Ground Clearance*
Safety Clearances
Clearances$
Switching Impulse
Lightning Impulse
Highest System
Normal System
Voltage (kV)
Voltage(kV)
Voltage(kV)
Voltage(kV)
(mm)
(mm)
(mm)
Between
Between
Phases
Phase
Earth
and
11 12 70 - 178 229 2600 3700
1050
(Ph-E) 3400 -
400 420 1425
1575 6400 8000
(Ph-Ph) - 4200
1550
(Ph-E) 6400 -
765 800 2100
2550 10300 13000
(Ph-Ph) - 9400
Frequency =50Hz
Type = Outdoor
= 172.5kV rms
= 184kV rms
From Equation (3.6), the discharge actor range from 2.4 to 3 and the value is 2.6
= 448.5kV (crest)
= 478.4kV (crest)
= 657.8kV (crest)
= 878.117 kV (crest)
= 651.176 kV (crest)
= 613.3525 kV (crest)
= 2552.264 kV
Ls = 3.88 x 478.4
= 1856.192 kV
Ls = 3.88 x 448.5
= 1740.18 kV
= 529 kV
= 545.1 kV
= 581.9 kV
= 206.57 kV
= 681.681 kV
= 0.146 x 13 =1.898 m
= 90%
Frequency =50Hz
Type = Outdoor
= 49.5kV rms
= 52.8kV rms
From Equation (3.6), the discharge actor range from 2.4 to 3 and the value is 2.6
Discharge voltage on 75% basis = 49.5 x 2.6
= 128.7kV (crest)
= 137.28kV (crest)
= 188.76kV (crest)
= 284.78 kV (crest)
= 219.66 kV (crest)
= 208.81 kV (crest)
Ls = 3.88 x 188.76
= 732.389 kV
Ls = 3.88 x 137.28
= 532.65 kV
Ls = 3.88 x 128.7
= 499.36 kV
Lp= 2.3 x 66
= 151.8 kV
Lp= 2.37 x 66
= 156.42 kV
Lp= 2.53 x 66
= 166.98 kV
= 59.28kV
= 196 kV
= 0.146 x 5 =0.73 m
Require Horn gap = 50cm =0.5m [From Table 4.3]
= 69%