
Es = 68600000000 x 0.3 + 0.7 sin
1 x 0.000597 x 50000000
Es = 2.1819E+10 N/m2

1 1
N = +
100000 x 3 1 x 21819334341.6285 x 0.000597

N = 3.4101E-06 1/N

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV SA & 33KV VT KDN RSM 0

3.04 Stress Factor (ζ) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (28))

(n x gn x m's x L)2 (1 x 9.81 x 2.002 x 3)^2


ζ = =
24 x Fst3 x N 24 x (490.5^3) x 0.0000034101

ζ = 0.3594

3.05 The Direction of Resulting force(δ1) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (21))

δ1 = arctan( r ) = arctan( 2.444 ) = 1.1824 radians

δ1 = 67.7465 degree

3.06 Equivalent Static conductor sag at midpoint (b c) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (22))

n x m's x gn x L2 1 x 2.002 x 9.81 x (3^2)


bc = = m
8 x Fst 8 x 490.5

bc = 0.045 m

3.07 Periods of the conductor Oscillations (T) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (23))

0.8 x bc 0.8 x 0.045


T = 2π x = 2π x
gn 9.81

T = 0.3807 secs

3.08 Resulting Period of the conductor oscillation during short circuit(T res)
T
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (24))
Tres = secs
4 π2 δ1 ^2
(1 + r2) x 1 -
### 90°

T
= secs
4 π2 67.7465 ^2
(1+2.444^2) x 1 -
### 90°

Tres = 0.2568 secs

3.09 The Load Parameter (φ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (32))

φ = 3x (1+r2) - 1 For Tk1 >= Tres / 4

= 3 x (r sinδk + cosδk-1) For Tk1 < Tres / 4

Tres 0.2568
= = 0.0642 Tk1 = 3 secs
4 4

Page 3 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV SA & 33KV VT KDN RSM 0

Page 4 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV SA & 33KV VT KDN RSM 0

For Tk1 >= Tres / 4

φ = 3x (1+r2) - 1 = 3x (1+2.444^2) - 1

φ = 4.922

3.10 The Factor ( ψ ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (33))

The factor ψ is a function of ζ & φ, which is

φ2 x ψ3 + φ(2 + ζ) x ψ2 +(1 + 2ζ)ψ-ζ(2 + φ) = 0

φ = 4.922 ζ = 0.3594

ψ = 0.317258305

4.922^2 x 0.3173^3 + 4.922(2 + 0.3594) x 0.32^2 +(1 + 2 x 0.3594)x0.3173-0.3594(2 + 4.922)

= 0.000
For the above equation to be zero,
ψ = 0.3173

3.11 The Tensile force due to short circuit( F t ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (34))

Ft = Fst x (1 + (ψ x φ)) = 490.5 x (1 + (0.3173 x 4.922) = 1256.54 N

Ft = 1.257 kN

4.00 TENSILE FORCE AFTER SHORT CIRCUIT, CAUSED BY DROP( DROP FORCE)

4.01 Drop Force (Ff) (IEC-865-I(1993) CLAUSE : 2.3.2.3 EQN (35))

Ff = 1.2 x Fst (1 + 8 x ζ x (δm/180))

Where,
δm = 1.25 arccos(χ) For 0.766 ≤ χ ≤ 1
= 10 + arccos(χ) For -0.985 < χ < 0.766
= 180° For χ < -0.985
χ = 1 - r sinδk For 0 ≤ δk ≤ 90
= 1-r For δk > 90

δk = δ1(1- cos(360 x Tk1/Tres)) For 0 ≤ Tk1/Tres ≤ 0.5


= 2δ1 For Tk1/Tres > 0.5
Tk1 3
= = 11.6822
Tres 0.2568

δk = 2 x 67.7465 = 135.493 For Tk1/Tres > 0.5

χ = 1 - 2.444 = -1.4440 For δk > 90

δm = 180 = 180 For X < -0.985

Ff = 1.2 x 490.5 (1 + 8 x 0.3594 x (180/180)) = 1158.7 N


Page 5 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV SA & 33KV VT KDN RSM 0
Ff = 1.2 x 490.5 (1 + 8 x 0.3594 x (180/180)) = 1158.7 N

Page 6 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV SA & 33KV VT KDN RSM 0

Ff = 1.16 kN

4.02 Horizontal Displacement (bh) and minimum air clearance(amin)


(IEC-865-I(1993) CLAUSE : 2.3.2.4 EQN (36))
Eela = N (Ft - Fst) = 0.0000034101 x (1256.54 - 490.5) = 0.0026138

Isc ^2 Tres Cth = 0.27*10^-18 for Aluminium/Steel > 6


Eth = Cth x x
n As 4 Cth = 0.17*10^-18 for Aluminium/Steel ≤ 6

20000 ^2 0.2568
= 0.27*10^(-18) x x
1x0.000597 4
= 1.94541E-05

CD = (1+(3/8) x ((L/bc)^2) x (Eela + Eth) = 2.3214

bh = CF x CD x bc x (Sinδ1) for δm ≥ δ1 δm = 180.0 δ1 = 67.7 from above cl.

CF = 1.05 For r ≤ 0.8 Where r = 2.444


= 0.97+0.1r For 0.8 < r < 1.8 from above cl. 3.02
= 1.15 For r ≥ 1.8
Hence CF = 1.15
bh = 1.15 x 2.3214 x 0.045 x sin(67.7465) = 0.1112
(IEC-865-I(1993) CLAUSE : 2.3.2.4 EQN (42))
amin = a - (2 x bh) = 1.25 - (2 x 0.1112)

amin = 1.0276 m

6.00 CONCLUSION
6.01 The tensile force due to short circuit Ft = 1.257 kN ( 0.13 T )

6.02 The tensile force after short circuit due to drop Ff = 1.16 kN ( 0.12 T )

6.04 The Short Circuit Tensile Force of 1.257kN can be used for associated Foundation & Structure
design

Page 7 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV SA & 33KV VT KDN RSM 0

Page 8 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 33KV VT & 33KV PI KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 33 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 1.25 m

1.12 Length of Jumper (Maximum length considered) LT = 2 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 48 N/m
2π x 1.25

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 48 * 2 = 96 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 9.79 kG

3.02 The Short Circuit Tensile Force of 9.79kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 33KV VT & 33KV PI KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 33KV PI & 33KV PI KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 33 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 1.25 m

1.12 Length of Jumper (Maximum length considered) LT = 1.5 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 48 N/m
2π x 1.25

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 48 * 1.5 = 72 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 7.34 kG

3.02 The Short Circuit Tensile Force of 7.34kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 33KV PI & 33KV PI KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 33KV PI & 33KV HDBD KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 33 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 1.25 m

1.12 Length of Jumper (Maximum length considered) LT = 1.5 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 48 N/m
2π x 1.25

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 48 * 1.5 = 72 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 7.34 kG

3.02 The Short Circuit Tensile Force of 7.34kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 33KV PI & 33KV HDBD KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV HDBD & 33KV CT KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 33 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Number of sub conductors n = 1

1.07 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.08 Cross sectional area of the conductor As = 0.000597 m2

1.09 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.10 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.11 = 490.5 N (50x9.81x1)
(=Tension per sub conductor x 9.81 x No. of Conductors)

1.12 Resultant spring constant of both supports of one span S = 100000 N/m

1.13 Phase to Phase spacing of the conductor a = 0.45 m

1.14 Chord length of main conductor in the span Lc = 2.3 m

1.15 Absolute permeability of vacuum μo = 4 π x 10-7 H/m

1.16 Acceleration due to gravity gn = 9.81 m/sec2

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV HDBD & 33KV CT KDN RSM 0

2.00 METHODOLGY AND ASSUMPTIONS

2.01 The Effect of short circuit force has been considered to be on the gantries having strung bus within the
substation to cater for the extreme operational situations.

2.02 Temperature rise due to short circuit and the subsequent reduction in tension to this effect is neglected.

3.00 TENSILE FORCE DURING SHORT CIRCUIT

3.01 Electromagnetic force per unit length (F' )

μo x 0.75 x Isc2 x Lc
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L
Where,
Lc = L

4πx 10-7 x 0.75 x (20000^2)


F' =
2π x 0.45

F' = 133.3333 N/m

3.02 The Parameter ' r '


F' 133.3333
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (20))
r = =
n x m's x gn 1 x 2.002 x 9.81

r = 6.789

3.03 Stiffness Norms (N) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (25))


1 1
N = +
SxL n x E s x As

Where,
Fst x 90
Es = E x 0.3+ 0.7sin For (Fst/nAs ≤ σfin)
(n x As x σfin)

Es = E For (Fst/nAs > σfin)

σfin = 5.00E+07 N/m2 Lowest value of s when Young's Modulus becomes constant.

490.5 x 90
Es = 68600000000 x 0.3 + 0.7 sin
1 x 0.000597 x 50000000
Es = 2.1819E+10 N/m2

1 1
N = +
100000 x 2.3 1 x 21819334341.6285 x 0.000597

N = 4.4246E-06 1/N

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV HDBD & 33KV CT KDN RSM 0

3.04 Stress Factor (ζ) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (28))

(n x gn x m's x L)2 (1 x 9.81 x 2.002 x 2.3)^2


ζ = =
24 x Fst3 x N 24 x (490.5^3) x 0.00000442459

ζ = 0.1628

3.05 The Direction of Resulting force(δ1) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (21))

δ1 = arctan( r ) = arctan( 6.789 ) = 1.4246 radians

δ1 = 81.6236 degree

3.06 Equivalent Static conductor sag at midpoint (b c) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (22))

n x m's x gn x L2 1 x 2.002 x 9.81 x (2.3^2)


bc = = m
8 x Fst 8 x 490.5

bc = 0.0265 m

3.07 Periods of the conductor Oscillations (T) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (23))

0.8 x bc 0.8 x 0.0265


T = 2π x = 2π x
gn 9.81

T = 0.2921 secs

3.08 Resulting Period of the conductor oscillation during short circuit(T res)
T
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (24))
Tres = secs
4 π2 δ1 ^2
(1 + r2) x 1 -
### 90°

T
= secs
4 π2 81.6236 ^2
(1+6.789^2) x 1 -
### 90°

Tres = 0.1278 secs

3.09 The Load Parameter (φ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (32))

φ = 3x (1+r2) - 1 For Tk1 >= Tres / 4

= 3 x (r sinδk + cosδk-1) For Tk1 < Tres / 4

Tres 0.1278
= = 0.032 Tk1 = 3 secs
4 4

Page 3 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV HDBD & 33KV CT KDN RSM 0

Page 4 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV HDBD & 33KV CT KDN RSM 0

For Tk1 >= Tres / 4

φ = 3x (1+r2) - 1 = 3x (1+6.789^2) - 1

φ = 17.5868

3.10 The Factor ( ψ ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (33))

The factor ψ is a function of ζ & φ, which is

φ2 x ψ3 + φ(2 + ζ) x ψ2 +(1 + 2ζ)ψ-ζ(2 + φ) = 0

φ = 17.5868 ζ = 0.1628

ψ = 0.178079536

17.5868^2 x 0.1781^3 + 17.5868(2 + 0.1628) x 0.18^2 +(1 + 2 x 0.1628)x0.1781-0.1628(2 + 17.5868)

= 0.000
For the above equation to be zero,
ψ = 0.1781

3.11 The Tensile force due to short circuit( F t ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (34))

Ft = Fst x (1 + (ψ x φ)) = 490.5 x (1 + (0.1781 x 17.5868) = 2026.85 N

Ft = 2.027 kN

4.00 TENSILE FORCE AFTER SHORT CIRCUIT, CAUSED BY DROP( DROP FORCE)

4.01 Drop Force (Ff) (IEC-865-I(1993) CLAUSE : 2.3.2.3 EQN (35))

Ff = 1.2 x Fst (1 + 8 x ζ x (δm/180))

Where,
δm = 1.25 arccos(χ) For 0.766 ≤ χ ≤ 1
= 10 + arccos(χ) For -0.985 < χ < 0.766
= 180° For χ < -0.985
χ = 1 - r sinδk For 0 ≤ δk ≤ 90
= 1-r For δk > 90

δk = δ1(1- cos(360 x Tk1/Tres)) For 0 ≤ Tk1/Tres ≤ 0.5


= 2δ1 For Tk1/Tres > 0.5
Tk1 3
= = 23.4742
Tres 0.1278

δk = 2 x 81.6236 = 163.247 For Tk1/Tres > 0.5

χ = 1 - 6.789 = -5.7890 For δk > 90

δm = 180 = 180 For X < -0.985

Ff = 1.2 x 490.5 (1 + 8 x 0.1628 x (180/180)) = 893.1 N


Page 5 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV HDBD & 33KV CT KDN RSM 0
Ff = 1.2 x 490.5 (1 + 8 x 0.1628 x (180/180)) = 893.1 N

Page 6 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV HDBD & 33KV CT KDN RSM 0

Ff = 0.89 kN

4.02 Horizontal Displacement (bh) and minimum air clearance(amin)


(IEC-865-I(1993) CLAUSE : 2.3.2.4 EQN (36))
Eela = N (Ft - Fst) = 0.00000442459 x (2026.85 - 490.5) = 0.0067984

Isc ^2 Tres Cth = 0.27*10^-18 for Aluminium/Steel > 6


Eth = Cth x x
n As 4 Cth = 0.17*10^-18 for Aluminium/Steel ≤ 6

20000 ^2 0.1278
= 0.27*10^(-18) x x
1x0.000597 4
= 9.68157E-06

CD = (1+(3/8) x ((L/bc)^2) x (Eela + Eth) = 4.498

bh = CF x CD x bc x (Sinδ1) for δm ≥ δ1 δm = 180.0 δ1 = 81.6 from above cl.

CF = 1.05 For r ≤ 0.8 Where r = 6.789


= 0.97+0.1r For 0.8 < r < 1.8 from above cl. 3.02
= 1.15 For r ≥ 1.8
Hence CF = 1.15
bh = 1.15 x 4.498 x 0.0265 x sin(81.6236) = 0.1356
(IEC-865-I(1993) CLAUSE : 2.3.2.4 EQN (42))
amin = a - (2 x bh) = 0.45 - (2 x 0.1356)

amin = 0.1788 m

6.00 CONCLUSION
6.01 The tensile force due to short circuit Ft = 2.027 kN ( 0.21 T )

6.02 The tensile force after short circuit due to drop Ff = 0.89 kN ( 0.09 T )

6.04 The Short Circuit Tensile Force of 2.027kN can be used for associated Foundation & Structure
design

Page 7 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV HDBD & 33KV CT KDN RSM 0

Page 8 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV CT & 33KV VCB KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 33 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Number of sub conductors n = 1

1.07 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.08 Cross sectional area of the conductor As = 0.000597 m2

1.09 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.10 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.11 = 490.5 N (50x9.81x1)
(=Tension per sub conductor x 9.81 x No. of Conductors)

1.12 Resultant spring constant of both supports of one span S = 100000 N/m

1.13 Phase to Phase spacing of the conductor a = 0.75 m

1.14 Chord length of main conductor in the span Lc = 0.6 m

1.15 Absolute permeability of vacuum μo = 4 π x 10-7 H/m

1.16 Acceleration due to gravity gn = 9.81 m/sec2

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV CT & 33KV VCB KDN RSM 0

2.00 METHODOLGY AND ASSUMPTIONS

2.01 The Effect of short circuit force has been considered to be on the gantries having strung bus within the
substation to cater for the extreme operational situations.

2.02 Temperature rise due to short circuit and the subsequent reduction in tension to this effect is neglected.

3.00 TENSILE FORCE DURING SHORT CIRCUIT

3.01 Electromagnetic force per unit length (F' )

μo x 0.75 x Isc2 x Lc
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L
Where,
Lc = L

4πx 10-7 x 0.75 x (20000^2)


F' =
2π x 0.75

F' = 80 N/m

3.02 The Parameter ' r '


F' 80
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (20))
r = =
n x m's x gn 1 x 2.002 x 9.81

r = 4.0734

3.03 Stiffness Norms (N) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (25))


1 1
N = +
SxL n x E s x As

Where,
Fst x 90
Es = E x 0.3+ 0.7sin For (Fst/nAs ≤ σfin)
(n x As x σfin)

Es = E For (Fst/nAs > σfin)

σfin = 5.00E+07 N/m2 Lowest value of s when Young's Modulus becomes constant.

490.5 x 90
Es = 68600000000 x 0.3 + 0.7 sin
1 x 0.000597 x 50000000
Es = 2.1819E+10 N/m2

1 1
N = +
100000 x 0.6 1 x 21819334341.6285 x 0.000597

N = 1.6743E-05 1/N

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV CT & 33KV VCB KDN RSM 0

3.04 Stress Factor (ζ) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (28))

(n x gn x m's x L)2 (1 x 9.81 x 2.002 x 0.6)^2


ζ = =
24 x Fst3 x N 24 x (490.5^3) x 0.00001674344

ζ = 0.0029

3.05 The Direction of Resulting force(δ1) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (21))

δ1 = arctan( r ) = arctan( 4.0734 ) = 1.3301 radians

δ1 = 76.2091 degree

3.06 Equivalent Static conductor sag at midpoint (b c) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (22))

n x m's x gn x L2 1 x 2.002 x 9.81 x (0.6^2)


bc = = m
8 x Fst 8 x 490.5

bc = 0.0018 m

3.07 Periods of the conductor Oscillations (T) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (23))

0.8 x bc 0.8 x 0.0018


T = 2π x = 2π x
gn 9.81

T = 0.0762 secs

3.08 Resulting Period of the conductor oscillation during short circuit(T res)
T
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (24))
Tres = secs
4 π2 δ1 ^2
(1 + r2) x 1 -
### 90°

T
= secs
4 π2 76.2091 ^2
(1+4.0734^2) x 1 -
### 90°

Tres = 0.0419 secs

3.09 The Load Parameter (φ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (32))

φ = 3x (1+r2) - 1 For Tk1 >= Tres / 4

= 3 x (r sinδk + cosδk-1) For Tk1 < Tres / 4

Tres 0.0419
= = 0.0105 Tk1 = 3 secs
4 4

Page 3 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV CT & 33KV VCB KDN RSM 0

Page 4 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV CT & 33KV VCB KDN RSM 0

For Tk1 >= Tres / 4

φ = 3x (1+r2) - 1 = 3x (1+4.0734^2) - 1

φ = 9.5831

3.10 The Factor ( ψ ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (33))

The factor ψ is a function of ζ & φ, which is

φ2 x ψ3 + φ(2 + ζ) x ψ2 +(1 + 2ζ)ψ-ζ(2 + φ) = 0

φ = 9.5831 ζ = 0.0029

ψ = 0.022710959

9.5831^2 x 0.0228^3 + 9.5831(2 + 0.0029) x 0.03^2 +(1 + 2 x 0.0029)x0.0228-0.0029(2 + 9.5831)

= 0.000
For the above equation to be zero,
ψ = 0.0228

3.11 The Tensile force due to short circuit( F t ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (34))

Ft = Fst x (1 + (ψ x φ)) = 490.5 x (1 + (0.0228 x 9.5831) = 597.67 N

Ft = 0.598 kN

4.00 TENSILE FORCE AFTER SHORT CIRCUIT, CAUSED BY DROP( DROP FORCE)

4.01 Drop Force (Ff) (IEC-865-I(1993) CLAUSE : 2.3.2.3 EQN (35))

Ff = 1.2 x Fst (1 + 8 x ζ x (δm/180))

Where,
δm = 1.25 arccos(χ) For 0.766 ≤ χ ≤ 1
= 10 + arccos(χ) For -0.985 < χ < 0.766
= 180° For χ < -0.985
χ = 1 - r sinδk For 0 ≤ δk ≤ 90
= 1-r For δk > 90

δk = δ1(1- cos(360 x Tk1/Tres)) For 0 ≤ Tk1/Tres ≤ 0.5


= 2δ1 For Tk1/Tres > 0.5
Tk1 3
= = 71.599
Tres 0.0419

δk = 2 x 76.2091 = 152.418 For Tk1/Tres > 0.5

χ = 1 - 4.0734 = -3.0734 For δk > 90

δm = 180 = 180 For X < -0.985

Ff = 1.2 x 490.5 (1 + 8 x 0.0029 x (180/180)) = 595.4 N


Page 5 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV CT & 33KV VCB KDN RSM 0
Ff = 1.2 x 490.5 (1 + 8 x 0.0029 x (180/180)) = 595.4 N

Page 6 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV CT & 33KV VCB KDN RSM 0

Ff = 0.6 kN

4.02 Horizontal Displacement (bh) and minimum air clearance(amin)


(IEC-865-I(1993) CLAUSE : 2.3.2.4 EQN (36))
Eela = N (Ft - Fst) = 0.00001674344 x (597.67 - 490.5) = 0.0017999

Isc ^2 Tres Cth = 0.27*10^-18 for Aluminium/Steel > 6


Eth = Cth x x
n As 4 Cth = 0.17*10^-18 for Aluminium/Steel ≤ 6

20000 ^2 0.0419
= 0.27*10^(-18) x x
1x0.000597 4
= 3.17416E-06

CD = (1+(3/8) x ((L/bc)^2) x (Eela + Eth) = 8.7251

bh = CF x CD x bc x (Sinδ1) for δm ≥ δ1 δm = 180.0 δ1 = 76.2 from above cl.

CF = 1.05 For r ≤ 0.8 Where r = 4.0734


= 0.97+0.1r For 0.8 < r < 1.8 from above cl. 3.02
= 1.15 For r ≥ 1.8
Hence CF = 1.15
bh = 1.15 x 8.7251 x 0.0018 x sin(76.2091) = 0.0175
(IEC-865-I(1993) CLAUSE : 2.3.2.4 EQN (42))
amin = a - (2 x bh) = 0.75 - (2 x 0.0175)

amin = 0.715 m

6.00 CONCLUSION
6.01 The tensile force due to short circuit Ft = 0.598 kN ( 0.06 T )

6.02 The tensile force after short circuit due to drop Ff = 0.6 kN ( 0.06 T )

6.04 The Short Circuit Tensile Force of 0.6kN can be used for associated Foundation & Structure
design

Page 7 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV CT & 33KV VCB KDN RSM 0

Page 8 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV VCB & 33KV LA KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 33 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Number of sub conductors n = 1

1.07 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.08 Cross sectional area of the conductor As = 0.000597 m2

1.09 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.10 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.11 = 490.5 N (50x9.81x1)
(=Tension per sub conductor x 9.81 x No. of Conductors)

1.12 Resultant spring constant of both supports of one span S = 100000 N/m

1.13 Phase to Phase spacing of the conductor a = 0.685 m

1.14 Chord length of main conductor in the span Lc = 2.4 m

1.15 Absolute permeability of vacuum μo = 4 π x 10-7 H/m

1.16 Acceleration due to gravity gn = 9.81 m/sec2

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV VCB & 33KV LA KDN RSM 0

2.00 METHODOLGY AND ASSUMPTIONS

2.01 The Effect of short circuit force has been considered to be on the gantries having strung bus within the
substation to cater for the extreme operational situations.

2.02 Temperature rise due to short circuit and the subsequent reduction in tension to this effect is neglected.

3.00 TENSILE FORCE DURING SHORT CIRCUIT

3.01 Electromagnetic force per unit length (F' )

μo x 0.75 x Isc2 x Lc
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L
Where,
Lc = L

4πx 10-7 x 0.75 x (20000^2)


F' =
2π x 0.685

F' = 87.5912 N/m

3.02 The Parameter ' r '


F' 87.5912
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (20))
r = =
n x m's x gn 1 x 2.002 x 9.81

r = 4.4599

3.03 Stiffness Norms (N) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (25))


1 1
N = +
SxL n x E s x As

Where,
Fst x 90
Es = E x 0.3+ 0.7sin For (Fst/nAs ≤ σfin)
(n x As x σfin)

Es = E For (Fst/nAs > σfin)

σfin = 5.00E+07 N/m2 Lowest value of s when Young's Modulus becomes constant.

490.5 x 90
Es = 68600000000 x 0.3 + 0.7 sin
1 x 0.000597 x 50000000
Es = 2.1819E+10 N/m2

1 1
N = +
100000 x 2.4 1 x 21819334341.6285 x 0.000597

N = 4.2434E-06 1/N

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV VCB & 33KV LA KDN RSM 0

3.04 Stress Factor (ζ) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (28))

(n x gn x m's x L)2 (1 x 9.81 x 2.002 x 2.4)^2


ζ = =
24 x Fst3 x N 24 x (490.5^3) x 0.00000424344

ζ = 0.1849

3.05 The Direction of Resulting force(δ1) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (21))

δ1 = arctan( r ) = arctan( 4.4599 ) = 1.3502 radians

δ1 = 77.3608 degree

3.06 Equivalent Static conductor sag at midpoint (b c) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (22))

n x m's x gn x L2 1 x 2.002 x 9.81 x (2.4^2)


bc = = m
8 x Fst 8 x 490.5

bc = 0.0288 m

3.07 Periods of the conductor Oscillations (T) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (23))

0.8 x bc 0.8 x 0.0288


T = 2π x = 2π x
gn 9.81

T = 0.3045 secs

3.08 Resulting Period of the conductor oscillation during short circuit(T res)
T
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (24))
Tres = secs
4 π2 δ1 ^2
(1 + r2) x 1 -
### 90°

T
= secs
4 π2 77.3608 ^2
(1+4.4599^2) x 1 -
### 90°

Tres = 0.1608 secs

3.09 The Load Parameter (φ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (32))

φ = 3x (1+r2) - 1 For Tk1 >= Tres / 4

= 3 x (r sinδk + cosδk-1) For Tk1 < Tres / 4

Tres 0.1608
= = 0.0402 Tk1 = 3 secs
4 4

Page 3 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV VCB & 33KV LA KDN RSM 0

Page 4 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV VCB & 33KV LA KDN RSM 0

For Tk1 >= Tres / 4

φ = 3x (1+r2) - 1 = 3x (1+4.4599^2) - 1

φ = 10.7119

3.10 The Factor ( ψ ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (33))

The factor ψ is a function of ζ & φ, which is

φ2 x ψ3 + φ(2 + ζ) x ψ2 +(1 + 2ζ)ψ-ζ(2 + φ) = 0

φ = 10.7119 ζ = 0.1849

ψ = 0.208790857

10.7119^2 x 0.2088^3 + 10.7119(2 + 0.1849) x 0.21^2 +(1 + 2 x 0.1849)x0.2088-0.1849(2 + 10.7119)

= 0.000
For the above equation to be zero,
ψ = 0.2088

3.11 The Tensile force due to short circuit( F t ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (34))

Ft = Fst x (1 + (ψ x φ)) = 490.5 x (1 + (0.2088 x 10.7119) = 1587.57 N

Ft = 1.588 kN

4.00 TENSILE FORCE AFTER SHORT CIRCUIT, CAUSED BY DROP( DROP FORCE)

4.01 Drop Force (Ff) (IEC-865-I(1993) CLAUSE : 2.3.2.3 EQN (35))

Ff = 1.2 x Fst (1 + 8 x ζ x (δm/180))

Where,
δm = 1.25 arccos(χ) For 0.766 ≤ χ ≤ 1
= 10 + arccos(χ) For -0.985 < χ < 0.766
= 180° For χ < -0.985
χ = 1 - r sinδk For 0 ≤ δk ≤ 90
= 1-r For δk > 90

δk = δ1(1- cos(360 x Tk1/Tres)) For 0 ≤ Tk1/Tres ≤ 0.5


= 2δ1 For Tk1/Tres > 0.5
Tk1 3
= = 18.6567
Tres 0.1608

δk = 2 x 77.3608 = 154.722 For Tk1/Tres > 0.5

χ = 1 - 4.4599 = -3.4599 For δk > 90

δm = 180 = 180 For X < -0.985

Ff = 1.2 x 490.5 (1 + 8 x 0.1849 x (180/180)) = 926.8 N


Page 5 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV VCB & 33KV LA KDN RSM 0
Ff = 1.2 x 490.5 (1 + 8 x 0.1849 x (180/180)) = 926.8 N

Page 6 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV VCB & 33KV LA KDN RSM 0

Ff = 0.93 kN

4.02 Horizontal Displacement (bh) and minimum air clearance(amin)


(IEC-865-I(1993) CLAUSE : 2.3.2.4 EQN (36))
Eela = N (Ft - Fst) = 0.00000424344 x (1587.57 - 490.5) = 0.0046572

Isc ^2 Tres Cth = 0.27*10^-18 for Aluminium/Steel > 6


Eth = Cth x x
n As 4 Cth = 0.17*10^-18 for Aluminium/Steel ≤ 6

20000 ^2 0.1608
= 0.27*10^(-18) x x
1x0.000597 4
= 1.21815E-05

CD = (1+(3/8) x ((L/bc)^2) x (Eela + Eth) = 3.6277

bh = CF x CD x bc x (Sinδ1) for δm ≥ δ1 δm = 180.0 δ1 = 77.4 from above cl.

CF = 1.05 For r ≤ 0.8 Where r = 4.4599


= 0.97+0.1r For 0.8 < r < 1.8 from above cl. 3.02
= 1.15 For r ≥ 1.8
Hence CF = 1.15
bh = 1.15 x 3.6277 x 0.0288 x sin(77.3608) = 0.1172
(IEC-865-I(1993) CLAUSE : 2.3.2.4 EQN (42))
amin = a - (2 x bh) = 0.685 - (2 x 0.1172)

amin = 0.4506 m

6.00 CONCLUSION
6.01 The tensile force due to short circuit Ft = 1.588 kN ( 0.16 T )

6.02 The tensile force after short circuit due to drop Ff = 0.93 kN ( 0.09 T )

6.04 The Short Circuit Tensile Force of 1.588kN can be used for associated Foundation & Structure
design

Page 7 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV VCB & 33KV LA KDN RSM 0

Page 8 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV LA & 33KV BUSHING KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 33 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Number of sub conductors n = 1

1.07 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.08 Cross sectional area of the conductor As = 0.000597 m2

1.09 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.10 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.11 = 490.5 N (50x9.81x1)
(=Tension per sub conductor x 9.81 x No. of Conductors)

1.12 Resultant spring constant of both supports of one span S = 100000 N/m

1.13 Phase to Phase spacing of the conductor a = 0.56 m

1.14 Chord length of main conductor in the span Lc = 1.3 m

1.15 Absolute permeability of vacuum μo = 4 π x 10-7 H/m

1.16 Acceleration due to gravity gn = 9.81 m/sec2

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV LA & 33KV BUSHING KDN RSM 0

2.00 METHODOLGY AND ASSUMPTIONS

2.01 The Effect of short circuit force has been considered to be on the gantries having strung bus within the
substation to cater for the extreme operational situations.

2.02 Temperature rise due to short circuit and the subsequent reduction in tension to this effect is neglected.

3.00 TENSILE FORCE DURING SHORT CIRCUIT

3.01 Electromagnetic force per unit length (F' )

μo x 0.75 x Isc2 x Lc
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L
Where,
Lc = L

4πx 10-7 x 0.75 x (20000^2)


F' =
2π x 0.56

F' = 107.1429 N/m

3.02 The Parameter ' r '


F' 107.1429
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (20))
r = =
n x m's x gn 1 x 2.002 x 9.81

r = 5.4554

3.03 Stiffness Norms (N) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (25))


1 1
N = +
SxL n x E s x As

Where,
Fst x 90
Es = E x 0.3+ 0.7sin For (Fst/nAs ≤ σfin)
(n x As x σfin)

Es = E For (Fst/nAs > σfin)

σfin = 5.00E+07 N/m2 Lowest value of s when Young's Modulus becomes constant.

490.5 x 90
Es = 68600000000 x 0.3 + 0.7 sin
1 x 0.000597 x 50000000
Es = 2.1819E+10 N/m2

1 1
N = +
100000 x 1.3 1 x 21819334341.6285 x 0.000597

N = 7.7691E-06 1/N

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV LA & 33KV BUSHING KDN RSM 0

3.04 Stress Factor (ζ) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (28))

(n x gn x m's x L)2 (1 x 9.81 x 2.002 x 1.3)^2


ζ = =
24 x Fst3 x N 24 x (490.5^3) x 0.00000776908

ζ = 0.0296

3.05 The Direction of Resulting force(δ1) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (21))

δ1 = arctan( r ) = arctan( 5.4554 ) = 1.3895 radians

δ1 = 79.6125 degree

3.06 Equivalent Static conductor sag at midpoint (b c) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (22))

n x m's x gn x L2 1 x 2.002 x 9.81 x (1.3^2)


bc = = m
8 x Fst 8 x 490.5

bc = 0.0085 m

3.07 Periods of the conductor Oscillations (T) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (23))

0.8 x bc 0.8 x 0.0085


T = 2π x = 2π x
gn 9.81

T = 0.1655 secs

3.08 Resulting Period of the conductor oscillation during short circuit(T res)
T
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (24))
Tres = secs
4 π2 δ1 ^2
(1 + r2) x 1 -
### 90°

T
= secs
4 π2 79.6125 ^2
(1+5.4554^2) x 1 -
### 90°

Tres = 0.08 secs

3.09 The Load Parameter (φ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (32))

φ = 3x (1+r2) - 1 For Tk1 >= Tres / 4

= 3 x (r sinδk + cosδk-1) For Tk1 < Tres / 4

Tres 0.08
= = 0.02 Tk1 = 3 secs
4 4

Page 3 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV LA & 33KV BUSHING KDN RSM 0

Page 4 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV LA & 33KV BUSHING KDN RSM 0

For Tk1 >= Tres / 4

φ = 3x (1+r2) - 1 = 3x (1+5.4554^2) - 1

φ = 13.6389

3.10 The Factor ( ψ ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (33))

The factor ψ is a function of ζ & φ, which is

φ2 x ψ3 + φ(2 + ζ) x ψ2 +(1 + 2ζ)ψ-ζ(2 + φ) = 0

φ = 13.6389 ζ = 0.0296

ψ = 0.090734052

13.6389^2 x 0.0908^3 + 13.6389(2 + 0.0296) x 0.1^2 +(1 + 2 x 0.0296)x0.0908-0.0296(2 + 13.6389)

= 0.000
For the above equation to be zero,
ψ = 0.0908

3.11 The Tensile force due to short circuit( F t ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (34))

Ft = Fst x (1 + (ψ x φ)) = 490.5 x (1 + (0.0908 x 13.6389) = 1097.94 N

Ft = 1.098 kN

4.00 TENSILE FORCE AFTER SHORT CIRCUIT, CAUSED BY DROP( DROP FORCE)

4.01 Drop Force (Ff) (IEC-865-I(1993) CLAUSE : 2.3.2.3 EQN (35))

Ff = 1.2 x Fst (1 + 8 x ζ x (δm/180))

Where,
δm = 1.25 arccos(χ) For 0.766 ≤ χ ≤ 1
= 10 + arccos(χ) For -0.985 < χ < 0.766
= 180° For χ < -0.985
χ = 1 - r sinδk For 0 ≤ δk ≤ 90
= 1-r For δk > 90

δk = δ1(1- cos(360 x Tk1/Tres)) For 0 ≤ Tk1/Tres ≤ 0.5


= 2δ1 For Tk1/Tres > 0.5
Tk1 3
= = 37.5
Tres 0.08

δk = 2 x 79.6125 = 159.225 For Tk1/Tres > 0.5

χ = 1 - 5.4554 = -4.4554 For δk > 90

δm = 180 = 180 For X < -0.985

Ff = 1.2 x 490.5 (1 + 8 x 0.0296 x (180/180)) = 654.6 N


Page 5 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV LA & 33KV BUSHING KDN RSM 0
Ff = 1.2 x 490.5 (1 + 8 x 0.0296 x (180/180)) = 654.6 N

Page 6 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV LA & 33KV BUSHING KDN RSM 0

Ff = 0.65 kN

4.02 Horizontal Displacement (bh) and minimum air clearance(amin)


(IEC-865-I(1993) CLAUSE : 2.3.2.4 EQN (36))
Eela = N (Ft - Fst) = 0.00000776908 x (1097.94 - 490.5) = 0.0047197

Isc ^2 Tres Cth = 0.27*10^-18 for Aluminium/Steel > 6


Eth = Cth x x
n As 4 Cth = 0.17*10^-18 for Aluminium/Steel ≤ 6

20000 ^2 0.08
= 0.27*10^(-18) x x
1x0.000597 4
= 6.06045E-06

CD = (1+(3/8) x ((L/bc)^2) x (Eela + Eth) = 6.5156

bh = CF x CD x bc x (Sinδ1) for δm ≥ δ1 δm = 180.0 δ1 = 79.6 from above cl.

CF = 1.05 For r ≤ 0.8 Where r = 5.4554


= 0.97+0.1r For 0.8 < r < 1.8 from above cl. 3.02
= 1.15 For r ≥ 1.8
Hence CF = 1.15
bh = 1.15 x 6.5156 x 0.0085 x sin(79.6125) = 0.0626
(IEC-865-I(1993) CLAUSE : 2.3.2.4 EQN (42))
amin = a - (2 x bh) = 0.56 - (2 x 0.0626)

amin = 0.4348 m

6.00 CONCLUSION
6.01 The tensile force due to short circuit Ft = 1.098 kN ( 0.11 T )

6.02 The tensile force after short circuit due to drop Ff = 0.65 kN ( 0.07 T )

6.04 The Short Circuit Tensile Force of 1.098kN can be used for associated Foundation & Structure
design

Page 7 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 33KV LA & 33KV BUSHING KDN RSM 0

Page 8 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV BUSHING & 11KV LA KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 11 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Number of sub conductors n = 1

1.07 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.08 Cross sectional area of the conductor As = 0.000597 m2

1.09 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.10 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.11 = 490.5 N (50x9.81x1)
(=Tension per sub conductor x 9.81 x No. of Conductors)

1.12 Resultant spring constant of both supports of one span S = 100000 N/m

1.13 Phase to Phase spacing of the conductor a = 0.425 m

1.14 Chord length of main conductor in the span Lc = 1.3 m

1.15 Absolute permeability of vacuum μo = 4 π x 10-7 H/m

1.16 Acceleration due to gravity gn = 9.81 m/sec2

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV BUSHING & 11KV LA KDN RSM 0

2.00 METHODOLGY AND ASSUMPTIONS

2.01 The Effect of short circuit force has been considered to be on the gantries having strung bus within the
substation to cater for the extreme operational situations.

2.02 Temperature rise due to short circuit and the subsequent reduction in tension to this effect is neglected.

3.00 TENSILE FORCE DURING SHORT CIRCUIT

3.01 Electromagnetic force per unit length (F' )

μo x 0.75 x Isc2 x Lc
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L
Where,
Lc = L

4πx 10-7 x 0.75 x (20000^2)


F' =
2π x 0.425

F' = 141.1765 N/m

3.02 The Parameter ' r '


F' 141.1765
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (20))
r = =
n x m's x gn 1 x 2.002 x 9.81

r = 7.1884

3.03 Stiffness Norms (N) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (25))


1 1
N = +
SxL n x E s x As

Where,
Fst x 90
Es = E x 0.3+ 0.7sin For (Fst/nAs ≤ σfin)
(n x As x σfin)

Es = E For (Fst/nAs > σfin)

σfin = 5.00E+07 N/m2 Lowest value of s when Young's Modulus becomes constant.

490.5 x 90
Es = 68600000000 x 0.3 + 0.7 sin
1 x 0.000597 x 50000000
Es = 2.1819E+10 N/m2

1 1
N = +
100000 x 1.3 1 x 21819334341.6285 x 0.000597

N = 7.7691E-06 1/N

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV BUSHING & 11KV LA KDN RSM 0

3.04 Stress Factor (ζ) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (28))

(n x gn x m's x L)2 (1 x 9.81 x 2.002 x 1.3)^2


ζ = =
24 x Fst3 x N 24 x (490.5^3) x 0.00000776908

ζ = 0.0296

3.05 The Direction of Resulting force(δ1) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (21))

δ1 = arctan( r ) = arctan( 7.1884 ) = 1.4326 radians

δ1 = 82.0819 degree

3.06 Equivalent Static conductor sag at midpoint (b c) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (22))

n x m's x gn x L2 1 x 2.002 x 9.81 x (1.3^2)


bc = = m
8 x Fst 8 x 490.5

bc = 0.0085 m

3.07 Periods of the conductor Oscillations (T) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (23))

0.8 x bc 0.8 x 0.0085


T = 2π x = 2π x
gn 9.81

T = 0.1655 secs

3.08 Resulting Period of the conductor oscillation during short circuit(T res)
T
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (24))
Tres = secs
4 π2 δ1 ^2
(1 + r2) x 1 -
### 90°

T
= secs
4 π2 82.0819 ^2
(1+7.1884^2) x 1 -
### 90°

Tres = 0.0705 secs

3.09 The Load Parameter (φ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (32))

φ = 3x (1+r2) - 1 For Tk1 >= Tres / 4

= 3 x (r sinδk + cosδk-1) For Tk1 < Tres / 4

Tres 0.0705
= = 0.0176 Tk1 = 3 secs
4 4

Page 3 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV BUSHING & 11KV LA KDN RSM 0

Page 4 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV BUSHING & 11KV LA KDN RSM 0

For Tk1 >= Tres / 4

φ = 3x (1+r2) - 1 = 3x (1+7.1884^2) - 1

φ = 18.7729

3.10 The Factor ( ψ ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (33))

The factor ψ is a function of ζ & φ, which is

φ2 x ψ3 + φ(2 + ζ) x ψ2 +(1 + 2ζ)ψ-ζ(2 + φ) = 0

φ = 18.7729 ζ = 0.0296

ψ = 0.087146969

18.7729^2 x 0.0872^3 + 18.7729(2 + 0.0296) x 0.09^2 +(1 + 2 x 0.0296)x0.0872-0.0296(2 + 18.7729)

= 0.000
For the above equation to be zero,
ψ = 0.0872

3.11 The Tensile force due to short circuit( F t ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (34))

Ft = Fst x (1 + (ψ x φ)) = 490.5 x (1 + (0.0872 x 18.7729) = 1293.45 N

Ft = 1.294 kN

4.00 TENSILE FORCE AFTER SHORT CIRCUIT, CAUSED BY DROP( DROP FORCE)

4.01 Drop Force (Ff) (IEC-865-I(1993) CLAUSE : 2.3.2.3 EQN (35))

Ff = 1.2 x Fst (1 + 8 x ζ x (δm/180))

Where,
δm = 1.25 arccos(χ) For 0.766 ≤ χ ≤ 1
= 10 + arccos(χ) For -0.985 < χ < 0.766
= 180° For χ < -0.985
χ = 1 - r sinδk For 0 ≤ δk ≤ 90
= 1-r For δk > 90

δk = δ1(1- cos(360 x Tk1/Tres)) For 0 ≤ Tk1/Tres ≤ 0.5


= 2δ1 For Tk1/Tres > 0.5
Tk1 3
= = 42.5532
Tres 0.0705

δk = 2 x 82.0819 = 164.164 For Tk1/Tres > 0.5

χ = 1 - 7.1884 = -6.1884 For δk > 90

δm = 180 = 180 For X < -0.985

Ff = 1.2 x 490.5 (1 + 8 x 0.0296 x (180/180)) = 654.6 N


Page 5 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV BUSHING & 11KV LA KDN RSM 0
Ff = 1.2 x 490.5 (1 + 8 x 0.0296 x (180/180)) = 654.6 N

Page 6 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV BUSHING & 11KV LA KDN RSM 0

Ff = 0.65 kN

4.02 Horizontal Displacement (bh) and minimum air clearance(amin)


(IEC-865-I(1993) CLAUSE : 2.3.2.4 EQN (36))
Eela = N (Ft - Fst) = 0.00000776908 x (1293.45 - 490.5) = 0.0062425

Isc ^2 Tres Cth = 0.27*10^-18 for Aluminium/Steel > 6


Eth = Cth x x
n As 4 Cth = 0.17*10^-18 for Aluminium/Steel ≤ 6

20000 ^2 0.0705
= 0.27*10^(-18) x x
1x0.000597 4
= 5.34077E-06

CD = (1+(3/8) x ((L/bc)^2) x (Eela + Eth) = 7.4702

bh = CF x CD x bc x (Sinδ1) for δm ≥ δ1 δm = 180.0 δ1 = 82.1 from above cl.

CF = 1.05 For r ≤ 0.8 Where r = 7.1884


= 0.97+0.1r For 0.8 < r < 1.8 from above cl. 3.02
= 1.15 For r ≥ 1.8
Hence CF = 1.15
bh = 1.15 x 7.4702 x 0.0085 x sin(82.0819) = 0.0723
(IEC-865-I(1993) CLAUSE : 2.3.2.4 EQN (42))
amin = a - (2 x bh) = 0.425 - (2 x 0.0723)

amin = 0.2804 m

6.00 CONCLUSION
6.01 The tensile force due to short circuit Ft = 1.294 kN ( 0.13 T )

6.02 The tensile force after short circuit due to drop Ff = 0.65 kN ( 0.07 T )

6.04 The Short Circuit Tensile Force of 1.294kN can be used for associated Foundation & Structure
design

Page 7 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV BUSHING & 11KV LA KDN RSM 0

Page 8 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV LA & 11KV CT KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 11 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Number of sub conductors n = 1

1.07 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.08 Cross sectional area of the conductor As = 0.000597 m2

1.09 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.10 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.11 = 490.5 N (50x9.81x1)
(=Tension per sub conductor x 9.81 x No. of Conductors)

1.12 Resultant spring constant of both supports of one span S = 100000 N/m

1.13 Phase to Phase spacing of the conductor a = 0.55 m

1.14 Chord length of main conductor in the span Lc = 2.5 m

1.15 Absolute permeability of vacuum μo = 4 π x 10-7 H/m

1.16 Acceleration due to gravity gn = 9.81 m/sec2

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV LA & 11KV CT KDN RSM 0

2.00 METHODOLGY AND ASSUMPTIONS

2.01 The Effect of short circuit force has been considered to be on the gantries having strung bus within the
substation to cater for the extreme operational situations.

2.02 Temperature rise due to short circuit and the subsequent reduction in tension to this effect is neglected.

3.00 TENSILE FORCE DURING SHORT CIRCUIT

3.01 Electromagnetic force per unit length (F' )

μo x 0.75 x Isc2 x Lc
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L
Where,
Lc = L

4πx 10-7 x 0.75 x (20000^2)


F' =
2π x 0.55

F' = 109.0909 N/m

3.02 The Parameter ' r '


F' 109.0909
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (20))
r = =
n x m's x gn 1 x 2.002 x 9.81

r = 5.5546

3.03 Stiffness Norms (N) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (25))


1 1
N = +
SxL n x E s x As

Where,
Fst x 90
Es = E x 0.3+ 0.7sin For (Fst/nAs ≤ σfin)
(n x As x σfin)

Es = E For (Fst/nAs > σfin)

σfin = 5.00E+07 N/m2 Lowest value of s when Young's Modulus becomes constant.

490.5 x 90
Es = 68600000000 x 0.3 + 0.7 sin
1 x 0.000597 x 50000000
Es = 2.1819E+10 N/m2

1 1
N = +
100000 x 2.5 1 x 21819334341.6285 x 0.000597

N = 4.0768E-06 1/N

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV LA & 11KV CT KDN RSM 0

3.04 Stress Factor (ζ) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (28))

(n x gn x m's x L)2 (1 x 9.81 x 2.002 x 2.5)^2


ζ = =
24 x Fst3 x N 24 x (490.5^3) x 0.00000407677

ζ = 0.2088

3.05 The Direction of Resulting force(δ1) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (21))

δ1 = arctan( r ) = arctan( 5.5546 ) = 1.3927 radians

δ1 = 79.7958 degree

3.06 Equivalent Static conductor sag at midpoint (b c) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (22))

n x m's x gn x L2 1 x 2.002 x 9.81 x (2.5^2)


bc = = m
8 x Fst 8 x 490.5

bc = 0.0313 m

3.07 Periods of the conductor Oscillations (T) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (23))

0.8 x bc 0.8 x 0.0313


T = 2π x = 2π x
gn 9.81

T = 0.3175 secs

3.08 Resulting Period of the conductor oscillation during short circuit(T res)
T
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (24))
Tres = secs
4 π2 δ1 ^2
(1 + r2) x 1 -
### 90°

T
= secs
4 π2 79.7958 ^2
(1+5.5546^2) x 1 -
### 90°

Tres = 0.1521 secs

3.09 The Load Parameter (φ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (32))

φ = 3x (1+r2) - 1 For Tk1 >= Tres / 4

= 3 x (r sinδk + cosδk-1) For Tk1 < Tres / 4

Tres 0.1521
= = 0.038 Tk1 = 3 secs
4 4

Page 3 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV LA & 11KV CT KDN RSM 0

Page 4 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV LA & 11KV CT KDN RSM 0

For Tk1 >= Tres / 4

φ = 3x (1+r2) - 1 = 3x (1+5.5546^2) - 1

φ = 13.9317

3.10 The Factor ( ψ ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (33))

The factor ψ is a function of ζ & φ, which is

φ2 x ψ3 + φ(2 + ζ) x ψ2 +(1 + 2ζ)ψ-ζ(2 + φ) = 0

φ = 13.9317 ζ = 0.2088

ψ = 0.206821818

13.9317^2 x 0.2069^3 + 13.9317(2 + 0.2088) x 0.21^2 +(1 + 2 x 0.2088)x0.2069-0.2088(2 + 13.9317)

= 0.000
For the above equation to be zero,
ψ = 0.2069

3.11 The Tensile force due to short circuit( F t ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (34))

Ft = Fst x (1 + (ψ x φ)) = 490.5 x (1 + (0.2069 x 13.9317) = 1904.35 N

Ft = 1.905 kN

4.00 TENSILE FORCE AFTER SHORT CIRCUIT, CAUSED BY DROP( DROP FORCE)

4.01 Drop Force (Ff) (IEC-865-I(1993) CLAUSE : 2.3.2.3 EQN (35))

Ff = 1.2 x Fst (1 + 8 x ζ x (δm/180))

Where,
δm = 1.25 arccos(χ) For 0.766 ≤ χ ≤ 1
= 10 + arccos(χ) For -0.985 < χ < 0.766
= 180° For χ < -0.985
χ = 1 - r sinδk For 0 ≤ δk ≤ 90
= 1-r For δk > 90

δk = δ1(1- cos(360 x Tk1/Tres)) For 0 ≤ Tk1/Tres ≤ 0.5


= 2δ1 For Tk1/Tres > 0.5
Tk1 3
= = 19.7239
Tres 0.1521

δk = 2 x 79.7958 = 159.592 For Tk1/Tres > 0.5

χ = 1 - 5.5546 = -4.5546 For δk > 90

δm = 180 = 180 For X < -0.985

Ff = 1.2 x 490.5 (1 + 8 x 0.2088 x (180/180)) = 961.9 N


Page 5 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV LA & 11KV CT KDN RSM 0
Ff = 1.2 x 490.5 (1 + 8 x 0.2088 x (180/180)) = 961.9 N

Page 6 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV LA & 11KV CT KDN RSM 0

Ff = 0.96 kN

4.02 Horizontal Displacement (bh) and minimum air clearance(amin)


(IEC-865-I(1993) CLAUSE : 2.3.2.4 EQN (36))
Eela = N (Ft - Fst) = 0.00000407677 x (1904.35 - 490.5) = 0.0057666

Isc ^2 Tres Cth = 0.27*10^-18 for Aluminium/Steel > 6


Eth = Cth x x
n As 4 Cth = 0.17*10^-18 for Aluminium/Steel ≤ 6

20000 ^2 0.1521
= 0.27*10^(-18) x x
1x0.000597 4
= 1.15224E-05

CD = (1+(3/8) x ((L/bc)^2) x (Eela + Eth) = 3.8501

bh = CF x CD x bc x (Sinδ1) for δm ≥ δ1 δm = 180.0 δ1 = 79.8 from above cl.

CF = 1.05 For r ≤ 0.8 Where r = 5.5546


= 0.97+0.1r For 0.8 < r < 1.8 from above cl. 3.02
= 1.15 For r ≥ 1.8
Hence CF = 1.15
bh = 1.15 x 3.8501 x 0.0313 x sin(79.7958) = 0.1364
(IEC-865-I(1993) CLAUSE : 2.3.2.4 EQN (42))
amin = a - (2 x bh) = 0.55 - (2 x 0.1364)

amin = 0.2772 m

6.00 CONCLUSION
6.01 The tensile force due to short circuit Ft = 1.905 kN ( 0.19 T )

6.02 The tensile force after short circuit due to drop Ff = 0.96 kN ( 0.1 T )

6.04 The Short Circuit Tensile Force of 1.905kN can be used for associated Foundation & Structure
design

Page 7 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV LA & 11KV CT KDN RSM 0

Page 8 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV CT & 11KV VSBD KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 11 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Number of sub conductors n = 1

1.07 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.08 Cross sectional area of the conductor As = 0.000597 m2

1.09 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.10 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.11 = 490.5 N (50x9.81x1)
(=Tension per sub conductor x 9.81 x No. of Conductors)

1.12 Resultant spring constant of both supports of one span S = 100000 N/m

1.13 Phase to Phase spacing of the conductor a = 0.6 m

1.14 Chord length of main conductor in the span Lc = 1.4 m

1.15 Absolute permeability of vacuum μo = 4 π x 10-7 H/m

1.16 Acceleration due to gravity gn = 9.81 m/sec2

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV CT & 11KV VSBD KDN RSM 0

2.00 METHODOLGY AND ASSUMPTIONS

2.01 The Effect of short circuit force has been considered to be on the gantries having strung bus within the
substation to cater for the extreme operational situations.

2.02 Temperature rise due to short circuit and the subsequent reduction in tension to this effect is neglected.

3.00 TENSILE FORCE DURING SHORT CIRCUIT

3.01 Electromagnetic force per unit length (F' )

μo x 0.75 x Isc2 x Lc
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L
Where,
Lc = L

4πx 10-7 x 0.75 x (20000^2)


F' =
2π x 0.6

F' = 100 N/m

3.02 The Parameter ' r '


F' 100
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (20))
r = =
n x m's x gn 1 x 2.002 x 9.81

r = 5.0917

3.03 Stiffness Norms (N) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (25))


1 1
N = +
SxL n x E s x As

Where,
Fst x 90
Es = E x 0.3+ 0.7sin For (Fst/nAs ≤ σfin)
(n x As x σfin)

Es = E For (Fst/nAs > σfin)

σfin = 5.00E+07 N/m2 Lowest value of s when Young's Modulus becomes constant.

490.5 x 90
Es = 68600000000 x 0.3 + 0.7 sin
1 x 0.000597 x 50000000
Es = 2.1819E+10 N/m2

1 1
N = +
100000 x 1.4 1 x 21819334341.6285 x 0.000597

N = 7.2196E-06 1/N

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV CT & 11KV VSBD KDN RSM 0

3.04 Stress Factor (ζ) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (28))

(n x gn x m's x L)2 (1 x 9.81 x 2.002 x 1.4)^2


ζ = =
24 x Fst3 x N 24 x (490.5^3) x 0.00000721963

ζ = 0.037

3.05 The Direction of Resulting force(δ1) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (21))

δ1 = arctan( r ) = arctan( 5.0917 ) = 1.3769 radians

δ1 = 78.8906 degree

3.06 Equivalent Static conductor sag at midpoint (b c) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (22))

n x m's x gn x L2 1 x 2.002 x 9.81 x (1.4^2)


bc = = m
8 x Fst 8 x 490.5

bc = 0.0098 m

3.07 Periods of the conductor Oscillations (T) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (23))

0.8 x bc 0.8 x 0.0098


T = 2π x = 2π x
gn 9.81

T = 0.1777 secs

3.08 Resulting Period of the conductor oscillation during short circuit(T res)
T
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (24))
Tres = secs
4 π2 δ1 ^2
(1 + r2) x 1 -
### 90°

T
= secs
4 π2 78.8906 ^2
(1+5.0917^2) x 1 -
### 90°

Tres = 0.0885 secs

3.09 The Load Parameter (φ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (32))

φ = 3x (1+r2) - 1 For Tk1 >= Tres / 4

= 3 x (r sinδk + cosδk-1) For Tk1 < Tres / 4

Tres 0.0885
= = 0.0221 Tk1 = 3 secs
4 4

Page 3 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV CT & 11KV VSBD KDN RSM 0

Page 4 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV CT & 11KV VSBD KDN RSM 0

For Tk1 >= Tres / 4

φ = 3x (1+r2) - 1 = 3x (1+5.0917^2) - 1

φ = 12.5669

3.10 The Factor ( ψ ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (33))

The factor ψ is a function of ζ & φ, which is

φ2 x ψ3 + φ(2 + ζ) x ψ2 +(1 + 2ζ)ψ-ζ(2 + φ) = 0

φ = 12.5669 ζ = 0.037

ψ = 0.101677448

12.5669^2 x 0.1017^3 + 12.5669(2 + 0.037) x 0.11^2 +(1 + 2 x 0.037)x0.1017-0.037(2 + 12.5669)

= 0.001
For the above equation to be zero,
ψ = 0.1017

3.11 The Tensile force due to short circuit( F t ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (34))

Ft = Fst x (1 + (ψ x φ)) = 490.5 x (1 + (0.1017 x 12.5669) = 1117.39 N

Ft = 1.118 kN

4.00 TENSILE FORCE AFTER SHORT CIRCUIT, CAUSED BY DROP( DROP FORCE)

4.01 Drop Force (Ff) (IEC-865-I(1993) CLAUSE : 2.3.2.3 EQN (35))

Ff = 1.2 x Fst (1 + 8 x ζ x (δm/180))

Where,
δm = 1.25 arccos(χ) For 0.766 ≤ χ ≤ 1
= 10 + arccos(χ) For -0.985 < χ < 0.766
= 180° For χ < -0.985
χ = 1 - r sinδk For 0 ≤ δk ≤ 90
= 1-r For δk > 90

δk = δ1(1- cos(360 x Tk1/Tres)) For 0 ≤ Tk1/Tres ≤ 0.5


= 2δ1 For Tk1/Tres > 0.5
Tk1 3
= = 33.8983
Tres 0.0885

δk = 2 x 78.8906 = 157.781 For Tk1/Tres > 0.5

χ = 1 - 5.0917 = -4.0917 For δk > 90

δm = 180 = 180 For X < -0.985

Ff = 1.2 x 490.5 (1 + 8 x 0.037 x (180/180)) = 670.1 N


Page 5 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV CT & 11KV VSBD KDN RSM 0
Ff = 1.2 x 490.5 (1 + 8 x 0.037 x (180/180)) = 670.1 N

Page 6 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV CT & 11KV VSBD KDN RSM 0

Ff = 0.67 kN

4.02 Horizontal Displacement (bh) and minimum air clearance(amin)


(IEC-865-I(1993) CLAUSE : 2.3.2.4 EQN (36))
Eela = N (Ft - Fst) = 0.00000721963 x (1117.39 - 490.5) = 0.0045303

Isc ^2 Tres Cth = 0.27*10^-18 for Aluminium/Steel > 6


Eth = Cth x x
n As 4 Cth = 0.17*10^-18 for Aluminium/Steel ≤ 6

20000 ^2 0.0885
= 0.27*10^(-18) x x
1x0.000597 4
= 6.70438E-06

CD = (1+(3/8) x ((L/bc)^2) x (Eela + Eth) = 5.9768

bh = CF x CD x bc x (Sinδ1) for δm ≥ δ1 δm = 180.0 δ1 = 78.9 from above cl.

CF = 1.05 For r ≤ 0.8 Where r = 5.0917


= 0.97+0.1r For 0.8 < r < 1.8 from above cl. 3.02
= 1.15 For r ≥ 1.8
Hence CF = 1.15
bh = 1.15 x 5.9768 x 0.0098 x sin(78.8906) = 0.0661
(IEC-865-I(1993) CLAUSE : 2.3.2.4 EQN (42))
amin = a - (2 x bh) = 0.6 - (2 x 0.0661)

amin = 0.4678 m

6.00 CONCLUSION
6.01 The tensile force due to short circuit Ft = 1.118 kN ( 0.11 T )

6.02 The tensile force after short circuit due to drop Ff = 0.67 kN ( 0.07 T )

6.04 The Short Circuit Tensile Force of 1.118kN can be used for associated Foundation & Structure
design

Page 7 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE BETWEEN 11KV CT & 11KV VSBD KDN RSM 0

Page 8 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV PI & 11KV PI KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 11 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 0.6 m

1.12 Length of Jumper (Maximum length considered) LT = 1.8 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 100 N/m
2π x 0.6

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 100 * 1.8 = 180 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 18.35 kG

3.02 The Short Circuit Tensile Force of 18.35kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV PI & 11KV PI KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV PI & 11KV DOF KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 11 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 0.6 m

1.12 Length of Jumper (Maximum length considered) LT = 1 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 100 N/m
2π x 0.6

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 100 * 1 = 100 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 10.2 kG

3.02 The Short Circuit Tensile Force of 10.2kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV PI & 11KV DOF KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV DOF & 11KV PI KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 11 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 0.6 m

1.12 Length of Jumper (Maximum length considered) LT = 1 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 100 N/m
2π x 0.6

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 100 * 1 = 100 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 10.2 kG

3.02 The Short Circuit Tensile Force of 10.2kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV DOF & 11KV PI KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV PI & 11KV BUS KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 11 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 0.6 m

1.12 Length of Jumper (Maximum length considered) LT = 3.1 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 100 N/m
2π x 0.6

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 100 * 3.1 = 310 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 31.61 kG

3.02 The Short Circuit Tensile Force of 31.61kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV PI & 11KV BUS KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE "A" FRAME STRUNG BUS KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 11 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = MOOSE ACSR

1.06 Number of sub conductors n = 1

1.07 Chord length of main conductor in the span Lc = 3.2 m

1.08 Unit weight of the one sub conductor + Clamp Weight m's = 2.423875 kg/m

1.09 Resulting mass perunit length of one sub conductor m'sc = 1.65E+01 kg/m

1.10 Cross sectional area of the conductor As = 0.000597 m2

1.11 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.12 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.13 = 2452.5 N (250x9.81)
(=Tension per sub conductor x 9.81)

1.14 Resultant spring constant of both supports of one span S = 100000 N/m

1.15 Phase to Phase spacing of the conductor a = 0.6 m

1.16 Centre line distance between two supports = 4.2 m

1.17 Length of the insulator string Li = 0.4 m

1.18 Width of the girder Wg = 0.2 m

1.19 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.20 Acceleration due to gravity gn = 9.81 m/sec2


NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE "A" FRAME STRUNG BUS KDN RSM 0

2.00 METHODOLGY AND ASSUMPTIONS

2.01 The Effect of short circuit force has been considered to be on the gantries having strung bus within the
substation to cater for the extreme operational situations.

2.02 Temperature rise due to short circuit and the subsequent reduction in tension to this effect is neglected.

3.00 TENSILE FORCE DURING SHORT CIRCUIT

3.01 Electromagnetic force per unit length (F' )

μo x 0.75 x Isc2 x Lc
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L
Where,
Lc = L- (2Li + Wg) = 4.2 - ((2 x 0.4) + 0.2) = 3.2 m

4πx 10-7 x 0.75 x (20000^2) x 3.2


F' =
2π x 0.6 x 4.2

F' = 76.1905 N/m

3.02 The Parameter ' r '


F' 76.1905
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (20))
r = =
n x m's x gn 1 x 16.5126 x 9.81

r = 0.4703

3.03 Stiffness Norms (N) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (25))


1 1
N = +
SxL n x Es x As

Where,
Fst x 90
Es = E x 0.3+ 0.7sin For (Fst/nAs ≤ σfin)
(n x As x σfin)

Es = E For (Fst/nAs > σfin)

σfin = 5.00E+07 N/m2 Lowest value of s when Young's Modulus becomes constant.

2452.5 x 90
Es = 68600000000 x 0.3 + 0.7 sin
1 x 0.000597 x 50000000
Es = 2.6760E+10 N/m2

1 1
N = +
100000 x 4.2 1 x 26760170351.4738 x 0.000597

N = 2.4436E-06 1/N
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE "A" FRAME STRUNG BUS KDN RSM 0

3.04 Stress Factor (ζ) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (28))

(n x gn x m's x L)2 (1 x 9.81 x 16.5126 x 4.2)^2


ζ = =
24 x Fst3 x N 24 x (2452.5^3) x 0.00000244355

ζ = 0.5351

3.05 The Direction of Resulting force(δ1) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (21))

δ1 = arctan( r ) = arctan( 0.4703 ) = 0.4396 radians

δ1 = 25.1872 degree

3.06 Equivalent Static conductor sag at midpoint (bc) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (22))

n x m's x gn x L2 1 x 16.5126 x 9.81 x (4.2^2)


bc = = m
8 x Fst 8 x 2452.5

bc = 0.1456 m

3.07 Periods of the conductor Oscillations (T) (IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (23))

0.8 x bc 0.8 x 0.1456


T = 2π x = 2π x
gn 9.81

T = 0.6847 secs

3.08 Resulting Period of the conductor oscillation during short circuit(Tres)


T
Tres (IEC-865-I(1993) CLAUSE : 2.3.2.1
= secs
EQN (24))
4 π2 δ1 ^2
(1 + r2) x 1 -
### 90°

0.6847
= secs
^2
4 π2 25.1872
(1+0.4703^2) x 1 -
64 90°

Tres = 0.6593 secs

3.09 The Load Parameter (φ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (32))

φ = 3x (1+r2) - 1 For Tk1 >= Tres / 4

= 3 x (r sinδk + cosδk-1) For Tk1 < Tres / 4

Tres 0.6593
= = 0.1648 Tk1 = 3 secs
4 4
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE "A" FRAME STRUNG BUS KDN RSM 0

For Tk1 >= Tres / 4

φ = 3x (1+r2) - 1 = 3x (1+0.4703^2) - 1

φ = 0.3152

3.10 The Factor ( ψ ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (33))

The factor ψ is a function of ζ & φ, which is

φ2 x ψ3 + φ(2 + ζ) x ψ2 +(1 + 2ζ)ψ-ζ(2 + φ) = 0

φ = 0.3152 ζ = 0.5351

ψ = 0.497139409

0.3152^2 x 0.4972^3 + 0.3152(2 + 0.5351) x 0.5^2 +(1 + 2 x 0.5351)x0.4972-0.5351(2 + 0.3152)

= 0.000
For the above equation to be zero,
ψ = 0.4972

3.11 The Tensile force due to short circuit( Ft ) (IEC-865-I(1993) CLAUSE : 2.3.2.2 EQN (34))

Ft = Fst x (1 + (ψ x φ)) = 2452.5 x (1 + (0.4972 x 0.3152) = 2836.85 N

Ft = 2.837 kN

4.00 TENSILE FORCE AFTER SHORT CIRCUIT, CAUSED BY DROP( DROP FORCE)

4.01 Drop Force (Ff) (IEC-865-I(1993) CLAUSE : 2.3.2.3 EQN (35))

Ff = 1.2 x Fst x (1 + 8 x ζ x (δm/180))

Where,
δm = 1.25 arccos(χ) For 0.766 ≤ χ ≤ 1
= 10 + arccos(χ) For -0.985 < χ < 0.766
= 180° For χ < -0.985
χ = 1 - r sinδk For 0 ≤ δk ≤ 90
= 1-r For δk > 90

δk = δ1(1- cos(360 x Tk1/Tres)) For 0 ≤ Tk1/Tres ≤ 0.5


= 2δ1 For Tk1/Tres > 0.5
Tk1 3
= = 4.5503
Tres 0.6593

δk = 2 x 25.1872 = 50.374 For Tk1/Tres > 0.5

χ = 1 - 0.4703 x SIN(50.374) = 0.6378 For 0 ≤ δk ≤ 90

δm = 10 + arccos(0.6378) = 60.37 For -0.985 < χ < 0.766

Ff = 1.2 x 2452.5 (1 + 8 x 0.5351 x (60.37/180)) = 4593.1 N


NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE "A" FRAME STRUNG BUS KDN RSM 0

Ff = 4.59 kN

4.02 Horizontal Displacement (bh) and minimum air clearance(amin)


(IEC-865-I(1993) CLAUSE : 2.3.2.4 EQN (36))
Eela = N (Ft - Fst) = 0.00000244355 x (2836.85 - 2452.5) = 0.0009395

Isc ^2 Tres Cth = 0.27*10^-18 for Aluminium/Steel > 6


Eth = Cth x x
n As 4 Cth = 0.17*10^-18 for Aluminium/Steel ≤ 6
2
20000 0.6593
= 0.27*10^(-18) x x
1x0.000597 4
= 4.99457E-05

CD = (1+(3/8) x ((L/bc)^2) x (Eela + Eth) = 1.144

bh = CF x CD x bc x (Sinδ1) for δm ≥ δ1 δm = 60.4 δ1 = 25.2 from above cl.

CF = 1.05 For r ≤ 0.8 Where r = 0.4703


= 0.97+0.1r For 0.8 < r < 1.8 from above cl. 3.02
= 1.15 For r ≥ 1.8
Hence CF = 1.05
bh = 1.05 x 1.144 x 0.1456 x sin(25.1872) = 0.0744
(IEC-865-I(1993) CLAUSE : 2.3.2.4 EQN (42))
amin = a - (2 x bh) = 0.6 - (2 x 0.0744)

amin = 0.4512 m

6.00 CONCLUSION
6.01 The tensile force due to short circuit Ft = 2.837 kN ( 0.29 T )

6.02 The tensile force after short circuit due to drop Ff = 4.59 kN ( 0.47 T )

6.04 The Short Circuit Tensile Force of 4.59kN can be used for tower and associated Foundation design
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE "A" FRAME STRUNG BUS KDN RSM 0
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV BUS & 11KV PI KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 11 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 0.6 m

1.12 Length of Jumper (Maximum length considered) LT = 1.2 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 100 N/m
2π x 0.6

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 100 * 1.2 = 120 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 12.24 kG

3.02 The Short Circuit Tensile Force of 12.24kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV BUS & 11KV PI KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV PI & 11KV AR (1) KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 11 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 0.6 m

1.12 Length of Jumper (Maximum length considered) LT = 1.5 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 100 N/m
2π x 0.6

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 100 * 1.5 = 150 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 15.3 kG

3.02 The Short Circuit Tensile Force of 15.3kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV PI & 11KV AR (1) KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV OHL & 11KV DOF KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 11 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 0.6 m

1.12 Length of Jumper (Maximum length considered) LT = 2 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 100 N/m
2π x 0.6

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 100 * 2 = 200 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 20.39 kG

3.02 The Short Circuit Tensile Force of 20.39kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV OHL & 11KV DOF KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV DOF & 11KV AR KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 11 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 0.6 m

1.12 Length of Jumper (Maximum length considered) LT = 1 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 100 N/m
2π x 0.6

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 100 * 1 = 100 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 10.2 kG

3.02 The Short Circuit Tensile Force of 10.2kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV DOF & 11KV AR KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV BUS & 11KV PI (1) KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 11 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 0.6 m

1.12 Length of Jumper (Maximum length considered) LT = 3.1 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 100 N/m
2π x 0.6

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 100 * 3.1 = 310 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 31.61 kG

3.02 The Short Circuit Tensile Force of 31.61kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV BUS & 11KV PI (1) KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV PI & 11KV PI KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 11 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 0.6 m

1.12 Length of Jumper (Maximum length considered) LT = 0.7 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 100 N/m
2π x 0.6

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 100 * 0.7 = 70 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 7.14 kG

3.02 The Short Circuit Tensile Force of 7.14kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV PI & 11KV PI KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV PI & 11KV AR (2) KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 11 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 0.6 m

1.12 Length of Jumper (Maximum length considered) LT = 1.5 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 100 N/m
2π x 0.6

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 100 * 1.5 = 150 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 15.3 kG

3.02 The Short Circuit Tensile Force of 15.3kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV PI & 11KV AR (2) KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV AR & 11KV DOF KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 11 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 0.6 m

1.12 Length of Jumper (Maximum length considered) LT = 1 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 100 N/m
2π x 0.6

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 100 * 1 = 100 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 10.2 kG

3.02 The Short Circuit Tensile Force of 10.2kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV AR & 11KV DOF KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV DOF & 11KV OHL KDN RSM 0

0.00 REFERENCES

0.01 IEC 865 Part - 1 1993

0.02 Mubofwe Dam 33/11kV Substation Electrical Layout - Plan, Drg No. NCC-ZES-MD-ELE-DRG-002

0.03 Mubofwe Dam 33/11kV Substation Electrical Layout - Section, Drg No. NCC-ZES-MD-ELE-DRG-002

1.00 SYSTEM DATA

1.01 System Nominal Voltage Vs = 11 kV

1.02 Symmetrical Short circuit current(3Ф) Isc = 20 kA

1.03 Duration of short circuit current tsc = 3 sec

1.04 System frequency f = 50 Hz

1.05 Type of Conductor = SINGLE MOOSE ACSR

1.06 Resulting mass perunit length of one sub conductor m's = 2.002 kg/m

1.07 Cross sectional area of the conductor As = 0.000597 m2

1.08 Modulus of Elasticity of the conductor E = 6.86E+10 N/m2

1.09 Overall diameter of the flexible conductor ds = 0.03178 m

Static Tensile force per phase Fst


1.10 = 490.5 N (50x9.81)
(=Tension per sub conductor x 9.81)

1.11 Phase to Phase spacing of the conductor a = 0.6 m

1.12 Length of Jumper (Maximum length considered) LT = 2 m

1.13 Absolute permeability of vacuum μo = 4π x 10-7 H/m

1.14 Acceleration due to gravity gn = 9.81 m/sec2

2.00 TENSILE FORCE DURING SHORT CIRCUIT

2.01 Electromagnetic force per unit length (F')

μo x 0.75 x Isc2 x LT
(IEC-865-I(1993) CLAUSE : 2.3.2.1 EQN (19))
F' = N/m
2π x a x L

Where, LT = L

4πx 10-7 x 0.75 x (20000^2)


F' = = F' = 100 N/m
2π x 0.6

2.02 Total Lateral Force due to SCF

Hence, total Lateral Force due to SCF = F' * LT = 100 * 2 = 200 N

3.00 CONCLUSION
3.01 The tensile force due to short circuit Ft = 20.39 kG

3.02 The Short Circuit Tensile Force of 20.39kG can be used for associated Foundation & Structure
design

Page 1 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID DOCUMENT No. DATE


PROJECT EXTENSION IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
SHORT CIRCUIT FORCE CALCULATION DESIGNED APPROVED REV.
TITLE JUMPER BETWEEN 11KV DOF & 11KV OHL KDN RSM 0

Page 2 of 30
NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID EXTENSION DOCUMENT No. DATE


PROJECT IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
MUBOFWE DAM 33/11KV SS DESIGNED APPROVED REV.
TITLE SHORT CIRCUIT FORCE CALCULATION - SUMMARY KDN RSM 0

CALCULATED VALUES :

CHORD PH. - PH. INITIAL TENSILE FORCE DROP FORCE


S.NO DESCRIPTION
LENGTH SPACING TENSION DUE TO SCF DUE TO SCF
1 33KV OHL - 33KV DOF 1.50 m 0.80 m - 11.47 kg -

2 33KV DOF - 33KV PI 1.50 m 0.80 m - 11.47 kg -

3 33KV PI - 33KV LA 1.50 m 0.80 m - 11.47 kg -

4 33KV OHL - 33KV LA 1.50 m 1.25 m - 7.34 kg -

5 33KV SA - 33KV VT 3.00 m 1.25 m 50 kg 128.14 kg 118.25 kg

6 33KV VT - 33KV PI 2.00 m 1.25 m - 9.79 kg -

7 33KV PI - 33KV PI 1.50 m 1.25 m - 7.34 kg -

8 33KV PI - 33KV HDBD 1.50 m 1.25 m - 7.34 kg -

9 33KV HDBD - 33KV CT 2.30 m 0.45 m 50 kg 206.63 kg 90.73 kg

10 33KV CT - 33KV VCB 0.60 m 0.75 m 50 kg 60.96 kg 61.16 kg

11 33KV VCB - 33KV LA 2.40 m 0.69 m 50 kg 161.88 kg 94.80 kg

12 33KV LA - 33KV BUSHING 1.30 m 0.56 m 50 kg 111.9 kg 66.26 kg

13 11KV BUSHING - 11KV LA 1.30 m 0.43 m 50 kg 131.91 kg 66.26 kg

14 11KV LA - 11KV CT 2.50 m 0.55 m 50 kg 194.19 kg 97.86 kg

15 11KV CT - 11KV VSBD 1.40 m 0.60 m 50 kg 113.97 kg 68.30 kg

16 11KV VSBD - 11KV PI 1.80 m 0.60 m - 18.35 kg -

17 11KV PI - 11KV DOF 1.00 m 0.60 m - 10.20 kg -

18 11KV DOF - 11KV PI 1.00 m 0.60 m - 10.20 kg -

19 11KV PI - 11KV BUS 3.10 m 0.60 m - 31.61 kg -

20 11KV 4.2m STRUNG BUS 3.20 m 0.60 m 250 kg 289.19 kg 467.89 kg

21 11KV BUS - 11KV PI 1.20 m 0.60 m - 12.24 kg -

22 11KV PI - 11KV AR (1) 1.50 m 0.60 m - 15.30 kg -

23 11KV OHL - 11KV DOF 2.00 m 0.60 m - 20.39 kg -

24 11KV DOF - 11KV AR (1) 1.00 m 0.60 m - 10.20 kg -

25 11KV BUS - 11KV PI (1) 3.10 m 0.60 m - 31.61 kg -

26 11KV PI - 11KV PI 0.70 m 0.60 m - 7.14 kg -

27 11KV PI - 11KV AR (2) 1.50 m 0.60 m - 15.30 kg -

28 11KV AR (2) - 11KV DOF 1.00 m 0.60 m - 10.20 kg -

29 11KV DOF - 11KV OHL 2.00 m 0.60 m - 20.39 kg -

30 33KV OHL LINE - - 250 kg - -


NATIONAL CONTRACTING COMPANY

CONSTRUCTION WORKS FOR POWER GRID EXTENSION DOCUMENT No. DATE


PROJECT IN THE CENTRAL REGION NCC-ZES-MD-ELE-DRG-XXX 23.04.2014
MUBOFWE DAM 33/11KV SS DESIGNED APPROVED REV.
TITLE SHORT CIRCUIT FORCE CALCULATION - SUMMARY KDN RSM 0