PO 59.13330.

2011 (Updated Edition SNIP 35-01-2001)


PROJECT PO 59.13330.2011

Set of rules
Accessibility of buildings for low mobile populations.
Updated edition SNIP 35-01-2001

This draft set of rules did not apply to his allegations

Preface
The objectives and principles of standardization in the Russian Federation establishes the Federal Law of 27 December 2002 №
184-FZ Federal Law "On technical regulation", and rules for the development of codes of practice - Government of the Russian
Federation "On the order of development and adoption of codes of practice" of 19 November 2008 № 858.
Introduction
This regulatory document is up to date edition of SNIP 35-01-2001 "The availability of buildings for low mobile groups" in the
format of the Code. The basis for the development of the instrument is the Federal Law of 30.12.2009, № 384-FZ "Technical
Regulations" On safety of buildings and structures "and the disposal of the Government of the Russian Federation of
21.06.2010, № 1047-p. SNIP 35-01-2001 actualization in the format set of rules held in the framework of the implementation of
paragraph 2 of the Action Plan for the creation of barrier-free environment for the XXII Olympic Winter Games and XI
Paralympic Winter Games 2014 in Sochi.
Set of rules drawn up in accordance with the principles of the UN Convention on the Rights of Persons with Disabilities, signed
by the Russian Federation in September 2008, including: the full and effective participation and inclusion of disabled persons in
society, equal opportunities and accessibility. For the first time in Russian regulatory document incorporated a new progressive,
the term "universal design", which is enshrined in the UN Convention on the Rights of Persons with Disabilities. The term
"universal design" means the design of products, environments, programs and services designed to make them as usable by all
people without the need to adapt. Application of the above principles to the design and construction creates easy access for the
disabled and other low mobile groups to buildings and facilities, the safety of their operation without the need for further
restructuring and adjustment.
Set of rules designed to meet the requirements of the International Olympic Committee International Paralympic Committee,
international experience, in the other documents in the field of standardization, establishing the requirements for accessibility
to buildings, facilities and infrastructure for low mobile populations.
This set of rules is the basic document of the complex system of 35 normative documents in construction "Providing
handicapping environments for disabled and other low mobile populations."
Items marked with a * text, as a result of the application on a mandatory basis, ensure compliance with the Federal Law of
30.12.2009, N 384-FZ "Technical Regulations on safety of buildings."
1. Scope
1.1 This code establishes minimum requirements for accessibility to buildings and facilities for the disabled and other low
mobile populations (hereinafter - mH), based on the principles of "universal design" and "reasonable accommodation" that
must be followed in the design of residential, public and industrial buildings and structures and their territories (the "Facilities")
to ensure equal living conditions for the disabled and other low mobile populations in the other categories of citizens in order
to ensure the Federal Law of 30.12.2009, № 384-FZ "Technical Regulations" On safety of buildings and facilities "and the Federal
Law of 29.12.2004 № 190-FZ" Urban Development Code of the Russian Federation. "
Reconstruction and adaptation of existing buildings and structures for the needs of inst should be carried out by applying the
principles of "universal design" and "reasonable accommodation".
1.2 This code is intended for use in designing new and renovating existing buildings and structures. It extends to the functional
elements of the planning of buildings, their sites or individual rooms are available for inst: input nodes, communications,
evacuation routes, emergency rooms (zones) of accommodation, services and places of employment, as well as their
information and engineering infrastructure.
1.3 The requirements of this regulatory document not subject to the design of military infrastructure, facilities, information
about which constitutes state secrets, manufacturing facilities, processing and storage of radioactive and explosive substances
and materials, facilities for the storage and destruction of chemical weapons and explosives and other objects, for which
establishes the requirements related to nuclear and radiation safety in the use of nuclear energy.
1.4 Ability and the degree of (sort of) adaptation of buildings of historic, artistic or architectural value to the requirements of
inst should be harmonized with the organ of executive power for the protection and use of monuments of history and culture
appropriate level.
1.5 Design decisions facilities meeting the accessibility requirements, must provide:
- Reach their target sites to visit and free movement within buildings and their territories;
- Safety traffic routes (including evacuation and rescue routes), as well as accommodation, maintenance and application of
labor;
- Evacuation of people (including people with disabilities and other characteristics of low mobile populations) to a safe area to
possible harm to their health and life due to the impact of fire;
- The timely receipt of all groups of high-grade and high-quality information to navigate in space, use of equipment (including
self), to receive services, participate in the employment and educational process, etc.;
- Convenience and comfort of living environment for all populations.
1.6 Projected available buildings and structures must ensure compliance with the Federal Law of 30.03.1999 № 52-FZ "On the
sanitary-epidemiological welfare of population".
2. Normative references
Legislative and regulatory documents that are in the text references are given in Appendix A.
3. Terms and definitions
Used in the text of terms and their definitions are in accordance with Annex B.
4. Requirements for the territory
4.1 Access to the path of movement and
4.1.1 * Access to the site should be provided or accessible for disabled items of information about the object in accordance with
GOST 25131, GOST R and GOST 51 256 52 875.
4.1.2 * The motion paths are not allowed to use mH opaque gate hinges on hinged double-acting, with rotating blades gate and
turnstiles.
4.1.3 * The project must provide at least one accessible route connecting accessible landing area \ landing on transportation
and entrance to the building, providing conditions for the smooth, safe and convenient movement of mH on the site to a
building or across the enterprise, complex structures.
4.1.4 * The design area should comply with the continuity of pedestrian routes. Ways to dock with the external to the area of
transport and communications pedestrian and public transport.
4.1.5 * The system of information support should be provided in all the ways the movement meets the requirements of
accessibility for the duration of operation in accordance with the requirements of GOST 25 131, GOST-R and GOST R 51 256 52
875.
4.1.6 * Transportation thoroughfares in the area and pedestrian ways on the path to the objects visited by the disabled, may be
combined, subject to town planning requirements for the parameters of traffic routes.
4.1.7 * At the intersection of pedestrian paths of vehicles at entrances to the building or area should be designed elements of
early warning at the intersection with traffic safety measures up to its regulation.
4.1.8 * Tactile means of warning information and alarms should be located no closer than 0.8 m from the zone change the
path.
4.1.9 * When combined on site traffic routes visitors to the passages for the transport recommended restrictive (lateral),
marking of pedestrian paths on the roads in accordance with the Rules of the road. The width of lanes should provide a safe gap
of people, including those using technical means of rehabilitation, with the car.
Lane disabled in wheelchairs and mechanical wheelchair is recommended to isolate the left side on a strip of pedestrian traffic
on the site, pedestrian roads, alleys.
The lines marking paths for the visually impaired should be carried out using a corrugated surface with overlapping colors and in
accordance with Appendix 2 of the Rules of traffic of the Russian Federation.
04/01/10 * Subject to availability in the territory or part of underground and surface transitions they should be equipped with
ramps or lifting devices, if you can not arrange land transfer.
04/01/11 * The width of the pedestrian path through the refuge in places of crossing the roadway shall be not less than 3 m,
length - not less than 2m. Slope of the transition should be within 2-5%.
04/01/12 * The width of the path of the area must be at least 1.5 m, and on meeting the disability movement in wheelchairs
must be at least 1.8 m taking into account the dimensions of wheelchairs according to GOST R 50 602.
Allowed in short segments to reduce the track width to 1.2 m. In the absence (in the current building) real opportunities to
achieve regulatory parameters width of pedestrian paths in the area should be provided every 60-100m horizontal platforms
(pocket) of at least 1.6 x1 , 6m to allow for siding with disabilities in wheelchairs.
Cross slope path of motion, in which persons with disabilities can travel in wheelchairs, shall not exceed 5%. Cross slope path of
movement should be within 1% -2%.
4.1.13 * When the device exits the sidewalk around the building and the ground is allowed to increase zatesnennyh longitudinal
gradient to 10% for no more than 10m.
04/01/14 * The height of the curbs at the edges of pedestrian paths in the area are advised to take at least 0.05 m.
The height of the stone board at the intersection of roadway pavement and curbs, elevation and side stones along the green
lawns and operated sites, adjacent to walking paths, must not exceed 0.025 m
04/01/15 * For open stairways on drops of relief are advised to take the width of the tread is not less than 0,35-0,4 m lifting
height of steps - no more 0,12-0,13 pm All levels of external stairs within one of the march should be similar in shape in plan,
the size of the tread width and height of lifting steps. Cross slope exterior steps should be in the range of 1-2%.
Surface levels should not prevent slipping when wet and snow and should not be smooth.
The number of ascents in the march should be at least three and not more than 12.
04/01/16 * Ladders must be duplicated by other means of ramps or lift. Outdoor stairs and ramps should have handrails in
accordance with technical requirements for supporting a stationary device according to GOST R 51 261.
01/04/17 * The maximum length of a continuous march of the ramp should not exceed 10.0 m, width of the ramp between
handrails shall be not less than 1.0 m, slope of 1:20 to 1:12.
Value bias ramp march to its length should not exceed the norms set forth in Table 1.
Table 1 - Limitations of the ramp ramp

The length of one march, m The maximum slope Maximum height, m

10 1:20 0.5

9 1:19 0.473

8 1:18 0.444
7 1:17 0.411

6 1:16 0.375

5 1:15 0.333

4 1:14 0.285

3 1:13 0.230

no more than 2 1:12 0.166

Ramp with a gauge length of 60.0 m and a height of more than 3.0 m should be replaced with lifting devices.
01/04/18 * The length of the horizontal area of direct access ramps must be at least 1.2 m, and in areas of intensive use of at
least 1.5 m. In the upper and lower terminals of the ramp should be provided free area of not less than 1,5 x1, 5 m and in areas
of intensive use - 2,1 x2, 1m
01/04/19 * Ramps, taller than 0.15 m should be double-sided fence with rails at a height of 0.9 meters (valid from 0.85 to 0.92
m) and 0.7 m. The distance between the rails should be in the range 0 ,95-1, 0 m Kolesootboynye unit height of 0.1 m should be
set at intermediate stages and at the congress.
04/01/20 * The need for heating the surface of the unit ramp, a canopy or shelter established for the design task.
01/04/21 * Tactile means performing the function of a warning on the cover of hiking paths on the site should be located not
less than 0.5 m from the object information, the beginning of the dangerous section, change direction, input, etc.
The width of the tactile strips taken within 0.5-0.6 m.
Cover the walkways, sidewalks and ramps made of hard materials should be smooth, rough, with no gaps, no vibrate when
driving, do not reflect light as well as non-slip, ie preserves the strong grip the soles of shoes, walking poles aids and wheelchair
wheels when wet and snow. Coating of sand and gravel is not allowed.
01/04/22 * It should, if possible, to avoid glare and shadows cross that prevent blind and partially sighted people to distinguish
between changes in the slope. You should not use the big shiny surface, causing light reflection and glare.
In the locations of ramps should be installed artificial lighting of at least 100 lux.
01/04/23 * Slope curb ramp is defined in Table 2.
Table 2 - Limitations of the ramp curb ramps

The maximum elevation difference, mm The slope of the ramp

150 from 1:10 to 1:12

75 from 1:8 to 1:10

The maximum length of curb ramps shall be not more than 2,0 m, width - not less than 1.0 m. The maximum slope of ways to be
immediately adjacent to the curb ramp should be 1:20 (5%). The maximum slope of the side slopes of ramp - 1:10 (10%).
Curb ramps shall be labeled with tactile markers, performing preventive function.
Curb ramps at pedestrian crossings should be fully located within the area reserved for pedestrians.
01/04/24 * Ribs sewer gratings, mounted on the paths of motion should be perpendicular to the direction of traffic, should
closely adhere to the surface of the cell lumina of gratings must be less than 13mm wide. The diameter of round holes in the
lattice should not exceed 18mm.
On how the movement should not be placed concave trays without a lattice covering.
04/01/25 * Devices and equipment (mailboxes, public telephones shelters, information boards, etc.) that are placed on the
walls of buildings or on separate constructs, as well as projecting elements and parts of buildings and structures should not
reduce the space for the passage of normalizable as well as travel and maneuver a wheelchair.
Facilities, leading edge which is located at a height of from 0.7 to 2.1 m from the pedestrian path should not speak for the plane
vertical construction of more than 0.1 m, and when they are placed on a detached pillar - more than 0.3 m
By increasing the size of the space under the projecting these objects must be allocated curbs, skirting a minimum height of
0.05 meters or railing with a minimum height of 0.7 m etc.
Around freestanding poles, posts or trees, located in the path of paving should include a warning in the form of a square or
circle at 0.5 m from the object.
4/1/26 * Pay phones and other specialized equipment for people with visual impairments should be placed on a horizontal
plane with corrugated cover, which should be the edge of the equipment installed at a distance of 0.7-0.8 m.
Shape and edge of the suspended equipment shall be rounded off.
04/01/27 * Temporary structures, outdoor lighting poles and signs, newspaper and trade stalls, garbage cans, etc. should be
located outside the traffic lanes and have a contrasting color.
4.2 Parking lots and parking
4.2.1 * The individual car parking near or inside buildings service agencies should provide designated areas for disabled vehicles
from the calculation:

5% .......... ... ... ... when the number of seats to 100, inclusive, but at least one location;

3% ................................................ ............................................. when the number of seats 101 - 200;

2% ................................................ ................................... when the number of seats from 201 to 1000;

20 seats plus at least 1% for each 100 over 1000 places ... ... ... ... ... with a total capacity of more than 1,000 parking cars.

These areas should be marked by signs, generally accepted international practice and the SDA on the plane stops and mirrored
on the vertical surface (wall, pole, rack, etc.). A sign on a vertical surface should be located at a height of not less than 1.5 m.
Note - The above guidelines should apply in the absence of regulatory requirements for certain types of institutions.
4.2.2 * Designated private vehicles should preferably be disabled near the entrance, accessible to persons with disabilities, but
not more than 50 m, while residential buildings - not more than 100 m. The width of the zone for a disabled parking space must
be at least 3.5 m.
Grounds for stopping the specialized public transport vehicles carrying only persons with disabilities, should be provided at a
distance of not more than 100 meters from the entrances to public buildings.
4.2.3 * Available from the path of the car park to the accessible entrance to the building should not interfere with the transport
routes.
4.2.4 * The entrance to the parking lot and parking arrangements for payment must be accessible and easy to use for people
with disabilities.
4.2.5 * When leaving the vehicle should provide space for the lift-carrier, which is usually fixed to the vehicle.
In cases where a disabled person is required to take out a wheelchair or a scooter driven through the rear or side door of the
vehicle should provide a special area.
Zone placement wheelchairs must be at least 0.9 m wide and 1.5 m in length. The width of the car parking for the disabled in a
wheelchair should not be less than 3.6 m.
The site area for turning a wheelchair in 90gradusov must be at least 1.3 x1, 3 m, to rotate 180 degrees - not less than 1,3 x1,
5m, to turn 360 degrees - not less than 1,5 x1, 5m.
In the presence of the parking lot of places for car parking, lounges which are adapted for the handicapped in wheelchairs, the
width of the lateral approaches to parking of such vehicles must be at least 2.5 m.
In some cases, specific sites must be capable of charging batteries.
4.2.6 Special parking spaces along the transport links should be placed under the condition of the road slope and curvature of
the profile of no more than 1:40 or ramp equipped with a blister coating, providing a smooth transition from parking areas to
the pavement.
In the landing sites and transport of handicapped persons from private cars to building entrances should be applied coating
slip.
4.2.7 Dimensions of special parking spaces located parallel to the curb, should provide access to the rear of the car to use a
ramp or a lifting device. The length of a special parking space, located parallel to the curb, must be at least 7.0 m, width - not
less than 2.4 m.
4.2.8 On each floor of a multi-level car park should be closed with informational displays.
4.2.9 Fire alarm buttons should be placed at a height of not more than 1.2 m above the ground.
02/04/10 loudspeakers warning system with low volume should be set at a distance of no more than 6m apart
4.2.11 The height of free space on the plane (floor) of the open car park to the bottom of the overlying structures shall be not
less than 3.3 m;
Underground bonded investment area must have headroom of at least 2.5 m.
04/02/12 In the mechanized garage parking must be arranged at least one accessible boarding area, where passengers
disembark and get in the vehicle.
4.3 Recreation
4.3.1 * In the territory of the main ways of traffic should be provided not less than 100 meters landscaped area recreation
available to mH, equipped with shelters, benches, telephones, pointers, lamps, alarm, etc.
4.3.2 * The benches are installed at the sides of the passages and are indicated by changes in road surface. Benches should
provide back support and have at least one armrest.Minimum foot space under the seat shall be not less than one third the
depth of the seat.
4.3.3 .* The minimum level of illumination in the recreation areas should be 20 lux. Objects of small architectural forms should
cover 1.5 times more coverage and adjacent areas.You should avoid flashing lights. If flashing lights are used, their frequency
should be less than 5 Hz.
5. Requirements for buildings, facilities and premises
In buildings and facilities accessible to mH, it must be accessible entrances, places of the basic processes of life: living, service
(receiving services), applications for work, leisure, health and sanitation facilities; devices and equipment in the
building. Available should be used in parts of buildings, groups of buildings, functional areas, the path of the inst.
5.1 Inputs
5.1.1 * The building must be at least one entrance accessible to the inst, from the ground and out of each available for an
underground or aboveground mH transition, coupled with the building.
5.1.2 * Outdoor stairs and ramps should have handrails in accordance with technical requirements for supporting a stationary
device according to GOST R 51 261.
With a width of stairs at the main entrances to the building of 2.5 m or more should provide further dividing rail.
5.1.3 * The input area at the entrance, accessible inst must have: a shed, drainage system, and depending on local climatic
conditions - heating, which is set by specifying the design.Size of the input area when you open the door leaf out to be not less
than 1,4 x2, 0 m or 1,5 x1, 85 m.
Surface coatings entrance vestibules and platforms must be firm, to prevent slipping when wet and have a cross slope in the
range of 1-2%.
5.1.4 * The entrance doors to buildings should have a clear width of not less than 1.2 m. The use of swinging doors at the hinges
and doors on the paths of movement of the turntables mH is not allowed.
In the paintings of exterior doors, available with disabilities, should include inspection panel, transparent and impact-resistant
filled material, the lower part of which must be located within the 0.3-0.9 m above floor level. The lower part of glass door
panels at a height of at least 0.3 m above floor level shall be protected by a shock-band.
Exterior doors of buildings available for mH, should not have thresholds. If necessary, the device thresholds, its height must not
exceed 0.013 m.
As the door locks should include pressure-handles. Door opening force should not exceed 50N.
5.1.5 * Clear doors at entrances and in the building, and fencing should be carried out of impact-resistant
material. Transparencies of the door should provide a vivid contrast markings with a minimum height of 0.1 m and a width of
0.2 m, located at a level of 1.2 m and 1.5 m above the surface of pedestrian paths.
Door frames and door leaf edge and the handle is recommended to be painted in non-leaf contrasting colors.
5.1.6 * The inputs of the appropriate use of automatic swing and sliding doors. With double doors, one working door width shall
be required to odnopolnyh doors.
At entrances and along the lines of traffic mH in buildings is not permitted to use revolving doors and turnstiles.
On the path of motion mH recommended door hinges on a single-acting with restraint in the provisions of "open" and
"closed". Doors should also be applied to ensure that delay automatic closing of not less than 5 seconds. Should be used with
hinged doors closers (with a force of 19.5 Nm).
5.1.7 * The depth of vestibules and air locks in the forward movement and one-way door opening should be at least 1.8 m and a
width of at least 1.35 m, and at a depth of 1.5 m width should be not less than 2 m.
In the lobbies and near emergency exits are not allowed to use mirrored walls (surface), and at the door - mirror glass.
Drainage and drainage grating, mounted in the floor vestibules or input pads must be installed flush with the floor covering. The
width of gaps of cells should not exceed 0.013 m and length 0.015 m. The preferred use of lattices with diamond-shaped or
square cells.
5.1.8 * If the control input should include the crossing devices and turnstiles clear width 0.9-0.95 m, adjusted for the passage of
the categories of disabilities, which will be available for the projected object.
5.1.9 * At the entrances to the building mass visit must have information for the visually impaired tactile mimic and blind
visitors, displaying information about the location searched the premises of the building. Place to mimic the right of the
entrance at a distance of 3-5 meters, providing tactile input from the guide strip with the height of the figure is not more than
2.5 mm.
05/01/10 * The premises where there may be handicapped in wheelchairs or with visual impairments, it is usually placed at the
entrance closest to the earth's surface. At another location on the premises of the building height, except for stairs, ramps
should be provided, lifting platforms, lifts or other devices for moving disabled persons.
5.2 Motion Paths in Buildings
5.2.1 Horizontal communication
5.2.1.1 * Road traffic to the premises, areas and places of service that is available mH, inside the building should be designed in
accordance with statutory requirements to the ways of evacuation of the building.
The width of the path of motion (in the corridors, rooms, galleries, etc.) to clean should be at least:
when driving a wheelchair in the same direction ... ... ... ... ... ... ... 1.5 m
with a head movement ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 1.8 m
The width of the corridor or move to another building to be taken - at least 2.0 m.
When moving down the corridor to the disabled wheelchair requires minimal space for:
- Turn to 90 0 equal to 1.2 x1, 2 m;
- Turn to 180 0 equal to 1.6 (W) x2 (L) m.
In the dead-end corridors should be possible to turn a wheelchair 180 0.
The height of the passages in light of their entire length and width must be at least 2.1 m.
Note - The reconstruction of buildings is allowed to reduce the width of the corridor, provided that a passing loops (pockets) for
a wheelchair measuring 2 m (length) and 1.8 m (width) in line of sight the next pocket.
The width of balconies and loggias to be generally at least 1.4 m in the world. Permissible to reduce the width to 1.2 m in an
available space of 1.3 m on either side of opening the balcony door.
5.2.1.2 * Approaches to the various equipment and furniture should be the width of not less than 0.9 m, and if necessary,
turning a wheelchair at 90 ° - not less than 1.2 m. The diameter of the zone for self-reversal by 180 ° with disabilities on the
couch -chair should be at least 1.4 m.
Around tables, counters and other places of service, in wall units, appliances and devices for the disabled in wheelchairs should
be provided free space for maneuver in terms of size not less than 0.9 x 1.5 m.
The depth of space for maneuvering a wheelchair in front of the door when you open the "away" should be not less than 1.2 m,
and when you open the "back" - at least 1.5 m and a width of at least 1.5 m.
The width of the aisle in a room with equipment and furniture should be not less than 1.2 m.
5.2.1.3 * Lots of sex on the paths of motion at a distance of 0.6 m in front of doorways and entrances to the staircases, as well
as before the turn of communication routes should be a warning grooved and / or contrasting colored surface, it is
recommended to provide beacons of light.
Zone "possible risk" with regard to movement of the projection leaf should be marked with a contrasting color of the
surrounding space, marking paint;
5.2.1.4 * The width of the door and open apertures in the wall, and exits from rooms and corridors of the stairwell must be at
least 0.9 m. The depth of the open doorway of the slope more than 1.0 m width of the opening should be the width of the
communication passage but not less than 1.2 m.
Doors on escape routes should be of a color contrasting with the wall.
Doorways in the room, as a rule, should not have rapids and drops the floor height. If necessary, the device thresholds of their
height or elevation should not exceed 0.013 m.
5.2.1.5 * The design elements in buildings and equipment, as well as decorative objects and sculptures to be placed in the
dimensions of the pathways of the walls and other vertical surfaces, must have rounded edges, and shall not project more than
0.1 m in height from 0.7 to 2.1 m above floor level. If the elements are the walls of the plane by more than 0.1 m, the space
under them shall be allocated rim height of at least 0.05 m. When placing the device, pointers to free-standing pole, they shall
not project more than 0.3 m
Under the open stair march and other hanging items inside the building, having a clear dimension of less than 1.9 m height,
install barriers, fences, etc.
5.2.1.6 * The premises are available mH, is not allowed to use pile carpets with high pile - more than 0.013 m.
Carpeting on how the movement should be tightly secured, especially at the junction of leaves and along the boundary of
dissimilar surfaces.
5.2.2 Vertical Communication
5.2.2.1 Stairs and ramps
5.2.2.1.1 * When the vertical drop in the building or structure should include stairs, ramps or other lifting devices are available
for inst.
At the height of the sharp change of sex in a room for fall protection should be put high fences 1-1.2 m.
Slope of stairs shall not exceed 1:2. The width of stair tread, but inside apartment should be 0.3 m (valid from 0.28 to 0.35 m)
and height of steps - 0.15 m (valid from 0.13 to 0.17 m).
Stair treads shall be smooth, without ridges and with a rough surface. Step edge must be rounded to a radius of no more than
0.05 m. The lateral edges of steps are not adjacent to the walls must have skirting height of at least 0.02 m.
Number of steps on how traffic should be not less than three.
5.2.2.1.2 * If there is no elevator width flight of stairs shall be not less than 1,35 m. In other cases, the width of the march
should take on SNIP SNIP 1.31 and 6.31.
5.2.2.1.3 If the calculated width of 2.5 m flight of stairs or more should provide additional dividing rail.
5.2.2.1.4 All stages within the march should be the same geometry and dimensions of the width of the tread and a lifting height
of the steps. Allowed to change the pattern tread lower levels first march of open stairways.
Stair treads and risers should be with, use of open levels (without risers) are not allowed.
5.2.2.1.5 * You should use a different color material step ladders and horizontal areas in front of them.
Tactile warning strips in front of the stairs should be carried out according to GOST R 52 875.
5.2.2.1.6 * The maximum height of a boom (March), the ramp should not exceed 0.8 m at a slope no more than 8%. In the
vertical drop to the floor how the movement of 0.2 m or less is allowed to increase the slope of the ramp up to 10%.
Ramps are longer than 60.0 m or vertical drop of more than 3.0 m should be replaced with elevators, lifts, escalators and the
like.
In exceptional cases include spiral ramps. The width of the helical ramp at full turn should be at least 3.0 m.
Every 9.0 m length of the ramp should be designed in a horizontal platform. The horizontal platform shall be arranged also
according to the direction of the ramp.
Area on the horizontal part of the ramp in the direct path of movement or rotation should be the depth of 1.2-1.5 m, on a screw
- not less than 2.0 m.
Ramps at its top and bottom should have a horizontal area measuring at least 1.5 m by 1.5 m.
The width of a ramp at one-way march or irregular movement should be at least 1.0 m, in other cases - take the width of the
lanes according to 5.2.1.1.
Inventory (sliding, collapsible and folding) ramps must be designed for loads less than 350 kg, and meet the requirements for
stationary ramps to the width and slope.
5.2.2.1.7 * Provisions should be skirting a minimum height of 0.05 m along the longitudinal edges of the marches of ramps to
prevent slipping sticks or legs.
The surface of the ramp should march visually contrast with the horizontal surface at the beginning and end of the
ramp. Allowed to identify the adjacent surfaces of the use of light beacons or light tape.
5.2.2.1.8 * Along both sides of all stairs and ramps, as well as all the elevation changes on horizontal surfaces than 0.45 meters
must be installed with the fence rails. Handrails should be placed at a height of 0.9 meters (may be from 0.85 to 0.92 m), the
ramps - in addition to a height of 0.7 m, while in day care - in addition to a height of 0.5 m.
Handrail railing on the inside stairway shall be continuous along its entire height.
The distance between the handrails of ramp take a range of 0.87 to 1.0 m.
The final part of the horizontal handrail should be longer than the march of a ramp or incline of 0.3 meters (may be from 0.27 to
0.33 m) and have not a traumatic end.
5.2.2.1.9 * Handrails are recommended circular cross section with a diameter ranging from 0.04 to 0.06 m. The distance
between the light into a guard rail and the wall should be at least 0.045 m for walls with smooth surfaces and at least 0.06 m for
walls with rough surfaces.
On the top or side, external to the march, the surface of the handrail handrail should be provided relief designation floors, as
well as warnings about the end of the strip railing.
5.2.2.2 Elevators and lifts
5.2.2.2.1 * The buildings should be equipped with passenger lifts or lifting platforms for disabled access in wheelchairs, on
floors above or below the floor of the main entrance to the building (first floor). Selecting the way to lift people with disabilities
and the potential for duplication of these methods is set to rise on job design.
5.2.2.2.2 * Lift shaft must have dimensions sufficient for the installation of lifts with the parameters of the elevator car,
intended for use by disabled in a wheelchair with an accompanying. Such booths shall have internal dimensions of not less than,
mm: width - 1100; depth - 1500. For new construction of public and industrial buildings with elevators are recommended width
of the aperture of 900 mm. In other cases, the size of the aperture and the internal arrangement is set in the job for the design
of GOST 51 631 53 770 and GOST.
The design of the elevator shaft should be capable of additional illumination area in front of the elevator.
Number of lifts installed in accordance with Annex B.
5.2.2.2.3 * In the basement or ground floor front door to the elevator for the disabled unit air locks.
5.2.2.2.4 * It is equipped with fully automated building elevator cabs with handrails at a height of 0.8 to 1.0 m and a folding
seat.
Floors the elevator must have non-slip surface.
Light and sound alarm informing that meets the requirements of GOST R 51 671 and the technical regulation on safety of lifts
shall be provided in each cabin, and at each elevator door, designed for people with disabilities. And also, and tactile floor level
indicators. Opposite the exit of such elevators to be numbered floors at a height of 1.5 m.
5.2.2.2.5 * The installation of lifting and transport means to overcome the stairs with disabilities with a lesion of the
musculoskeletal system, including wheelchairs, should be provided in accordance with the requirements of GOST R 51 630.
The outputs of the lift should be provided only in the level of floors with space for living or visiting the target people with
disabilities.
The empty space in front of lifting devices shall not be less than 1.6 x1, 6 m
Supervise the work of the lift must be carried out for mH dispatch service through video surveillance.
Note - Stair lift device may be used only in the reconstruction and adaptation of buildings, where it is impossible to establish a
standard elevator.
5.2.2.3 Escalators & Moving Walks
5.2.2.3.1 Escalators, not a means to escape, creating convenience for the majority of inst. They must be fitted with tactile
warning signs at the upper edge, and have a high-contrast labeling (bright yellow) of all edges of steps the side edges. Should be
provided free, well-lit approach of not less than 2.5 m above and below the escalator.
If an escalator or moving walkways located on the main path of movement along them and each of their end should provide
security guards for the Blind and Visually Impaired
5.2.2.3.2 The level of illumination on the escalators should be at least 200 lux.
5.3 Sanitary accommodation
5.3.1 * All buildings that meet accessibility requirements, as part of sanitary facilities should be provided for specially equipped
for inst: place in dressing rooms, versatile cabin washrooms and showers and bathrooms.
5.3.2 * In the restrooms of public and industrial buildings should provide at least one universal cab, accessible to all citizens.
5.3.3 * In all public buildings with the estimated number of visitors 50 and over or under estimated the duration of staying in
the building 60 minutes or more - should be provided with a universal toilet cubicle. The share of the universal toilet cubicles in
the unit should be 7% but not less than one.
5.3.4 * In areas of public shower rooms shall be provided at least one car equipped for the disabled in a wheelchair in front of
which should provide space for a wheelchair entrance.
5.3.5 * Provisions should be made for persons with disabilities in violation of the musculoskeletal and visual impairment closed
showers with doors opening outwards and entrance directly from the dressing room with non-slip flooring and pallet-free
threshold.
5.3.6 * Universal stall restroom should have a common size in terms of not less than, m: Width - 1.65 Depth - 1.8, width of
doors - 0.9 m In the cabin next to the toilet should be provided a space of at least 0.75 m to accommodate wheelchairs, as well
as hooks for clothing, crutches and other supplies. The cab must be free space with a diameter of 1.4 m for turning a
wheelchair. Doors should open outwards.
In the universal cab and other sanitation facilities, intended for use by all categories of citizens, including persons with
disabilities should be capable of installation in case of necessity of folding the support rails, rods, turning or folding seats. One of
the urinals in the toilets should be sited at a height from the floor no more than 0.4 m or use a urinal vertical form.Bowls should
be used with back support.
5.3.7 At the door of sanitary facilities or a specialist stalls (toilet, shower, bathroom, etc.) should include special characters
(including relief) at a height of 1,35 m.
Specialty booths must be equipped with alarm systems, providing a link to the placement of permanent staff on duty (guard
post or administration of the object). Above the entrance to the premises is recommended to install the flashing light alarms
that trigger when you press the panic button.
5.3.8 * Geometric parameters of the zones used by persons with disabilities, including those in wheelchairs, the sanitary
facilities of public and industrial buildings, should be taken from Table 3:
TABLE l and n and 3

Index
Name
m, at least

Size in terms of
(Clean)

Cubicle showers:
closed, 1.8 x 1.8
open and with a through passage; poludushey. 1.2 x 0.9
Cabins women's personal hygiene. 1.8 x 2.6

Note - Dimensions in pp 5.3.7 and 5.3.8 * * may be specified in the design process, depending on the equipment and its
placement.
5.3.9 * The width of aisles between the rows should be taken, however, m:
Shower cubicles for private and public, group and single sinks, toilets, urinals ... ... .... ... ... ... .... ... ... ... ... ... ... ... ... .. 1.8;
for wardrobes with benches (with benches) ... ... ... ... 2.4;
However, no benches ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 1.8.
05/03/10 * The bathrooms toilets should be used with seat height 0,44-0,46 m, sink and dressing table should be set at a height
of 0.85 m from the floor with leg room for the equipment of at least 0.67 m and a depth of 0 , 6 pm
03/05/11 * Recommended use faucets with lever handle and a thermostat and if possible - with Automatic Faucet-contact
type. The use of cranes with separate hot and cold running water is not allowed.
Recommended for use with automatic flushing toilets or water with a manual push-button control, which should be placed on
the side wall of the cab, which made landing on the toilet.
5.4 Recreational zones
5.4.1 In the design of lobbies, foyers, recreation, places (zones) expectations, etc. premises should be for every person with
disabilities with a lesion of the musculoskeletal system to provide additional space at the rate of not less than 0.5 m 2 each.
5.4.2 On the Road traffic mH in the building should be provided adjacent to their place of rest and wait 25-30 m, but not less
than one per floor.
In places of rest or standby should include at least one place for a disabled person in a wheelchair or crutches, which enjoys
(walking stick), as well as his companion.
The boundary of a reserve area for the possible deployment of a wheelchair should have a markup.
5.4.3 Place the installation of sculptures or containers of plants in the areas of recreation should be fencing (a side) with a
height of at least 0.05 m.
5.5 The internal fixtures and fittings
5.5.1 When selecting the type of internal equipment used mH, and its location in the building premises to take into account
their compliance with GOST R 53 453.
You must use a contrasting color combinations in the applicable hardware (door - a wall, a handle, sanitary apparatus - floor,
wall, wall - switches, etc.).
5.5.2 * The illumination on the escape routes and places of delivery (provision) of services for inst in public buildings and
industrial purposes should be increased by one level compared to the requirements of SNIP 5.23.
Difference of light between adjacent rooms and areas shall not exceed 1:4.
5.5.3 * Synchronous (sound and light), alarm linked to the fire warning system, disaster and emergency situations should be
provided and areas of public buildings frequented by mH, and manufacturing facilities that have jobs for the disabled.
For emergency audio alarm devices should be used to ensure the sound level is not less than 15 dBA for 30 seconds, exceeding
the maximum level of sound in the room by 5 dBA.
Sound beacons (electrical, mechanical or electronic) must satisfy the requirements of GOST 21 786. The equipment drive them
to action should be not less than 0.8 m to avoidable stretch of track.
Noise indicators should be used in rooms with good sound insulation or in rooms with significant noise levels of subjective
origin.
5.5.4 * In the lobbies of public buildings should include the installation of sound whistle-type call-boxes, which can be used by
visitors with visual impairments and Textphone for hearing-impaired visitors. Similarly, reference should be equipped with all
types, ticket office sales outlets, etc.
Visual information should be placed on a contrasting background, at a height of not less than 1.5 m and not more than 4.5 m
above floor level.
5.5.5 * Devices for opening and closing doors, horizontal rails, as well as handles, levers, valves and buttons of various devices,
opening trade, drinking, and ticket machines, holes and other chipkart control systems and other devices that may be used
inside the inst buildings should be set at a height of not more than 1.1 m and not less than 0.85 m from the floor and at least 0.4
m from the side walls of the room or other vertical plane.
Switches on the premises shall be provided at a height of 0.8 m above floor level. Allowed to use, in accordance with the terms
of reference, switches / switches remote control lighting, electronic devices and other equipment.
5.5.6 * Should use the door handles, locks, latches and other devices for opening and closing doors, which should be shaped so
that a disabled person to control them with one hand and does not require too much effort or significant bends in the hands of
the wrist. It is advisable to focus on the use of manageable devices and mechanisms, and U-shaped handles.
Handles on the canvases of sliding doors shall be installed so that the door is fully open when the pens are easily accessible
from both sides of the wall.
Door handles, located at the corner of the corridor or room should be located away from the side wall of at least 0.6 m.
5.5.7 * The front door to the spaces in which dangerous and strictly prohibited to find mH (boilers, ventilation chambers,
transformer units, etc.), install locks that exclude the free hit into the room. Door handles similar premises must have a surface
with the identification notches or irregularities, perceived tactilely.
5.5.8 * used in the project materials, equipment, equipment, goods, equipment used or disabled in contact with them should
have a sanitary certificate of the state sanitary-epidemiological service. The materials cover the working surfaces of tables and
other equipment should not blikovat.
5.5.9 * Tables and other equipment used, including disabled people in wheelchairs should have the leg room for up to a
maximum of 0.75 m above floor level, with a minimum width of 0.75 m, depth of at least 0.49 m. The height of working table
and other equipment must not exceed 0,85 m. The distance from the edge of the table to the outer edge of support, the use of
tables with a round top and a central pillar, shall be not less than 0.49 m.
5.6 Audio-visual information systems
5.6.1 * Available for mH elements of the building and land must be identified by the International characters available in the
following locations:
- Accessible parking spaces,
- Available landing area of the passengers,
- Inputs are available, if not all entrances to the building, structure are available,
- Place in the overall bathrooms,
- Accessible walk-in closets, dressing, dressing rooms in buildings in which not all such rooms are available,
- Accessible elevators and other lifting devices,
- Affordable security zone
- Available in the aisles teller area and other places of service mH, where not all aisles are accessible.
Direction signs pointing the way to the next available element should be set at the following locations:
- Inaccessible entrances to the building,
- Inaccessible to the public toilets, showers, bathrooms,
- Elevators, not suitable for handicapped,
- Exits and stairs, are not ways to evacuate people with disabilities.
5.6.2 * Systems media and signaling the dangers that are placed on the premises (except premises with wet processes)
designed to host all types of disabilities and how their movement must be comprehensive and include visual, aural and tactile
information indicating the direction of movement and places of service provision. They must comply with the requirements of
GOST 51 671, GOST 51 764, and also consider the requirements of the BNP 104.
The means of information (including signs and symbols) should be identical within a building or complex of buildings and
structures that are placed in one area within an enterprise, a transport route, etc. and comply with signs, established by existing
regulations on standardization. It is advisable to use international characters.
5.6.3 * When the inputs must be installed mimic information (tactile traffic pattern), displaying information on facilities in the
building accessible to the visually impaired. It should be located on the right side while moving at a distance of 3-5 m. There
should be a tactile guide.
5.6.4 * In a building massive attendance of people should be capable of duplication of visual, audio and voice information.
5.6.5 * In residential buildings must be possible to implement two-way intercommunication on duty (concierge) at a house
entrance or UDF manager of apartments, from which received an alarm message, and voice warning residents about an
emergency and evacuation procedures and assist inst.
5.6.6 * System media zones and facilities that are available to visit or stay mH (especially in places of mass public), as well as
available to them input nodes and traffic routes must ensure continuity of information, timely and unambiguous identification
of the orientation of objects and places to visit. It must be capable of receiving information about the range of services, location
and purpose of the functional elements, location of evacuation routes, to warn of the dangers in extreme situations, etc.
Building or structure on the instructions of the design can be additionally equipped with radio beacons (radio-labels) for the
blind or visually impaired visitors with radio-informants.Beacons are placed above doorways and on the walls of buildings.
5.6.7 * Visual information should be placed on a contrasting background to the size of signs, corresponding to the distance the
review to be linked with the art deco and at a height of at least 1.5 m and not more than 4.5 m above floor level.
In addition to the visual should be provided for alarm, as well as on the instructions of the design - troboskopicheskaya alarm
system (in the form of intermittent light signals), signals that should be visible in public places. The maximum frequency of
stroboscopic pulse - 1-3 Hz.
5.6.8 * The closed space of buildings (rooms for various applications, toilet cubicle, lift, dressing cubicle, etc.) with a disability,
including hearing-impaired, may be one, as well as elevator lobbies and the security zone, must be equipped with two-way
communication with the controller or on duty. Two-way communication system shall be equipped with audible and visual
emergency signaling devices. Outside of the room above the door should provide a combined audible and visual alarms.
In other cases, should include the bell. In a public restroom electric bell or the detector must be displayed in the duty room.
In these rooms (cabins) must provide emergency lighting.
5.6.9 * Informed designation of premises within the building must be duplicated and posted signs embossed next to the door
from the door handle and attached at a height of 1.3 to 1.4 m.
Numbering cabinets in dressing rooms must be done Braille and on a contrasting background.
5.7 Escape routes
5.7.1 * The design solutions of buildings and structures must ensure the safety of visitors in accordance with the "Technical
Regulations on Fire Safety» № 1123-FL and GOST 12.1.004, always bearing the psychophysiological features of various
categories of disabled persons, their number and location of the building or construction.
5.7.2 * Locations of service and permanently disabled shall be located at the lowest possible distances from the emergency
exits from the premises, with floors of buildings outside.
5.7.3 * The width (in light) areas of evacuation routes used mH should not be less than, m:
doors of the premises, with the number of persons with disabilities are in them no more than 15 people ....................................
.................................................. ...................... 0.9;
openings and doors in the remaining cases, passes inside pomescheniy1, 2;
transient loggias and balconies, corridors mezhkvartirnyh (when opening the door inside) ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...
.... ... ... ... 1.5;
corridors, ramps, disabled people are used to evacuate ... 2.0.
5.7.4 The ramp, which serves as an escape route from the second floor and overlying must be directly related to the exit out of
buildings, structures.
5.7.5 * If the project is impossible to ensure the timely evacuation of mH for the required time, then save them on escape
routes should be provided a safe haven from which they can evacuate a longer time or be in it until the arrival of rescue teams.
Maximum allowable distance from the outermost point of the room with the presence mH-to-door in a security zone must be
within reach for the required time of evacuation. As a security zone is allowed to use elevators elevator halls used by people
with disabilities.
Distance from the security zone to escape stairwells and elevators that are suitable for the salvation of persons with disabilities
should not exceed 15 m.
5.7.6 * The area of security should be provided to all persons with disabilities who remain on the calculation on the floor, on the
basis of the specific area to be carried by one rescued, if feasible, to maneuver, m 2 / person.:
invalid in a chair - a wheelchair ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... 2.40;
invalid in a chair - a wheelchair with an accompanying ... ... .. ... ... ... ... ... ... .2,65;
disability, moving on their own ... ... ... ... ... ... ... ... .. ... ... 0.75;
disability, moving with the accompanying ... ... ... ... ... ... .. ... ... .1,00.
The composition of the security zone can include the area adjacent loggia or balcony, separated by fire barriers from the rest of
the premises.
The security zone should be designed in accordance with design requirements and requirements for materials finishing joint
venture 1.13130.
When sound is used as a safety zone nezadymlyaemoy stairway, stairwell size should be increased based on the size of the
projected area.
5.7.8 Each area of security of public buildings must be equipped with an intercom or other device with a control room or rescue
service.
5.7.9 The upper and lower levels in each march escape stairs should be painted in a contrasting color or use tactile warning
inserts, contrasting color with respect to the adjacent floor surface, a width of 0.3 m. Can be used for guidance and assistance
to blind and visually impaired protective angle profile at each step of the width of the march. The material must be wide 0,05-
0,065 m tread and riser 0,03-0,055 m and should visually contrast with the rest of the stage.
The edges of steps or handrails of stairs to escape routes should be painted with paint that shines in the darkness or the light on
them glued tape.
07/05/10 Do not provide an escape route open to inst exterior metal stairs.
6. Specific requirements for low mobile activity among groups
6.1 Residential buildings and premises
6.1.1 Accessibility for all categories of inst should have houses adjoining pedestrian path of motion and grounds, areas of the
building entrance to the zone of disabled persons (apartment, living cell, a room) and area of residence in apartment houses
and hostels, residential and service parts (group rooms) hotels and other buildings, a temporary stay.
6.1.2 Login to the site of residential single-family homes should be equipped with protective and control devices or alarm
devices, feeding information to the housing for people with visual impairments and hearing-impaired.
6.1.3 Overall scheme of the pathways of functional areas and are calculated on the movement of the disabled in wheelchairs
and on equipment - also for the visually impaired, blind and deaf.
6.1.4 * Houses and accommodation of public buildings should be designed to ensure the needs of persons with disabilities,
including:
- Availability of apartments or living quarters of the entrance to the territory before entering the building;
- Availability of apartments or living quarters of the entrance to the building;
- The availability of apartments or living quarters of all service areas;
- Use equipment that meets the needs of persons with disabilities;
- Safety and convenience equipment and instruments;
- Equipment and local area actually building the necessary information systems.
6.1.5 When taking into account the needs of disabled persons in a specialized form of living adjustment of buildings and their
facilities is recommended on the individual program, taking into account the tasks defined in task design.
6.1.6 * When apartments for families with disabilities, in wheelchairs at ground floor level should provide the opportunity to
enter directly on the local area or prikvartirny site. For a single entrance through the apartment lobby and the lift device is
recommended to increase the area of the apartment at 12 m 2. Parameters take the lift to GOST R 51 633.
In the social housing fund purposes apartments for people with disabilities, especially in wheelchairs should usually include a
ground floor level, providing the opportunity to reach out and directly to the local area.
6.1.7 Residential zone for disabled persons should have at least the living room, bathroom with toilet, accessible to the
disabled, the front hall, an area not less than 4 m2 and its own communication.
6.1.8 * The minimum size of the dwelling shall be:
- A disabled person moving on a wheelchair, no less than 12m 2;
- For the disabled, self employed, 16 m 2 or more (if necessary).
6.1.9 * The width of the living room for disabled persons must be at least 3.0 m (for the infirm - 3.3 m moving on a wheelchair -
3.6 m). The depth of the living room should be not more than double its width. If you have room in front of the old space width
of 1.5 m and a depth of a room should not exceed 4.5 m.
01/06/10 * The width of the sleeping rooms for disabled persons must be at least 2.0 m (for the infirm - 2.5 m, moving in a
wheelchair - 3.0 m). The depth of the room should be at least 2.5 m.
01/06/11 * Position the bed and the arrangement of furniture in the sleeping room for wheelchair users in general should
provide the free space of at least 1.5 m for turning a wheelchair. On one side of the bed should provide for the passage of not
less than 0.915 m.
01/06/12 * The depth at the forward movement of vestibules and a unilateral opening of doors shall be not less than 1.8 m at a
depth of 1.5 m width should be at least 2.0 m.
01/06/13 * The area common room (living room) is recommended, as a rule, take at least: a one-bedroom apartment - 18m2,
three or four-room apartments - 20-22 m 2.
6.1.14 Height of window sill in the room for the disabled wheelchair should not exceed 0.6 m.
01/06/15 * Kitchen area of apartments in residential social housing should be at least 9 m 2. The width of such food should be
not less than:
2.3 m - at unilateral placement of equipment,
2.9 m - at the bilateral or the corner placement of equipment.
Kitchens should be equipped with electric stoves.
Arrangement of furniture in the kitchen for wheelchair users must provide clearance of at least 1.5 m for turning a wheelchair.
Switches and controls should be installed in the kitchen at 0, 75 and 1.2 m along the central lines of the floor.
01/06/16 * The overall level of lighting in the kitchen should be within 200-300 lx at the level of the working surface.
01/06/17 * Size of sanitary facilities in the apartments must meet the requirements specified in 5.3.8 *.
06/01/18 * The width of outbuildings shall not be less than, m:
front (with the possibility of storing a wheelchair) ... ... ... ... ... ... ... ... .1,6;
distribution inside the corridors ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 1.15.
opening width of interior doors in the world should be at least ... ... 0.9.
06/01/19 * The houses of the municipal social housing should provide for a device, if necessary, in the pantry area of the
apartment no less than 4m 2 for storing tools, materials and products used and produced by disabled people in work at home,
as well as to accommodate tiflotehniki and Braille literature.
06/01/20 In a one-sided development of residential housing galleries width must be at least 2.4 m.
06/01/21 * The distance from the fence balconies, loggias to the outer wall must be at least 1.4 m, height barriers - ranging
from 1.05 to 1.15 m. The threshold of the front door to the balcony, or loggia should not exceed 0.013 m .
Note - If you have free space on the balcony door opening on each side of at least 1.2 m, the distance from the fence to the wall
can be shortened to 1.2 m.
06/01/22 Enclosures for balconies and loggias for moving to a wheelchair in the area between the heights of 0.45 to 0.7 m
should be transparent in order to ensure that a disabled person with a good overview of the level of a wheelchair.
06/01/23 * All kinds of alarm systems should be designed taking into account the perception of all categories of disabilities and
the requirements of GOST R 51 764. Placement and the appointment of sensors is determined in the job for the design.
Should be used intercoms with audible and visual alarms.
Accommodation for permanent living with disabilities should be equipped with autonomous fire detectors.
6.2 The buildings and premises of the educational purpose
6.2.1 The buildings of educational institutions is recommended to make available to all categories of students with disabilities,
with the exception of professional educational institutions that have restrictions on the admission of students in certain health
profession under the law.
Building rehabilitation and special education institutions, which combine training with the correction and compensation for the
shortcomings of a certain type of disease are projected on a special assignment for the design to meet the requirements of this
instrument.
6.2.2 Elevator for disabled students, traveling in a wheelchair, in general education, as well as primary and secondary vocational
education should be provided in a special elevator lobby, with limited access to his other students
6.2.3 If the width of the band less than 1.8 m is recommended to provide every 10-15 m long corridor, but at least one passage,
pocket depth of 1.8 m, length - 3,0 m.
6.2.4 Student places for students with disabilities must be placed identically in similar classrooms, an academic institution.
6.2.5 In the first training facility in a series of tables by the window in the middle lane to provide for students with visual
impairments and hearing defects, and for students who are traveling in a wheelchair - to allocate 2.1 first table in a row in the
doorway.
6.2.6 In the assembly halls of educational institutions should provide places for disabled people in wheelchairs from the
calculation: in the hall for 50-150 seats - 3-5 seats, the hall seats 150-300 - 5-7 seats, a hall for 300 -500 seats - 7-10 seats, in the
hall for 500-800 seats - 10-15 people and places on the stage, in dressing rooms and other spaces for artists.
Places for students with disabilities with a lesion of the musculoskeletal system should provide in horizontal floor, in rows
adjacent to the aisles and in the same level as entrance to the auditorium.
6.2.7 * The place or area for spectators in wheelchairs in the auditorium of the amphitheater, visual and lecture halls should
include security measures (fencing, buffer strip, etc.).
6.2.8 * In the classroom, visual and lecture halls with a capacity of more than 50 people, equipped with fixed seating, must be
provided not less than 4% of seats with built-in personal listening systems.
6.2.9 * Places for people with hearing disabilities should be placed at a distance of 10 meters from the sound source, or to
equip the special personal sound amplification devices.
May be used in the halls of an induction loop or other personal wireless devices. These sites should be located in the area of
good visibility and the scene of an interpreter of sign language. The need for additional area for the interpreter is set to the task
design.
6.2.10 reading room of the educational institution at least 5% of reading places should be provided taking into account access of
students with disabilities. With this purpose in the reading room should provide separate no-go zones for the placement of
special places: for students with disabilities, traveling in wheelchairs and using other means of individual rehabilitation of
walking and separately - for students with visual impairments. Workplace for the visually impaired should have an additional
Surround lighting.
6.2.11 Stand-barrier issue to the subscription books in secondary schools, wardrobe racks should meet the requirements
specified in section 5.5.9 *.
6.2.12 In a dining room must be provided for students with disabilities in their own no-go zone, which equipment should take
into account the possibility of using children in wheelchairs.
6.3 Buildings and facilities of health and social services
6.3.1 available for low mobile populations should be building health care facilities that directly provide medical care. These are
institutions that are visited by the public, including persons with disabilities: outpatient clinics (polyclinics, dispensaries and
centers) of different service levels (from village to national), in various fields (multidisciplinary, dental, physiotherapy, family,
etc.) and different purposes (basic, consulting, diagnostic, etc.) - then hospitals.
6.3.2 Facilities intended for hospital stay of patients, including disabled and other low mobile populations: - hospitals (hospitals
and clinics) at different levels of service (from rural to national), in various fields (multidisciplinary, mental health, cardiology,
rehabilitation, etc.) are established physicians in the specification.
6.3.3 Travmapunkt, infectious room and reception area health facilities, dairy food, optics, and pharmacies should have exterior
entrances, accessible to persons with disabilities.Travmapunkt should be placed on the ground floor.
Outer vestibule of one of the boxes must be infectious department is designed for disabled access
6.3.4 In the parking lot of visitors outpatient for at least 10% of seats shall be provided for disabled vehicles. For patients and
visitors to rehabilitation facilities that specialize in treating people with limitations in movement should be allocated for parking
up to 20% of the seats.
Zone boarding should be provided in accessible entrance to a medical facility, where people receive medical care or treatment.
6.3.5 * In the ward offices of the general type of beds for disabled persons in wheelchairs should be 3% of the total number of
beds in the ward, but not less than one.
6.3.6 Inputs to health services for patients and visitors must have a visual, tactile and acoustic information indicating the groups
of rooms, which can be accessed through this entrance.
6.3.7 The width of corridors that are used to waiting for a bilateral arrangement of rooms shall be not less than 3.2 m, with one-
sided - at least 2.8 m.
6.3.8 Not less than one of the sections of the hall and therapeutic mud baths, including dressing rooms with him, must be
adapted for the disabled in a wheelchair.
6.4 Buildings and premises of public service
6.4.1 Trade Enterprises
6.4.1.1 Availability of inst should be provided primarily in retail trade - non-food grocery stores and in supermarkets, chain
stores and shopping centers.
6.4.1.2 Places for handicapped persons must be placed no farther than 50 meters from the entrance is available for inst.
6.4.1.3 Equipment and placement of equipment in the trading rooms are available with disabilities, should be designed to
service persons traveling in wheelchairs and with their own attendant, disabled people on crutches, as well as the visually
impaired. Tables, counters, cash settlement plane cabins should be located at a height not exceeding 0.85 m above floor
level. The maximum depth of the shelves (at the entrance close) should not exceed 0.5 m.
6.4.1.4 All sizes of passes (excluding a one-sided) should allow a full rotation of 360 0 and disability services at the front
wheelchair with attendant.
6.4.1.5 At least one of the control of cash positions in the room must be equipped in accordance with the requirements of
accessibility for the disabled. Aisle width about cash management unit should be not less than 0.9 m in cash and settlement
area should be adapted at least one available cash register (see Table 4).
Table 4 - Available passages teller area

The total number of passes The number of available passes min.

4.1 1

8.5 2

9-15 3

More than 15 3 + 20% of additional aisles

6.4.1.6 In order to emphasize customers with visual impairments in the required information should be actively use tactile (the
recommended height placement - 0.75 m above floor level), illuminated signs, displays and icons, as well as the contrasting
color design and interior elements.
6.4.1.7 In a convenient for the visitor - the visually impaired and place in an accessible form for him to have information about
the location of sales areas and sections of the range of products, as well as communications with the administration.
6.4.2 Power Companies
6.4.2.1 In the power plants and areas reserved for specialist disability services are encouraged to provide waiter service. In the
absence of a building, elevators, dining rooms should be placed on the ground floor. The area of such dining rooms is
determined by the standard area of not less than 3m 2 in place.
6.4.2.2 In the self-service facilities is recommended to remove up to 10% of the seats, but at least for persons traveling in
wheelchairs and visually impaired, with an area of not less than 3m 2 in each place.
6.4.2.3 The width of the passage around the shelves for dishes servirovaniya must be at least 0.9 m. In order to ensure the free
passage of rounding in a wheelchair passage width is recommended to increase to 1.1 m.
6.4.2.4 The premises catering arrangement of furniture and equipment should ensure the unimpeded movement of people with
disabilities. In coffee shops and eateries should be at least one table conforming to 5.5.9 *.
6.4.2.5 * In the halls catering seating (tables) for the disabled should be located near the entrance, but not in a passing zone.
6.4.3 Network of service
6.4.3.1 Network of service (reception facilities, Fashion houses, ateliers, shops, hairdressers, laundry businesses, dry cleaners,
etc.), as well as rentals home wares, office complex services have to be the accessibility requirements for disabled and other
low mobile groups.
6.4.3.2 In the changing room provided for the project, fitting rooms, locker rooms, etc., not less than 5% must be accessible to
persons with disabilities.
Equipment closets, fitting rooms, locker rooms - hooks, hangers, shelves for clothes should be available for mH, and for other
citizens.
6.4.4 Buildings stations all modes of transport
6.4.4.1 Premises station buildings of different types of passenger transport (rail, road, air, river and sea), passages, platforms
and other facilities intended for passenger services should be available for inst.
6.4.4.2 At the open parking lots at stations should provide space for private vehicles with disabilities. The number of such places
should be taken from the calculation:
4% ... ... ... ... ... ... ... ... ... ... ... ... with the total number of parking spaces to 100;
3% ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. when the number of seats from 101 to 200;
2% ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... when the number of seats from 201.
6.4.4.3 In passenger station buildings of different types of transport should be available to provide:
- Premises and facilities maintenance: lobbies, operating rooms and cash registers; luggage carry-on luggage, check-in point of
passengers and baggage, special facilities and leisure expectations - deputy rooms, rooms for mothers and children, long rest
rooms;
- Buildings, areas in which additional services or facilities: shopping (dining) room of restaurants, cafes, cafeterias, snack bars,
shopping, retail and other stalls, barber shops, halls of slot machines, trade and other machines, items of communication
enterprises, public telephones;
- Offices: reception, medical facilities, health, etc.
6.4.4.4 In the waiting rooms of buildings stations should include a selection of special recreation areas, and waiting for the
disabled and other low mobile passengers and accessibility to them.
The area of these zones is determined by the rate - 2.1 m 2 per seat. Part of the sofas or benches for seating in the rooms should
be located no closer than 2.7 m apart.
6.4.4.5 Special waiting area and rest in the waiting rooms should be provided away from the main flow of passengers (main
passages), isolated from the most bustling areas and connect with the special aprons outputs.
Special waiting area and rest should be placed on the main floor, level with the entrance of the station building and exits to the
platforms (the platform, berths) in providing clear, safe and short transitions between them.
Waiting rooms should have a comfortable relationship with the lobby, restaurant (cafe-snack bar) and Outputs to the platform,
situated usually in the same level with them.
6.4.4.6 In the vicinity of the special waiting areas and recreation should include universal cab for the disabled - in a separate
room or in the toilets for passengers, but not less than one booth for both men and women.
6.4.4.7 Special waiting area and rest, if there are no departmental rules should provide for a rate of 5% of the total number of
seats in the waiting rooms, but at least one seat for those with damage to the musculoskeletal system, for persons with
impaired hearing , visual impairments, as well as cardiovascular and pulmonary disease.
6.4.4.8 Seats in a special holding area and the rest should be provided with individual means of information and
communications headsets, connected to the system of information support stations, display of overlapping images of placards
and audio ads, technical means of emergency communication with the administration, accessible tactile perception; other
special systems of signal-information management (computers, information on the phone, etc.).
6.4.4.9 At the railway stations where passengers access to the platforms at the station square or opposite to it a residential area
overlaps with the intensity of railway trains up to 50 pairs per day and the rate of passage of trains to 120 km / h, for the
transport of disabled people in wheelchairs allowed to use transitions in the level of the rails, equipped with automatic alarms
and lighting of signs. Throughout this transition along the railway (including the end of the ramp on the platform) that provide a
protective barrier height of not less than 0.9 m located at the same height of handrails.
6.4.4.10 In the field of automatic storage rooms be reserved are located in the bottom row and to adapt for disabled passengers
at least 5% of the seats in the number of storage rooms to 200, and 10 storage rooms, plus 2% of the total amount of more than
200 cameras.
6.4.4.11 At the edge of the landing platform should support a precautionary warning strips along the edges of the platform, as
well as tactile indicators for people with visual impairment.
On the platforms must be capable of duplicating the visual and auditory information, including the location of cars.
6.4.4.12 To register, tickets and baggage with disabilities should be special racks in height from floor level not exceeding 0.85 m.
Stands filling declarations are available for inst, at the airports of international airlines have to be the requirements specified in
5.5.9 *.
6.4.4.13 In the bus terminals to serve the low mobile passengers are not recommended for use island platforms. Aprons from
the shore, or peninsular location at bus stations pirsovym long-distance transport must be equipped with fixed or mobile lifts
for embarkation / disembarkation of persons with disabilities buses are not equipped with such means.
6.4.4.14 In each row of turnstiles entrance / exit should be provided at least one extended passage for the passage of
wheelchairs. It should be placed beyond the control of tickets, equipped with horizontal rails at a distance of 1.2 m, secreting
area in front of the passage, and denote the corresponding international symbol.
6.5 The objects of physical training, sports and fitness and leisure destination
6.5.1 * In the open parking lots and athletic sports and entertainment facilities should provide space for private vehicles with
disabilities. The number of such places should be taken at the rate of 6% of total capacity, but at least 2 dedicated parking
spaces.
6.5.2 * Dimensions elevator car to sport and sports and entertainment facilities should not be less than, mm: 2100x1500. The
width of the elevator door opening at least 950 mm.
6.6.3 * The number of places for disabled people in the stands and athletic sports and entertainment facilities make the rate of
not less than 1.5% to 1,000 people, plus one space for each additional 100 seats.
6.5.4 * Places for people with disabilities in sports and sports and entertainment facilities should be provided as in the
grandstands and in front of the stands (including at the zone level of competition).
Places for people with disabilities should be located near emergency exits.
6.5.5 * Places for the accompanying persons must be placed in close proximity to people with disabilities (they can either
alternate with places for the disabled, or placed directly behind them).
6.5.6 * Places are available for people with disabilities in violation of the musculoskeletal system in the grandstands and athletic
sports and entertainment facilities should be provided in an area immediately adjacent to the exit on the podium. These areas
should be protected from the crowds.
6.5.7 When used in a room darkening ramps and steps should be light.
6.5.8 It is recommended to ensure accessibility for people with disabilities in all secondary rooms (except, as a rule,
administrative offices and technical) in training sports and athletic facilities: entrance and recreational areas (hallways, dressing
rooms, recreational areas, coffee shops), changing room block , showers and toilets, coaching and teaching facilities, medical
and rehabilitation facilities (medical rooms, saunas, massage, etc.).
6.5.9 * The sports and entertainment facilities width of all paths of motion that could potentially be used by spectators, must be
at least 1.8 m.
6.5.10 Removing service facilities for dealing with, including disabled people, from places of sports and sporting activities should
not exceed 150m.
Available 05/06/11 path of movement must be provided, at least to 5% bowling, but not less than one track of each type.
06/05/12 In the disposition of equipment in gyms to consider driveways for the disabled in wheelchairs. On the area of the gym
space should be provided with special training equipment for training people with disabilities.
06/05/13 To guide the people with complete loss of vision and visually impaired are encouraged to: along the walls in the
specialized bathing pool and the entrance of the premises for changing and showers should be installed horizontal rail at a
height from the floor in the range of 0.9 to 1.2 m and in the halls with a swimming pool for children - at 0.5 m above the floor.
05/06/14 At the main traffic routes through the halls of the pool and bypass lanes should be provided special tactile strips for
information and guidance. The width of the bands for the orientation of the open bath - not less than 1.2 m.
On the area of the bypass lanes should provide storage space for wheelchairs.
06/05/15 In the shallow end bath should be no sloping ladder with the size, not less risers - 0.14 m and tread - 0.3 m. It is
recommended to arrange a ladder outside dimensions of the bath.
6.5.16 Bypass path around the perimeter of bath must be a minimum width of 2 m and 2.5 m covered by the open bath.
6.5.17 edge of the bath around the perimeter of the pool should be allocated a strip having a contrasting color with respect to
the bypass lane.
05/06/18 * The changing room facilities for sports facilities for dealing with persons with disabilities should include:
- Storage space for wheelchairs;
- Individual cabins (each area of not less than 4 m 2) at the rate of one in three cab at the same time dealing with disabilities who
use wheelchairs;
- Individual lockers (at least) no higher than 1.7 m, including storage of crutches and prostheses;
- A bench of not less than 3 m, a width of 0.7 m and a height from the floor up to 0.45 m.
Around the bench should be provided free space for the wheelchair entrance. If it is impossible island bench unit should be
provided along one wall of the installation of the bench of not less than 0.6 x 2.5 m.
06/05/19 Area dressing rooms with the possibility of visiting the disabled are encouraged to take:
- 1 engaged in the halls - at least 3.8 m 2, 1 engaged in the swimming pools with room training sessions - 4.5 m 2 (for general
separation-shaft);
- In the changing room to store clothes in a separate room closet - 2.1 m 2 for the individual booths - 4-5 m 2;
- In the family changing room for disabled with assistance - 6-8 m 2.
The size of the passage between the benches in the common changing room should be at least 1.8 m.
Specific indicators include the area of space for changing rooms, lockers for storing clothes in a home shared dressing rooms,
wash the legs.
6.5.20 Number of showers for the disabled should be made at the rate - one shower a grid of 3 dealing with disabilities, but not
less than one.
06/05/21 * The rest room in dressing rooms should provide additional space at the rate of not less than 0.4 m 2 each at the
same time dealing with disabled persons in wheelchairs, and recreation room with sauna should be an area of not less than 20
m 2.
5/6/22 Game equipment for outdoor sports grounds need to be painted in bright contrasting colors
05/06/23 Around the playground and in the halls of simulators should provide the security zone.
6.5.24 It should bury in a niche in the wall of the rail, which is equipped gym for the Blind. The walls of rooms must be
completely smooth, with no ledges. All mounting hardware equipment, controls, electrical switches must be installed flush with
the wall or bury.
06/05/25 For sports persons with disabilities in wheelchairs should use the meeting rooms with rough, springy flooring made of
synthetic materials or sports flooring.
06/05/26 For sports persons with visual impairments border playgrounds marked relief glued strips.
6.5.27 If the stands of sports and entertainment facilities provide sound information, it must be duplicated text information.
05/06/28 at sports and sports and entertainment facilities to ensure that the walking areas for guide dogs and other dogs.
6.6 The buildings and premises for cultural, educational, entertainment and leisure destination, and religious organizations
6.6.1 Spectator facilities
6.6.1.1 * Places for disabled people in hall-room, you should have available to them in the hall area, providing: full perception of
demonstration, entertainment, information, music programs and materials, easy meals (lunch in the halls or corridors in the
halls), recreation ( in the waiting room).
6.6.1.2 * In the hall-room of at least two dispersed output should be adjusted for the passage of inst.
6.6.1.3 * In each room there should be seats with arm rests and without them, at a cost - at least one chair with armrests to 5
chairs without armrests. Benches should provide good support for your back and the space under the seat depth of not less
than one third the depth of the bench.
6.6.1.4 The number of places for disabled people in wheelchairs in the audience are encouraged to take the capacity of the hall,
but not least:

50 - 75 seats in the hall ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 3

76 - 100 at the same ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 4

101 - 150 - "- ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 5

151 - 200 - "- ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 6

201 - 300 - "- ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .... ... ... ... .. 7

301 - 400 - "- ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 8

More than 400 - "- ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 9

6.6.1.5 In multi-level rooms should provide space for the disabled in a wheelchair on the first floor level, as well as one of the
intermediate. Necessary to provide space for wheelchairs in the club boxes, boxes, etc.
At least 5% of the total seats in the aisles, but at least one must be a special place, located as close as possible to the available
paths of motion.
6.6.1.6 * Places for disabled people in auditorium is preferable to have as a rule, in separate rows, with a separate escape route
that does not intersect with the ways of evacuating the rest of the audience. In the auditorium of the number of seats 800 and
more seats for disabled people in wheelchairs should disperse in different zones, placing them in close proximity to the
emergency exit, but at the same place no more than three.
Distance from any seat in the hall-room with disabilities to escape out into the hallway, foyer, or outside to hatch an escape
tribune sports and entertainment hall shall not exceed 40 m. The width of aisles shall be increased by the width of the free
travel wheelchair (0.9 m .)
6.6.1.7 * front of the stage or at the end of the room near the doorway and exit should be provided free area clear width of at
least 1.8 m for spectators in wheelchairs.
Provision should be made available to the performers on stage, backstage in the dressing room and other auxiliary facilities.
6.6.1.8 Recommended variety of types O-2 and E-3, but with increasing depth of the flat plate up to 9 - 12 m and the
proscenium - up to 2.5 m for the opportunity to participate in programs with disabilities in wheelchairs. Recommended height
of the stage - 0.8 m
To rise to the stage, except ladders shall be provided for an attached or fixed ramp with a minimum width of 0.9 m with a slope
of 8% and the bumpers on the sides. Stairs and ramps leading to the stage, on the one hand must have a double fence rails at a
height of 0,5 / 0,7 / 0,9 m.
6.6.1.9 In each room the sound system must support the auditory system.
Rooms for more than 800 seats is recommended to additionally equip the TV monitors.
6.6.1.10 The existing circuses be allowed to use the service entrance for spectators access to the sites, located on a flat floor in
front of the first row. Places for disabled people in the halls of circuses should be placed near the escape hatch in the series,
whose plane is on one level to the lobby. In this case, the passage area should be increased to not less than 2.2 m (in places
where it is supposed location of the disabled).
6.6.2 Cultural Institutions
6.6.2.1 In the design of museums should use common universal path of movement and adaptation to the needs of low mobile
groups of premises.
6.6.2.2 * If you can not use visual information for the disabled in areas with specific requirements to address the artistic
interiors, in the halls of art museums, exhibitions, etc., is allowed to use other compensatory measures.
6.6.2.3 Considering the needs of disabled visitors to museums with an exhibition area of 2,000 m 2 is recommended location of
the exposition in the same level.
6.6.2.4 Zone are encouraged to create a permanent exhibition with anfiladnym or circular routes. Dead-end planning is not
desirable.
Ramps should be used to implement a consistent movement and simultaneous examination of the exposure.
6.6.2.5 Suspended cabinet should be at a height accessible to visual perception in a wheelchair (bottom to mark no more than
0.85 m above floor level).
Horizontal cabinet must have a space for handicapped entrance in a wheelchair
In shop windows at a height of 0.8 m must be a horizontal handrail device with rounded corners for people with visual
impairments around the table to provide a warning of the exhibition textured color bar width from 0.6 to 0.8 m in floor level.
6.6.2.6 It should protect the speakers and free-standing objects.
6.6.2.7 The number of seats for readers, specially equipped and designed for library services to persons with disabilities of all
categories shall be not less than 5% of the total number of seats for readers in the libraries of the centralized library network,
including service disabled in wheelchairs at least 4 special places.
6.6.2.8 All the passages within the zone must have a minimum width of 1.2 m. The size of workplace disability (excluding the
table) should be 1.5 x0, 9m. Recommended to make optimal size of the surface area of the table the reader with visual
impairments to work with the Secretary-reader - 1.5 x 0.7 meters in the cabs, polukabinah or offices.
6.6.2.9 In the area of services for people with visual impairments, and special reading room with literature racks in braille
should be equipped with an additional lighting. Necessary to provide a high level of natural illumination of the reading zone
(RED-2, 5%), and the level of artificial lighting library table - at least 1,000 lux.
6.6.2.10 Clubs, engineered with the needs of low mobile populations may be the usual composition of buildings designed for
mixed groups - Option "A" and with additional rooms, specially equipped for the disabled - Option "B". These areas include:
circle the room for music, dancing, various crafts, as well as auxiliary facilities health unit.
6.6.2.11 Premises circles with disabilities encouraged to project no more than 10-12 people. Disabled persons in wheelchairs
can reach up to 25% of the total circle.
6.6.2.12 Specific surface areas of circles and versatile bands to a visitor in the mixed composition of course participants are
encouraged to take a 20-50% higher than the maximum value, taken off to the public, but not least, m 2:

In universal premises:
2.2 (2.7)
Room ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...
2.0 (2.6)
Hall ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... Recreation ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...
3.8 (4.8).

Note - In parentheses is given the optimum value.


In the hall-room of at least two dispersed output should be adjusted for the passage of inst.
In each room there should be seats with arm rests and without them, the rate of one chair with armrest for 5 chairs without
armrests. Benches should provide good support for your back and the space under the seat depth of not less than one third the
depth of the bench.
6.6.2.13 Ramps, in lecture halls, leading to a series of tiered amphitheaters, should have handrails on the walls.
6.6.3 Places of worship, ritual (ritual) and memorial buildings and structures
6.6.3.1 architectural environment of buildings, structures and facilities for religious services and rituals (ritual) sites for all types
of ceremonies, funeral and memorial sites must meet accessibility requirements for low mobile users, as well as confessional
requirements in terms of locations and equipment places of worship and religious services.
6.6.3.2 is not recommended to use the information tools available to people with disabilities, creating interference of light and
sound architecture of the memorial.
6.6.3.3 Road traffic destined for the disabled and other low mobile populations, can not enter the zone of movement of
religious and other ceremonial processions and entrance ways of tuples.
When the device in religious and ceremonial buildings and structures, as well as on their sites, places of ablution must be at
least one place to equip low mobile persons.
6.6.3.4 The device in the confessional at least one space for disabled and low mobile confession of persons according to use
means of rehabilitation.
6.6.3.5 In the area of seating at least 3% of the seats set aside for disabled persons recommended for wheelchairs (but not less
than one).
In multi-level buildings for religious purposes, where the second floor or at the intermediate level is located not more than 25%
of parishioners, all the seats for wheelchairs can be placed at ground level.
6.6.3.6 Distance from the raised parts of the floor at the placement of relics, as well as from the pulpit, seats, porch, chairs,
bowls, fonts and other elements of the interior to the speakers horizontally to the side ways movement of interior parts must
be at least 1.8 m height elevated part of the floor at the relics, and salts from the pulpit and the podium should be at least 0.1
m.
6.6.3.7 Removal of seats laid flowers and wreaths, garlands, stones, amulets, install icons, candles, lamps, distributing holy
water should not exceed 0.6 m from the edge of the path of motion. Height - 0.6 to 1.2 m above floor level.
The front approach to the place of worship - not less than 0.9
6.6.3.8 In areas of cemeteries and cemeteries should be accessible low mobile populations:
- To the sites of burials to Columbariums of all kinds;
- To the administration building, trade and domestic buildings for visitors to public toilets;
- To standpipes and devices for watering bowls;
- To the exhibition sites;
- Memorial of public facilities;
6.6.3.9 On the path of motion of cemeteries should be not less than 300 m to provide recreation.
6.6.3.10 a place should be provided in all types of tombs, burial plot for each, as well as about mass graves, collective burial
places of public worship, outdoor columbarium.
6.7 The buildings and premises for a temporary stay
6.7.1 * In hotels, motels, resorts, campgrounds, etc., usually 5% of residential rooms should be designed universal, taking into
account the settlement of all categories of visitors (if you specify the design is not specified the number of rooms, equipped
with a universal or specialization principle).
6.7.2 In the parking lots of hotels, motels, resorts, campgrounds, etc. necessary to ensure that the number of special seats for
disabled vehicles were not less than the number of available rooms.
6.7.3 There should be room in the space of diameter 1.4-1.5 m in front of a door, a bed, cupboards and front windows. The bed
should be a space for transplantation of at least 0.75 m.
6.8 Building maintenance facilities of state and society
6.8.1 All kinds and types of buildings and premises of institutions and organizations associated with the admission (care) of the
population and placed in buildings with a cabinet-office structure to be accessible to design inst. These include:
- Administrative organization - committees, administration, departments and divisions, including the bodies of social protection,
governance, consumer protection, as well as prefectures, municipalities, etc.;
- Judicial and legal institutions - the legal offices and consulting, bar associations, notaries, insurance companies and
foundations;
- Utilities - DES, REU, etc.;
- Tax inspection and management and the Visa and Registration (Visa Office)
- The organization of employment - federal agencies, management and employment centers, employment agencies and other
institutions and organizations.
6.8.2 General Requirements for a core group of premises where there is low mobile device users are:
- Preferred placement in the level of entry;
- The obligatory presence of the reference and information service; possible combination of reference and information services
and office duty admission;
- If the shared use of facilities (conference rooms, meeting rooms, etc.) is desirable to place them no higher than the second
level (floor).
In all types of building facilities for servicing the society and state should be the selection of zones or locations for specialized
service categories low mobile users with the possibility of support, including people with disabilities (including disabled persons
in wheelchairs, the visually impaired).
Stand information in areas of specialized services should be visible from the entrance and is easily distinguished blind and
visually impaired visitors
The path from the entrance to the reception of information should be straight, free from obstacles and have durable, non-slip
surface and allow the disabled to easily maneuver a wheelchair.
The zone of specialized services should be provided with seating.
6.8.3 In buildings of social protection than general-purpose facilities, it is recommended to ensure availability for low mobile
users in the following areas:
- Account inquiry service;
- Office of the chief (duty office administration);
- Staff offices, reception of visitors in the leading parts of the assignment and allocation of pensions, benefits and welfare
services;
- A medical office (if any);
- Lawyer's office (if available).
6.8.4 Under the judicial, legal institutions and prosecutors' offices, subject to accessibility requirements, mainly for legal
services and notary public services (such as the establishment of open access). The minimum size of floor space (office or car)
for individual reception (per workstation) are encouraged to take 12m 2.
6.8.5 Each courtroom facilities must be available for all types of disabilities.
On the bench, jurors should be provided for the disabled in a wheelchair. Place the plaintiff and counsel, including the
Department should be available.
If provided detention cell at room sidany oud, is one of the cameras should be accessible to the disabled in a wheelchair. Such a
chamber can be designed for more than one courtroom.
The solid walls, security glass or separation tables that separate visitors from detainees at the premises visits prisons, should
have at least one place, accessible for the disabled on each side.
6.8.6 Lobby facilities for servicing the society and state should be equipped with signs and symbols that indicate ifty, stairs,
restrooms, paths of motion and other visual information should be clear and legible for slovidyaschih visitors. In the lobby area
should provide service machines (phones, pay phones, sales, etc.) and a backup area for kiosks.
Flooring hallways must ensure the elimination of water and mud from shoes and wheels of a wheelchair.
6.8.7 In areas receiving visitors in a few places of service should be available for mH:
- One of the places of service;
- A few places of service, arranged in a common area;
- Visitors' area of the entire room (all room service).
6.8.8 In the department of retirement benefits should be provided with each unit is two-way communication.
6.8.9 In buildings, institutions and enterprises, containing in its structure the operational and ticket halls, designed to cater to
visitors, should be readily accessible to comply with inst.In all buildings of financial institutions and post offices, is
recommended to provide system installation organized by the reception of visitors, consisting of: apparatus, issuing stamps
indicating the order of admission; lighting panels above the doors of the cabinets and windows, indicating the number of the
next visitor.
08.06.10 For the convenience of low mobile users should also provide designated areas for private car parking (temporary car
parks), recreational facilities in the areas of institutions and enterprises,
06/08/11 On the open parking lot for customers of the bank it is desirable to adapt a place for disabled users for every three
seats in the operating room. The total number of specialized areas is defined by specifying the design.
06/08/12 Inputs, including separate entrances to the pass office and hall self-recommended universal design (ie take into
account the use of all categories of users).
08/06/13 premises to banking institutions access to the first zone (in which the admission of clients is not limited by the
technological requirements) should include:
- Cash box (cash hall and depository) banks;
- Operating unit (entrance room, operating room and offices) Savings institutions;
- Support and service facilities (meeting rooms with customers and processing the loan, lobby, advances to the lobby, office
spaces).
6.8.14 In addition to the operational and cash room, visitors' access to the area businesses are encouraged to include:
- The entrance with a vestibule (the generic type - for all groups of visitors);
- Dobarernuyu (visitors') part of the delivery department, combined if necessary with an area of individual storage subscriptions
and correspondence;
- Call office (with areas of long-distance telephone booths, including the manufacturer, and expectations);
- Currency exchange kiosks and sales (if available).
06/08/15 With a few island (Autonomous) jobs tellers, one adapted to serve the disabled.
06/08/16 In the assembly halls, conference rooms and other crowded places should be equipped accessible path of motion,
directly linking performance area with seating seats.
6.9 Places of employment
6.9.1 * The design of institutions, organizations and businesses should provide jobs for people with disabilities.
The number and types of jobs for persons with disabilities (special or regular), and their placement in space-planning structure
of the building (or dispersed in specialized shops, production areas and special areas), as well as the required additional facilities
are installed in the job for the design.
6.9.2 * Jobs with disabilities should be safe for health, rationally organized. They should have sanitary-epidemiological
conclusion of local Rospotrebnadzor. The second type design should be established to specialize and, if appropriate, include a
set of furniture, equipment and assistive devices, specially adapted for a specific disease. This includes taking into account the
GOST 25 131 51 645 and GOST.
6.9.3 * The work area (the space of a job) or room should be provided with performance of a complex of sanitary-hygienic
requirements for microclimate in accordance with existing regulations and additional requirements established depending on
the type of disease with disabilities.
6.9.4 * The area of the premises should be the basis of selection for every working person with disabilities who uses a
wheelchair, however, m 2:
in clerical, administrative and office buildings ... ... ... 5.7;
in design offices ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 7.7.
6.9.5 * The distance to the toilet, smoking, facilities for heating or cooling poludushey, devices, drinking water supply of jobs for
disabled persons with lesions of the musculoskeletal system and visually impaired, must be not more than m:
within buildings ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 60;
within the territory of institutions, enterprises ... ... ... ... ... ... ... ... 150.
6.9.6 * Sanitary service workers with disabilities must be provided in accordance with the SNP -2010 02/09/04, and this set of
rules.
6.9.7 * When the difficulty of access for disabled wheelchair to places of public catering enterprises and institutions should
provide an additional room, eating area at the rate of 1.65 m 2 for each disabled person, but not less than 12 m 2.
6.10 Buildings and premises of industrial and warehouse use
6.10.1 * When designing buildings with rooms and warehouse purposes should have access mH to all workplaces in the event of
an independent stay in the company of people with disabilities. If the company provides work wheelchairs in the project should
include measures and means to ensure such groups mH accessibility of the building.
The number and types of jobs for persons with disabilities (special or regular), and their placement in space-planning structure
of the building (or dispersed in specialized shops, production areas and special areas), as well as the required additional facilities
are installed in the job for the design.
6.10.2 * Jobs with disabilities should be safe for health, rationally organized. They should have sanitary-epidemiological
conclusion of local Rospotrebnadzor. The second type design should be established to specialize and, if appropriate, include a
set of furniture, equipment and assistive devices, specially adapted for a specific disease. This includes taking into account the
GOST 25 131 51 645 and GOST.
6.10.3 * The work area (the space of a job) or room should be provided with performance of a complex of sanitary-hygienic
requirements for microclimate in accordance with existing regulations and additional requirements established depending on
the type of disease with disabilities.
6.10.4 * The area of the premises should be the basis of selection for every working person with disabilities who uses a
wheelchair, however, m 2:
in clerical, administrative and office buildings ... ... ... ... .5,7;
in design offices ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 7.7.
6.10.5 * The distance to the toilet, smoking, facilities for heating or cooling poludushey, devices, drinking water supply of jobs
for disabled persons with lesions of the musculoskeletal system and visually impaired, must be not more than m:
within buildings ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 60;
within the territory of institutions, enterprises ... ... ... ... ... ... ... .. 150.
6.10.6 * Sanitary service workers with disabilities must be provided in accordance with the requirements of SNIP 2/9/04 -2010,
and this document.
6.10.7 * If a quandary access for disabled people in wheelchairs to places of public catering enterprises and institutions should
provide an additional room, eating area at the rate of 1.65 m 2 for each disabled person, but not less than 12 m 2.
6.10.8 * Pedestrian paths and path of movement within buildings and warehouse use must contrast in color to provide visual
contrast.
6.10.9 The equipment in buildings and warehouse purposes should generally be available and suitable for use inst. This
requirement does not apply to access to technology and equipment for the purpose of maintenance.
10.06.10 Hazardous materials available in the buildings and warehouse purposes, should be marked and contrasting color so
that they could easily be seen while in a sitting position in wheelchair

Appendix A
(Required)
Normative references
This rulebook references to the following regulations:
Federal Law of March 30, 1999 № 52-FZ "On the sanitary-epidemiological welfare of population".
Federal Law of 29 December 2004 № 191-FZ "City Planning Code of the Russian Federation."
Federal law of July 22, 2008 № 123-FZ "Technical regulations for fire safety requirements."
Federal Law of 30 December 2009 № 384-FZ "Technical Regulations on safety of buildings."
"Technical Regulations on safety of lifts", approved by RF Government Decree of October 2, 2009 № 782.
GOST R 25131-2003 Information display sign for the disabled.
GOST R 50602-93 Wheelchairs. Maximum dimensions.
GOST R 50605-93 Wheelchairs. Methods for determining the dimensions, weight, minimum turning radius and the minimum
width of the spread.
GOST R 51256-99 Means of traffic. Marking the road. Types and basic parameters.
GOST R 51261-99 devices supporting stationary rehabilitation. General technical requirements.
GOST R 51630-2000 Lift platforms with vertical and oblique movement of persons with disabilities. Specifications for
accessibility.
GOST R 51631-2008 Passengerlifts. Specifications for accessibility, including accessibility for disabled and other low mobile
populations.
GOST R 51633-2000 rehabilitative devices and accessories used by disabled people in residential premises. General technical
requirements.
GOST R 51645-2000 jobs for disabled people by type-specific computer.
GOST R 51671-2000 Communications and information technology public access for the handicapped. classification. Accessibility
requirements and safety.
GOST R 51764-2001 Communications, Computer and electronic alarm systems rehabilitation. General specifications.
GOST R 52131-2003 Information display sign for the disabled. Technical requirements.
GOST R 52875-2007 Pointers tactile surface for the visually impaired. Technical requirements.
GOST R 53453-2009 Ergonomics of the thermal environment. Application of the standard requirements for people with special
needs.
GOST 53770-2010 Passengerlifts. Basic parameters and dimensions.
Standard 12.1.004-91 * Fire safety. General requirements.
SNiP 23-05-95 Natural and artificial lighting.
SNIP 01.31.2003 residential apartment buildings.
SNIP 03/31/2001 Industrial buildings.
SNIP 05/31/2003 Public buildings for administrative purposes.
SNIP 31/06/2009 Public buildings and facilities.
SNIP 2.09.04-87 * Administrative and everyday buildings.
SNIP 41-01-2003 heating, ventilation and air conditioning.
SP 1.13130.2009 Fire protection systems. Evacuation routes and exits.
NPB 104-95 Design of warning people about a fire in buildings.
Note - When using this set of rules appropriate to test the effect of reference standards and classifications in the information
system of common use - the official website of the national authority of the Russian Federation for Standardization on the
Internet or on annual basis to the information sign "national standards", which was published on January 1, this year, and the
respective monthly published by the Information Index, published in the current year. If the reference document changed
(changed), then use this set of rules should govern replaced (modified) document. If the reference document canceled without
replacement, then the position in which reference is made to him, applies to the extent not affecting the link.
Appendix B
(Required)
Terms and definitions
Adaptation: The adaptation to new conditions, there is: a device built environment, buildings and structures, taking into
account the needs of low mobile populations.
Apparel: (here) construction bill for a flight of stairs or through an obstacle for the passage of the disabled in a wheelchair.
Improvement area (territory): (here) a set of measures to ensure availability and low mobile users including: landscaping
(planting), paving for pedestrian and roadway, outdoor lighting device, creating recreation areas, sports and entertainment in
the area, as well as information provision to visitors.
Border: fence motion paths and spaces, homogeneous elements of small height, combining the functions of the safety criteria
and informative
Visual media (here), media information transmitted to people with impaired hearing in the form of visually distinct texts, signs,
symbols, lights.
Log adapted: (here) input, adapted for the passage of low mobile users, including those in wheelchairs.
Dimensions: (here) internal ("in light") and external ("clean") dimensions of the elements of the architectural environment
(objects and spaces) at their extreme protruding.
Available for mH buildings and structures: buildings and structures, which implemented a set of architectural planning,
engineering, ergonomics, design and institutional arrangements that meet the regulatory requirements for accessibility and
safety mH these buildings and structures.
Accessible route of travel: the rooms, room service, allowing unimpeded reach places and to use the service.
Reach: property maintenance sites with options that let you take advantage of the opportunity, to reach the object, the object
of use.
Safety zone: a part of buildings, the fire compartment, isolated rooms, a dedicated fire barriers to protect people from hazards
of fire and other extreme events (for the time to complete the rescue) provided by the complex arrangements for the
evacuation and rescue.
Area: (here) and configuration parameters are functionally organized space is not completely isolated envelopes.
Zone Service (Service): A collection of places of service in the room or on the site.
Invalid: a man with health problems with persistent disorder of body functions, including the defeat of the musculoskeletal
system, visually impaired and hearing-impaired, leading to disability and its causes need social protection.
Visually Impaired: a citizen whose vision is completely absent or residual vision acuity does not exceed 10%, or field of view is
not more than 20%.
Pocket (here) niche, the space adjacent to the boundary of the premises or the communications path beyond their limits.
Communication ways: part of communication spaces used exclusively for the movement.
Lift lobby: a special room, situated by the entrance to the elevator, limited, usually doors.
Low mobile populations; inst: people who have difficulties with self-moving, receiving services, relevant information or
orientation in space. For low mobile groups here include: the disabled, people with temporary health conditions, pregnant
women, elderly, people with prams etc.
Places of service: (here) parts of buildings, structures, premises, areas organized and equipped to provide services to the
visitor. Include the workplace, the place served, perhaps - a place of waiting.
Fence: Building design that is installed on pedestrian surfaces drop marks, sex, more than 0.45 m.
Ramp: the construction of which has a continuous sloped surface on the direction of motion, designed to move from one level
to the horizontal surface of the path to another.
Note - The path of motion with a slope of less than 1: 20 is not considered a ramp.
Curb ramp: a new building intended for launching from the sidewalk to the road surface.
Ramp inventory: construction of a temporary or occasional use, for example. collapsible, folding, sliding, etc.
Sign Language Interpreters (sign language interpreter): specialist performing translation of sound information on sign language
for deaf-mutes.
Icon: a symbolic representation of the activity, indicate the action or purpose of the premises.
The platform lift (PP): Fixed intermittent hoisting machine for lifting and lowering of users that are located on the platform. PP
with a vertical displacement moves vertically with a slope of no more than 15 from the vertical. PP tilting movement moves on
rigid rails at an angle of inclination to the horizon of not more than 75.
The rise of: the difference between the levels (vertical size) between adjacent horizontal planes oblique path of motion.
Lane: a pedestrian way, intended for the movement in one row in one direction.
Putting personal service: cab or office, where the self-service or low mobile visitor staff establishment (enterprise). Cabin (the
cabinet) must consider, as a rule, the possibility of accommodation and accompanying persons.
Cross slope: slope of the surface perpendicular to the direction of motion.
Handrail: Component stairs or ramp, which sets the direction and provides support at the hands of the motion. Approx. - The
rail may be riding the fence.
House territory: land apartment building, including driveways and parking lots of guest vehicles, a platform for residents of the
home: children's, sports, recreation, garbage. The boundaries of the territory shall be established in the cadastral plan.
Cross slope: slope of the surface parallel to the direction of motion.
Pass: Walking the space between the structural and (or) functional elements (facilities).
Way traffic: the pedestrian path that is used inst, including disabled people in wheelchairs to move around the site (paths,
sidewalks, ramps, etc.), as well as inside buildings and structures (horizontal and vertical communication).
Reasonable accommodation, "the introduction, when it's needed in a particular case, necessary and appropriate modification
and adjustments not imposing a disproportionate or undue burden, in order to ensure the enjoyment or exercise on an equal
basis with others of all human rights and fundamental freedoms" (UN Convention on the Rights of Persons with Disabilities .)
System resources (information resources): (here) the set of media, providing for mH, early orientation in space, contributing to
security and ease of movement, as well as informing about the properties of built environments.
Specialized agency: the establishment of social and medical supplies for the ongoing care and maintenance of mH, including -
nursing home, hospice, nursing home, rehabilitation center, a residential home for the elderly, etc.
Specialized element (here), the element to which (as an object of regulation) imposed specific requirements on the adaptation
to the individual or combined defects of human health.
Tactile media: media information transmitted by the visually impaired and perceived by touch.
Tactile ground indicators: a tool to display information representing a specific band of embossed pattern and color that allows
visually impaired people to navigate in space by touch, feet, a cane or using the residual vision. Separated by type on the road
and floor, as well as warning and guide.
Textphone: an apparatus for sending, receiving, and dialogue on the phone with hearing disabilities in text mode. The unit is
equipped with a keyboard and a display for displaying textual information.
Typhlo-technical tools: tools to help visually impaired people work, and assimilation of information (tape recorders, voice
recorders, writing utensils, Braille typewriter).
Universal design (draft): "design (design) of products, environments, programs and services to make them as much as possible
usable by all people without the need for adaptation or specialized design. Universal design does not exclude assistive
(specialized) devices for particular groups of persons with disabilities where appropriate "(UN Convention on the Rights of
Persons with Disabilities).
Universal element (here) element, the planned taking into account all the possible use of (any) categories of the population.
Plot: (here) the area is functionally related to the building.
Braille: a special Braille for persons with complete loss of vision (blind) and the visually impaired. Here, one of the main means
of adapting the environment for the category low mobile persons.
Element: part of something here: the architectural, technical or mechanical components of buildings, structures, premises or
land, for example. - Workplace, a place of rest, shower, telephone booth, the door control device etc.
Appendix B
(Required)
Calculation of the number of elevators needed to save the disabled
from the security zones
B.1 The required number of elevators "n", accessible to the disabled and used to rescue them in case of fire in a building is
defined as:
n = T p / T c, (B.1)
where: T p - the estimated time saving one elevator with.;
T c - possible time saving of 10 minutes.
Elevator for transporting fire units can be used to rescue persons with disabilities during a fire.
B.2 Estimated time to save the T p is given by:
T p = T K, (B.2)
where: T - time of flight of the circular elevator in the rescue of persons with disabilities, defined by (B3);
K - the estimated number of flights required to rescue persons with disabilities, defined by (B.4).
T H = 2Σ i / m V + 93, (B.3)
where: Σ N i - the amount of marks levels of floors, from which will be the salvation of persons with disabilities, the level of the
ground floor, m;
m - number of floors, from which will be the salvation of people with disabilities;
V - rated speed of the elevator, m / s;
K = 1.43 ΣM / E, (B.4)
where: ΣM - the total number of disabled persons and persons accompanying them, people. given in the design task;
E - nominal capacity of the elevator, people.
Appendix D
(Required)
Materials for the calculation of the level of fire safety
low mobile populations
If you use Schedule 2 to GOST 12.1.004 (Section 2 "Basic calculations based") - to account for the specific movement mH on
escape routes should be used more calculated values of motion parameters mH:
D.1 of the mobile quality of the people in the stream are evacuated from buildings and structures should be divided into 4
groups according to Table D.1:
TABLE l and q and D.1

Average area
Group
horizontal projection
mobility Common characteristics of people mobility group
of thepeople, f, m 2

M1 People with no restrictions on mobility, including the hearing-impaired 0.1

Infirm people whose mobility is reduced due to aging (disabled by old age) with disabilities
M2 in prosthetics, disabled people with visual impairments who use a white cane, people with 0.2
mental disabilities.

MH People with disabilities, using the motion of additional supports (crutches, sticks). 0.3

M4 Handicapped persons traveling in wheelchairs, powered manually. 0.96

D.2 Estimated value of the speed and traffic flow of people with different mobility group should be determined by the
formulas:

m / min, with D> D 0, j; (D.1)

m / min, where (D.2)

and - Speed and traffic flow of people in the j-th mean way at a flux density D i;
D - density of the human stream in the area escape route, m 2 / m 2;
D 0, j - density human stream in the form of the j-th path at which the flux density begins to affect the speed of movement of
people in the thread;
V 0, j - the average speed of the free movement of people on the j-th mean path for the values of flux density D D 0, j;
a j - factor reflecting the degree of influence of the density of human stream to its speed in the j-th mean way;
The values of D 0, j, V 0, j, a j for different groups of people flows mobility of (D.1) and (D.2) are shown in Table D.2.
TABLE l and q and D.2

The value of options by type of path (j)


Group mobility Parameter values
rampant
horizontal stairs down stairs up ramp up
down
V 0, j 100 100 60 115 80
M1 D 0, j 0.051 0.089 0.067 0.171 0.107
aj 0.295 0.400 0.305 0.399 0.399

V 0, j 30 30 20 45 25
M2 D 0, j 0.135 0.139 0.126 0.171 0.146
aj 0.335 0.346 0.348 0.438 0.384

V 0, j 70 20 25 105 55
MH D 0, j 0.102 0.208 0.120 0.122 0.136
aj 0.350 0.454 0.347 0,416 0,446

V 0, j 60 115 40
M4 D 0, j 0.135 0.146 0.150
aj 0.400 0.424 0.420

D.3 Moving flows of people with mH for sections in front of doorways, do not create the flux densities above 0.5. In this case

the estimated maximum value of traffic through hole mobility of different groups should be equal: M1 -19.6 m / min, M2 -
9.7 m / minute, M3 -17.6 m / min, M4 -16.4 m / min.