Академический Документы
Профессиональный Документы
Культура Документы
By
Keith Lofland
-
January 31, 2017
0
7557
One might say, “OK, what’s the big deal; what’s the harm?” When put to
work carrying the load they are intended to carry (such as a lighting load),
the enclosed conductors produce heat from current flow associated with
these loads. These conductors must have ample free space to allow proper
dissipation of heat from the conductor to not cause damage to the
surrounding insulation of these said conductors. A crowded elevator heats
up fairly quickly because you and the other heat radiators (bodies) don’t
have ample room to dissipate the produced body heat. The same principle
applies to conductors enclosed in a confined space, such as a switch box.
Metal boxes usually have a means for connecting the box to an equipment
grounding conductor. Typically, this consists of a 10-32 tapped hole. Some
nonmetallic boxes contain an integral means for bonding switches and
metal faceplates to the equipment grounding conductor. The bonding
means may be a metal strap or band that links the device mounting screw
to an equipment grounding terminal [see NEC 314.40(D)].
This total volume (space) determines the number and size of conductors
and wiring devices permitted to be contained in the box. Conductors,
internal clamps, support fittings, barriers, and devices such as switches and
receptacles take up space within the box. The Code assigns to each
conductor, clamp, support fitting, barrier, device, and equipment grounding
conductor an associated volume allowance. This volume allowance is listed
in cubic inches or cubic centimeters. NEC Table 314.16(B) lists the volume
allowance as a function of conductor size. The volume allowance for each
conductor, clamp, support fitting, barrier, device, and equipment grounding
conductor is added together. The box must have a volume that equals or
exceeds the total volume required for the contained items.
Photo 1. Double
4-Square metallic box with plaster extension ring
Where a box is provided with one or more securely installed barriers, the
volume is to be allocated to each of the resulting spaces. Each barrier, if
not marked with its volume, is to be considered to take up 8.2 cm 3 (1∕2 in3)
if metal, and 16.4 cm3 (1.0 in3) if nonmetallic. These volume considerations
for barriers were added to the 2017 NEC [see NEC314.16(A)]. Each space
within a box installed with a barrier must be calculated as separate boxes
on each side of the barrier [see NEC 314.16(B)].
Figure 2. Box
volume for standard boxes
Table 314.16(A) in the NEC provide box dimension and trade size in inches
for standard metal boxes. The minimum cubic millimeter (cubic inch)
capacity for each standard size metal box is given along with the maximum
number of conductors of sizes 18 AWG through 6 AWG permitted in the
box. As shown in the table, the number of conductors permitted applies
only where all conductors are the same size. Where a box contains
conductors of different sizes, the required volume of the box must be
calculated.
Figure 3.
Conductor fill for nonstandard other boxes
Requirements for determining the maximum number of conductors
permitted in non-standard or nonmetallic boxes are given
in NEC 314.16(B). The individual volume of each conductor, clamp, and
fitting is provided in this volume allowance table. The minimum volume of
the box is the total of the individual volumes required for each conductor,
device, barrier, or fitting.
A typical nonmetallic, single-gang device box typically used for new
construction does not have internal clamps. The openings on a single-gang
nonmetallic box are considered knockouts. As a result, no volume
allowance for clamps is required on a single-gang nonmetallic box if the
installation complies with 314.17(C), Exception. Multiple-gang device
nonmetallic boxes and round or octagonal boxes have internal clamps.
These clamps may be field-installed or incorporated into the box by the
manufacturer. A single volume allowance is made for one or more internal
clamps that are present in the box. The volume allowance for clamps that
are an integral part of the box construction is included in the marked
volume of the box. This requirement will be discussed in further detail later
in this article.
Figure 4. Fixture
wire luminaire conductors entering a ceiling-mounted box
Conductor Fill
The Code requires each conductor that originates outside the box and
terminates or is spliced within the box to be counted once. Each conductor
that passes through the box without splice or termination is also required to
be counted once. A looped, unbroken conductor 300 mm (12 in.) or longer
is counted as two conductors. A conductor which originates in, and of which
no part leaves the box, is not required to be counted. These are often
jumpers or “pigtails” to wiring devices.
An exception to this rule applies to the conductors that are part of the
luminaire wiring. It permits equipment grounding conductor(s) or not more
than four fixture wires smaller than 14 AWG, or both, to be omitted from
the fill calculations. The conductors must enter a box from a domed
luminaire or similar canopy, and are required to terminate within the outlet
box.
Photo 2. Single-
gang nonmetallic box with Type NM cable with box fill calculated by the
volume required per conductor, device, clamps, etc.
Clamp Fill
The Code provides information on the volume required for clamp fill. Where
one or more internal cable clamps, whether factory or field-supplied, are
present in the box, a single volume allowance in accordance with NEC Table
314.16(B) is required to be made based on the largest conductor present in
the box. This section requires a single volume allowance for all the clamps
that are internal to the box, regardless of the number of clamps. Volume
allowance is required for nonmetallic boxes (other than single-gang
nonmetallic boxes) with integral cable clamps. Before the total box volume
can be determined on nonmetallic boxes (other than single-gang boxes),
the manufacturer is required to remove the internal clamping mechanism;
then total box volume is determined by a nationally recognized testing
laboratory (NRTL). Single-gang boxes are determined to have knockouts
rather than cable clamps, so no deduction is required for cable clamps for
single-gang nonmetallic boxes when securing nonmetallic-sheathed cable
within 200 mm (8 in.) of the box as allowed by NEC 314.17(C) Exception.
No allowance is required to be made for a cable connector with its clamping
mechanism outside the box. A clamp assembly listed and marked for use
with specific nonmetallic boxes that incorporates a cable termination for the
cable conductors have been introduced to the electrical industry in recent
years. Conductors that originate within the clamp assembly shall be
included in conductor fill calculations as though they entered from outside
the box.
Where both a fixture stud and a hickey are present in the box, two volume
allowances must be made. One volume allowance is made for the fixture
stud; the other, for the hickey. Each volume allowance is based on the
largest conductor present in the box [see NEC 314.16(B)(3)].
Photo 3. Same
single-gang nonmetallic box with conductors pulled out of the box for ease
of counting total conductors.
Table 3. Volume
allowance required per conductor Table 314.16(B)
Each device or equipment is considered individually where more than one
item is contained in the box. For example, if a switch has 14 AWG wire
connected to it, a volume allowance of 2 x 2.0 cubic inches or 4 cubic
inches is required. If a receptacle has 12 AWG wire connected to it, a
volume allowance of 2 x 2.25 or 4.5 cubic inches must be made for that
particular device.
Figure 5.
Conductor fill requirements for boxes with multiple gangs
Conclusion
As this article has demonstrated, several factors must be taken into
consideration when determining the maximum number of conductors a box
is allowed to contain without creating a Code violation. Are cable clamps
involved? How many devices will be installed in the box along with these
conductors at final installation? These are just some of the questions that
must be answered to arrive at a compliant installation for box fill.
Deduction for cable clamps, devices, barriers, etc. is also why you cannot
go with the simple information provided in Table 314.16(A) for the
maximum number of conductors a particular sized box can contain. As
stated previously, these contained conductors must have ample free air
around the conductor and its insulation to allow proper dissipation of self-
generated heat from the conductor itself.
Proper box fill calculations is a vital cog in the safe installation of the
electrical wiring installed in commercial and residential buildings. I can
testify that checking for box fill provisions will eventually become second
nature to the inspector and the installer if they make it a normal part of
their daily inspection or installation routine. It might be cumbersome at
first, but eventually, a box that contains too many conductors will jump off
the wall at you if you make box fill calculations an everyday normal
practice.