Ministry of Interior South Border Housing Project, K.S.A.

ADMINISTRATION BUILDING B02b. MODEL-1.


WATER SUPPLY PIPE SIZING CALCULATIONS.

22 September 2016

Prepared for:

Meinhardt Arabia
P O Box 8089, Riyadh 11482
7th Floor, North Tower
Faisal Foundation - Al Khaiyria Building
King Fahd Highway, Olaya, Riyadh
Kingdom of Saudi Arabia
Tel: +966 112011080
Fax: +966 112011668
www.meinhardtgroup.com
TABLE OF CONTENTS

Project South Borders Security Housing Compound KSA Revision: 00


Model : 1-B02b Date: 22-Sep-16
Job No : 160611.S1 Model-1 Prepared by: M.A

1 TABLE OF CONTENTS

i REFERENCES

2 ABBREVIATION

3 DISTRIBUTION PIPE SIZING

4 FIXTURE COUNT

4a FIXTURE COUNT FOR POTABLE WATER SUPPLY

4b REFERENCE

5 FRICTION LOSS FOR BOOSTER WATER PUMP

REFERENCES

1 SASO - SAUDI ARABIAN STANDARD ORGANIZATION.

2 ANSI - AMERICAN NATIONAL STANDARD INSTITUTE.

3 UPC - UNIFORM PLUMBING CODE.

4 NPC - NATIONAL PLUMBING CODE.

5 UBC - UNIFORM BUILDING CODE.

6 ASTM - AMERICAN SOCIETY FOR TESTING AND MATERIAL.

7 ASHRAE - AMERICAN SOCIETY OF HEATING REFRIGERATION,

AND AIR CONDITIONING ENGINEERS.

8 PRACTICAL PLUMBING DESIGN GUIDE

9 IPC 2012 - INTERNATIONAL PLUMBING CODE.

10 SBC-701 - SAUBI BUILDING CODE SECTION 701.

11 ASPE - AMERICAN SOCIETY OF PLUMBING ENGINEERS

12 NFPA - NATIONAL FIRE PROTECTION ASSOCIATION


ABBREVIATION

Project : South Borders Security Housing Compound KSA Revision: 00


Model :1-B02b Date: 22-Sep-16
Job No : 160611.S1 Model-1 Prepared by: M.A

ABBREVIATIONS :

AF - ABLUTION FAUCET
HB - HOSE BIBB
hwrt - HOT WATER RECOVERY RATE
JS - JANITOR SINK
KS - KITCHEN SINK
LAV - LAVATORY
SHO - SHOWER HEAD
TDH - TOTAL DYNAMIC HEAD
WC - WATER CLOSET

ft - FEET
gals - GALLONS
gph - GALLON PER HOUR
gpm - GALLON PER MINUTE
kg - KILOGRAM
KW - KILOWATT
l/day - LITERS PER DAY
l/min - LITERS PER MINUTE
LPH - LITERS PER HOUR
l/s - LITERS PER SECOND
l/tree/day - LITERS PER TREE PER DAY
l/m2/day - LITERS PER SQUARE METER PER DAY
m - METER
m/s - METER PER SECONDS
m2 - SQUARE METER
m3 - CUBIC METER
m3/day - CUBIC METERS PER DAY
m3/min - CUBIC METERS/MINUTE
3
m /s - CUBIC METERS/SECOND
min - MINUTE
mm - MILLIMETER
pcs - PIECES
psi - POUNDS PER SQUARE INCH
qty - QUANTITY
SEC - SECONDS
WSFU - WATER SUPPLY FIXTURE UNIT
INTERNAL WATER SUPPLY CALCULATIONS

Project : South Borders Security Housing Compound KSA Revision: 00


Site :1-B02b Date: 22-Sep-16
Job No : 160612.S1 Model-1 Prepared by: M.A
Checked by: W.M
REFERENCE
[1] NPC 2006, TABLE B.5.2 WATER SUPPLY FIXTURE UNITS

1
INTERNAL WATER SUPPLY CALCULATIONS

Project : South Borders Security Housing Compound KSA Revision: 00


Site :1-B02b Date: 22-Sep-16
Job No : 160612.S1 Model-1 Prepared by: M.A
Checked by: W.M
REFERENCE
[2] NPC 2006, Table B.5.4

2
INTERNAL WATER SUPPLY CALCULATIONS

Project : South Borders Security Housing Compound KSA Revision: 00


Site :1-B02b Date: 22-Sep-16
Job No : 160612.S1 Model-1 Prepared by: M.A
Checked by: W.M
REFERENCE
[2] NPC 2006, Table B.7.3

3
FIXTURE COUNT

Project : South Borders Security Housing Compound KSA Revision: 00


Model : 1-B02b Date: 22-Sep-16
Job No : 160612.S1 Model-1 Prepared by: M.A

1. Fixture Count:
FLOOR NO. /BLDG WC WC-1 WC-6 Laundary LAV-2 KS Shower/Bathtub PS HB (Roof) SUB-TOTAL
GF B06 (PRELIMANARY BOYS SCHOOL)
Public 0 0 0 0 0 0 0 0 2 2
Private 6 0 0 1 8 2 4 6 0 27
TOTAL 6 0 0 1 8 2 4 6 2 29
`
2. Total Water Supply Fixture Unit 3. Total RAW Water Minimum Required Flow Rate:
(Based on NPC 2006 Table 10.14.2A )
FIXTURES NO WSFU TOTAL From demand load chart, for system based on Flush Tank
WC (Western, Flush Tank, Public, Handicap) 6 x 2.5 15 Refer to NPC 2006 Table 10.14.2B
WC-1 (Western, Flush Tank, Public) 0 x 2.5 0
WC-1 (Western, Flush Tank, Private) 0 x 2.5 0
WC-6 (Eastern, Flush Tank, Public) 0 x 2.5 0 Total WSFU = 50.6 wsfu
WC-6 (Eastern, Flush Tank, Private) 0 x 2.5 0
Laundry 1 x 2.0 2
LAV-2 (Private) 8 x 0.7 5.6 Minimum Require Flow Rate = 29.2 gpm
LAV-2(Public) 0 x 1.0 0
KS (Public) 2 x 1.5 3 = 1.84 L/S
Shower 4 x 2.0 8
PS 6 x 2.0 12
HB 2 x 2.5 5

TOTAL 50.6 `

1
PROJECT: MODEL-1 B02b
BOOSTER PUMP WATER PRESSURE CALCULATION
Head loss calculation using ( 2 ) HAZEN-WILLIAMS Formula

Total heal (DH+GH) / pipe


Local factors of fittings

Accumulative Pressure
ID Pipe Inner diameter

RE Reynolds number
DN Nominal diameter

Loss m per 100 m


C Hazen constant

Total local factors

V Mean Velocity

dh(2) Local loss


dh(1) Liner loss
1.0 discharge outlet
no. part of pipe

0.2 elbow ( 45 leg.)

0.3 elbow ( 90 leg.)

GH Static heal

Loss m per m
0.6 Butterfly valve

DH Total loss
L Pipe length

Q Flow rate

8.0 Globe valve


2.0 check valve
0.2 gate valve

2.0 Strainer
0.5 reducer
0.9 tee
no. DN mm m mm L/S l/s 1/1 m m/s 1/1 1/1 m m m m m m

A-B (From Pump) 50 pvc 42.6 0.5 145 1.84 1.84 1 1 2 1 1 4.2 1.2909 54994.384 0.04317 4.317 0.022 0.357 0.378 0.38 0.3783389
B-C 40 pvc 34 3 145 0.82 0.82 1 1 1.2 0.9032 30707.542 0.02898 2.898 0.087 0.05 0.137 0.14 0.136842
C-D 40 pvc 34 6.4 145 0.41 0.41 2 1 1.5 0.4516 15353.771 0.00803 0.803 0.051 0.016 0.067 0.07 0.066975
D-E 32 pvc 27.2 8.2 145 0.41 0.41 1 3 1 3.5 0.7056 19192.214 0.02381 2.381 0.195 0.089 0.284 0.28 0.2840289
E-F 25 pvc 21.2 1.5 145 0.19 0.19 1 2 2 0.5383 11411.109 0.01929 1.929 0.029 0.03 0.058 0.06 0.0584649
F-G 25 pvc 21.2 1.5 145 0.13 0.13 2 2 1 2.9 0.3683 7807.601 0.00955 0.955 0.014 0.02 0.034 0.03 0.0343741
G-H 20 pvc 17 0.9 145 0.06 0.06 1 1 1 1.4 0.2776 4718.476 0.00732 0.732 0.007 0.005 0.012 0.01 0.0120845

TOTAL 22 2 16.7 0.405 0.566 0.971 0.97

Static head = m
total friction loss = 0.97 m
total dynamic head = 0.97 m

Total dynamic head = 0.97


safety factor 10 % = 0.0971
Minimum pressure required to operate a sanitary fixture = 20 m

Total Head with factor of safety 10 % = 21.06m Say 22 m

Booster Pump required is of 2.2 bar pressure.


T
ILE
TO

KI
TC
HE
ILET N
TO

MATERIAL SPECIFICATION
TO
ILE COLD WATER PIPES uPVC PIPES CLASS-5
T
TO HOT WATER PIPES CPVC PIPES CLASS5
ILE
T

REV DATE ISSUED


00 14/12/2015 ISSUED FOR CONSTRUCTION

LA
UN
DR
Y

TO
ILE
T

CLIENT :

MINISTRY OF INTERIOR
KINGDOM OF SAUDI ARABIA
Planing & Development
Modernization Program

CONSULTANT :
TO
ILE
T

1 LAVATORY 1.0

2 WATER CLOSET 2.5

3 BATH TUB 4.0


CONTRACTOR :

4 SHOWER 4.0

5 KITCHEN SINK 1.5

6 LAUNDARY SINK 2.0

DESIGNER :
PO Box 8089 Riyadh 11482
WATER SUPPLY PIPES ARE UPVC CLASS 5

SOUTH BORDERS SECURITY


HOUSING COMPOUND

COLD & HOT WATER PLUMBING SERVICES ISOMETRIC DIAGRAM B02b-VILLA TYPE-A
MODEL - 1

WATER SERVICES
ISOMETRIC DIAGRAM
BOOSTER WATER PUMP SIZING

Project South Borders Security Housing Compound KSA Revision: 00


Site : 1-B02b Date: 22-Sep-16
Job No 160612.S1 Model-1 Prepared by: M.A

1. Location: Site Pump Room

a. System Capacity

For Cold Water Supply System


The cold water pump is responsible to transfer the cold water from site pump room to all buildings in the site.

Total No. of Fixture for potable Water Supply = 29 fixtures

Water Supply Fixture Unit = 50.6 wsfu

Cold Water Flow Rate (Qw) = 1.84 l/s

b. System's Total Dynamic Head (TDH)

Total Dynamic Head (TDH) = 22.00 m

c. System Requirement

TOTAL SYSTEM CAPACITY = 1.84 l/s Vs 22.00 m

Two Booster Pump One Duty, One Standby

1.84
CAPACITY FOR EACH BOOSTER PUMP = 1.84 l/s Vs 22.00 m

d. Cold Water Pump Motor Power


Pm = qpgh/(3,600,000 x np x nm)
Where:
Pm = Motor Power (kW)
3
q = flow capacity (m /hr)
3 3
p = density of fluid (kg/m ) 1000 kg/m for water
2 2
g= gravity (m/s ) 9.81 m/s
h = head (m)
np = pump efficiency 65% (estimate)
nm = motor efficiency 85% (estimate)

P= 0.72 kW
P= 0.80 kW

CAPACITY FOR EACH PUMP = 1.84 l/s


TOTAL DYNAMIC HEAD (TDH) = 22.00 m
MOTOR POWER = 0.80 kW