Академический Документы
Профессиональный Документы
Культура Документы
Sign InJoin
22
Owlcation»
STEM»
Electrical Engineering
OSBERT JOEL C
more
Contact Author
Definition
A current transformer is an instrument transformer, used along with measuring or protective
devices, in which the secondary current is proportional to the primary current (under normal
conditions of operation) and differs from it by an angle that is approximately zero.
Functions
Current transformers perform the following functions:
Current transformers supply the protective relays with currents of magnitude proportional
to those of power circuit but sufficiently reduced in magnitude.
The measuring devices cannot be directly connected to the high magnitude supplies.
Hence current transformers are used to supply those devices with currents of magnitude
proportional to those of power.
A current transformer also isolates the measuring instruments from high voltage circuits.
Current Transformer
Principle
The basic principle of the current transformer is the same as that of the power transformer. Like
the power transformer, the current transformer also contains a primary and a secondary winding.
Whenever an alternating current flows through the primary winding, alternating magnetic flux is
produced, which then induces alternating current in the secondary winding. In the case of current
transformers, the load impedance or “burden” is very small. Therefore the current transformer
operates under short circuit conditions. Also the current in the secondary winding does not
depend on load impedance but instead depends on the current flowing in the primary winding.
The current transformer basically consists of an iron core upon which primary and secondary
windings are wound. The primary winding of the transformer is connected in series with the load
and carries the actual current flowing to the load, while the secondary winding is connected to a
measuring device or a relay. The number of secondary turns is proportional to the current
flowing through the primary; i.e., the larger the magnitude of current flowing through the
primary, more the number of secondary turns.
The ratio of primary current to the secondary current is known as the current transformation ratio
of the CT. Usually the current transformation ratio of the CT is high. Normally the secondary
ratings are of the order 5 A, 1 A, 0.1 A, whereas the primary ratings vary from 10 A to 3000 A or
more.
The CT handles much less power. Rated burden can be defined as the product of current and
voltage at the secondary side of the CT. It is measured in volt ampere (VA).
The secondary of a current transformer should not be disconnected from its rated burden while
current is flowing in the primary. As the primary current is independent of the secondary current,
the entire primary current acts as a magnetizing current when secondary is opened. This results
in deep saturation of the core, which cannot return to normal state and so the CT is no longer
usable.
Types
Based on the function performed by the current transformer, it can be classified is follows:
1. Measuring current transformers. These current transformers are used along with the
measuring devices for the measurement of current, energy, and power.
2. Protective current transformers. These current transformers are used along with the
protection equipments such as trip coils, relays, etc.
1. Bar Type. This type consists of a bar of suitable size and material forming an integral
part of the transformer.
2. Wound Type. This type has a primary winding of ore than one full turn wound over the
core.
3. Window Type. This type has no primary winding. The secondary wind of the CT is
placed around the current flowing conductor. The magnetic electric field created by
current flowing through the conductor induces current in the secondary winding, which is
used for measurement.
Errors
The ideal current transformer may be defined as one in which any primary condition is
reproduced in the secondary circuit in the exact ratio and phase relationship. The phasor diagram
for an ideal current transformer is shown in Figure 1.
Ip / Is = Ts / Tp
Therefore the ratio of primary and secondary winding currents equal to the turns ratio. Also the
primary and secondary winding currents are exactly 1800 in phase.
In an actual transformer, the windings have resistance and reactance and also the transformer has
magnetizing and loss component of current to maintain the flux (see Figure 2). Therefore, in an
actual transformer the ratio of current is not equal to the turns ratio and also there is a phase
difference between the primary current and the secondary currents reflected back on the primary
side and consequently we have ratio error and phase angle error.
Kn = turns ratio
Io = exciting current,
R = Ip / Is
= (Kn – R) / R x 100 %
The disadvantage of making transformers with lower secondary current ratings is that they
produce much higher voltage if they are ever accidentally left open circuited. For this reason, it is
better to adopt 5 A rating at the secondary.
Turns Compensation
Turns compensation is used in current transformers in order to reduce ratio error. If the phase
angle of secondary is zero;
R = Kn + Il/ Is
The reduction in the number of secondary turns will reduce the actual transformation ratio b an
equal percentage. Usually the best number of secondary turns is 1 or 2 fewer than the number
that will make Kn equal to the nominal current ratio of the transformer.
Current error (ratio error). The percentage error in the magnitude of the secondary current is
defined by the following formula:
Kn = turns ratio
Accuracy class. Accuracy class tells you how accurate the current transformer is. Accuracy class
shall be 0.2, 0.5, 1, 3 or 5. For example, if the accuracy class of a current transformer is 1, then
the ratio error will be ±1% at the rated primary value.
Phase displacement. The difference in phase between the primary and the secondary current
phasors, the direction of the phasors being chosen such that the angle is zero for a perfect
transformer.
Rated secondary current. The value of rated secondary current shall be 5 A. The secondary
currents rating of 2 and 1 A may also be used in some case.
Rated burden. The product of current and voltage at the secondary side of the CT is called the
rated burden. It is measured in volt ampere (VA).
Temperature Rise
The temperature rise of the current transformer's winding when carrying a rated primary current,
at rated frequency and with rated burden, should not exceed the approximate values given in
Table 2.
Related
Electrical Engineering
Electrical Engineering
Medical Science
by Anthropophobia3
Physics
by CyberFreak2
Popular
Electrical Engineering
by Sherry Hewins42
Electrical Engineering
Comments
Sign in or sign up and post using a HubPages Network account.
BONNY
3 days ago
when the ct secondary is open circuited there will be high voltage, and when we connect
the burden to the secondary- does it mean the burden has high voltage rating?which
corresponds to the open circuit voltage of ct secondary?
Jagadeesh
6 months ago
shivdeimittal@gmail.com
10 months ago
10 months ago
Oh nice dear
AUTHOR
OSBERT JOEL C
Please check your CT rating and input the primary in the controller.
abel
13 months ago
Please advice.
Thanks.
AUTHOR
OSBERT JOEL C
Anudeep
16 months ago
i want to know what happens to a 500.5A, class 5p15 , 30VA CT When 12 KA fault
current flows through it?
ravindra napit
17 months ago
Very nice
saud alam
2 years ago
Thanks sir
chintan vyas
2 years ago
wkaar
2 years ago
jitender chauhan
2 years ago
sijil rajan
2 years ago
abilash
2 years ago
trilok sinha
3 years ago
chandan kumar
3 years ago
AUTHOR
OSBERT JOEL C
environments (135ºC). these transformers can be mounted directly upon the energized
busbar.
fazlullah
3 years ago
Mohit yadav
3 years ago
Good answer but i suggest important points are write in point wise. Thank you sir
AUTHOR
OSBERT JOEL C
rabindra sahoo
4 years ago
Good answer
About Us
Editorial Policy
Copyright
Terms of Use
Privacy Policy
Copyright © 2018 HubPages Inc. and respective owners. Other product and company names
shown may be trademarks of their respective owners. HubPages® is a registered Service Mark of
HubPages, Inc. HubPages and Hubbers (authors) may earn revenue on this page based on
affiliate relationships and advertisements with partners including Amazon, Google, and others.