Вы находитесь на странице: 1из 35

␣ Collection␣ Technique␣ ..........................................................................

Cahier technique no. 193

MV breaking techniques

S. Théoleyre
"Cahiers Techniques" is a collection of documents intended for engineers
and technicians, people in the industry who are looking for more in-depth
information in order to complement that given in product catalogues.

Furthermore, these "Cahiers Techniques" are often considered as helpful


"tools" for training courses.
They provide knowledge on new technical and technological developments
in the electrotechnical field and electronics. They also provide better
understanding of various phenomena observed in electrical installations,
systems and equipments.
Each "Cahier Technique" provides an in-depth study of a precise subject in
the fields of electrical networks, protection devices, monitoring and control
and industrial automation systems.

The latest publications can be downloaded from the Schneider Electric


internet web site.
Code: http://www.schneider-electric.com
Section: Experts' place

Please contact your Schneider Electric representative if you want either a


"Cahier Technique" or the list of available titles.

The "Cahiers Techniques" collection is part of the Schneider Electric’s


"Collection technique".

Foreword
The author disclaims all responsibility subsequent to incorrect use of
information or diagrams reproduced in this document, and cannot be held
responsible for any errors or oversights, or for the consequences of using
information and diagrams contained in this document.

Reproduction of all or part of a "Cahier Technique" is authorised with the


prior consent of the Scientific and Technical Division. The statement
"Extracted from Schneider Electric "Cahier Technique" no. ....." (please
specify) is compulsory.
no. 193
MV breaking techniques

Serge THEOLEYRE

Dr. Theoleyre joined Schneider Electric in 1984 after having obtained


a Doctorate in Engineering from the “Ecole Nationale Supérieure
d’Ingénieurs Electriciens” in Grenoble in 1983. Initially he took charge
of research and development and then marketing for the Power
Capacitor activity.
Since 1995, he has been responsible for Schneider Electric’s actions
in the fields of standardization and technical communication within
the Transmission and Distribution Business sector (HV/MV).

ECT 193 first issue, June 1999

Cahier Technique Schneider Electric no. 193 / p.1


Lexicon

Breaking Capacity: Re-striking:


A presumed current value that a switching Resumption of current between the contacts of a
device must be capable of breaking under the mechanical switching device during a breaking
recommended conditions of use and behavior. operation, after a quarter cycle after passing to 0
Earthing fault: current.
Fault due to the direct or indirect contact of a Short-circuit:
conductor with the earth or the reduction of its An accidental or intentional connection through a
insulation resistance to earth below a specified resistance or relatively low impedance, of two or
value. more points on a circuit normally existing at
Fault: different voltages.
Accidental modification affecting normal Switching device:
operation. Device intended to establish or interrupt current
Ir: in an electrical circuit.
Rated current corresponding to the rms. value of Switchgear:
the current that the device must be capable of General term applicable to switching devices and
withstanding indefinitely under the recommended their use in combination with control,
conditions of use and operation. measurement, protection, and command devices
Isc: with which they are associated.
Short-circuit current. Time constant for de-ionization:
Time at the end of which arc resistance will have
Overvoltage:
doubled assuming that its rate of variation
Any voltage between a phase conductor and the
remains constant.
earth or two neutral phase conductors where the
peak value exceeds the highest voltage Transient recovery voltage:
acceptable for the equipment. Recovery voltage between the contacts of a
switching device during the time where it
Overvoltage factor:
presents an noticeable transient character.
Ratio between the overvoltages’ peak value and
the peak value of the maximum voltage Ur:
acceptable by the device. Rated voltage corresponding to the rms. value of
Rated value: the voltage that the device must be capable of
Value generally set by the manufacturer for withstanding indefinitely under the recommended
given operating conditions for a component, a conditions of use and operation.
mechanism or piece of equipment.
Re-ignition:
Resumption of current between the contacts of a
mechanical switching device during a breaking
operation, within a quarter cycle after passing to
0 current.

Cahier Technique Schneider Electric no. 193 / p.2


MV breaking techniques

The ability to break current in an electrical circuit is essential in order to


guarantee the safety of people and property in the case of faults, as well as
to control the distribution and use of electrical energy.
The aim of this Cahier Technique is to detail the advantages,
disadvantages and applicational fields of past and present Medium Voltage
breaking techniques.
Having defined the currents to be broken and discussed breaking on a
theoretical level, the author goes on to present breaking in air, oil, and in
SF6, finishing with two comparative tables.
To date, breaking using electrical arcing remains the only viable solution,
whether in SF6 or under vacuum; it requires expertise that this
Cahier Technique invites you to share.

Contents
1 Introduction p. 4
2 Breaking load and fault currents 2.1 Breaking principle p. 6
2.2 Breaking load currents p. 9
2.3 Breaking fault currents p. 13
3 Breaking techniques 3.1 Breaking medium p. 17
3.2 Breaking in air p. 18
3.3 Breaking in oil p. 19
3.4 Breaking under vacuum p. 21
3.5 Breaking in SF6 p. 24
3.6 Comparison of the various techniques p. 29
3.7 What possibilities for other techniques? p. 30
4 Conclusion p. 31
Bibliography p. 32

Cahier Technique Schneider Electric no. 193 / p.3


1 Introduction

Electrical energy is transmitted from the c electrodynamic (fault current),


generating power station to consumer points via c mechanical.
an electrical network (shown in figure 1 ). The most important stresses are those which
It is essential to be able to interrupt the current at occur during transient operation and breaking,
any point in the network in order to operate or which are accompanied by electrical arcing
maintain the network or to protect it when a fault phenomena. Arcing behavior is difficult to predict
occurs. It is also necessary to be able to restore despite current modeling techniques.
current in various normal or fault situations.
In order to choose the devices intended to Experience, know-how and experimentation still
accomplish this task, information on the current play a large part in designing breaking devices.
to break and the field of application is crucial They are called “electromechanical” devices,
(see fig. 2 ). It can fall into one of three since at present static breaking in medium and
categories: high voltage is not technically and economically
viable.
c Load current, which is normally smaller than
the rated current Ir. The rated current, Ir is the Of all of these breaking devices, circuit breakers
rms. value of current that the equipment must be are the most interesting since they are capable
capable of withstanding indefinitely under the of making, withstanding, and breaking currents
recommended conditions of use and operation. under normal and abnormal conditions (short-
circuit). This Cahier Technique will mainly
c Overload current, when the current exceeds its
discuss breaking alternating current using circuit
rated value.
breakers.
c Short-circuit current, when there is a fault on
The voltage range considered is that of Medium
the network. Its value depends on the generator,
Voltage (1 kV - 52 kV), since it is in this voltage
the type of fault and the impedances upstream of
range that the greatest number of breaking
the circuit.
techniques exist. The first part of the document
Furthermore, when opening, closing or in will deal with phenomena occurring during
continuous service the device is subjected to breaking and closing. The second part presents
several stresses: the four most wide-spread types of breaking
c dielectrical (voltage), techniques currently used i.e. breaking in air, oil,
c thermal (normal and fault currents), vacuum and SF6.

EHV HV MV LV
transmission network subtransmission network distribution network distribution network
800 kV - 300 kV 300 kV - 52 kV 52 kV - 1 kV 1 kV - 220 V

Power EHV/HV HV/MV MV/LV


station transformer transformer transformer
substations substations substations

HV MV LV
consumers consumers consumers

Fig. 1 : diagram of an electrical network.

Cahier Technique Schneider Electric no. 193 / p.4


c IEC definition Opening Closing Isolating

c Function

Disconnector c Mechanical connection device yes no no yes no yes v yes


which in an open position
guarantees asatisfactory isolating
distance under specific conditions.
c Intended to guarantee safe
isolation of a circuit, it is often
associated with an earthing switch.

Earthing c Specially designed switch for yes no no yes no yes v no


switch connecting phase conductors to the earth.
c Intended for safety in case of work
on the circuits, it relays the de-energized
active conductors to the earth.

Switch c Mechanical connection device capable yes yes no yes yes yes yes v
of establishing, sustaining and breaking
currents under normal circuit conditions
eventually including overload currents in
service.
c Intended to control circuits (opening
and closing), it is often intended to
perform the insulating function.
In public and private MV distribution
networks it is frequently associated
with fuses.

Contactor c Mechanical connection device with yes yes no yes yes yes no
a single rest position, controlled other
than by hand, capable of establishing,
sustaining and breaking currents under
normal circuit conditions, including
overvoltage conditions in service.
c Intended to function very frequently,
it is mainly used for motor control.

Circuit c Mechanical connection device capable yes yes yes yes yes yes no
breaker of establishing, sustaining and breaking
currents under normal circuit conditions
and under specific abnormal circuit
conditions such as during a short-circuit.
c General purpose connection device.
Apart from controlling the circuits it
guarantees their protection against
electrical faults. It is replacing contactors
in the control of large MV motors.

= at no load = under load = short-circuit v = depending on the case

Fig. 2 : various switching devices, their functions and their applications

Cahier Technique Schneider Electric no. 193 / p.5


2 Breaking load and fault currents

2.1 Breaking principle


An ideal breaking device would be a device c withstanding the overvoltage (Ldi/dt) appearing
capable of breaking current instantaneously. across the terminals of the device and which
However, no mechanical device is capable of would have an infinite value if passing from
breaking current without the help of electrical insulator to conductor occurred in an infinitely
arcing. This phenomenon limits overvoltages and small period of time. This would inevitably lead to
dissipates the electromagnetic energy of the dielectric breakdown.
electrical circuit, but it delays complete breaking Assuming that these problems have been
of the current. eliminated and that perfect synchronization has
been achieved between the natural passing of
The ideal switch
the current to 0 and the device’s insulator-
Theoretically speaking, being able to break conductor transition, there still remains another
current instantaneously, it involves being able to difficult aspect to take into consideration, that of
pass directly from the state of conductor to the transient recovery voltage (TRV).
state of insulator. The resistance of the “ideal”
In fact, just after the current has been
switch must therefore pass immediately from
interrupted, the recovery voltage across the
zero to infinity, (see fig. 3 ).
switch’s terminals joins the network voltage
This device must be capable of: which is at its maximum at this moment for
c absorbing the electromagnetic energy reactive circuits. This occurs without an abrupt
accumulated in the circuit before breaking, i.e. discontinuity due to the parasite capacitances of
1 2
the network. An unsteady state is set up whilst
Li in case of a short-circuit due to the the voltage comes back in line with that of the
2
network. This voltage, called transient recovery
reactive nature of the networks;
voltage (TRV), depends on network
characteristics and the rate of increase (dv/dt) of
this voltage can be considerable (several kV /
R L microsecond). To put it simply this means that to
avoid breaking failure, the ideal switch must be
capable of withstanding several kV less than one
microsecond after the transition from conductor-
e Load insulator.

Breaking using electrical arcing


Two reasons explain the existence of electrical
arcing:
i c It is practically impossible to separate the
contacts exactly at the natural 0 current point
Break
due to the uncertainty in the measurement-order:
for an rms. value of 10 kA, the instantaneous
current 1 ms before 0 is still at 3,000 A. The
instantaneous overvoltage Ldi/dt which would
t
appear across the terminals of the device if it
immediately became insulating would be infinite
R and lead to the immediate breakdown across the
inter-contact gap which is still small.
c Separation of the contacts must be
accomplished at sufficient speed for the
dielectric strength between the contacts to
t remain greater than the transient recovery
Fig. 3 : breaking by an ideal switch. voltage. This requires mechanical energy close
to infinity, that no device can provide in practice.

Cahier Technique Schneider Electric no. 193 / p.6


The electrical arcing breaking process takes t arc
place in three phases : W = ∫t0 Ua idt where t0 is the moment of arc
v the sustained arc phase, initiation and tarc is the moment of breaking.
v the arc extinction phase, In medium voltage and high voltage, it always
v the post-arcing phase. remains well below network voltages and does
c Arc propagation phase not therefore have a limiting effect, except in
particular cases discussed further on. Breaking
Before reaching zero current the two contacts
is therefore near the “natural” zero of the
separate causing dielectric breakdown of the
alternating current.
inter-contact medium. The arc which appears is
made up of a plasma column composed of ions c Arc extinction phase
and electrons from the inter-contact medium or Interrupting of the current corresponding to arc
metal vapor given off by the electrodes extinction is accomplished at zero current on
(see fig. 4 ). This column remains conductive as condition that the medium quickly becomes
long as its temperature is maintained at a insulating again. For this to occur, the channel of
sufficiently high level. The arc is thereby ionized molecules must be broken. The
“sustained” by the energy that it dissipates by the extinction process is accomplished in the
Joule effect. following manner: near zero current, resistance
The voltage which appears between the two to the arc increases according to a curve which
contacts due to the arc’s resistance and the mainly depends on the de-ionization time
surface voltage drops (cathodic and anodic constant in the inter-contact medium (see fig. 5 ).
voltage) is called the arcing voltage (Ua).
Its value, which depends on the nature of the
arc, is influenced by the intensity of the current a R
and by the heat exchange with the medium
(walls, materials, etc.). This heat exchange
Rr
which is radiative, convective and conductive is
characteristic of the device’s cooling capacity.
The arc voltage’s role is vital since the power
dissipated in the device during breaking strongly
depends on it.
Re

Anode
t

b i, u
ur
ion –
e

e
N ue
e
ion +

ir t
ion +

e Post arc
e current

ie
Cathode
Fig. 5 : change in arc resistance [a] current and
voltage [b] during the extinction phase in case of
Fig. 4 : electrical arcing in a gaseous medium. successful breaking (r) or thermal failure (e).

Cahier Technique Schneider Electric no. 193 / p.7


At zero current, this resistance has a value which A circuit breaker must be capable of breaking all
is not infinite and a post-arcing current once currents less than its breaking capacity for all
again crosses the device due to the transient TRVs whose value is less than the rated TRV
recovery voltage which appears across the value.
terminals.
If the power dissipated by the Joule effect exceeds
the characteristic cooling capacity of the device, a U
the medium no longer cools down: thermal
runaway followed by another dielectric breakdown
takes place: resulting in thermal failure.
If on the other hand the increase in voltage does
not exceed a certain critical value, the arc’s
resistance can increase sufficiently quickly so
that the power dissipated into the medium
remains less than the cooling capacity of the
device thereby avoiding thermal runaway.
c Post-arcing phase
In order for breaking to be successful, it is also 0 t
necessary for the rate of dielectric recovery to be
much quicker than that of the TRV (see fig. 6 )
b U
otherwise dielectric breakdown occurs.
At the moment when dielectric failure occurs, the
medium once again becomes conductive,
generating transient phenomena which will be
looked at in more detail further on.
These post-breaking dielectric failures are called:
v re-ignition if it takes place within the quarter of
a period following the zero current,
v re-striking if it takes place afterwards.
c TRV in the standards
Even though the rate of increase of TRV has a 0 t
fundamental impact of on the breaking capacities
of devices, this value cannot be precisely Recovery voltage
determined for all network configurations.
Standard IEC 60056 defines a TRV range for Dielectric regeneration curves
each rated voltage corresponding to the
requirements normally encountered (see fig. 7 ). Recovery voltage if no restriking
The breaking capacity of a circuit breaker is
therefore defined as: the highest current that it Recovery voltage with restriking
can break at its rated voltage with the Fig. 6 : dielectric recovery curves:
corresponding rated TRV. successful breaking [a] or dielectric failure [b].

UTRV

UC
Rated voltage 7.2 12 17.5 24 36 52
(Ur in kV)
Peak TRV value 12.3 20.6 30 41 62 89
(Uc in kV)
Time t3 (in µs) 52 60 72 88 108 132
Rate of increase 0.24 0.34 0.42 0.47 0.57 0.68
(Uc / t3)
t3 t
Fig. 7 : rated transient recovery voltage in the case of a short-circuit across the terminals of a circuit breaker
(§ 4.102 IEC standard 60056).

Cahier Technique Schneider Electric no. 193 / p.8


2.2 Breaking load currents
Under normal operation, in MV, circuit breaking arc instability and an oscillating phenomena
occurs: occurs which is “seen” by the breaking device
c with a load current from a few to a few hundred and the inductances (see fig. 9 and fig. 10 ).
amperes, a low value relative to the short-circuit During this high frequency oscillation (of around
current (from 10 to 50 kA); 1 MHz) passing to zero current is possible and
the circuit breaker can interrupt the current
c with a power factor greater than or equal to
before it passes to its natural zero at the
0.8. The phase shift between the electrical circuit
industrial frequency (50 Hz).
voltage and the current is small and the
minimum voltage occurs around the current’s
minimum (highly resistant circuit).
The voltage across the terminals of the breaking Ua U
L
device is established while network voltage is
practically without any transient phenomena
(see fig. 8 ).
Under such conditions, breaking generally L1 C1 U1 U2 C2 L2
occurs without any problems since the device is
dimensioned for high currents in quadrature with
the voltage.
L1 , C1 = upstream inductance and capacity
Breaking inductive currents (supply source),
c Current chopping L2 , C2 = downstream inductance and capacity
Breaking inductive currents can give rise to (transformer primary),
overvoltages caused by early breaking of the L = connection inductance downstream of circuit
current, otherwise known as “current chopping” breaker D (busbars or cables).
phenomena. Fig. 9 : diagram of the circuit on breaking a low
For low inductive currents (from a few amperes inductive current.
to a several dozens of amperes), the cooling
capacity of the devices dimensioned for the
short-circuit current is much higher in relation to i
the energy dissipated in the arc. This leads to

U (between contacts)

a100 V i

i ii
ia

Natural t
t current zero
Arc period

i = current in the circuit breaker,


Separation Effective current ii = current value leading to instability,
of contacts breaking ia = chopped current value.

Fig. 8 : there are very few transient phenomena during Fig. 10 : high frequency oscillating phenomena or
the breaking of a resistive load current. “current chopping” on breaking an inductive current.

Cahier Technique Schneider Electric no. 193 / p.9


This phenomenon, called “current chopping”, is On the supply side, the voltage value is equal to
accompanied by a transient overvoltage mainly the value of the chopping voltage tending
due to the oscillatory state which is set up on the towards the network voltage, Un with an
load side (see fig. 11 ). oscillating state depending on C1 and L1. The
The maximum value of the overvoltage (UCmax) voltage value between the contacts of the circuit
on the load side is given by the following breaker is equal to the difference between these
equation: two voltages.
These equations clearly show the influence of
 η L i2 
2
UCmax = ua2 +  m 2 a  the network’s characteristics, bearing in mind
 C2  that the chopping current depends strongly on
C1 and on the concerned device.
in which:
ua = chopping voltage, c Re-ignition
ia = chopping current, Another phenomena can lead to high
ηm = magnetic efficiency. overvoltages. It is re-ignition during opening.
Generally speaking, re-ignition is inevitable for
short arcing periods since the distance between
Current to be interrupted contacts is not sufficient to withstand the voltage
which appears across the terminals of the
device. This is the case each time an arc appears
just before the current passes to natural zero.
The voltage on the load side rejoins the voltage
on the supply side with an unsteady state
oscillating at high frequency (around 1 MHz).
t The peak value of the oscillation, determined by
the load voltage of the downstream parasite
capacitances is therefore twice the preceding
Load voltage value.
Source voltage If the circuit breaker is capable of breaking high
frequency currents, it will manage to break the
current the first time it passes to zero a few
microseconds after re-ignition. Re-ignition is very
likely to reoccur due to the increase in the
amplitude of oscillation and the phenomena is
repeated causing an escalation in voltage which
t can be dangerous for the load
(see Cahier Technique no. 143).
It should be noted that the same phenomena
appears during device closure: it causes pre-
striking when the contacts are brought
sufficiently close together. As in cases of
successive re-ignition, the stored energy
Voltage across the increases at each breaking attempt but the
circuit-breaker terminals voltage increase is limited by the bringing
Source voltage
together of the contacts.
c Field of application
In Medium Voltage this involves the magnetizing
currents of transformers under no load or low
load, motors and shunt inductances.
t
v Transformers under no load or low load
Transformers can be operated under low load
conditions (e.g. at night) for network
management requirements. The currents
corresponding to their magnetizing currents vary
from a few amperes to several dozens of
amperes and their chopping factor can be very
high. However, even if the current is chopped at
Fig. 11 : voltage and current curves at the time of its peak value, the possible overvoltage factors
breaking low inductive currents. are generally low taking into account the
capacitances and the inductances involved.

Cahier Technique Schneider Electric no. 193 / p.10


In overhead distribution, the risk related to the interrupts the current, the voltage across the
appearance of overvoltage current is even lower terminals of the generator is at its maximum
since it is limited by lightning arrestors. since the current and the voltage are out of
Furthermore, standards relating to transformers phase by π/2; since the capacitor remains
define impulse wave tests which confirm their charged at this value after current breaking, the
capacity to withstand operational overvoltages. voltage across the terminals of the switch,
v Shunt inductances initially at 0, slowly increases without TRV and
with a derivative in relation to time (dv/dt) equal
These inductances are used to compensate for
to zero at the origin.
the reactive component of the lines or to avoid
increases in voltage on very long lines with low c On the other hand re-striking problems are
loads. They are most often used in HV but can difficult. In fact, after a 1/2-period, the network
also be used in MV. voltage is reversed and the voltage across the
Breaking overvoltages generally remain below terminals of the switch reaches twice the peak
an overvoltage factor of 2.5 due to the value. The risk of re-striking between the
impedances involved. If there is a risk that the contacts is therefore increased and this is
breaking overvoltage will exceed this limit, proportional to the slowness of opening.
lightning arrestors and breaking resistors are If there is re-striking at peak voltage, the
connected in parallel with the circuit breaker. capacitor is discharged in the circuit’s inductance
creating an oscillating current with a peak
v Motors voltage of 3 (see fig. 12 ). If breaking is effective
Stator and rotor windings of motors are so that at the following zero current, the capacitor
the current absorbed under no load conditions by remains charged at a voltage of 3.
these motors as well as the start-up currents are
basically inductive. Given the great number of
switching operations, overvoltages occur very u
L
often and can become critical because of the
progressive deterioration in the insulation that
they engender, in particular if opening occurs I
during the start-up phases. Ua Ub
As a general rule, circuit breakers must be e C C
chosen that do not re-strike or that have a low
probability of re-striking. Otherwise, R-C systems
can also be placed across the motor’s terminals
in order to deviate high frequency transient
currents or ZnO type voltage limiting systems. Ub Current
c Breaking inductive currents and the standards. Peak oscillations
International standards do not exist regarding the voltage
breaking of inductive currents, however IEC
technical report 61233 stipulates tests for circuit
breakers used to supply the motors and shunt I Ua
inductances.
v Motors
For circuit breakers with rated voltages between
1 kV and 17.5 kV, a standardized circuit
simulating a blocked motor is specified for
laboratory tests.
v Shunt inductances Voltage
oscillations
They are not very wide-spread in MV,
Current after
nevertheless, they are sometimes used in 36 kV. restriking
The tests carried out in a laboratory are solely
Ub after
defined for three phase circuits with a rated
restriking
voltage greater than 12 kV.

Breaking capacitive currents -3 peak voltage


Breaking capacitive currents can cause to Fig. 12 : diagram of a circuit with a capacitive load:
overvoltages due to re-striking during the voltage during breaking if the circuit breaker does not open
recovery phase. quickly enough, successive re-striking can cause
c In theory, capacitive currents can be broken dangerous overvoltages for the load.
without any difficulty. In fact, when the device

Cahier Technique Schneider Electric no. 193 / p.11


When voltage “e” is once again reversed, the
peak voltage across the terminals of the switch L0 L
becomes equal to 5. The overvoltage can
therefore lead to re-striking again. The
phenomena can continue with a voltage across
the terminals of the switch capable of reaching
values of 7, 9, etc. e C
For all re-striking occurring 1/4 of the period
following zero current, an “escalation of voltage”
can be observed which can lead to unacceptable
peak values for loads.
On the other hand re-striking, which occurs SA
depending on the breaking device’s dimensions, Network voltage (upstream
overvoltage)
is tolerable: the oscillating voltage across the
terminals of the capacitor remains at an absolute
value less than the peak value of the generator’s
voltage, which does not represent any particular
danger for the devices.
As a reminder, capacitor overvoltage testing is
performed at 2.25 times the rated voltage value.
SB
Dielectric recovery of the inter-contact medium
(downstream
must therefore be sufficiently quick for no re- overvoltage)
striking to occur after the quarter period.
Capacitor voltage
c Making capacitive currents and pre-striking
When closing the control device supplying
capacitive loads, phenomena specific to
capacitive circuits are produced.
Thus, energizing a capacitor bank causes a high
Ip
overcurrent at high frequency (see fig. 13 ) for (peak closing
which the peak magnitude is given by the current)
equation:
U 2 C Capacitor current
Ip =
3 L0 + L
where
L0 = upstream network inductance fe (oscillating
L = capacitor bank link inductances, generally frequency)
low in relation to L0. Fig. 13 : shapes of voltage and current (pre-strike
overvoltage) during the coupling of a single stage
In the case of multi-stage banks, the phenomena
capacitor to the network.
is even more accentuated by the presence of the
energy stored in the already energized
capacitors: the transient currents can reach The aforementioned equation becomes:
several hundreds of times the rated current with
frequencies of several kHz due to the low values U 2 C n
Ip =
of link inductance between stages of the banks. 3 L n +1
During pre-striking at the breaking device where
contacts (ignition of a conductive arc before the n = number of capacitor bank stages with a
contacts join) these high transient currents cause value of C.
early erosion of the breaking device contacts and L = limiting inductances (impulse impedances),
eventually weld them. Limiting inductances higher in relation to L0.
(impulse impedances) are series connected with Note that devices adapted to this application
the bank in order to limit these phenomena. exist and must be specified.

Cahier Technique Schneider Electric no. 193 / p.12


c Fields of application protect cables which may have no load. Its
Capacitive currents mainly have two origins: application is not mandatory and it is considered
cables and lines, and capacitor banks. inappropriate for voltages less than 24 kV.
v Cables and lines Regarding the rated breaking capacity of lines
under no load, the specification is limited to
This involves load currents in no-load cables and
devices with a rated voltage of 72 kV.
long overhead lines (compensated or not). In a
number of European countries (especially No value has been specified for capacitor banks.
countries in Southern Europe, France, Italy, IEC 60056 also specifies switching tests
Spain, etc.), MV overhead networks are long and (see fig. 14 ) for protection and control devices
therefore particularly sensitive to atmospheric under capacitive current conditions for lines and
overvoltages meaning a high amount of tripping cables under no load and for single stage
occurs on these lines… therefore a lot of re- capacitor banks but does not specify anything for
striking. long lines nor for banks of filters.
v Capacitor banks Standards for capacitive current applications are
tending to develop towards the definition of
Capacitor banks are series connected to the
devices with a low probability of re-striking
networks and are used to compensate for the
together with a broader specification of values
lines’ reactive energy (transmission network) and
and a higher number of switching operations in
loads (MV/LV). They enable the transmitted
order to guarantee their suitability to the
active power to be increased and line losses to
application.
be reduced. They can be:
- used alone in the case of low compensation
and a stable load,
Testing Isc of the supply Testing
- staggered (multiple or divided). This type of duty circuit as a function current
bank is widely used by major industries (high of circuit breaker’s (% of rated
installed power) and by utilities companies. It is breaking capacity Icapa)
associated with an automatic control and the (Isc / Breaking
number of operations can be high (several capacity) x100
operations per day): devices capable of
withstanding a suitable number of operations 1 < 10 20 to 40
should be specified. 2 < 10 > 100

c Breaking capacitive currents and the 3 100 20 to 40


standards 4 100 >100
The current IEC standard 60056 (4th edition, Fig. 14 : testing specified by IEC 60056 for capacitive
1987) gives values, for all voltages, of the rated currents.
breaking capacity of circuit breakers used to

2.3 Breaking fault currents


In the case of a short circuit, the phase shift c an extinction phase,
between the current and the voltage is always c a recovery phase.
very large (0.07 i cosϕ i 0.15), since networks are
basically inductive. When the current passes to 0, Short-circuit currents
network voltage is at, or almost at, its maximum. c The various fault types
In MV, short-circuit current reaches values of a (see Cahier Technique no. 158)
few tens of thousands of amperes. Among the various types of faults (three-phase,
Consequently, breaking takes place without two phase, single phase and earthing), the most
current chopping since the arc is very stable. As frequent fault is the single phase earthing fault
for load currents, arcing can be broken down into (80% of short-circuits). It is generally caused by
three phases: phase-earth insulation faults following over-
c a sustained arc phase till passing through zero voltages of atmospheric origin, due to broken or
current, faulty insulation or due to civil engineering works.

Cahier Technique Schneider Electric no. 193 / p.13


Three-phase short-circuits are rare (5% of the c Shape of the short-circuit current plot
cases) but serve as a test reference since the The intensity of the current corresponding to the
short-circuit current and the TRV are higher than transient period during a short-circuit is the sum
in single phase or two phase faults. of two components, one symmetric or periodical
Calculation of the fault current requires (ia) and the other asymmetric or continuous (ic)
information on the network’s characteristics and (see fig. 16 ).
the neutral arrangement (insulated, directly
earthed or impedant neutral). Methods of
calculating have been developed and
X1 X2
standardized (IEC 60909). Currently, calculation
through computer simulation is fairly wide-spread,
and all Schneider departments have developed
software which they have at their disposal
e1 Iscfeeders e2
enabling them to obtain very reliable results.
c Fault location
v Faults on the circuit breaker’s downstream
terminals X1 Isccoupling X2
It is under these conditions that short-circuit
current is greatest since it is only limited by the
impedances situated upstream of the device.
Even though this type of fault is quite rare, it is e1 e2
the one that is chosen for MV circuit breaker
specifications.
v Line faults
with e1 = e2 = e and X1 = X2 = X
This type of fault is more common than the
e e 2e
previous type in overhead networks, but in MV, Iscfeeder = + =
circuit breaker arcing characteristics and circuit X X X
breaker/ cable / line connections mean that the 2e e
Isccoupling = =
stresses generated are less than those caused 2X X
by a short-circuit across the terminals. There are Fig. 15 : breaking under out-of-phase conditions
therefore no specific tests for MV circuit breakers. during the coupling of two generators which are out
In HV, this type of short-circuit requires specific of synchronization.
tests for near-by faults since wave reflection
phenomena cause extremely damaging TRVs.
v Phase opposition type coupling (see fig. 15 ) i
This is a special short-circuit scenario occurring
when two unsynchronized generators are
coupled.
When the two generators are out of
synchronization, the voltage across the terminals
of the coupling circuit breaker is equal to the sum
of the voltages of each generator. The current ia
which the circuit breaker must break can reach
half the value of the current corresponding to a ic
short-circuit at the point of coupling. The t
maximum is then attained during phase
opposition type coupling.
IEC standard 60056 (§4.106) in this case requires
that the device must be capable of breaking 25% Fig. 16 : during a short-circuit the current is the sum of
of the fault current across the terminals at a the two components, one symmetric or periodical (ia)
voltage of 2.5 times the voltage to earth, and the other asymmetric or continuous (ic).
covering the values encountered in practice.

Cahier Technique Schneider Electric no. 193 / p.14


The symmetric component (ia) is created by the The device must be capable of breaking all
alternating source which supplies the short- short-circuit currents with a periodic component
circuit current. less than its breaking capacity and a certain
The continuous component (ic) is created by the percentage of the aperiodic components that do
electromagnetic energy stored in the inductance not exceed the defined value.
at the time of the short-circuit. Its value at the According to the type of device, some fault
moment of the fault is opposite and equal to that currents less than the breaking capacity can
of the symmetric component to ensure the prove difficult to break. They cause long arcing
continuity of current. It decreases with a time times with risks of non-breaking.
constant L/R, characteristic of the network, for c Three phase breaking
which the standardized value is 45 ms, resulting
in the following equation: Due to the phase shift of three phase currents,
breaking occurs in the following manner:
ia = I sin(ωt + θ)
v The circuit breaker breaks the current in the
ic = - I sinθ e(-t/(L/R)) first phase (phase 1 in figure 17 ) in which the
I = maximum intensity = E/Zcc current passes to zero.
θ = electrical angle which characterizes the time The arrangement becomes two-phased and
between the initial moment of the fault and the everything occurs as if point N is shifted to N’.
beginning of the current wave. The voltage established in the first phase, across
Two extreme cases: the terminals of the open AA’ contact, is that
v The short-circuit occurs at the moment at already existing between A and N’, it therefore
which voltage (e) passes to 0. The symmetric equals:
component and the continuous component are at UAA’ = kV = kUr / e
their maximum value. This state is called fully k is the factor of the first pole. Its value varies
asymmetrical. from 1 to 1.5 depending on whether the neutral
v The initial moment of the short-circuit coincides is directly earthed or perfectly insulated.
with the 0 point of the current’s alternating v 1/2 a period later each of the other two phases
component: the continuous component is zero pass to zero, the circuit breaker breaks and the
and this state is called symmetrical. network becomes stable again in relation to the
neutral point.
Breaking capacity The TRV therefore depends on the neutral
Short-circuit breaking capacity is defined as the arrangement. The standard specifies the chosen
highest current that a device can break under its values for the tests taking a value of 1.5 for MV
rated voltage in a circuit in which the TRV meets in insulated neutral type networks and a value of
a specific specification. 1.3 for other cases.

1 A A'
1 A

3 B B' Ur / e
Ur N 1.5 Ur / e
N

3
2 C C'
2 N'
A', B, B', C, C'

Fig. 17 : voltage UAA’ withstood by the first pole which opens in a three phase device.

Cahier Technique Schneider Electric no. 193 / p.15


c Closing of a circuit breaker under a fault standardized exponential decay is 45 ms.
current Other greater values are currently under
Since faults are often spurious, it is common research in certain particular cases.
practice under normal operation to reclose the Short-circuit breaking tests are carried out at
circuit breaker after interrupting a fault current. defined TRV values, for current values of 10, 30,
However some faults are permanent and the 60 and 100% breaking capacity according to the
circuit breaker must be able to restore the short- table in figure 18 .
circuit current. The rated switching operation sequence is
Closure accompanied by pre-striking causes a defined as follows, apart from in special
high gradient voltage wave in which the current’s circumstances:
peak can reach 2.5 Isc, supposing complete v for devices without quick automatic reclosing:
asymmetry, a time constant of 45 ms at 50 Hz O - 3 mn - CO - 3 mn - CO
and no phase shift between the poles. A closing
or
capacity is therefore required for circuit breakers.
CO - 15 s - CO,
c Standardized breaking capacity
v for devices intended for quick automatic
Circuit breaker compliance with standards reclosing:
notably shows their ability to break all currents O – 0.3 s - CO - 3 mn - CO.
up to the rated breaking current, including the
so-called critical currents. with:
IEC Standard 60056 (4.104) requires a series of O = opening operation,
tests enabling the validation of the device’s CO = closing operation immediately followed by
breaking capacity and the verification of its an opening operation.
capability in terms of repeated opening and
closing switching operations.
The rated breaking capacity is characterized by Testing % de Ia % de Ic
two values. duty (symmetric (asymmetric
v The rms. value of the periodic component, component) component)
generally called breaking capacity 1 10 < 20
The standardized values of the rated breaking 2 30 < 20
capacity are taken from the Renard series (6.3, 8,
3 60 < 20
10, 12.5, 16, 20, 25, 31.5, 40, 50, 63, 80, 100 kA),
knowing that in practice short-circuit currents 4 100 < 20
have values between 12.5 kA and 50 kA in MV. 5* 100 according to the
v The asymmetric component percentage standardized
decay curve
This corresponds to the value attained at the end
of a period τ equal to the minimal duration of *: for circuit breakers with a time τ less than 80 ms.
circuit breaker opening, to which is added a half- Fig. 18 : defined values of TRV for short circuit
period of the rated frequency for devices with breaking testing of circuit breakers.
auxiliary sources. The time constant for

Cahier Technique Schneider Electric no. 193 / p.16


3 Breaking techniques

In order to break load or fault currents, mediums: air, oil, vacuum and SF6. While
manufacturers have developed and perfected breaking in air or oil is tending to disappear, the
breaking devices, and in particular circuit same cannot be said for breaking under vacuum
breakers and contactors, using various breaking or in SF6, the “champion” of medium voltage.

3.1 Breaking medium


The preceding chapter described how successful This insulating quality is measured by the
breaking occurs when: dielectric strength between the contacts which
c the power dissipated in arcing through the depends on the gas pressure and the distance
Joule effect remains less than cooling capacity of between the electrodes. The Paschen curve
the device, (see fig. 20 and 21 ), which gives the breakdown
c the de-ionization rate of the medium is high, voltage as a function of the inter-electrode
c and the inter-contact space has sufficient distance and the pressure, enables three zones
dielectric strength. to be determined according to gas pressure.
The choice of breaking medium is therefore an
important consideration in designing a device. In
fact this medium must: Vs (V)
c have high thermal conductivity, and especially 106

in the extinction phase to remove the arc’s


thermal energy,
105
c recover its dielectric properties as soon as
possible in order to avoid spurious re-striking
104
( figure 19 shows the special properties of SF6
in this regard), 103
c at high temperatures, it must be a good
electrical conductor to reduce arc resistance thus 102 pds
the energy to be dissipated, (bar.cm)
-5 -4 -3 -2 -1
c at low temperatures, it must be a good electrical 10 10 10 10 10 1 10
insulator to make it easier to restore the voltage. Fig. 20 : change in the dielectric strength of air as a
function of the pressure, in a slightly heterogeneous
field (Paschen curves).
θ (µs) Air
150 Voltage in kV
He
100 Ar 300
H2 SF6 at 5 bars
250
50 CO2 Oil (hydrogen)
Vacuum
200
ρ (bar)
0 5 10 15 150
θ (µs)
SF6 at 1 bar
100
0.50
0.25 SF6
50
ρ (bar)
Air at 1 bar
0 5 10 15 0
ρ pressure 0 10 20 30
θ deionization time constant Distance between electrode in mm
Fig. 19 : deionization time constants as a function of Fig. 21 : influence of inter-electrode gap on dielectric
the pressure of various gases. strength.

Cahier Technique Schneider Electric no. 193 / p.17


1- The high pressure zone called the
“atmospheric state” in which the dielectric
strength is proportional to the gas pressure and Voltage
(kV)
the inter-contact distance.
800
2- The low pressure zone in which dielectric
strength reaches a true minimum between 200
and 600 V depending on the gas used (Paschen 220
minimum). It is reached at a determined value of
the product of the pressure and the inter-contact
distance at around 10 2 mbar.cm.
3- The vacuum zone in which breakdown voltage
only depends on the inter-contact gap and 36
contact surface condition. Conductivity is
provided by the electrons and the atoms pulled 24
off of the contacts under vacuum and in a gas by
the quick ionization of the gas’ molecules. 12

These curves highlight the performances that are 3


possible as a function of the breaking medium:
air at atmospheric pressure or high pressure, Air Compressed Oil Vacuum SF6
air
hydrogen produced by the decomposition of oil,
vacuum or SF6. Figure 22 shows the voltage Fig. 22 : types of breaking devices used according to
ranges in which each of these techniques is voltage values.
currently used.

3.2 Breaking in air


Devices breaking in air at atmospheric pressure
were the first to be used (magnetic circuit
breakers).
Despite its relatively weak dielectric strength and
its high de-ionization time constant (10 ms), air
at atmospheric pressure can be used to break
voltages up to around 20 kV.
For this it is necessary to have sufficient cooling
capacity and a high arcing voltage after the
current passes to zero in order to avoid thermal
runaway.

The air breaking mechanism


The principle involves maintaining a short arc as
long as the intensity is high in order to limit the
dissipated energy, then lengthening it just as the
current nears zero.
This principle has led to the creation of a Fig. 23 : lengthening of an electrical arc between
breaking chamber for each pole of the device. ceramic refractory panels in a breaking chamber of an
The breaking chamber, situated around the inter- air breaking circuit breaker (Solénarc type Circuit
contact space is made up of a volume divided by Breaker - Merlin Gerin Brand).
refractory panels (panels with a high specific
heat capacity) (see fig. 23 ) which the arc
stretches between. until its arcing voltage becomes greater than that
In practice, when the current decreases, the arc, of the network. The arcing resistance therefore
which is subjected to electromagnetic forces, greatly increases. The energy which is provided
penetrates between these panels. It lengthens by the network then remains less than the
and cools on contact with the refractory material cooling capacity and breaking takes place.

Cahier Technique Schneider Electric no. 193 / p.18


Due to the high deionization time constant for In Solenarc type devices, the extreme length of
this technology, the arcing energy to be the arc (several meters at 24 kV) is achieved in a
dissipated remains high. However, the risk of reasonable volume thanks to the development of
overvoltage at breaking is virtually non-existent the arc in the form of a solenoid. Taking into
(see fig. 24 ). account the required rate of opening of the
contacts, (i.e. a few m/s), the operating energy is
Main characteristics of an air breaking device of the order of a few hundreds of Joules.
The dimensions of the breaking chamber are
mainly defined by the network short-circuit power Fields of application for breaking in air
(in MVA). This type of device was commonly used in all
applications but it remains limited to use with
voltages of less than 24 kV. For higher voltages,
compressed air is used to improve dielectric
Ideal Air breaking strength, cooling and deionization rate. The arc
i,u i,u is therefore cooled by high pressure puffer
systems (between 20 and 40 bars). This
technique has been used for high performance
i r circuit breakers or for higher voltages (up to
r 800 kV).
i
The air breaking technique at atmospheric
pressure is universally used in LV due to its
simplicity, its endurance, its absence of
0 0 overvoltage and the limiting effect obtained by
u
R R the lengthening of the relatively high voltage arc.
In MV other techniques have taken its place
u since breaking in air has several disadvantages:
c size of device (greater dimensions due to
E E length of arc),
c breaking capacity influenced by the presence
t t of metal partitions of the cubicle containing the
0 0
device and air humidity,
c cost and noise.
Fig. 24 : behavior comparison between an ideal device
and an air breaking device. MV circuit breakers using air breaking are
practically no longer manufactured today.

3.3 Breaking in oil


Oil, which was already used as an insulator, has methane (≈10%) and free carbon. An arcing
been used since the beginning of the century as energy of 100 kJ produces approximately
a breaking medium because it enables relatively 10 liters of gas. This gas forms a bubble which,
simple and economic devices to be designed. Oil because of the inertia of the oil’s mass, is
circuit breakers are mainly used for voltages subjected during breaking to a dynamic pressure
from 5 to 150 kV. which can reach 50 to 100 bars. When the
current passes to 0, the gas expands and blows
The principle on the arc which is extinguished.
The hydrogen obtained by the cracking of the oil
molecules serves as the extinction medium. It is The various types of oil breaking
a good extinguishing agent due to its thermal technologies
properties and its deionization time constant c High volume oil circuit breakers
which is better than air, especially at high In the first devices using oil, the arc developed
pressures. freely between the contacts creating unconfined
The contacts are immersed in a dielectric oil. On gas bubbles. In order to avoid re-striking
separation, the arc causes the oil to break down between phases or the terminals and earth,
releasing hydrogen (≈70%), ethylene (≈20%) these bubbles must not in any case reach the

Cahier Technique Schneider Electric no. 193 / p.19


tank or join together (see fig. 25 ). These successive set of chambers, then it expands
devices can consequently be extremely large. through a duct in the arcing zone when the
In addition to their cumbersome size, these current passes to 0. The latter is therefore
devices have numerous disadvantages such as energetically swept, thus restoring the inter-
the lack of safety due to the hydrogen produced contact dielectric properties.
which accumulates under the lid and the high v Impact of the current value on breaking
level of maintenance necessary to monitor the capacity
purity of the oil and maintain its dielectric For large currents, the quantity of hydrogen
properties. produced and the corresponding pressure
To eliminate these disadvantages (hazards, increases are very high. In consequence the
large devices), manufacturers have developed minimum arcing times are short.
low oil volume circuit breakers. On the other hand, for small currents the
c Low oil volume circuit breakers pressure increases are slight and the arcing time
The arc and the bubble are confined in an is long. This arcing time increases up to a critical
insulating breaking chamber. The gas pressure level where it becomes difficult to accomplish
increases as the arc passes through a breaking. Complementary puffer mechanisms at
the end of the sequence can improve this point.
v Main characteristics of low oil volume circuit
breakers
Short-circuit current or rated current values
require the mobile contact to have a minimal
diameter. The length of the breaking chamber
and the travel of the mobile components are
practically proportional to the applied voltage.
To avoid excessive pressure, the minimum
arcing time to break a high current must be less
than 10 ms and it must remain less than 40 ms
for critical currents.
The insulating enclosure of the breaking
chamber must also be designed to withstand the
much higher pressure caused by consecutive
faults, since the reduction of pressure requires
approximately one second.
However, despite the reduction in the volume of
oil, this technique still has certain drawbacks:
- Oil breakdown is not reversible.
- Oil breakdown and contact wear deteriorate
dielectric strength thus causing supplementary
maintenance costs.
- In the case of quick reclosing the pole remains
at a high pressure and its breaking capacity is
reduced.
- The risk of explosion and fire is not completely
eliminated.

Fields of application for breaking in oil


This breaking technique has been widely used in
electrical energy transmission and distribution. It
is progressively being replaced by vacuum and
SF6 breaking techniques which do not have any
Fig. 25 : cross sectional diagram of high oil volume
of the disadvantages detailed in the preceding
circuit breakers.
paragraphs.

Cahier Technique Schneider Electric no. 193 / p.20


3.4 Breaking under vacuum
The dielectric properties of vacuum have been discussed where this column is mainly made up
known for a long time and have been used e.g. of inter-contact gas ionized by collisions.
in vacuum bulbs and x-ray tubes. The use of It can occur in two ways, diffused arcing or
vacuum in switchgear had been considered as concentrated arcing, depending on the current
early as 1920, but it was never applied at an intensity that is present.
industrial level until 1960 because of v For high current values (u 10,000 A) the arc is
technological contingencies. Since the 1970s, concentrated and single, as in traditional fluids
the vacuum technique has been increasingly (see fig. 26a ). Cathodic and anodic spots of
used due to the advantages that it offers: several mm2 are raised to extremely high
reduced dimensions, improved safety and temperatures. A fine layer of contact material is
greater endurance. vaporized and the arc develops in a metal vapor
atmosphere which occupies all of the space.
Dielectric properties of vacuum When the current decreases, these vapors
In theory the vacuum is an ideal dielectric condense on the electrodes themselves or on
medium: there is no substance therefore there is the metal screen placed for this purpose. In this
no electrical conduction. However, the vacuum is arrangement, arcing voltage can reach 200 V.
never perfect and in any case has a dielectric v For current values less than a few thousand
strength limit. amperes, this arc becomes a diffuse shape. It is
In spite of this, a true “vacuum” offers made up of several arcs separated from one
outstanding performance levels: at 10-6 bar another and conical in shape with the peak at the
pressure, dielectric strength in a uniform field cathode (see fig. 26b ). The cathodic roots of the
can reach a peak value of 200 kV for an inter- arcs, called spots, have a very small surface
electrode distance of 12 mm. area (10-5 cm2) and current density is very high
The mechanism at the origin of dielectric there (105 to 107 A/cm2). The extremely high
breaking under vacuum is linked to cold local temperature (3,000 K) leads to very intense
electronic emission phenomena, without any combined thermo-electronic / field effect
ionization snowballing effect. This is why the emission, though the evaporation of contact
dielectric strength is almost independent of material remains limited. The current is therefore
pressure as soon as the latter is less than basically caused by the flux of electrons.
10-6 bar. It then depends on the nature of the The positive metal ions produced at the cathode
materials, electrode shape (in particular the have sufficient kinetic energy (between 30 and
presence of poinys or asperities) and inter- 50 eV) that they fill all of the space up to the
electrode distance. The shape of the curve of the anode. Thus they neutralize the inter-contact
breakdown voltage as a function of the inter- space charges, resulting in a low potential
contact distance (see fig. 21) shows why the gradient and low arc voltage (80 V maximum).
applicational scope of vacuum technology
remains limited in terms of voltage. In fact the
required distances for dielectric strength
a b
increase quite quickly as soon as the voltage
exceeds 30 to 50 kV which leads to prohibitive
costs in relation to other technologies. In addition,
Anode
more x-rays would be emitted at higher voltages.

The vacuum breaking mechanism


Breaking under vacuum is fairly unique due to
the specific characteristics of the arc under
vacuum.
c Electrical arcing under vacuum Cathode
The arcing column is made up of metal vapor and
electrons coming from the electrodes as opposed Fig. 26 : concentrated arcing [a] and diffused arcing [b].
to the other breaking techniques previously

Cahier Technique Schneider Electric no. 193 / p.21


c Passing to 0 current c Choice of magnetic field
In a diffuse arcing arrangement, either obtained Two types of magnetic fields are used: radial or
instantly or long enough after a single axial.
concentrated arc so that the metal vapor has had v Radial magnetic field technology (see fig. 27 )
time to condense, breaking occurs easily at zero
The field is created by the current circulating in
current.
the electrodes designed for this purpose. In the
In fact, when the current nears zero, the number
case of concentrated arcing, the roots of the arc
of spots decreases until the last one which
move in a circular motion, the heat is uniformly
disappears when the energy provided by the arc
distributed limiting erosion and metal vapor
is no longer sufficient to maintain a high enough
density. When the arc is diffused, the spots
temperature at the foot of the arc. The abrupt
move freely on the surface of the cathode as if it
extinction of the last spot is the reason behind
were a solid disk.
the chopping phenomena frequently
encountered with this type of technology. It The fairly complex dielectrode shapes used with
should be noted that at voltage reversal, the this technology make dielectric strength between
anode becomes a cathode, but since it is cold it electrodes more difficult.
cannot emit electrons. This thus corresponds to
an excessively small deionization time constant.
Vacuum devices can in consequence break
currents with extremely high TRV gradients as
well as high frequency currents.
For high currents, an arc plasma may remain at
0 current and breaking becomes uncertain. It is
therefore essentially the density of the residual
metal vapor which determines the breaking I
capacity.
c Re-ignition and re-striking phenomena
These occur when the contacts release too →
much metal vapor. We consider that if vapor F
density after zero current exceeds 1022/m3 the
probability of breaking is almost non-existent.

Generally speaking, these phenomena are B
almost impossible to reproduce and difficult to
model. Numerous tests are then required to
validate the designs. In particular, dielectric
failures can be observed late after breaking,
eventually becoming spurious, linked to the
presence of metal particles or condensation
I
products.

The various types of vacuum breaking


technology Fig. 27 : contacts creating a radial magnetic field. The
All manufacturers have been confronted with the arc obeys electromagnetic laws, therefore it moves
same requirements: from the center to the outside of the “petals”.
v reducing current chopping phenomena to avoid
overvoltage problems, v Axial magnetic field technology (see fig. 28 )
v avoiding early erosion of the contacts to The application of an axial magnetic field
maintain greater endurance, requires the ions to take a circular trajectory
v delaying the appearance of the concentrated which stabilizes the diffuse arc and delays the
arc state to increase the breaking capacity, appearance of the concentrated state. The
v limiting the production of metal vapor to avoid appearance of the cathodic spot is avoided,
re-striking, erosion is limited and this enables fairly high
v maintaining the vacuum, essential to retaining breaking capacities to be reached.
breaking properties, throughout the device’s life. This magnetic field can be generated by internal
They have developed mainly in two ways: arc or external bulb windings in which the current
control by magnetic field and contact material flows permanently. Internally they must be
composition. protected from the arc.

Cahier Technique Schneider Electric no. 193 / p.22


I
I Axial current
incomer

4 turn quarters

Contact plates
(the slits stop induced
currents flowing opposing the
current flowing through the turns)

4 turn quarters
→ →
B B
Axial current
feeder
I I

Fig. 28 : contacts creating an axial magnetic field.

Externally this risk is eliminated, but in this case, v High metal vapor pressure enables arc
dimensions are larger and limits could arise due stabilization and limits current chopping
to the risk of the turns over-heating. phenomena (overvoltages).
The table in figure 29 compares both of these v In contrast, low metal vapor pressure is more
technologies. favorable to the interruption of high currents.
c Choice of materials Furthermore it is necessary for its resistance to
be low, for it to have a low tendency to weld and
In order to maintain the quality of the vacuum, it
good mechanical strength.
is essential that the materials used for the
contacts and the surfaces in contact with the Copper/chrome alloy contacts (50-80 % Cu,
vacuum be very pure and gas-free. 50-20 % Cr) are mainly used in circuit breakers
due to their corrosion resistance, their low
The materials that the contacts are made of is
equally important since the saturating vapor electrical resistance and their low vapor pressure.
pressure in the bulbs must not be too high nor Other materials such as copper/bismuth
too low: (98% Copper, 2% Bismuth) or more recently
Ag/W/C are used in high switching rate devices
(e.g. contactors) since they do not cause
chopping and have a low tendency to weld.
Concerning the other components in contact with
Radial Axial
the vacuum, ceramic materials used with the
field field
high temperature welding process are for the
Contact resistance/ + – moment the most suitable to maintain a high
temperature vacuum level (pressure usually less than
Arcing voltage – + 10-6 mbar).
Contact erosion – + c Chamber and breaking device design
Breaking capacity/ = = The key constraint is that of sealing the bulb
diameter under vacuum: e.g. mobile inserting parts must
be avoided.
Fig. 29 : table comparing radial field and axial field Particle sensitivity and the possibility of cold
technology. welding means that sliding contacts are not used
under vacuum. Consequently, the contacts are

Cahier Technique Schneider Electric no. 193 / p.23


simply placed end to end and the operating This technology is also used for contactors which
energy for such devices is therefore low (30 to require high endurance, but rarely for switches
50 J). On the other hand, contact pressure must for economic reasons.
be high in order to minimize contact resistance In low voltage the use of this technique has
and avoid separation of the contacts when a remained marginal for reasons of cost and the
short-circuit current passes. The required contact absence of limiting power. Generally speaking, in
pressure leads to high mechanical stresses. LV its use is limited to the range between 800
Considering the small insulation distances under and 2,500 A rated current and for breaking
vacuum and the simplicity of the mechanisms, capacities less than 75 kA.
bulbs can be very compact. Their volume is a High voltage applications (U to 52 kV) remain for
function of the breaking capacity (bulb diameter) the future.
however it is the dielectric strength of the
external enclosure which becomes important in Comments :
defining the device size. c When breaking capacitive current, post-
This technology is now well mastered by major breaking dielectric strength under vacuum is
manufacturers and the devices have a life- random, and leads to a high risk of re-striking.
expectancy greater than 20 years. It must be Vacuum circuit breakers are therefore poorly
noted that permanent monitoring of the vacuum suited to protection of capacitive networks with
in operation is not possible since it requires a voltages greater than 12 kV or those containing
suitable metering device and de-energizing of capacitor banks .
the equipment. The predictive maintenance c For vacuum contact type switches: there is a
required, for accidental leaks, in order to monitor risk of welding the contacts after closing under
the reliability of the MV electrical switchboards is short-circuit conditions. This is the case in
therefore not appropriate with this technology. certain circumstances e.g. fault locating or during
standards testing cycles.
Fields of application for vacuum breaking In fact, welding occurs when the contacts are
This breaking technique currently enables closed under load. When consequently opening
devices to be produced with great electrical under no load, the lack of arcing means that the
endurance, and greatly increased TRV roughness, that remains from the breaking of the
gradients. weld, is not eliminated. This deterioration of
This technique is most widely used in MV: surface condition makes pre-arcing even easier
general purpose circuit breakers are now during successive closures and increases the
available for various applications with all of the degree of the welding, with the risk of definitive
usual breaking capacities (up to 63 kA). They are welding taking place.
used for protection and control of: The use of these switches therefore requires
c overhead cables and lines, certain precautions.
c transformers, c For motor control: it is necessary to take
special precautions due to the fact that the circuit
c single bank capacitors,
breakers or contactors are breaking high
c shunt motors and inductances. frequency currents (re-ignition phenomena)
They are particularly well suited for controlling which therefore cause overvoltages. Even
arcing furnaces (high electrical endurance) but though there exist specific devices, it is
must be used with care for controlling parallel preferable to associate these circuit breakers
connected multi-bank capacitors. with ZnO type overvoltage protection devices.

3.5 Breaking in SF6


Sulfur hexafluoride -SF6-, is a gas that is It is chemically inert: all chemical bonds on the
appreciated for its many chemical and dielectric molecule are saturated and it has a high
qualities. The breaking technique using this gas dissociation energy (+1,096 kJ/mol) as well as a
was first developed in the 1970s similarly to high evacuation capacity for the heat produced
vacuum-type breaking. by arcing (high enthalpy).
During the arcing phase, in which the temperature
Properties of SF6
can reach between 15,000 K and 20,000 K the
c Chemical properties SF6 breaks down. This decomposition is virtually
In its pure state SF6 is a non-polluting colorless, reversible: when the current is reduced the
odorless, uninflammable and non-toxic gas. It is temperature is reduced and the ions and
insoluble in water. electrons can reform to make the SF6 molecule.

Cahier Technique Schneider Electric no. 193 / p.24


A small number of by-products are obtained from The SF6 breaking mechanism
SF6 breakdown in the presence of impurities like c Electrical arcing in SF6
sulfur dioxide or carbon tetrafluoride. These by- Thermal study of electrical arcing has enabled it
products remain confined in the bulb and are to be described as being formed by a dissociated
easily absorbed by active compounds, such as SF6 plasma, in a cylindrical shape, made up of a
aluminium silicate, which are often placed in the very high temperature core surrounded by a colder
breaking environment. sheath of gas. The core and the sheath are
IEC report 61634 on the use of SF6 in breaking separated by a temperature difference related to
switchgear gives standard values which can be the dissociation temperature of the molecule.
encountered after several years of use. The Around 2,000°C this threshold remains unchanged
quantities produced remain low and are not as the current intensity varies (see fig. 31 ).
hazardous for people or the environment: During this arcing phase the sum total of the
air (a few ppmv), CF4 (40 ppmv to 600 ppmv), current is carried by the core since the threshold
SOF2 and SO2F2 (in negligible quantities). temperature at this stage is less than the
minimum ionization temperature and the external
c Physical properties
sheath remains insulating.
v Thermal properties The characteristic magnitudes of the arc depend
The thermal conductivity of SF6 is equal to that on the type of breaking used (self-compression,
of air but research on SF6’s thermal conductivity rotary arc, self-expansion) and are given in the
curve at high temperature reveals a peak at paragraphs discussing each of these breaking
SF6’s dissociation temperature (see fig. 30 ). types.

-1 -1 -2
Thermal conductivity (W cm K 10 ) Temperature
4 (x 103K)

15
3.5

2.5

2 High electrical
conductivity
1.5

0.5
5 Ionization level
0
0 2 4 6 8 10 12 14 Good electrical
3 insulation
Temperature (K 10 )
Thermal
2 threshold
Fig. 30 : SF6 thermal conductivity curve as a function i < iarc < iarc
Very good arc
of temperature. electrical insulation

v Dielectric properties
SF6 has a very high dielectric gradient due to the
electronegative properties of fluorine (see fig. 21):
- The life span of the free electrons remains very
low and with the SF6 molecules they form heavy
ions with low mobility. The probability of Arc core
dielectric failure by a snowballing effect is
thereby delayed. Fig. 31 : temperature distribution curve of an arc
- This gives this medium an extremely low de- contained in a cylindrical tube filled with SF6.
ionization time constant of 0.25 ms (see fig. 19).

Cahier Technique Schneider Electric no. 193 / p.25


c Passing to 0 current c Self compression breaking
With the decrease in current, the temperature of In this type of circuit breaker, the arc is blown out
the core drops and therefore electrical by the release of a volume of SF6 compressed
conductivity also begins to fall. by a piston action: when the device opens, a
Approaching zero current, the thermal cylinder attached to the mobile contact moves
exchanges between the sheath and the core and compresses a volume of SF6 (see fig. 32a ).
become very high. The former disappears A puffer nozzle channels the gas in the arc axis
leading to the disappearance of conductivity with which is then ejected in the hollow contacts.
a time constant that is extremely low (0.25 ms) At high currents, the arc causes a blocking effect
but not sufficient to break high frequency which contributes to the accumulation of
currents (no re-ignition). compressed gas. When the current nears zero,
the arc is first of all cooled then extinguished due
Various types of SF6 breaking technology
to the injection of new SF6 molecules.
and their fields of application
The average value of the arc’s voltage is
In SF6 devices, the contacts are located within a
between 300 and 500 V.
sealed enclosure filled with gas in which the
pressure varies according to voltage and design This technology enables all currents up to the
parameters. These enclosures are generally breaking capacity to be broken without any
sealed for life since the leakage rate can be kept problems and without any critical current, since
to a very low level. Pressure and / or density the energy required to blow out the arc is
measurement systems can be installed which produced by the mechanical order which is
enable permanent monitoring of gas pressure in independent of the current to be broken.
the enclosure. v Characteristic values
Several types of SF6 device technology exist, The relative pressure of SF6 generally used varies
differing in terms of arc cooling methods and from 0.5 bar (16 kA, 24 kV) to 5 bars (52 kV),
each having varying characteristics and which enables the achievement of sealed leak-
applicational fields. proof enclosures with guaranteed safety.

a
Mobile contact

Fixed contact

High pressure zones


Mechanical and thermal compression
b

Low pressure zone

Movement of the mobile contacts


Movement of the gases
Movement of the arc

Fig. 32 : principles of self-compression [a], and rotary arc [b] breaking.

Cahier Technique Schneider Electric no. 193 / p.26


The factors influencing the dimensions of the appears. The resulting Laplace force accelerates
breaking chamber are the following: the arc in a circular movement. The arc contacts
- The test voltage withstand of the input/output have the shape of circular tracks which can be
which determines the insulation distance either concentric (radial arc and axial field) or
between the open contacts. It can be constant face to face as seen in figure 32b (axial arc and
and of the order of 45 mm depending on the SF6 radial field). The arc is thereby cooled in a
pressure used. uniform manner in the SF6. The device’s cooling
- The short-circuit current to be broken determines capacity therefore depends directly on the value
the diameter of the nozzle and the contacts. of the short-circuit current which gives these
- The short-circuit power to be broken determines devices a gentle breaking capacity only requiring
the puffer piston dimensions (at 24 kV the low operating energy: the energy required on
volume of gas blast is of the order of 1liter for a breaking is completely supplied by the arc and
breaking capacity of 40 kA). the low currents are broken without chopping or
overvoltages.
The opening energy of 200 J (16 kA) to 500 J
Because of the quick movement of the arc’s
(50 kA) remains relatively high despite the
roots, hot spots releasing metal vapors are
compactness of the devices due to the energy
avoided and contact erosion is minimized in
required for gas compression.
particular in the case of axial geometry.
v Fields of application for self-compression It must be noted that nearing zero current, the
breaking magnetic field is reduced. It is important that it
The principle of self-compression is the oldest of keeps a non-zero value in such a way that the
them all and has been used for all types of arc is kept moving in the cold SF6 when the TRV
general purpose circuit breakers. It involves appears, thereby avoiding the appearance of
relatively low overvoltages since there is little critical currents This is achieved by inserting
chopping phenomena and there is no risk of short-circuit rings which force the magnetic field
successive re-ignition. to be in slight phase displacement relative to the
Self-compression circuit-breakers are well suited current.
to capacitor bank operation since they have a v Characteristic values
low re-strike probability as well as a high
In MV, the arc rotating in SF6 has a voltage of
endurance to closing currents. between 50 and 100 V for a length of 15 to
However, the relatively high operating energy 25 mm.
leads to quite high stresses on the operating Due to the low breaking energy, the devices are
mechanism and possibly to a limitation in terms very compact even at a relatively low filling
of the number of operations. pressure (of around 2.5 bar) and opening energy
This technology is still widely used today is less than 100 J.
especially for high intensity devices and voltages
v Fields of application
greater than 24 kV.
Rotary arc breaking is well suited to operating
c Rotary arc breaking devices sensitive to overvoltages such as MV
In this technology, the arc cools through its own motors and alternators. Its excellent endurance,
movement through the SF6. The high speed due to low contact wear and low control energy
rotary movement of the arc (which can exceed make it of use in applications with a high number
the speed of sound) is caused by the magnetic of switching operations (contactor function).
field created by a winding through which the fault The rotary arc technique used on its own only
current flows. enables a limited breaking capacity to be
When the main contacts open, the current is achieved (25/30 kA at 17.5 kV) and only applies
switched to the winding and the magnetic field to voltages less than 17.5 kV.

Cahier Technique Schneider Electric no. 193 / p.27


c Self expansion zone reduces the dielectric performance of the
Self-expansion breaking uses the thermal energy SF6 during the restoring phase, which leads to
dissipated by the arc to increase the pressure of an increase in the inter-electrode gap and
a small volume of SF6 which escapes through an contact displacement rates, and even the
orifice crossed by the arc (see fig. 33a ). As long pressure of the SF6.
as the current in the arc is high, it has a blocking - Magnetic guiding (rotary arc type)
effect which prevents the outflow of gas through (see fig. 33c )
the orifice. The temperature of the cold gas An appropriately dimensioned magnetic field
blocked in the volume increases due to the enables the centering of the arc in the SF6
thermal dissipation of the arc (mainly by expansion zone while giving it a rapid rotational
radiation), therefore its pressure increases as movement similar to that with rotary arc
well. At zero current the plug disappears and the technology. This technology, which requires
SF6 expands and blows out the arc. The puffer expertise in design and simulation, offers the
effect depends on the current value, which advantage of avoiding having substances other
enables low control energy and gentle breaking, than SF6 in the arcing zone. Thermodynamic
but with a risk of critical currents as well. These efficiency is optimum and the SF6 keeps all of its
are generally found at approximately 10% of the dielectric qualities. Therefore the insulation
breaking capacity. distances can be reduced to their minimum and
v Two methods of arc guiding have been the required control energy is low.
developed, mechanical guiding and magnetic v Characteristic values
guiding, which enable the stabilization of the arc For low currents the puffer action is almost non-
in the puffer zone as well as the elimination of existent and arc voltage generally does not
critical currents. exceed 200 V.
- Mechanical guiding (self-compression type) The bulb filling pressure is close to atmospheric
(see fig. 33b ) pressure and thermal puffer volume is between
The arc is maintained centered between the two 0.5 and 2 liters.
contacts by insulating walls confining the Control energy under 24 kV is less than 100 J.
gaseous flux in a manner similar to the nozzles All of these characteristics mean that the self-
used in self-compression. breaking technique is the best performing
This technique is safe and simple but it technology to date. The breaking capacities can
increases the energy required for control. In fact, be very high while still having low pressure and
the presence of these mechanisms in the arc control energy, therefore giving great reliability.

a b c

Coil

∆P

Guiding
zone
Insulating
walls

Fixed contact
Mobile contact
Movement of the mobile contact
Movement of the expanding gas

Fig. 33 : self-expansion, its principle [a] and the two methods of arc guiding, mechanical [b] and magnetic [c].

Cahier Technique Schneider Electric no. 193 / p.28


v Fields of application piston assisted self-compression. It is then used
This technology, developed for breaking fault in devices intended for MV and even in HV for all
currents, is well suited for breaking capacitive applications.
currents since it accepts overcurrents and The performance levels achieved by combining
overvoltages. It is also suitable for breaking thermal expansion and rotary arcing are such
slightly inductive currents. that the technique is considered for use in circuit
Without any additional means thermal expansion breakers used in extremely demanding
devices have limited breaking capacity and applications, e.g. to protect power station
operating voltages. The self-expansion alternators (high asymmetry and TRV) or for
technique is often associated with rotary arc or applications requiring great endurance.

3.6 Comparison of the various techniques


Currently in the LV sector, magnetic breaking in
air is, with the exception of a few rare cases, the %
only technique used. 100
In EHV, the SF6 breaking technique is practically
the only one used. 80
In MV applications, where all the technologies
can be used, SF6 breaking and vacuum breaking 60
have replaced breaking in air for reasons of cost
and space requirements (see fig. 34 ), and 40
breaking in oil for reasons of reliability, safety
and reduced maintenance (see fig. 35 ). 20
Vacuum or SF6 breaking techniques have similar
performance levels and their respective qualities 0
mean that one or other is better suited for certain 1980 82 84 86 88 90 92 94 96
applications.
Air Oil Vacuum SF6
According to the country, one or other of these
technologies is primarily used mainly for Fig. 34 : development of the MV circuit breaker market
historical reasons or manufacturer’s choice. in Europe.

Oil Air SF6 / Vacuum


Safety Risk of explosion and fire if Significant external effects No risk of explosion nor of
increase in pressure (hot and ionized gas external effects.
(multiple operations) causes emissions during breaking).
failure.
Size Fairly large device volume. Installation requiring large Small.
distances.
(unconfined breaking).
Maintenance Regular oil replacement Replacement of arcing Nothing for the breaking
(irreversible oil breaking-down contacts when possible. components.
during each break). Regular maintenance of Minimal lubrification of the
the control mechanism. control mechanisms.
Sensitivity to The breaking environment can be changed by the environment Insensitive: sealed for life type
the environment itself (humidity, dust, etc.). bulb.
Quick cycle The long pressure reduction The slow evacuation of hot Both SF6 and the vacuum
breaking time requires de-rating of the air requires the breaking recover their dielectric
breaking capacity if there is capacity to be de-rated. properties very quickly:
a risk of successive breaks. no need to de-rate the
breaking capacity.
Endurance Mediocre. Average. Excellent.

Fig. 35 : comparison of performances of various breaking techniques.

Cahier Technique Schneider Electric no. 193 / p.29


The following table figure 36 summarizes the to be more easily achieved (voltage or short-
respective features of each of these two circuit current).
techniques. v Vacuum technology is widely used in control
v SF6 and vacuum circuit breakers are general functions (contactor) (moderate voltage or current,
purpose circuit breakers and can be adapted to high endurance requirement) despite the
all applications. precautions to be taken concerning overvoltages.
Technological progress in terms of vacuum bulb On the other hand, it is almost non-existent in
production has enabled very reliable and switch functions for economic reasons; in
competitive devices to be obtained in the same particular, the excellent dielectric strength of SF6
way as SF6 devices. after breaking enables a single device to integrate
The vacuum breaking technique is easier to the functions of switching and isolation, which is
implement at low voltages (voltage less than not possible under vacuum. Today, most major
7.2-12 kV). On the other hand, the SF6 breaking manufacturers use both these breaking techniques
technique enables higher breaking performances in their switchgear according to their requirements.

SF6 Vacuum
Applications Motors, All. Relatively suited to high breaking All. Relatively suited to low voltages
furnaces, performances (I and U). and very quick TRVs.
lines, etc.
Circuit All. Isolating functions are prohibited.
breakers,
contactors,
etc.
Characteristics Endurance Satisfactory for all current applications. Can be very high for certain special
applications.
Overvoltage No risk for low inductive currents. Overvoltage protection device
Very low probability of re-striking for recommended for motor and
capacitive currents. capacitor bank switching.
Isolation Very stable, enabling isolating functions.
between
contacts
Dimension Very compact at low voltages.
Functioning Loss of Up to 80% of performances
safety tightness maintained at Patm.
Possibility of continuous monitoring.
Maintenance Reduced for the control mechanism. Reduced for the control mechanism.
Possibility of permanent monitoring Occasional control of the vacuum
of gas pressure. possible.
Number of Very low (< 4/10,000), mainly due to Very low if the bulb production
failures the auxiliaries. procedure is well controlled.

Fig. 36 : compared features of SF6 and vacuum breaking techniques.

3.7 What possibilities for other techniques?


For several decades, engineers have been c high thermal dissipation,
seeking to develop circuit breakers without arcs c high sensitivity to overvoltages and
or mobile parts, notably by using electronic overcurrents,
components. c leakage current in a blocked state,
Thyristors enable breaking devices to be c limitation in reverse voltage.
produced in which the behavior can be near to These features make it necessary to combine
the ideal switch since they break the current them with:
when it passes to zero; furthermore, their c radiators,
endurance is exceptional under normal c overvoltage protection devices,
conditions of operation. Unfortunately, apart from c ultra-quick fuses,
their cost, static components have a few c switches or isolators,
disadvantages: c and of course electronic control systems.

Cahier Technique Schneider Electric no. 193 / p.30


Semi-conductors: thyristors, GTO, IGBT have In MV, applications are very rare and static
made enormous progress and are widely used in circuit breakers remain in the prototype phase;
LV in various applications, e.g. to produce this is because, in addition to their weaknesses
contactors every time the operating rate is very listed above, it is necessary to use several
high. components in series to withstand the rated
In HV, thyristors are placed in impedance voltage.
regulation control devices comprising self-reactors In conclusion, except for very specific
and capacitors, in FACTS -Flexible Alternating applications, static breaking currently does not
Current Transmission Systems-, whose role is to have a very bright future.
optimize and stabilize the network and in Custom Electrical arc breaking currently remains the
Power for distribution networks. unavoidable solution.

4 Conclusion

Of all the MV breaking techniques only SF6 and c Reliability: few moving parts and low control
vacuum breaking offer significantly better energy which means high availability, reduced
performance levels. maintenance and a very long life span.
The choice between vacuum and SF6 depends c Placing these devices in enclosures and the
entirely on the applicational field and the production of very compact ready-made
technological choices made by each country and MV switchboards is another important advantage
manufacturer: resulting in the differences in since the breaking capacity is not affected by the
geographic spread of the devices using SF6 or presence of metal partitions.
vacuum breaking techniques. Due to current computing technology, which
Currently no other technique capable of enables modeling and simulation, switchgear is
replacing vacuum or SF6 breaking is on the constantly improving.
horizon. These two techniques have numerous However, the most important gains in terms of
advantages relative to the older techniques: operational dependability of installations
(reliability, safety, maintainability) are related to
c Safety: no risk of explosion or fire and external the widespread use of equipment that is in a
effects during breaking. factory-made and tested enclosure, associated
c Compactness: vacuum and SF6 are very good with the integrated protection, monitoring and
insulators, thus the devices are not as big. control systems.

Cahier Technique Schneider Electric no. 193 / p.31


Bibliography

Standards Various works


c IEC 60034: Rotating electrical machines. c High Voltage Circuit Breakers-Design and
c IEC 60056: High-voltage alternating-current Applications-. RUBEN, D. GARZON.
circuit-breakers. c Disjoncteurs HAUTE TENSION : Comparaison
c IEC 60909: Short-circuit current calculation in des différents mode de coupure.
three-phase AC systems. B. JOYEUX-BOUILLON (GEC ALSTHOM) &
J.-P. ROBERT (Merlin-Gerin)
c IEC 61233 report: High-voltage alternating
current circuit-breakers - Inductive load c Disjoncteurs SF6 : Evolution de 1959 à 1994.
switching. D. DUFOURNET, (GEC ALSTHOM- T&D).

c IEC 61634 report: High-voltage switchgear and c Manœuvre des courants capacitifs - Etat de
controlgear - Use and handling of sulphur l’art -. ELECTR n°155, Août 1994.
hexafluoride (SF6) in high-voltage switchgear c Etude des technologies existantes des
and controlgear. disjoncteurs de distribution. IREQ, Avril 1991.
c Guide technique du disjoncteur.
Schneider Electric’s Cahiers Techniques P. POLO & P. ATTIER, 1993.
c Analyse des réseaux triphasés en régime
perturbé à l’aide des composantes symétriques.
B. DE METZ-NOBLAT, Cahier Technique no. 18.
c The breaking process with a Fluarc SF6 puffer-
type circuit-breaker.
J. HENNEBERT, Cahier Technique no. 112.
c Calculation of short-circuit currents.
B. DE METZ-NOBLAT, G. THOMASSET,
R. CALVAS and A. DUCLUZAUX,
Cahier Technique no. 158.
c Control, monitoring and protection of HV motors.
J.-Y. BLANC, Cahier Technique no. 165.
c Breaking by auto-expansion.
G. BERNARD, Cahier Technique no. 171.
c SF6 properties, and use in MV and HV
switchgear.
D. KOCH, Cahier Technique no. 188.
c Manœuvre et protection des batteries de
condensateurs.
D. KOCH, Cahier Technique no. 189.

Cahier Technique Schneider Electric no. 193 / p.32


© 1999 Schneider Electric

Schneider Electric Direction Scientifique et Technique, DTP: AXESS - Saint-Péray (07)


Service Communication Technique Edition: Schneider Electric
F-38050 Grenoble cedex 9 Printing: Imprimerie du Pont de Claix - Claix - France - 1000
Fax: (33) 04 76 57 98 60 - 100 FF -

28299 06-99

Вам также может понравиться