Академический Документы
Профессиональный Документы
Культура Документы
t s s t 0 l tE t r c T 0
RT E c]H' i l 0 Utri l T E R i l A T t 0 N A L E
(affilide
h l'0rganisation
lnternationale - lS0)
de Normalisation
R E C ( l M M A N I l A T ID
l lE
l {[ A C E I
INTERNATI(lIE
{ AL LE C T R ( l T E C H N ICC( A
l ML M I S S I ( l l ' I
(affiliated
to theInternational
0rganization - lS0)
for Standardization
IECRECtlMMENDATIllII
Publicalion
56-l
Troisidme - Third
6dition edition
1971
v
Disjoncteurs
i courant
alternatif
i haute
lension
partie:
Premiire Gdn6ralilfs
etdflinitions
Hig gealternatin
h-uolta g-currentcircuit-brea
kers
Partl: General
anddefinilions
Droits
dereproduction - Copyright
rdservds - allrights
reserved
Bureau
Central
delaCommission
Electrotechnique
Internationale
l, ruedeVarembd
Oendve,
Suisse
J.
lI
!{
--.1
j=g*e*r*"*r;*r*t
C. D. U./U. D.G. : 621.316.57. O25
c 0 MM l s s l 0 E rl 0
lrElrcTB0TEcHN 1u'ITERNATT0iTALE
(affili6e
h l'0rganisation
lnternationale
deNormalisation - lS0)
E lLt A c E l
f l E C 0 M M A l t 0 A T0l 0
I N T E R N A T I ( l lE
{ AL LE C T R ( l T E C H N C
I C( |AMLM I S S I t l N
(affiliated
lo theInternational - lS0)
for Standardization
0rganization
IECREC(lMMENIlATI(lII
PERPITST.\KAAN
*rynnT
Publication
Troisidme
56-l
- Thirdedition
6dition
1971
ffi;;itry
I,EMFnGnrylariAr""'
TanSSoi
Disjoncteurs
i courant
alternatif
i haute
tension
partie:Gfn6ralit6s
Premiire etddlinitions
High-uoltage
allernating-currsnt
circuit-breakers
Partl: General
anddelinitions
Droits
dereproduction - Copyright
rdserv6s - all rightsreserved
Aucunepartie de cette publicationne peut €tre reproduiteni utilis6esous No part of this publicationmay be reproduced or utilized in any
quelqueforme que ce soit et par aucun procdd6,dlectronique ou m6ca- form or by any means,electronicor mechanical,includingphotocopying
nique,y comprisla photocopie
et les microfilms,
sansI'accord
6critde l'6diteur, and microfilmwithoutpermission
in writingfrom the publisher.
B u r e aCu e n t r d
ael l a C o m m i s s iEolne c t r o t e c h nIinqtueer n a t i o n a l e
1,ruedeVarembd
0endve,
Suisse
PrixFr,s. 31.b0
PriceS,Fr.1'l
-3- PEitPLrsTAri,A"\N
LEMIAGA tffla*SAr,.$t KA'I!.NAGA"4J{
,
CONTENTS
Page
ij,,lr*'oRo 5
P e r rr c e 5
t--:;..:se
SEcrroNOxr - GeNrnar
Scope
Normal service conditions
SEcrroNTwo - DnprNrrIoNS
Publication 56 has beendivided into the following six parts which are published as separatebooklets:
Part L: Generalanddefinitions
FOREWORD
l) The formal decisionsor agreementsof the IEC on technicalmatters,preparedby TechnicalCommitteeson which all the
National Committeeshaving a specialinterest therein are represented,express,as nearly as possible,an international
consensusof opinion on the subjectsdealt with.
2) They have the form of recommendationsfor international use and they are acceptedby the National Committeesin that
sense.
3) In order to promote this international unification, the IEC expressesthe wish that all National Committeeshaving as
yet no national rules, when preparing such rules, should use the IEC recommendationsas the fundamental basis for
theserules in so far as national conditions will permit.
4) The desirabilityis recognizedof extendinginternational agreementon thesemattersthrough an endeavourto harmonize
national standardizationrules with these recommendationsin so far as national conditions will permit. The National
Committeespledge their influencetowards that end.
PREFACE
Part 1: Generalanddefinitions
Scope
This Recommendation applies to a.c. circuit-breakers, designed for indoor and outdoor
installation and for operation at frequenciesup to and including 60 Hz on systemshaving voltages
above 1000 V. It only applies to three-pole circuit-breakers for use in three-phase systems and
single-pole circuit-breakers for use in single-phasesystems.
This Recommendation also applies to the operating devices of circuit-breakers and to their
auxiliary equipment.
This Recommendation applies for the time being to circuit-breakers in exposed installations
only. Rules for circuit-breakersin non-exposedinstallations are under consideration.
The switching of overhead lines, cables and single capacitor banks in normal conditions is
covered, the applicability of tests for these operations being indicated in Sub-clauses15.1, 16.1
andl7.1 of IEC Publication 56-4, Type Tests and Routine Tests. Circuit-breakersfor use with
overhead lines which include seriescapacitors, are not within the scope of this Recommendation.
Note. - Tests to prove the performance when switching overhead lines, cables or single capacitor banks under
fault and other abnormal conditions should be subject to agreement between manufacturer and user.
Such other abnormal conditions are, for instance,caseswhere the voltage is higher than the rated voltage
of the circuit-breaker, conditions which may occur due to sudden loss of load on long lines or cables.
A circuit-breaker with a closing mechanism for dependent manual operation is not covered
by this Recommendation as a rated short-circuit making-current cannot be guaranteed, and such
dependent manual operation may be objectionable becauseof safety considerations.
This Recommendation does not apply to starting switches, contactors, tap-switches and
similar apparatus.
This Recommendation does not take into account the possible effect of pollution.
I
This Recommendation does not necessarilyapply to circuit-breakersfor special conditions
of service,for example, those produced by two earth faults one of which occurs on one side of
the circuit-breaker and the other on another phase on the other side of the circuit-breaker.
a) The ambient air temperature does not exceed40'C and its averagevalue, measuredover a
period of 24 h, does not exceed35'C.
Tlsrr I
c) The altitude does not exceed 1000 m (3300 ft). For installation at altitudes above 1000 m,
the manufacturer should be consulted.
d) The ambient air is not materially polluted by dust, smoke, corrosive or flammable gasesand
vapours, or salts.
f) For outdoor circuit-breakers,the wind pressuredoes not exceed700 N/mz (0.1 lb/inz).
s) Agreement should be reached between manufacturer and user in caseswhere earth tremors
can be expected.
h) For indoor circuit-breakers,the humidity conditions, including the degreeof allowable con-
densation, are under consideration.
11-
A device desisnedto make or break the current in one or more electric circuits.
A switching device designed to close and open one or more electric circuits by means of
separablecontacts.
( M echanical) circuit-breaker
A mechanical switching device, capable of making, carrying and breaking currents under
normal circuit conditions and also making, carrying for a specified time and breaking currents
under specifiedabnormal circuit conditions such as those of short-circuit.
A circuit-breaker suitable for installation in the open air, i.e. capable of withstanding wind,
rain, snow, dirt deposits,condensation,ice and hoar frost.
Exposed installation
Note. - Such installations are usually connectedto underground cable networks. In the case of an installation
connectedto the secondaryside of a transformer the primary of which is in an exposedsituation, the
insulation co-ordination requires specialconsideration.
A system which has no intentional connection to earth except through indicating, measuring,
or protective devices of very high impedance.
l t
l
t
l
t
,
I
t3-
A system earthed through a reactor, the reactance being of such value that during a single
line-to-earth fault, the power frequency inductive current passed by this reactor substantially
neutralizes the power frequency capacitive component of the earth-fault current.
Note-- residual
current
in thefaultislimitedto suchanextent
thatan
YIlffi:i,1X, ni|;:-,r_ffiilfrule
A system in which the neutral is connected to earth, either directly, or through a resistance
or reactanceof low enough value to reduce materially transient oscillations and to ensure a cur-
rent suffi.cientfor selectiveearth-fault protection.
For a given system layout, the ratio, expressedas a percentage,of the highest r.m.s. line-to-
earth power frequency voltage on a sound phase at the location of the circuit-breaker during a
fault to earth (affectingone or more phasesat any point), to the line-toline r.m.s. power frequency
voltage which would be obtained at the same location with the fault removed.
_r.l2 Re-ignition
i.r3 Restrike
A device which indicates, at the location of the circuit-breaker, whether the contacts of the
main circuit are in the open or closed position.
-15-
A device which makes the operation of a circuit-breaker dependent upon the position or
operation of one or more other piecesof equipment.
All the conducting parts of a circuit-breaker included in the circuit which it is designedto
close or open.
All the conducting parts of a circuit-breaker, other than the main circuit, used for controlling
the closing operation or opening operation or both.
3.20 Pole
The portion of a circuit-breaker associated exclusively with one electrically separated con-
ducting path of its main circuit and excluding those portions which provide a meansfor mounting
and operating all poles together.
Note.- A circuit-breaker if it hasonly onepole.If it hasmorethanonepole,it maybe called
is calledsingle-pole
multipole(two-pole,three-pole,etc.)providedthe polesare or canbe coupledin sucha manneras to
operatetogether.
3.2r Closedposition
o The position in which the predetermined continuity of the main circuit is secured.
The position in which the predetermined clearancebetween open contacts in the main circuit
is secured.
3.23 Operation
A successionof operations from one position to another and back to the first position through
all other positions, if any.
Note.- A succession
of operations
not formingan operatingcycleis referredto asan operating
series.
3.25 Operatingsequence
The temperature, determined under prescribed conditions, of the air surrounding the com-
plete circuit-breaker (e.g. for enclosedcircuit-breakers,it is the air outside the enclosure).
The differencebetweenthe temperature of the part and the ambient air temperature.
A bank of shunt capacitors in which the inrush current is limited by the inductance of the
supply system and the capacitance of the bank of capacitors being energized,there being no other
capacitors connected in parallel to the system sufficiently close to increase the inrush current
appreciably.
3.30 Overvoltage
A voltage to earth, expressedas a peak voltage, which is greater than the normal peak voltage
corresponding to the highest system voltage (seeIEC Publication 71, lnsulation Co-ordination,
Clause4).
I. Constructional elements
-1.I Terminal
1.2 Contact
Two or more conductors designedto establish circuit continuity when they touch, and which,
due to their relative motion during operation, open or close a circuit.
A contact included in the main circuit of a circuit-breaker, intended to carry the current of
the main circuit in the closed position.
A control or auxiliary contact which is closed when the main contacts of the circuit-breaker
are closed and open when they are open.
A control or auxiliary contact which is open when the main contacts of the circuit-breaker
are closed and closed when they are open.
2. - Themeans
controllingthe voltagedistributionbetweenunitsmay differfrom unit to unit.
4.tl Release
4.I2 Instantaneousreleqse
* The term "mechanically" implies any link by mechanical, pneumatic or hydraulic means.
- 2 1-
4.13 Making-curuentrelease
A releasewhich permitsa circuit-breakerto open,without any intentionaltime delay,during
a closingoperation,if the making current exceedsa predeterminedvalue,and which is rendered
inoperatiyewhenthe circuit-breakeris in the closedposition.
A release which permits a circuit-breaker to open with or without delay when the voltage
acrossthe terminals of the releasefalls below a predeterminedvalue.
5. Operstion
I'
5.1 Closingoperation
I
a An operationby which the circuit-breakeris brought from the open position to the closed
oosition.
An operation by which the circuit-breaker is brought from the closed position to the open
position.
-23 -
5.3 Auto-reclosing
The operating sequenceof a circuit-breaker whereby, following its opening, it closes auto-
matically after a predetermined time.
An operation executed solely by means of directly applied manual energy, such that the
speedand force of the operation are dependentupon the action of the operator.
An operation by means of energy other than manual, where the completion of the operation
is dependentupon the continuity of the power supply (of solenoids,electric or pneumatic motors,
etc.).
An operation by means of energy stored in the mechanism itself prior to the completion of
the operation and suffi.cientto complete it under predeterminedconditions.
A stored energy operation where the energy originates from manual power, stored and re-
leasedin one continuous operation, such that the speedand force of the operation are independent
of the action of the operator.
A circuit-breaker the moving contacts of which return to and remain in the open position
when the opening operation is initiated after the initiation of the closing operation, even if the
closing command is maintained.
Note.- To ensureproper breakingof the currentwhich may havebeenestablished,
it may be necessary
that the
contactsmomentarilyreachthe closedposition.
A circuit-breaker in which none of the moving contacts can make current if the closing com-
mand is initiated while the conditions which should cause the opening operation remain estab-
lished.
5 . 1I Unit test
A test made on a making or breaking unit or group of units at the making current, or the
breaking current, specified for the test on the complete pole of a circuit-breaker and at the appro-
priate fraction of the applied voltage, or the recovery voltage, specifiedfor the test on the complete
pole of the circuit-breaker
I
l
I
-25 -
I
tI
1
6. Characteristic quantities *
A stated value of any one of the characteristic values that serve to define the working con-
ditions for which the circuit-breaker is designed and built.
Note.- See IEC Publication56-2, High-voltageAlternating-currentCircuit-breakers,
Part 2, Rating, for
individualratedvalues.
The current that would flow in the circuit, if each pole of the circuit-breaker were replaced
by a conductor of negligible impedance.
Note.- Theprospective currentmaybe qualifiedin the samemannerasan actualcurrent,e.g.prospective
break-
ing current,prospective
peakcurrent,etc.
The peak value of the first major loop of the prospective current during the transient period
following initiation.
Note.- The definitionassumes that the currentis madeby an idealcircuit-breaker,i.e. with instantaneousand
simultaneous transitionof its impedanceacrossthe terminalsof eachpolefrom infinityto zero.Thepeak
valuemay differfrom onepole to another;it depends on the instantof currentinitiationrelativeto the
voltagewaveacrossthe terminalsof eachpole.
The prospective peak current when the initiation of current takes place at the instant which
leads to the highest possiblevalue.
Note.- For a polyphase
circuit,the maximumprospective
peakcurrentoccursin onephaseonly.
The peak value of the first major loop of the current in a pole of a circuit-breaker during
the transient period following the initiation of current during a making operation.
Notes/. - The peakvaluemay differfrom onepole to anotherand from oneoperationto anotherasit depends
on the instantof currentinitiationrelativeto the waveof the appliedvoltage.
-
2. Where,for a polyphasecircuit,a singlevalueof (peak)makingcurrentis referredto, this is, unless
otherwisestated,the highestvaluein anyphase.
The peak value of the first major loop of current during the transient period following ini-
tiation.
The current in a pole of a circuit-breaker at the instant of initiation of the arc during a
breaking operation.
Note.- The wayin whichthe breakingcurrentis evaluated
andexpressed
is specified
in IEC Publication56-2.
A making or breaking capacity for which the specified conditions of use and behaviour in-
clude a short-circuit at the terminals of the circuit-breaker.
6 . 1I Short-line fault
A short-circuit on an overhead line at a short, but significant, distance from the terminals
C of the circuit-breaker.
Note.- As a rule this distance
is not morethan a few kilometres.
A making or breaking capacity for which the specified conditions of use and behaviour in-
clude the loss or the lack of synchronism between the parts of an electrical system on either side
of the circuit-breaker.
A breaking capacity for which the specified conditions of use and behaviour include the
opening of an overhead line operating at no load.
A breaking capacity for which the specified conditions of use and behaviour include the
opening of an insulated cable operating at no load.
A breaking capacity for which the specified conditions of use and behaviour include the
opening of a single capacitor bank.
The current which the main circuit of a circuit-breaker is capable of carrying continuously
under specified conditions of use and behaviour.
i
I
I
I
i
:
-29 -
The current that a circuit-breaker ean carry in the closed position during a specifiedshort
time under specifiedconditions of use and behaviour.
The value of peak current that a circuit-breaker can withstand in the closed position under
specifiedconditions of use and behaviour.
The voltage which exists across the terminals of a pole of a circuit-breakerjust before the
making of the current.
The voltage which appearsacrossthe terminals of a pole of a circuit-breaker after the break-
ing of the current.
-
No'|e j:#:Jlxh atransient
voltage
*IJ?:lffiffil,T::Jji1":;1t,,L"-',ffinffi:j?:lT,i"ijiTjillJ
The recovery voltage during the time in which it has a significant transient character.
Notes 1- - The transient voltage may be oscillatory or non-oscillatory or a combination of these depending on
the characteristicsof the circuit and the circuit-breaker.It includes the voltage shift of the neutral of
a polyphasecircuit.
2--The transient recovery voltage in three-phasecircuits is, unless otherwise stated, that acrossthe first
pole to clear becausethis voltage is generallyhigher than that acrosseach of the other two poles.
The recovery voltage after the transient voltage phenomena have subsided.
6.23 Prospective transient recovery voltage (of a circuit, and with respect to a circuit-breaker)
The transient recovery voltage following the breaking of a prospective current without any
direct current component by an ideal circuit-breaker.
Notes 1. - The definition assumesthat the circuit-breakerfor which the prospectivetransient recovery voltage is
sought is replaced by an ideal circuit-breaker,i.e. with instantaneoustransition from zero to infinite
impedanceat the very instant of zeto current (i.e. at the oonatural"current zeto).
2- - For three-phasecircuits, the definition further assumesthat the breaking of the current by the ideal
circuit-breakertakes place only in the first pole to clear.
The ratio between the maximum excursion and the initial value of the line transient voltage
to earth of a phase of an overhead line after the breaking of a short-line fault current.
Note. - The initial value of the transientvoltagecorrespondsto the instant of arc extinction in the pole considered.
I
3 1-
The ratio of the power frequency voltage between a sound phase and the other two phases
during a two-phase short-circuit, which may or may not involve earth, at the location of the
circuit-breaker, to the phase-to-neutral voltage which would be obtained at the same location
with the short-circuit removed.
The values of the impulse withstand voltage and the power frequency withstand voltage,
which together characterize the insulation of the circuit-breaker with regard to its ability to with-
stand the electric stresses.
The r.m.s. value of the sinusoidalalternating voltage at power frequencywhich the insulation
of the circuit-breaker withstands under specifiedtest conditions.
The ratio of the resistanceto the impedance at power frequency of an equivalent circuit
supposedto be formed by an inductance and a resistancein series.
The opening time until separation of the arcing contacts of a circuit-breaker is defined ac-
cording to the type of its opening releaseas stated below and with any time delay device forming
an integral part of the circuit-breaker adjusted to its minimum setting or, if possible, cut out
entirely:
a) For a circuit-breaker tripped by any form of auxiliary power, the opening time is measured
from the instant of application of the auxiliary power to the opening release of the circuit-
breaker when in the closed position, to the instant when the arcing contacts have separated
in all poles.
b) For a circuit-breaker tripped by a current in the main circuit without the aid of any form
of auxiliary power, the opening time is measured from the instant at which, the circuit-
breaker being in the closed position, the current in the main circuit reaches the operating
value of the over-current release,to the instant when the arcing contacts have separated in
all poles.
i
I
L
i
-33 -
f
I 6.35 Make time
The interval of time between the initiation of the closing operation and the instant when the
a
current begins to flow in the main circuit.
i
I Notes /. - The make time includes the operating time of any auxiliary equipment necessaryto close the circuit-
t
breaker and forming an integral part of the circuit-breaker.
ta
2.-For circuit-breakerswhich embody switching resistors,it may be necessaryto make a distinction be-
. tween the make time up to the instant at which current is first establishedthrough the resistorsand the
j make time up to the instant at which the full current is established.
{
6.36 Dead time (during auto-reclosing)
The interval of time between final arc extinction in all poles in the opening operation and the
first re-establishment of current in any pole in the subsequent closing operation.
Note. - For circuit-breakerswhich embody switchingresistors,it may be necessaryto make a distinction between:
a) The dead time which excludesthe time interval betweenthe instants of extinction of main arc and
of resistancecurrent arc and also excludesthe time interval betweenthe instants of establishmentof
resistancecurrent and of full current.
b) The dead times which include one or both of thesetime intervals.
i
d
-35-
I
{
il 6.37 Loop
The part of the wave of the current embraced by two successivecurrent zero crossings.
$
F Note.- A distinctionis madebetweena majorloop and a minor loop depending on the time intervalbetween
*r two successivecurrentzerocrossings
beinglongeror shorterthan the half-periodof the alternatingcom-
F ponentofthe current.
The value of the operating current for which the releaseis adjusted and in accordance with
which its operating conditions are defined.
6.40 Clearance
The distance between two conducting parts along a string stretched the shortest way between
these conducting parts.
6.40.1 Clearancebetweenpoles
The clearance between any conducting parts and any parts which are earthed or intended
to be earthed.
L
-37 -
Ur tension entre les bornes du premier pdle qui tz instant de la disparition des ph6nomdnestransi-
coupe toires de tension dans le dernier pdle qui coupe
voltage acrossthe terminals of the first pole to the instant when the transient voltage phenom-
clear ena have subsidedin the last pole to clear
It courant dans le premier pdle qui coupe 5
tl'
(valeur de crOtedu) courant 6tabli
current in the first pole to clear (peak) making current
Uz, Us tensionsentre les bornes des deux autres pdles courant coup6
voltage across the terminals of the two other breaking current
poles
7.1 valeur de cr€te de la composantep6riodique
Iz, Ia courants dans les deux autres pdles peak value of the alternating component
currents in the two other poles
7.2 composanteap6riodique
C commande de fermeture, par exemple tension
direct current component
aux bornes du d6clencheurde fermeture
closing command, e.g. voltage acrossthe termi- 19 tension appliqu6e
nals of the closing release applied voltage
o commanded'ouverture,par exempletensionaux
20 tension de r6tablissement
bornes du d6clencheurd'ouverture
recovery voltage
openingcommand,e.g. voltage acrossthe termi-
nals of the opening release 2l tension transitoire de rdtablissement
tt instant du d6but de la maneuvre de fermeture transient recoveryvoltage (restriking voltage)
the instant of initiation of the closing operation
30
tensionde r6tablissementir fr6quenceindustrielle
power frequency recovery voltage