MEMO

Peerless Pump Company


2005 Dr. Martin Luther King Jr. Street
Indianapolis, IN • 46202

phone - 317.924.7294 • fax - 317.924.7333 Ddixon@grundfos.com


www.peerlesspump.com • www.labour-taber.com

To: Eng. Khidr Chmes @ Naffco - Qatar

From: Dan Dixon

CC:

Date: May 17, 2012

Re: Flexible Pipe Couplings

Dear Eng. Khidr,

This memo is to address your concerns regarding the use of flexible pipe connections in Fire Pump installations.

NFPA 20 does not require the use of flexible pipe connections. As a manufacturer of NFPA compliant Fire Fighting
pumps, we do not recommend or discourage their use.

Proper mounting and alignment procedures should be followed. These procedures will eliminate most causes of system
vibration.

Fire Pumps are Emergency Service equipment. Some additional noise and vibration in the pipe system is of little concern
where life and property are at risk.

Please let me know if you have any questions or concerns.

Respectfully,
Dan Dixon
Dan Dixon
Senior Application Engineer