DC SUPPLY
GENERATOR & MAINS (UTILITY)
VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
DSE6110 MKII
26 V to 719 V AC (Ph to Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
INPUTS
DIGITAL INPUTS A to F
Negative switching
ANALOGUE INPUT A
Configurable as:
Negative switching digital input
0 V to 10 V
4 mA to 20 mA
0 Ω to 240 Ω
ANALOGUE INPUTS B TO D
Configurable as:
Negative switching digital input
0 Ω to 480 Ω
OUTPUTS
OUTPUT A (FUEL)
10 A short term, 5 A continuous,
KEY FEATURES 4 to 20 mA oil pressure sensors • J1939-75 instrumentation output, at supply voltage
• Large back-lit text display • 6 configurable digital inputs configurable CAN instrumentation
• Multiple display languages • Configurable staged loading and alarms OUTPUT B (START)
• Heated display option available outputs • Start on low battery 10 A short term, 5 A continuous,
at supply voltage
• DSENet® expansion compatible • CAN, MPU and alternator speed • Enhanced alarm functionality
• Data logging facility sensing in one variant • Low load alarm AUXILIARY OUTPUTS C, D, E & F
• Fully configurable via PC using • 3 engine maintenance alarms KEY BENEFITS 2 A DC at supply voltage
USB communication • Engine speed protection • Automatically transfers between DIMENSIONS
• Front panel configuration • Engine hours counter mains (utility) and generator OVERALL
• Efficient power save mode • Engine pre-heat (DSE6120 MKII only) 216 mm x 158 mm x 43 mm
8.5’’ x 6.2” x 1.5”
• 3 phase generator sensing • Engine run-time scheduler • Increased input and output
• 3 phase mains (utility) sensing • Engine idle control for starting & expansion capability via DSENet® PANEL CUT-OUT
(DSE6120 MKII only) stopping • User-friendly set-up and button 184 mm x 137 mm
• Generator/load power monitoring • Fuel pump control layout for ease of use 7.2’’ x 5.3”
(kW, kV A, kV Ar, pf) • Real time clock • Multiple parameters are monitored MAXIMUM PANEL THICKNESS
• Accumulated power monitoring • Battery voltage monitoring simultaneously which are clearly 8 mm
(kW h, kVA h, kVAr h) • Start on low battery voltage displayed on a large back-lit text 0.3”
• Generator/load current monitoring • Configurable remote start input display via multiple languages STORAGE TEMPERATURE RANGE
and protection • 1 alternative configuration • The module can be configured to -40 °C to +85 °C
• Generator overload protection (kW) • Comprehensive warning, electrical suit a wide range of applications -40 °F to +185 °F
• Breaker control via fascia buttons trip or shutdown protection upon • Uses DSE Configuration Suite
OPERATING TEMPERATURE RANGE
• Fuel and start outputs, configurable fault condition PC Software for simplified NON HEATED DISPLAY VARIANT
when using CAN • LCD and LED alarm indication configuration -30°C to +70°C
• 4 configurable DC outputs • Customisable information screens • Licence-free PC software -22 °F to +158 °F
• 4 configurable analogue/digital • Configurable event log (100) • IP65 rating (with optional gasket) HEATED DISPLAY VARIANT
inputs • Tier 4 ECO engine support offers increased resistance to water -40 °C to +70 °C
• Support for 0 to10 V & including exhaust fluids & filters ingress -40 °F to +158 °F
OPTIONAL PARTS
RELATED MATERIALS
TITLE PART NO. PART PART NUMBER
IP65 Gasket 020-521
DSE6110/20 MKII Installation Instructions 053-173
DSE6110/20 MKII Operator Manual 057-226
DSE6110/20 MKII Configuration Suite PC Manual 057-224
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
AUTO START & AUTO MAINS FAILURE EMC Generic Immunity Standard for
the Industrial Environment
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment
The DSE6110 MKII Auto Start Control Electronic J1939 (CAN) and non- Using the DSE Configuration Suite
Module and the DSE6120 MKII Auto electronic MPU and alternator sensing PC Software the controller is easy TEMPERATURE
Mains (Utility) Failure Control Module engine support for diesel, gas and to use and configure which allows BS EN 60068-2-1
Ab/Ae Cold Test -30 ºC
are suitable for a wide variety of single petrol engines all in one variant. With alteration of operating parameters, BS EN 60068-2-2
gen-set applications. a number of flexible inputs, outputs sequences, timers and alarms. Bb/Be Dry Heat +70 ºC
and protections, the modules can be
VIBRATION
Monitoring engine speed, oil pressure, easily adapted to suit a wide range of
AVAILABLE VARIANTS BS EN 60068-2-6
coolant temperature, frequency, applications. Ten sweeps in each of three
voltage, current, power and fuel level, 6110-03 Auto Start with real time clock
major axes
the modules give comprehensive Through USB Communication both 5 Hz to 8 Hz at +/-7.5 mm,
8 Hz to 500 Hz at 2 GN
engine and alternator protection. This modules can be configured using the 6120-03 Auto Mains Failure with real
time clock
is indicated on a large back-lit LCD DSE Configuration Suite PC Software HUMIDITY
text display via an array of warning, or through the module’s front panel BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 ºC
electrical trip and shutdown alarms in editor. at 95% RH 48 Hours
multiple languages. BS EN 60068-2-78
Cab Damp Heat Static 40 ºC
at 93% RH 48 Hours
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 GN in 11 mS
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the optional sealing gasket.
DSE2130
DSE2157 6 4 4
DSE2548
DSE6110/20 MKII
7
OTHER
MAINS (UTILITY) DC OUTPUT GENERATOR/ DC OUTPUT GENERATOR CHARGE FUEL & START ELECTRONIC
SENSING 1 OF 4 LOAD CURRENT 1 OF 4 SENSING ALTERNATOR OUTPUTS ENGINES OR
(DSE6120 MKII) (Flexible with CAN) MAGNETIC PICK-UP
VOLTS
+
VOLTS
D+
+ W/L +