Totally Integrated

Automation Portal

=E01+R01_F003
=E01+R01_F003
Author: z003nxdj
Creation time: 4/24/2018 2:04:52 PM
Last modified time: 7/24/2018 1:57:52 AM
Modified by: Unnamed User
Totally Integrated
Automation Portal

=E01+R01_F003
Device information
Device details
Name Value
Name =E01+R01_F003
IEC 61850 name T1_F003
IEC 61850 Edition IEC 61850 Edition 1
Type 7UT85
Serial number BM1508000990
Configuration version V07.50.12
Communication configuration version V07.50.12
Product code 7UT85-DAAA-AA0-0AAAA0-AH0112-23111B-BAA000-000AA0-CC1BA1-CL0CE0-
CG0CG0
Short product code P1F114631
CPU type CP200

Function points
Function-points consumption: Used 56 out of 100

Function-chart (CFC) statistics


Name Value
Ticks for task Interlocking and Measurement 0 out of 83349
Ticks for task Event-Triggered 1474 out of 9159
Ticks for task Fast Event-Triggered 137 out of 500
Totally Integrated
Automation Portal

=E01+R01_F003
Hardware and protocols
Binary inputs
Binary input Terminals Module User label Threshold value
1.1 1D11-1D9 Base module BI 1.1 Low: 44 V, High: 88 V
1.2 1D12-1D10 Base module BI 1.2 Low: 44 V, High: 88 V
1.3 1D11-1D13 Base module BI 1.3 Low: 44 V, High: 88 V
1.4 1D12-1D14 Base module BI 1.4 Low: 44 V, High: 88 V
2.1 2B11-2B12 Base module BI 2.1 Low: 44 V, High: 88 V
2.2 2B11-2B14 Base module BI 2.2 Low: 44 V, High: 88 V
2.3 2B11-2B13 Base module BI 2.3 Low: 44 V, High: 88 V
3.1 3C13-3D1 Expansion module 3 BI 3.1 Low: 44 V, High: 88 V
3.2 3C14-3D2 Expansion module 3 BI 3.2 Low: 44 V, High: 88 V
3.3 3D3-3D5 Expansion module 3 BI 3.3 Low: 44 V, High: 88 V
3.4 3D4-3D6 Expansion module 3 BI 3.4 Low: 44 V, High: 88 V
3.5 3D7-3D9 Expansion module 3 BI 3.5 Low: 44 V, High: 88 V
3.6 3D8-3D10 Expansion module 3 BI 3.6 Low: 44 V, High: 88 V
3.7 3D11-3D13 Expansion module 3 BI 3.7 Low: 10 V, High: 19 V
3.8 3D12-3D14 Expansion module 3 BI 3.8 Low: 10 V, High: 19 V
4.1 4A1-4A3 Expansion module 4 BI 4.1 Low: 44 V, High: 88 V
4.2 4A2-4A4 Expansion module 4 BI 4.2 Low: 44 V, High: 88 V
4.3 4A5-4A7 Expansion module 4 BI 4.3 Low: 44 V, High: 88 V
4.4 4A6-4A8 Expansion module 4 BI 4.4 Low: 44 V, High: 88 V
4.5 4A9-4A11 Expansion module 4 BI 4.5 Low: 44 V, High: 88 V
4.6 4A10-4A12 Expansion module 4 BI 4.6 Low: 44 V, High: 88 V
4.7 4A13-4B1 Expansion module 4 BI 4.7 Low: 44 V, High: 88 V
4.8 4A14-4B2 Expansion module 4 BI 4.8 Low: 44 V, High: 88 V
4.9 4B3-4B5 Expansion module 4 BI 4.9 Low: 44 V, High: 88 V
4.10 4B4-4B6 Expansion module 4 BI 4.10 Low: 44 V, High: 88 V
4.11 4B7-4B9 Expansion module 4 BI 4.11 Low: 44 V, High: 88 V
4.12 4B8-4B10 Expansion module 4 BI 4.12 Low: 44 V, High: 88 V
5.1 5A1-5A3 Expansion module 5 BI 5.1 Low: 44 V, High: 88 V
5.2 5A2-5A4 Expansion module 5 BI 5.2 Low: 44 V, High: 88 V
5.3 5A5-5A7 Expansion module 5 BI 5.3 Low: 44 V, High: 88 V
5.4 5A6-5A8 Expansion module 5 BI 5.4 Low: 44 V, High: 88 V
5.5 5A9-5A11 Expansion module 5 BI 5.5 Low: 44 V, High: 88 V
5.6 5A10-5A12 Expansion module 5 BI 5.6 Low: 44 V, High: 88 V
5.7 5A13-5B1 Expansion module 5 BI 5.7 Low: 44 V, High: 88 V
5.8 5A14-5B2 Expansion module 5 BI 5.8 Low: 44 V, High: 88 V
5.9 5B3-5B5 Expansion module 5 BI 5.9 Low: 44 V, High: 88 V
5.10 5B4-5B6 Expansion module 5 BI 5.10 Low: 44 V, High: 88 V
5.11 5B7-5B9 Expansion module 5 BI 5.11 Low: 44 V, High: 88 V
5.12 5B8-5B10 Expansion module 5 BI 5.12 Low: 44 V, High: 88 V
5.13 5D5-5D7 Expansion module 5 BI 5.13 Low: 44 V, High: 88 V
5.14 5D6-5D8 Expansion module 5 BI 5.14 Low: 44 V, High: 88 V
5.15 5D9-5D11 Expansion module 5 BI 5.15 Low: 44 V, High: 88 V
5.16 5D10-5D12 Expansion module 5 BI 5.16 Low: 44 V, High: 88 V
6.1 6A1-6A3 Expansion module 6 BI 6.1 Low: 44 V, High: 88 V
6.2 6A2-6A4 Expansion module 6 BI 6.2 Low: 44 V, High: 88 V
6.3 6A5-6A7 Expansion module 6 BI 6.3 Low: 44 V, High: 88 V
6.4 6A6-6A8 Expansion module 6 BI 6.4 Low: 44 V, High: 88 V
6.5 6A9-6A11 Expansion module 6 BI 6.5 Low: 44 V, High: 88 V
6.6 6A10-6A12 Expansion module 6 BI 6.6 Low: 44 V, High: 88 V
6.7 6A13-6B1 Expansion module 6 BI 6.7 Low: 44 V, High: 88 V
6.8 6A14-6B2 Expansion module 6 BI 6.8 Low: 44 V, High: 88 V
6.9 6B3-6B5 Expansion module 6 BI 6.9 Low: 44 V, High: 88 V
6.10 6B4-6B6 Expansion module 6 BI 6.10 Low: 44 V, High: 88 V
6.11 6B7-6B9 Expansion module 6 BI 6.11 Low: 44 V, High: 88 V
6.12 6B8-6B10 Expansion module 6 BI 6.12 Low: 44 V, High: 88 V
6.13 6D5-6D7 Expansion module 6 BI 6.13 Low: 44 V, High: 88 V
6.14 6D6-6D8 Expansion module 6 BI 6.14 Low: 44 V, High: 88 V
6.15 6D9-6D11 Expansion module 6 BI 6.15 Low: 44 V, High: 88 V
6.16 6D10-6D12 Expansion module 6 BI 6.16 Low: 44 V, High: 88 V

Binary outputs
Binary output Terminals Module User label
1.1 1D1-1D2 Base module BO-F make 1.1
1.2 1D3-1D4 Base module BO-F make 1.2
1.3 1D5-1D6 Base module BO-F make 1.3
1.4 1D7-1D8 Base module BO-F make 1.4
2.1 2B3-2B4 Base module BO make 2.1
2.2 2B5-2B6-2B8 Base module BO change-over 2.2
4.1 4B11-4B12 Expansion module 4 BO make 4.1
4.2 4B13-4B14 Expansion module 4 BO make 4.2
4.3 4C1-4C2 Expansion module 4 BO make 4.3
4.4 4C3-4C4 Expansion module 4 BO make 4.4
4.5 4C5-4C6 Expansion module 4 BO make 4.5
4.6 4C7-4C8 Expansion module 4 BO make 4.6
4.7 4C9-4C10 Expansion module 4 BO make 4.7
4.8 4C11-4C12 Expansion module 4 BO make 4.8
4.9 4C13-4C14 Expansion module 4 BO make 4.9
4.10 4D1-4D2 Expansion module 4 BO make 4.10
4.11 4D3-4D4 Expansion module 4 BO make 4.11
4.12 4D5-4D6 Expansion module 4 BO make 4.12
Totally Integrated
Automation Portal

Binary output Terminals Module User label


4.13 4D7-4D8 Expansion module 4 BO make 4.13
4.14 4D9-4D10 Expansion module 4 BO make 4.14
4.15 4D11-4D12 Expansion module 4 BO make 4.15
4.16 4D13-4D14 Expansion module 4 BO make 4.16
5.1 5B11-5B12 Expansion module 5 BO make 5.1
5.2 5B13-5B14 Expansion module 5 BO make 5.2
5.3 5C1-5C2 Expansion module 5 BO make 5.3
5.4 5C3-5C4 Expansion module 5 BO make 5.4
5.5 5C5-5C6 Expansion module 5 BO make 5.5
5.6 5C7-5C8 Expansion module 5 BO make 5.6
5.7 5C11-5C12 Expansion module 5 BO make 5.7
5.8 5C13-5C14 Expansion module 5 BO make 5.8
6.1 6B11-6B12 Expansion module 6 BO make 6.1
6.2 6B13-6B14 Expansion module 6 BO make 6.2
6.3 6C1-6C2 Expansion module 6 BO make 6.3
6.4 6C3-6C4 Expansion module 6 BO make 6.4
6.5 6C5-6C6 Expansion module 6 BO make 6.5
6.6 6C7-6C8 Expansion module 6 BO make 6.6
6.7 6C11-6C12 Expansion module 6 BO make 6.7
6.8 6C13-6C14 Expansion module 6 BO make 6.8

Current transformers
Current transformer Terminals Module User label
1A1 1A1-1A2 Base module I P 1A1
1A2 1A3-1A4 Base module I P 1A2
1A3 1A5-1A6 Base module I P 1A3
1A4 1A7-1A8 Base module I P 1A4
1B1 1B1-1B2 Base module I P 1B1
1B2 1B3-1B4 Base module I P 1B2
1B3 1B5-1B6 Base module I P 1B3
1B4 1B7-1B8 Base module I P 1B4

Voltage transformers
Voltage transformer Terminals Module User label
3.1 3A1-3A2 Expansion module 3 V 3.1
3.2 3A3-3A4 Expansion module 3 V 3.2
3.3 3A5-3A6 Expansion module 3 V 3.3
3.4 3A7-3A8 Expansion module 3 V 3.4
3.5 3A11-3A12 Expansion module 3 V 3.5
3.6 3A13-3A14 Expansion module 3 V 3.6
3.7 3C1-3C2 Expansion module 3 V 3.7
3.8 3C3-3C4 Expansion module 3 V 3.8

Function keys
Function key Module User label
1 Base module Mode (controllable)
2 Base module Mode (controllable)
3 Base module Mode (controllable)
4 Base module Mode (controllable)
5 Base module Mode (controllable)
6 Base module Mode (controllable)
7 Base module Mode (controllable)
8 Base module Mode (controllable)

LEDs
LED Module User label
1.1 Base module LED 1.1
1.2 Base module LED 1.2
1.3 Base module LED 1.3
1.4 Base module LED 1.4
1.5 Base module LED 1.5
1.6 Base module LED 1.6
1.7 Base module LED 1.7
1.8 Base module LED 1.8
1.9 Base module LED 1.9
1.10 Base module LED 1.10
1.11 Base module LED 1.11
1.12 Base module LED 1.12
1.13 Base module LED 1.13
1.14 Base module LED 1.14
1.15 Base module LED 1.15
1.16 Base module LED 1.16
3.1 Expansion module 3 LED 3.1
3.2 Expansion module 3 LED 3.2
3.3 Expansion module 3 LED 3.3
3.4 Expansion module 3 LED 3.4
3.5 Expansion module 3 LED 3.5
3.6 Expansion module 3 LED 3.6
3.7 Expansion module 3 LED 3.7
3.8 Expansion module 3 LED 3.8
3.9 Expansion module 3 LED 3.9
3.10 Expansion module 3 LED 3.10
Totally Integrated
Automation Portal

LED Module User label


3.11 Expansion module 3 LED 3.11
3.12 Expansion module 3 LED 3.12
3.13 Expansion module 3 LED 3.13
3.14 Expansion module 3 LED 3.14
3.15 Expansion module 3 LED 3.15
3.16 Expansion module 3 LED 3.16

Key switches
Type Address Module User label
FM_KeySwitch 1 Expansion module 3 FM_KeySwitch 1
FM_KeySwitch_Test 2 Expansion module 3 FM_KeySwitch_Test 2

Ethernet configurations
Onboard Ethernet(Slot J)
IP address: 172.16.60.60
Subnet mask: 255.255.255.0

ETH-BB-2FO(Slot E)
Subnet: IEC61850
IP address: 192.168.0.206
Subnet mask: 255.255.0.0

Interfaces
Slot Module Protocol info
J Onboard Ethernet Ethernet-interface settings: DCP
E ETH-BB-2FO Channel 1: DCP,SNTP,Homepage,RSTP,IEC 61850-8-1

SNTP (E\ETH-BB-2FO\Channel 1): SNTP


Number Settings Value
102.1031.0.103 Time source 1 192.168.0.204
102.1031.0.104 Time source 2 0.0.0.0
102.1031.0.105 Time interval 15 s
102.1031.0.106 Start time 20 s

Homepage (E\ETH-BB-2FO\Channel 1): Homepage


Number Settings Value
102.1031.0.104 Homepage Mode on

RSTP (E\ETH-BB-2FO\Channel 1): RSTP


Number Settings Value
102.1031.0.103 Bridge hello time 2s
102.1031.0.107 Bridge priority 32768
102.1031.0.119 Bridge identifier 2048
102.1031.0.104 Bridge max. age time 40 s
102.1031.0.105 Bridge forward delay 21 s
102.1031.0.110 Port priority port 1 128
102.1031.0.114 Port priority port 2 128
102.1031.0.109 Auto edge port 1 off
102.1031.0.113 Auto edge port 2 off
102.1031.0.111 Port path cost port 1 200000
102.1031.0.115 Port path cost port 2 200000
102.1031.0.106 Transmit hold count 10
Totally Integrated
Automation Portal

=E01+R01_F003
Measuring-points routing
Current-measuring points
Measuring point Connection type Terminals
Meas.point I-3ph 1 3-phase + IN I A: 1A1-1A2
I B: 1A3-1A4
I C: 1A5-1A6
IN: 1A7-1A8
Meas.point I-3ph 2 3-phase + IN I A: 1B1-1B2
I B: 1B3-1B4
I C: 1B5-1B6
IN: 1B7-1B8

Voltage-measuring points
Measuring point Connection type Terminals
Meas.point V-3ph 1 3 ph-to-gnd voltages V A: 3A1-3A2
V B: 3A3-3A4
V C: 3A5-3A6
Meas.point V-1ph 1 V B: 3A7-3A8
Totally Integrated
Automation Portal

=E01+R01_F003
Function-group connections
Measuring point to function-group connections
Measuring point Interface
Meas.point I-3ph 1[ID 1] Transformer side 1:I 3ph
Meas.point I-3ph 1[ID 1] Q0:I 3ph
Meas.point I-3ph 2[ID 2] Transformer side 2:I 3ph
Meas.point I-3ph 2[ID 2] IN-33KV:I 3ph
Meas.point V-3ph 1[ID 3] Transformer side 1:V 3ph
Meas.point V-3ph 1[ID 3] Q0:V sync1
Meas.point V-1ph 1[ID 4] Q0:V sync2
Meas.point V-1ph 1[ID 4] Lado 33kV:V

Function group to circuit-breaker group connections


Protection group Circuit-breaker group(s)
Transformer side 1 Q0
Transformer side 1 IN-33KV
Transformer side 2 Q0
Transformer side 2 IN-33KV
Transformer diff. 1 Q0
Transformer diff. 1 IN-33KV

Protection-function group to protection-function group connections


Protection group Transformer group(s)
Transformer side 1 Transformer diff. 1:side
Transformer side 2 Transformer diff. 1:side
Totally Integrated
Automation Portal

=E01+R01_F003
Information routing
Legend
Abbreviation Description
BI Binary input
FK Function keys
BO Binary output
D Display
L Logs
FR Fault recorder

General
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
91.500 General >SG choice bit 1 SPS O
91.501 General >SG choice bit 2 SPS O
91.502 General >SG choice bit 3 SPS O
91.503 General >Sw. authority local SPS O
91.504 General >Sw. authority remote SPS O
91.505 General >Sw. mode interlocked SPS O
91.506 General >Sw. mode non-interl. SPS O
91.510 General >Test mode on SPS O
91.511 General >Test mode off SPS O
91.507 General >Device funct.logoff on SPS O
91.508 General >Dev. funct.logoff off SPS O
91.509 General >Block monitoring dir. SPS O
91.315 General Device logged off SPS O
91.53 General Health ENS O
91.54 General Protection inactive SPS O
91.309 General Sw.authority key/set ENS O
91.310 General Sw.mode key/set ENS O
91.311 General Switching authority ENS O
General Switching authority\local SPS X
General Switching authority\remote SPS X
91.312 General Switching mode ENS O
General Switching mode\interlocked SPS X
General Switching mode\non-inter‐ SPS X
locked
91.317 General Block monitoring dir. SPS O
91.318 General Active settings group INS O
91.51 General Test mode ENC O
91.321 General Protection on SPC O
91.319 General Device logoff SPC O
91.308 General Switching auth. station SPC O
91.300 General Act. settings group 1 SPC O
91.301 General Act. settings group 2 SPC O
91.302 General Act. settings group 3 SPC O
91.303 General Act. settings group 4 SPC O
91.304 General Act. settings group 5 SPC O
91.305 General Act. settings group 6 SPC O
91.306 General Act. settings group 7 SPC O
91.307 General Act. settings group 8 SPC O

Device
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
4171.501 Device >GOOSE Stop SPS O
4171.301 Device Physical health ENS O
4171.303 Device Device startup SPS O
4171.304 Device Life contact SPS O
4171.305 Device Battery failure SPS O
4171.306 Device Clock fail SPS O
4171.310 Device Error meas. trans. ENS O
4171.312 Device Compensation error ENS O
4171.314 Device Offset error ENS O
4171.316 Device DIGSI active SPS O
4171.317 Device Simulation mode active SPS O
4171.318 Device Commiss. mode active SPS O
4171.319 Device Error memory SPS O
4171.320 Device Auxiliary Power Fail SPS O
4171.321 Device Cyber Security state ENS O
4171.322 Device Cyber-security event ENS O
4171.323 Device Event lost SPS O
4171.324 Device Chatter blocking SPS O
4171.325 Device Flash disk health ENS O
Totally Integrated
Automation Portal

Alarm handling
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
5971.503 Alarm handling >Group Alarm SPS O
5971.504 Alarm handling >Group Warning SPS O
5971.505 Alarm handling >Group indication SPS O
5971.300 Alarm handling Group alarm SPS O
5971.301 Alarm handling Group warning SPS O
5971.302 Alarm handling Group indication SPS O
5971.52 Alarm handling Behavior ENS O
5971.53 Alarm handling Health ENS O

Time sync.
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
8851.305 Time sync. Time sync. error SPS O X

Data
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
Data Fll Polaridad PT2 SPS H1.1 O
Data PT2 Indisponible SPS H2.2 O X
Data PT1 en prueba SPS L2.3 O X
Data Q0 33kV Abierto SPS H3.2 O X
Data Alarma Sist. Contrainc SPS H3.3 O
Data =E03 MCB Barra Oper SPS L3.4 O X
Data Error sinc de tiempo SPS X O
Data Sw Authority DPS X O X
Data Sw Mode DPS X O
Data Sw Mode\open SPS X
Data Alarma grave BH SPS X O
Data Dif. angulo excedido SPS X O
Data Dif. frecuencia excedido SPS X O
Data Dif. voltaje excedido SPS X O

Q0
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
6362.53 Q0 Health ENS O
Q0 Mando Cierre Manual SPS H4.1 O
Q0 Bloqueo SF6 SPS H4.2 O X
Q0 Perdida SF6 SPS H4.3 O
Q0 Proteccion Motor SPS H4.4 O X
Q0 Sup. carrera motor SPS H4.5 O X
Q0 Resorte Destensado SPS H4.6 O X
Q0 Anomalia SF6 SPS H4.9 O
Q0 Enclavamiento SPS X O X
Q0 Falla circuito disparo 1 SPS X O X
Q0 Alarma grave Q0 SPS X
Q0 Permisivo de cierre Q0 SPS X U2.1

Prot. Mecanicas
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
Prot. Mecanicas Disp Alta Temp Aceite SPS H6.1 L1.1,L3 R(X) O X
.1
Prot. Mecanicas Disp Rele Detector Gas SPS H6.2 L1.1,L3 R(X) O X
.2
Prot. Mecanicas Disp Valv Aliv Presion SPS H6.3 L1.1,L3 R(X) O X
.3
Prot. Mecanicas Disp Prot Conmutador SPS H6.4 L1.1,L3 R(X) O X
.4
Prot. Mecanicas Disp Valvula Autom SPS H6.5 L1.1,L3 R(X) O X
.5
Prot. Mecanicas Disp Indic Temp Bobina SPS H6.6 L1.1,L3 R(X) O X
.6
Prot. Mecanicas Disp Rele Presion Sub SPS H6.7 L1.1,L3 R(X) O X
.7
Prot. Mecanicas Alar Alta Temp Aceite SPS H6.9 L3.9 R(X) O X
Prot. Mecanicas Alar Rele Detector Gas SPS H6.10 L3.10 R(X) O X
Prot. Mecanicas Alar Max Niv Oil Trafo SPS H6.11 L3.11 R(X) O X
Prot. Mecanicas Alar Min Niv Oil Trafo SPS H6.12 L3.12 R(X) O X
Prot. Mecanicas Alar Rele Sup Conserv SPS H6.13 L3.13 R(X) O X
Prot. Mecanicas Alar Alta Temp Bobina SPS H6.14 L3.14 R(X) O X
Prot. Mecanicas Alar Rele Bloqueado SPS H6.15 L3.15 R(X) O X
Totally Integrated
Automation Portal

QZ1
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
QZ1 Enclavamiento SPS X O X

QZ1/
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
QZ1/ Enclavamiento SPS X O X

QZ9
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
QZ9 Enclavamiento SPS X O X

QZ9/
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
QZ9/ Enclavamiento SPS X O X

Q15
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
Q15 Enclavamiento SPS X O X
Q15 Fll Alim Señalizacion SPS H1.3 O X

Q8
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
Q8 Enclavamiento SPS X O X
Q8 Operacion Manual SPS H4.10 O X

Goose
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
Goose Pos\open SPS X
Goose Pos2\open SPS X
Goose FllCtoDis2 SPS X
Goose BloqSF6 SPS X
Goose Tr\general SPS X
Goose PT1Indisp SPS X

GIS
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
GIS Desbloqueo General SPS H3.1 O X
GIS Fll MCB AC AlimTabOp SPS H4.7 O
GIS Fll MCB DC AlimTabOp SPS H4.8 O
GIS Fll MCB AlimContSeñ SPS H4.11 O
GIS Panel Alarmas Indisp SPS H4.12 O
GIS Local/Remoto DPS CH5.15 O X
,OH5.1
6
GIS Local/Remoto\closed SPS X

R86
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
R86 Operado SPS H2.1 R(X) O X
R86 Reponer SPC On1.4 O

[FBI011_GAPC_CFC_CHART_c645a15d_a9d2_4502_ab74_18dd060b2421]ERROR: Textpool data with TextRef: 1:5 not found in loaded Textpool
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
0.0 [FBI011_GAPC_CFC_CHART_c645a15d_a OL0128 SPS
9d2_4502_ab74_18dd060b2421]ER‐
ROR: Textpool data with TextRef: 1:5 not
found in loaded Textpool

Power system
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
11.2311.500 General >Phs-rotation reversal SPS O
Totally Integrated
Automation Portal

Number Group Signal Type Source Destination


BI FK CFC BO LED FR L CFC D
11.2311.501 General >Invert Phases SPS O
11.2311.321 General Freq.out of oper.range SPS O
11.931.8881.3 Meas.point I-3ph 1\CT 3-phase Phases AB inverted SPS O
19
11.931.8881.3 Meas.point I-3ph 1\CT 3-phase Phases BC inverted SPS O
20
11.931.8881.3 Meas.point I-3ph 1\CT 3-phase Phases AC inverted SPS O
21
11.931.3841.3 Meas.point I-3ph 1\CT 1 Sampled val. current SAV X
00
11.931.3842.3 Meas.point I-3ph 1\CT 2 Sampled val. current SAV X
00
11.931.3843.3 Meas.point I-3ph 1\CT 3 Sampled val. current SAV X
00
11.931.3844.3 Meas.point I-3ph 1\CT 4 Sampled val. current SAV X
00
11.931.2491.8 Meas.point I-3ph 1\Supv. balan. I >Block function SPS O
2
11.931.2491.5 Meas.point I-3ph 1\Supv. balan. I Behavior ENS O
2
11.931.2491.5 Meas.point I-3ph 1\Supv. balan. I Inactive SPS O
4
11.931.2491.5 Meas.point I-3ph 1\Supv. balan. I Health ENS O
3
11.931.2491.7 Meas.point I-3ph 1\Supv. balan. I Failure SPS O
1
11.931.2551.8 Meas.point I-3ph 1\Supv. ph.seq.I >Block function SPS O
2
11.931.2551.5 Meas.point I-3ph 1\Supv. ph.seq.I Behavior ENS O
2
11.931.2551.5 Meas.point I-3ph 1\Supv. ph.seq.I Inactive SPS O
4
11.931.2551.5 Meas.point I-3ph 1\Supv. ph.seq.I Health ENS O
3
11.931.2551.7 Meas.point I-3ph 1\Supv. ph.seq.I Failure SPS O
1
11.931.2431.8 Meas.point I-3ph 1\Supv. sum I >Block function SPS O
2
11.931.2431.5 Meas.point I-3ph 1\Supv. sum I Behavior ENS O
2
11.931.2431.5 Meas.point I-3ph 1\Supv. sum I Health ENS O
3
11.931.2431.5 Meas.point I-3ph 1\Supv. sum I Inactive SPS O
4
11.931.2431.7 Meas.point I-3ph 1\Supv. sum I Failure SPS O
1
11.931.2401.8 Meas.point I-3ph 1\Supv.ADC sum I >Block function SPS O
2
11.931.2401.5 Meas.point I-3ph 1\Supv.ADC sum I Behavior ENS O
2
11.931.2401.5 Meas.point I-3ph 1\Supv.ADC sum I Inactive SPS O
4
11.931.2401.5 Meas.point I-3ph 1\Supv.ADC sum I Health ENS O
3
11.931.2401.7 Meas.point I-3ph 1\Supv.ADC sum I Failure SPS O
1
11.932.8881.3 Meas.point I-3ph 2\CT 3-phase Phases AB inverted SPS O
19
11.932.8881.3 Meas.point I-3ph 2\CT 3-phase Phases BC inverted SPS O
20
11.932.8881.3 Meas.point I-3ph 2\CT 3-phase Phases AC inverted SPS O
21
11.932.3841.3 Meas.point I-3ph 2\CT 1 Sampled val. current SAV X
00
11.932.3842.3 Meas.point I-3ph 2\CT 2 Sampled val. current SAV X
00
11.932.3843.3 Meas.point I-3ph 2\CT 3 Sampled val. current SAV X
00
11.932.3844.3 Meas.point I-3ph 2\CT 4 Sampled val. current SAV X
00
11.932.2491.8 Meas.point I-3ph 2\Supv. balan. I >Block function SPS O
2
11.932.2491.5 Meas.point I-3ph 2\Supv. balan. I Behavior ENS O
2
11.932.2491.5 Meas.point I-3ph 2\Supv. balan. I Inactive SPS O
4
11.932.2491.5 Meas.point I-3ph 2\Supv. balan. I Health ENS O
3
11.932.2491.7 Meas.point I-3ph 2\Supv. balan. I Failure SPS O
1
11.932.2551.8 Meas.point I-3ph 2\Supv. ph.seq.I >Block function SPS O
2
11.932.2551.5 Meas.point I-3ph 2\Supv. ph.seq.I Behavior ENS O
2
11.932.2551.5 Meas.point I-3ph 2\Supv. ph.seq.I Inactive SPS O
4
11.932.2551.5 Meas.point I-3ph 2\Supv. ph.seq.I Health ENS O
3
Totally Integrated
Automation Portal

Number Group Signal Type Source Destination


BI FK CFC BO LED FR L CFC D
11.932.2551.7 Meas.point I-3ph 2\Supv. ph.seq.I Failure SPS O
1
11.932.2431.8 Meas.point I-3ph 2\Supv. sum I >Block function SPS O
2
11.932.2431.5 Meas.point I-3ph 2\Supv. sum I Behavior ENS O
2
11.932.2431.5 Meas.point I-3ph 2\Supv. sum I Health ENS O
3
11.932.2431.5 Meas.point I-3ph 2\Supv. sum I Inactive SPS O
4
11.932.2431.7 Meas.point I-3ph 2\Supv. sum I Failure SPS O
1
11.932.2401.8 Meas.point I-3ph 2\Supv.ADC sum I >Block function SPS O
2
11.932.2401.5 Meas.point I-3ph 2\Supv.ADC sum I Behavior ENS O
2
11.932.2401.5 Meas.point I-3ph 2\Supv.ADC sum I Inactive SPS O
4
11.932.2401.5 Meas.point I-3ph 2\Supv.ADC sum I Health ENS O
3
11.932.2401.7 Meas.point I-3ph 2\Supv.ADC sum I Failure SPS O
1
11.941.8911.3 Meas.point V-3ph 1\VT 3-phase Phases AB inverted SPS O
15
11.941.8911.3 Meas.point V-3ph 1\VT 3-phase Phases AC inverted SPS O
17
11.941.8911.3 Meas.point V-3ph 1\VT 3-phase Phases BC inverted SPS O
16
11.941.3811.3 Meas.point V-3ph 1\VT 1 Sampled val. voltage SAV X
00
11.941.3812.3 Meas.point V-3ph 1\VT 2 Sampled val. voltage SAV X
00
11.941.3813.3 Meas.point V-3ph 1\VT 3 Sampled val. voltage SAV X
00
11.941.2521.8 Meas.point V-3ph 1\Supv. balan. V >Block function SPS O
2
11.941.2521.5 Meas.point V-3ph 1\Supv. balan. V Behavior ENS O
2
11.941.2521.5 Meas.point V-3ph 1\Supv. balan. V Inactive SPS O
4
11.941.2521.5 Meas.point V-3ph 1\Supv. balan. V Health ENS O
3
11.941.2521.7 Meas.point V-3ph 1\Supv. balan. V Failure SPS O
1
11.941.2581.8 Meas.point V-3ph 1\Supv. ph.seq.V >Block function SPS O
2
11.941.2581.5 Meas.point V-3ph 1\Supv. ph.seq.V Behavior ENS O
2
11.941.2581.5 Meas.point V-3ph 1\Supv. ph.seq.V Inactive SPS O
4
11.941.2581.5 Meas.point V-3ph 1\Supv. ph.seq.V Health ENS O
3
11.941.2581.7 Meas.point V-3ph 1\Supv. ph.seq.V Failure SPS O
1
11.941.2461.8 Meas.point V-3ph 1\Supv. sum V >Block function SPS O
2
11.941.2461.5 Meas.point V-3ph 1\Supv. sum V Behavior ENS O
2
11.941.2461.5 Meas.point V-3ph 1\Supv. sum V Inactive SPS O
4
11.941.2461.5 Meas.point V-3ph 1\Supv. sum V Health ENS O
3
11.941.2461.7 Meas.point V-3ph 1\Supv. sum V Failure SPS O
1
11.941.2641.5 Meas.point V-3ph 1\VT miniatureCB >Open SPS L3.4 O
00
11.961.3811.3 Meas.point V-1ph 1\VT 1 Sampled val. voltage SAV X
00
11.961.2641.5 Meas.point V-1ph 1\VT miniatureCB >Open SPS O
00

Recording
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
51.7441.52 Grnd.-flt log Behavior ENS O
51.7441.53 Grnd.-flt log Health ENS O
51.7441.310 Grnd.-flt log Fault number INS O,G
51.7441.311 Grnd.-flt log Ground-fault log is full INS G
51.791.2761.5 Fault recorder\Control >External start SPS X O
02
51.791.2761.5 Fault recorder\Control >Manual start SPS O
03
51.791.2761.3 Fault recorder\Control Fault number INS O,F
10
51.791.2761.3 Fault recorder\Control Tmax reduced SPS O
27
Totally Integrated
Automation Portal

Number Group Signal Type Source Destination


BI FK CFC BO LED FR L CFC D
51.791.2761.3 Fault recorder\Control Fault log is full INS F
24
51.791.2761.3 Fault recorder\Control Start record SPC O
00
51.791.2761.3 Fault recorder\Control Reset memory SPC O
05
51.791.2761.3 Fault recorder\Control Clear memory SPC O
06

J:Onboard Ethernet
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
101.2311.53 General Health ENS O

E:ETH-BB-2FO
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
102.2311.53 General Health ENS O
102.1031.0.30 Channel 1\SNTP Channel Live SPS O
4
102.1031.0.53 Channel 1\SNTP Health ENS O
102.1031.0.30 Channel 1\RSTP Channel Live SPS O X
4
102.1031.0.53 Channel 1\RSTP Health ENS O
102.1031.0.30 Channel 1\RSTP Redund. Channel Live SPS O X
5
Channel 1\RSTP Fail_CH1 SPS X
Channel 1\RSTP Fail_CH2 SPS X
102.1031.0.30 Channel 1\IEC 61850-8-1 Channel Live SPS O
1
102.1031.0.53 Channel 1\IEC 61850-8-1 Health ENS O

Transformer side 1
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
Group indicat. Pickup\general SPS U4.15
Group indicat. Pickup\phs A SPS L1.2
Group indicat. Pickup\phs B SPS L1.3
Group indicat. Pickup\phs C SPS L1.4
Group indicat. Pickup\gnd SPS L1.5
Group indicat. Operate\general SPS U4.16
911.4141.52 Inrush detect. Behavior ENS O
911.4141.53 Inrush detect. Health ENS O
911.4141.54 Inrush detect. Inactive SPS O
911.4141.55 Inrush detect. Pickup ACD F
911.4141.300 Inrush detect. 2.harmonic phase A SPS F
911.4141.301 Inrush detect. 2.harmonic phase B SPS F
911.4141.302 Inrush detect. 2.harmonic phase C SPS F
911.4141.305 Inrush detect. CWA SPS F
911.4141.306 Inrush detect. Crossblocking SPS F
911.1131.4681 Process monitor\Closure detec. Closure SPS F
.300
300.0 Fund./sym.comp.\Fundam Iph:A CMV X
300.0 Fund./sym.comp.\Fundam Iph:B CMV X
300.0 Fund./sym.comp.\Fundam Iph:C CMV X
911.191.601.5 49 Th.overl.-A 1\49 Th.overl. 1 >Block stage SPS O
00
911.191.601.5 49 Th.overl.-A 1\49 Th.overl. 1 >Reset thermal replica SPS O
01
911.191.601.5 49 Th.overl.-A 1\49 Th.overl. 1 >Emergency start SPS O
02
911.191.601.5 49 Th.overl.-A 1\49 Th.overl. 1 Behavior ENS O
2
911.191.601.5 49 Th.overl.-A 1\49 Th.overl. 1 Health ENS O
3
911.191.601.5 49 Th.overl.-A 1\49 Th.overl. 1 Inactive SPS O
4
911.191.601.5 49 Th.overl.-A 1\49 Th.overl. 1 Pickup ACD F
5
911.191.601.5 49 Th.overl.-A 1\49 Th.overl. 1 Operate ACT F
7
911.191.601.3 49 Th.overl.-A 1\49 Th.overl. 1 Operate alarm only ACT O
00
911.191.601.3 49 Th.overl.-A 1\49 Th.overl. 1 Current warning SPS O
01
911.191.601.3 49 Th.overl.-A 1\49 Th.overl. 1 Thermal warning SPS O
02
911.191.601.3 49 Th.overl.-A 1\49 Th.overl. 1 Block close SPS O
03
911.201.661.8 50/51 OC-3ph-A1\Definite-T 1 >Block stage SPS O
1
Totally Integrated
Automation Portal

Number Group Signal Type Source Destination


BI FK CFC BO LED FR L CFC D
911.201.661.5 50/51 OC-3ph-A1\Definite-T 1 >Block delay & op. SPS F
00
911.201.661.5 50/51 OC-3ph-A1\Definite-T 1 Behavior ENS O
2
911.201.661.5 50/51 OC-3ph-A1\Definite-T 1 Health ENS O
3
911.201.661.5 50/51 OC-3ph-A1\Definite-T 1 Inactive SPS O
4
911.201.661.5 50/51 OC-3ph-A1\Definite-T 1 Pickup ACD F
5
911.201.661.5 50/51 OC-3ph-A1\Definite-T 1 Operate ACT F
7
50/51 OC-3ph-A1\Definite-T 1 Operate\general SPS R(X)
911.201.661.6 50/51 OC-3ph-A1\Definite-T 1 Inrush blocks operate ACT F
0
911.201.662.8 50/51 OC-3ph-A1\Definite-T 2 >Block stage SPS O
1
911.201.662.5 50/51 OC-3ph-A1\Definite-T 2 >Block delay & op. SPS F
00
911.201.662.5 50/51 OC-3ph-A1\Definite-T 2 Behavior ENS O
2
911.201.662.5 50/51 OC-3ph-A1\Definite-T 2 Health ENS O
3
911.201.662.5 50/51 OC-3ph-A1\Definite-T 2 Inactive SPS O
4
911.201.662.5 50/51 OC-3ph-A1\Definite-T 2 Pickup ACD F
5
911.201.662.5 50/51 OC-3ph-A1\Definite-T 2 Operate ACT F
7
911.201.662.6 50/51 OC-3ph-A1\Definite-T 2 Inrush blocks operate ACT F
0
911.201.691.8 50/51 OC-3ph-A1\Inverse-T 1 >Block stage SPS O
1
911.201.691.5 50/51 OC-3ph-A1\Inverse-T 1 >Block delay & op. SPS F
00
911.201.691.5 50/51 OC-3ph-A1\Inverse-T 1 Behavior ENS O
2
911.201.691.5 50/51 OC-3ph-A1\Inverse-T 1 Health ENS O
3
911.201.691.5 50/51 OC-3ph-A1\Inverse-T 1 Inactive SPS O
4
911.201.691.5 50/51 OC-3ph-A1\Inverse-T 1 Pickup ACD F
5
911.201.691.5 50/51 OC-3ph-A1\Inverse-T 1 Operate ACT F
7
50/51 OC-3ph-A1\Inverse-T 1 Operate\general SPS R(X)
911.201.691.5 50/51 OC-3ph-A1\Inverse-T 1 Disk emulation running SPS F
9
911.201.691.6 50/51 OC-3ph-A1\Inverse-T 1 Inrush blocks operate ACT F
0
50/51 OC-3ph-A1\Group indicat. Pickup\phs A SPS R(X)
50/51 OC-3ph-A1\Group indicat. Pickup\phs B SPS R(X)
50/51 OC-3ph-A1\Group indicat. Pickup\phs C SPS R(X)
50/51 OC-3ph-A1\Group indicat. Operate\general SPS L1.7 R(X)
911.211.751.8 50N/51N OC-gnd-A1\Definite-T 1 >Block stage SPS O
1
911.211.751.5 50N/51N OC-gnd-A1\Definite-T 1 >Block delay & op. SPS F
00
911.211.751.5 50N/51N OC-gnd-A1\Definite-T 1 Behavior ENS O
2
911.211.751.5 50N/51N OC-gnd-A1\Definite-T 1 Health ENS O
3
911.211.751.5 50N/51N OC-gnd-A1\Definite-T 1 Inactive SPS O
4
911.211.751.6 50N/51N OC-gnd-A1\Definite-T 1 Inrush blocks operate ACT F
0
911.211.751.5 50N/51N OC-gnd-A1\Definite-T 1 Operate ACT F
7
911.211.751.5 50N/51N OC-gnd-A1\Definite-T 1 Pickup ACD F
5
911.211.752.8 50N/51N OC-gnd-A1\Definite-T 2 >Block stage SPS O
1
911.211.752.5 50N/51N OC-gnd-A1\Definite-T 2 >Block delay & op. SPS F
00
911.211.752.5 50N/51N OC-gnd-A1\Definite-T 2 Behavior ENS O
2
911.211.752.5 50N/51N OC-gnd-A1\Definite-T 2 Health ENS O
3
911.211.752.5 50N/51N OC-gnd-A1\Definite-T 2 Inactive SPS O
4
911.211.752.6 50N/51N OC-gnd-A1\Definite-T 2 Inrush blocks operate ACT F
0
911.211.752.5 50N/51N OC-gnd-A1\Definite-T 2 Operate ACT F
7
911.211.752.5 50N/51N OC-gnd-A1\Definite-T 2 Pickup ACD F
5
911.211.781.8 50N/51N OC-gnd-A1\Inverse-T 1 >Block stage SPS O
1
Totally Integrated
Automation Portal

Number Group Signal Type Source Destination


BI FK CFC BO LED FR L CFC D
911.211.781.5 50N/51N OC-gnd-A1\Inverse-T 1 >Block delay & op. SPS F
00
911.211.781.5 50N/51N OC-gnd-A1\Inverse-T 1 Behavior ENS O
2
911.211.781.5 50N/51N OC-gnd-A1\Inverse-T 1 Disk emulation running SPS F
9
911.211.781.5 50N/51N OC-gnd-A1\Inverse-T 1 Health ENS O
3
911.211.781.5 50N/51N OC-gnd-A1\Inverse-T 1 Inactive SPS O
4
911.211.781.6 50N/51N OC-gnd-A1\Inverse-T 1 Inrush blocks operate ACT F
0
911.211.781.5 50N/51N OC-gnd-A1\Inverse-T 1 Operate ACT F
7
911.211.781.5 50N/51N OC-gnd-A1\Inverse-T 1 Pickup ACD F
5
50N/51N OC-gnd-A1\Group indicat. Operate\general SPS L1.8

Transformer side 2
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
Group indicat. Pickup\general SPS U4.15
Group indicat. Pickup\phs A SPS L1.2
Group indicat. Pickup\phs B SPS L1.3
Group indicat. Pickup\phs C SPS L1.4
Group indicat. Pickup\gnd SPS L1.5
Group indicat. Operate\general SPS U4.16
912.4141.52 Inrush detect. Behavior ENS O
912.4141.53 Inrush detect. Health ENS O
912.4141.54 Inrush detect. Inactive SPS O
912.4141.55 Inrush detect. Pickup ACD F
912.4141.300 Inrush detect. 2.harmonic phase A SPS F
912.4141.301 Inrush detect. 2.harmonic phase B SPS F
912.4141.302 Inrush detect. 2.harmonic phase C SPS F
912.4141.305 Inrush detect. CWA SPS F
912.4141.306 Inrush detect. Crossblocking SPS F
912.1131.4681 Process monitor\Closure detec. Closure SPS F
.300
300.0 Fund./sym.comp.\Fundam Iph:A CMV X
300.0 Fund./sym.comp.\Fundam Iph:B CMV X
300.0 Fund./sym.comp.\Fundam Iph:C CMV X
912.201.661.8 50/51 OC-3ph-A1\Definite-T 1 >Block stage SPS O
1
912.201.661.5 50/51 OC-3ph-A1\Definite-T 1 >Block delay & op. SPS F
00
912.201.661.5 50/51 OC-3ph-A1\Definite-T 1 Behavior ENS O
2
912.201.661.5 50/51 OC-3ph-A1\Definite-T 1 Health ENS O
3
912.201.661.5 50/51 OC-3ph-A1\Definite-T 1 Inactive SPS O
4
912.201.661.5 50/51 OC-3ph-A1\Definite-T 1 Pickup ACD F
5
912.201.661.5 50/51 OC-3ph-A1\Definite-T 1 Operate ACT F
7
912.201.661.6 50/51 OC-3ph-A1\Definite-T 1 Inrush blocks operate ACT F
0
912.201.662.8 50/51 OC-3ph-A1\Definite-T 2 >Block stage SPS O
1
912.201.662.5 50/51 OC-3ph-A1\Definite-T 2 >Block delay & op. SPS F
00
912.201.662.5 50/51 OC-3ph-A1\Definite-T 2 Behavior ENS O
2
912.201.662.5 50/51 OC-3ph-A1\Definite-T 2 Health ENS O
3
912.201.662.5 50/51 OC-3ph-A1\Definite-T 2 Inactive SPS O
4
912.201.662.5 50/51 OC-3ph-A1\Definite-T 2 Pickup ACD F
5
912.201.662.5 50/51 OC-3ph-A1\Definite-T 2 Operate ACT F
7
912.201.662.6 50/51 OC-3ph-A1\Definite-T 2 Inrush blocks operate ACT F
0
912.201.691.8 50/51 OC-3ph-A1\Inverse-T 1 >Block stage SPS O
1
912.201.691.5 50/51 OC-3ph-A1\Inverse-T 1 >Block delay & op. SPS F
00
912.201.691.5 50/51 OC-3ph-A1\Inverse-T 1 Behavior ENS O
2
912.201.691.5 50/51 OC-3ph-A1\Inverse-T 1 Health ENS O
3
912.201.691.5 50/51 OC-3ph-A1\Inverse-T 1 Inactive SPS O
4
912.201.691.5 50/51 OC-3ph-A1\Inverse-T 1 Pickup ACD F
5
Totally Integrated
Automation Portal

Number Group Signal Type Source Destination


BI FK CFC BO LED FR L CFC D
912.201.691.5 50/51 OC-3ph-A1\Inverse-T 1 Operate ACT F
7
912.201.691.5 50/51 OC-3ph-A1\Inverse-T 1 Disk emulation running SPS F
9
912.201.691.6 50/51 OC-3ph-A1\Inverse-T 1 Inrush blocks operate ACT F
0
50/51 OC-3ph-A1\Group indicat. Operate\general SPS L1.9
912.211.751.8 50N/51N OC-gnd-A1\Definite-T 1 >Block stage SPS O
1
912.211.751.5 50N/51N OC-gnd-A1\Definite-T 1 >Block delay & op. SPS F
00
912.211.751.5 50N/51N OC-gnd-A1\Definite-T 1 Behavior ENS O
2
912.211.751.5 50N/51N OC-gnd-A1\Definite-T 1 Health ENS O
3
912.211.751.5 50N/51N OC-gnd-A1\Definite-T 1 Inactive SPS O
4
912.211.751.6 50N/51N OC-gnd-A1\Definite-T 1 Inrush blocks operate ACT F
0
912.211.751.5 50N/51N OC-gnd-A1\Definite-T 1 Operate ACT F
7
912.211.751.5 50N/51N OC-gnd-A1\Definite-T 1 Pickup ACD F
5
912.211.752.8 50N/51N OC-gnd-A1\Definite-T 2 >Block stage SPS O
1
912.211.752.5 50N/51N OC-gnd-A1\Definite-T 2 >Block delay & op. SPS F
00
912.211.752.5 50N/51N OC-gnd-A1\Definite-T 2 Behavior ENS O
2
912.211.752.5 50N/51N OC-gnd-A1\Definite-T 2 Health ENS O
3
912.211.752.5 50N/51N OC-gnd-A1\Definite-T 2 Inactive SPS O
4
912.211.752.6 50N/51N OC-gnd-A1\Definite-T 2 Inrush blocks operate ACT F
0
912.211.752.5 50N/51N OC-gnd-A1\Definite-T 2 Operate ACT F
7
912.211.752.5 50N/51N OC-gnd-A1\Definite-T 2 Pickup ACD F
5
912.211.781.8 50N/51N OC-gnd-A1\Inverse-T 1 >Block stage SPS O
1
912.211.781.5 50N/51N OC-gnd-A1\Inverse-T 1 >Block delay & op. SPS F
00
912.211.781.5 50N/51N OC-gnd-A1\Inverse-T 1 Behavior ENS O
2
912.211.781.5 50N/51N OC-gnd-A1\Inverse-T 1 Disk emulation running SPS F
9
912.211.781.5 50N/51N OC-gnd-A1\Inverse-T 1 Health ENS O
3
912.211.781.5 50N/51N OC-gnd-A1\Inverse-T 1 Inactive SPS O
4
912.211.781.6 50N/51N OC-gnd-A1\Inverse-T 1 Inrush blocks operate ACT F
0
912.211.781.5 50N/51N OC-gnd-A1\Inverse-T 1 Operate ACT F
7
912.211.781.5 50N/51N OC-gnd-A1\Inverse-T 1 Pickup ACD F
5
50N/51N OC-gnd-A1\Group indicat. Operate\general SPS L1.10

Transformer diff. 1
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
Group indicat. Pickup\general SPS U4.15
Group indicat. Pickup\phs A SPS L1.2
Group indicat. Pickup\phs B SPS L1.3
Group indicat. Pickup\phs C SPS L1.4
Group indicat. Operate\general SPS U4.16
300.0 87T diff. prot. 1\General I diff.:A CMV X
300.0 87T diff. prot. 1\General I diff.:B CMV X
300.0 87T diff. prot. 1\General I diff.:C CMV X
87T diff. prot. 1\General I diff.\phs A MV R(X)
87T diff. prot. 1\General I diff.\phs B MV R(X)
87T diff. prot. 1\General I diff.\phs C MV R(X)
301.0 87T diff. prot. 1\General I restr.:A CMV X
301.0 87T diff. prot. 1\General I restr.:B CMV X
301.0 87T diff. prot. 1\General I restr.:C CMV X
87T diff. prot. 1\General I restr.\phs A MV R(X)
87T diff. prot. 1\General I restr.\phs B MV R(X)
87T diff. prot. 1\General I restr.\phs C MV R(X)
901.1691.2311 87T diff. prot. 1\General I diff. operate phA MV F
.311
901.1691.2311 87T diff. prot. 1\General I diff. operate phB MV F
.312
901.1691.2311 87T diff. prot. 1\General I diff. operate phC MV F
.313
Totally Integrated
Automation Portal

Number Group Signal Type Source Destination


BI FK CFC BO LED FR L CFC D
901.1691.2311 87T diff. prot. 1\General I restr. operate phA MV F
.314
901.1691.2311 87T diff. prot. 1\General I restr. operate phB MV F
.315
901.1691.2311 87T diff. prot. 1\General I restr. operate phC MV F
.316
901.1691.1104 87T diff. prot. 1\I-DIFF >Block stage SPS O
1.81
901.1691.1104 87T diff. prot. 1\I-DIFF Behavior ENS O
1.52
901.1691.1104 87T diff. prot. 1\I-DIFF Health ENS O
1.53
901.1691.1104 87T diff. prot. 1\I-DIFF Inactive SPS O
1.54
901.1691.1104 87T diff. prot. 1\I-DIFF Pickup ACD F
1.55
87T diff. prot. 1\I-DIFF Pickup\phs A SPS R(X)
87T diff. prot. 1\I-DIFF Pickup\phs B SPS R(X)
87T diff. prot. 1\I-DIFF Pickup\phs C SPS R(X)
901.1691.1104 87T diff. prot. 1\I-DIFF Operate ACT F
1.57
87T diff. prot. 1\I-DIFF Operate\phs A SPS R(X)
87T diff. prot. 1\I-DIFF Operate\phs B SPS R(X)
87T diff. prot. 1\I-DIFF Operate\phs C SPS R(X)
901.1691.1104 87T diff. prot. 1\I-DIFF Slope 1 MV F
1.301
901.1691.1104 87T diff. prot. 1\I-DIFF Incr. of char. (Start) SPS R(X) O,F
1.302
901.1691.1104 87T diff. prot. 1\I-DIFF Increase of char. (DC) SPS R(X) F
1.303
901.1691.1104 87T diff. prot. 1\I-DIFF Blocked by inrush SPS F
1.304
901.1691.1104 87T diff. prot. 1\I-DIFF Blocked by 2.Harmon. ACT F
1.305
87T diff. prot. 1\I-DIFF Blocked by 2.Harmon.\phs A SPS R(X)
87T diff. prot. 1\I-DIFF Blocked by 2.Harmon.\phs B SPS R(X)
87T diff. prot. 1\I-DIFF Blocked by 2.Harmon.\phs C SPS R(X)
901.1691.1104 87T diff. prot. 1\I-DIFF Crossblock by 2.Harm. SPS R(X) F
1.306
901.1691.1104 87T diff. prot. 1\I-DIFF Blocked by CWA SPS R(X) F
1.307
901.1691.1104 87T diff. prot. 1\I-DIFF Blocked by 3.Harmon. ACT F
1.308
901.1691.1104 87T diff. prot. 1\I-DIFF Crossblock by 3.Harm. SPS F
1.309
901.1691.1104 87T diff. prot. 1\I-DIFF Blocked by 5.Harmon. ACT F
1.310
87T diff. prot. 1\I-DIFF Blocked by 5.Harmon.\phs A SPS R(X)
87T diff. prot. 1\I-DIFF Blocked by 5.Harmon.\phs B SPS R(X)
87T diff. prot. 1\I-DIFF Blocked by 5.Harmon.\phs C SPS R(X)
901.1691.1104 87T diff. prot. 1\I-DIFF Crossblock by 5.Harm. SPS R(X) F
1.311
901.1691.1104 87T diff. prot. 1\I-DIFF Blocked by ext. fault ACT F
1.312
87T diff. prot. 1\I-DIFF Blocked by ext. fault\phs A SPS R(X)
87T diff. prot. 1\I-DIFF Blocked by ext. fault\phs B SPS R(X)
87T diff. prot. 1\I-DIFF Blocked by ext. fault\phs C SPS R(X)
901.1691.1104 87T diff. prot. 1\I-DIFF Crossbl. by ext. fault SPS R(X) F
1.313
901.1691.1104 87T diff. prot. 1\I-DIFF CWA int. fault detected SPS R(X) F
1.316
901.1691.1107 87T diff. prot. 1\I-DIFF fast >Block stage SPS O
1.81
901.1691.1107 87T diff. prot. 1\I-DIFF fast Behavior ENS O
1.52
901.1691.1107 87T diff. prot. 1\I-DIFF fast Health ENS O
1.53
901.1691.1107 87T diff. prot. 1\I-DIFF fast Inactive SPS O
1.54
901.1691.1107 87T diff. prot. 1\I-DIFF fast Pickup ACD F
1.55
87T diff. prot. 1\I-DIFF fast Pickup\phs A SPS R(X)
87T diff. prot. 1\I-DIFF fast Pickup\phs B SPS R(X)
87T diff. prot. 1\I-DIFF fast Pickup\phs C SPS R(X)
901.1691.1107 87T diff. prot. 1\I-DIFF fast Operate ACT F
1.57
87T diff. prot. 1\I-DIFF fast Operate\phs A SPS R(X)
87T diff. prot. 1\I-DIFF fast Operate\phs B SPS R(X)
87T diff. prot. 1\I-DIFF fast Operate\phs C SPS R(X)
87T diff. prot. 1\Group indicat. Operate\general SPS U1.3 L1.6
Totally Integrated
Automation Portal

Q0
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
Trip logic Trip indication\general SPS U1.1,U L1.1 R(X) X
1.2,U6.
1
201.4261.500 Circuit break. >Ready SPS O
201.4261.501 Circuit break. >Acquisition blocking SPS O
201.4261.504 Circuit break. >Reset AcqBlk&Subst SPS O
201.4261.502 Circuit break. >Reset switch statist. SPS O
201.4261.503 Circuit break. External health ENS O
201.4261.53 Circuit break. Health ENS O
201.4261.300 Circuit break. Trip/open cmd. SPS U4.1,U O,F
5.1
201.4261.301 Circuit break. Close command SPS X4.2,X O,F
5.2
201.4261.303 Circuit break. Definitive trip SPS F
201.4261.311 Circuit break. Break.-current phs A MV F
201.4261.312 Circuit break. Break.-current phs B MV F
201.4261.313 Circuit break. Break.-current phs C MV F
201.4261.317 Circuit break. Break. current 3I0/IN MV F
201.4261.58 Circuit break. Position DPC CH5.2, O
OH5.1
Circuit break. Position\open SPS U6.3 R(X) X
Circuit break. Position\closed SPS R(X) X
201.6541.500 Manual close >Input SPS H4.1 O
201.6541.501 Manual close >Block manual close SPS O
201.6541.300 Manual close Detected SPS O
201.4201.53 Control Health ENS O
201.4201.58 Control Cmd. with feedback DPC O X
201.4231.500 Interlocking >Enable opening SPS X
201.4231.501 Interlocking >Enable closing SPS X
201.4231.53 Interlocking Health ENS O
201.6151.53 CB test Health ENS O
201.6151.301 CB test Test execution ENS O
201.6151.302 CB test Trip command issued ENS O
201.6151.303 CB test Close command issued ENS O
201.6151.304 CB test Test canceled ENS O
201.4411.82 74TC sup.2BI 1 >Block function SPS O
201.4411.500 74TC sup.2BI 1 >Trip relay SPS H3.7
201.4411.503 74TC sup.2BI 1 >CB auxiliary contact SPS H3.8
201.4411.52 74TC sup.2BI 1 Behavior ENS O
201.4411.53 74TC sup.2BI 1 Health ENS O
201.4411.54 74TC sup.2BI 1 Inactive SPS O
201.4411.71 74TC sup.2BI 1 Trip-circuit failure SPS O X
201.4411.301 74TC sup.2BI 1 Input sig. not routed SPS O
201.1151.2311 25 Synchronization\General Blocked no V selected SPS O
.304
201.1151.2311 25 Synchronization\General Multiple selection SPS O
.303
201.1151.5071 25 Synchronization\Synchrocheck 1 >Block stage SPS O
.81
201.1151.5071 25 Synchronization\Synchrocheck 1 >Block close command SPS O
.501
201.1151.5071 25 Synchronization\Synchrocheck 1 >Op. mode 'dir.cls.cmd' SPS O
.508
201.1151.5071 25 Synchronization\Synchrocheck 1 >Selection SPS O
.500
201.1151.5071 25 Synchronization\Synchrocheck 1 >Stop syn. process SPS O
.504
201.1151.5071 25 Synchronization\Synchrocheck 1 >Start syn. process SPS O
.503
201.1151.5071 25 Synchronization\Synchrocheck 1 >Start / stop syn.proc. SPS H4.1 O
.502
201.1151.5071 25 Synchronization\Synchrocheck 1 >Op. mode 'V1>V2<' SPS O X
.505
201.1151.5071 25 Synchronization\Synchrocheck 1 >Op. mode 'V1<V2>' SPS O X
.506
201.1151.5071 25 Synchronization\Synchrocheck 1 >Op. mode 'V1<V2<' SPS O X
.507
201.1151.5071 25 Synchronization\Synchrocheck 1 α dif.too large(α2>α1) SPS O X
.321
201.1151.5071 25 Synchronization\Synchrocheck 1 α dif.too large(α2<α1) SPS O X
.322
201.1151.5071 25 Synchronization\Synchrocheck 1 Angle difference OK SPS O
.326
201.1151.5071 25 Synchronization\Synchrocheck 1 Behavior ENS O
.52
201.1151.5071 25 Synchronization\Synchrocheck 1 Health ENS O
.53
201.1151.5071 25 Synchronization\Synchrocheck 1 Frequency f1 > fmax SPS O
.309
201.1151.5071 25 Synchronization\Synchrocheck 1 f dif.too large(f2>f1) SPS O X
.319
201.1151.5071 25 Synchronization\Synchrocheck 1 Frequency f1 < fmin SPS O
.310
201.1151.5071 25 Synchronization\Synchrocheck 1 Frequency f2 > fmax SPS O
.311
Totally Integrated
Automation Portal

Number Group Signal Type Source Destination


BI FK CFC BO LED FR L CFC D
201.1151.5071 25 Synchronization\Synchrocheck 1 f dif.too large(f2<f1) SPS O X
.320
201.1151.5071 25 Synchronization\Synchrocheck 1 Frequency f2 < fmin SPS O
.312
201.1151.5071 25 Synchronization\Synchrocheck 1 Frequency diff. OK SPS O
.327
201.1151.5071 25 Synchronization\Synchrocheck 1 In progress SPS O
.328
201.1151.5071 25 Synchronization\Synchrocheck 1 Inactive SPS O
.54
201.1151.5071 25 Synchronization\Synchrocheck 1 Max. time exceeded SPS O
.304
201.1151.5071 25 Synchronization\Synchrocheck 1 Release close cmd. SPS O
.324
201.1151.5071 25 Synchronization\Synchrocheck 1 Setting error SPS O
.323
201.1151.5071 25 Synchronization\Synchrocheck 1 All sync. conditio. OK SPS O X
.305
201.1151.5071 25 Synchronization\Synchrocheck 1 Voltage V1 > Vmax SPS O
.313
201.1151.5071 25 Synchronization\Synchrocheck 1 Cond. V1>V2< fulfilled SPS O
.306
201.1151.5071 25 Synchronization\Synchrocheck 1 V dif.too large(V2>V1) SPS O X
.317
201.1151.5071 25 Synchronization\Synchrocheck 1 Voltage V1 < Vmin SPS O
.314
201.1151.5071 25 Synchronization\Synchrocheck 1 Cond. V1<V2> fulfilled SPS O
.307
201.1151.5071 25 Synchronization\Synchrocheck 1 Cond. V1<V2< fulfilled SPS O
.308
201.1151.5071 25 Synchronization\Synchrocheck 1 Voltage V2 > Vmax SPS O
.315
201.1151.5071 25 Synchronization\Synchrocheck 1 V dif.too large(V2<V1) SPS O X
.318
201.1151.5071 25 Synchronization\Synchrocheck 1 Voltage V2 < Vmin SPS O
.316
201.1151.5071 25 Synchronization\Synchrocheck 1 Voltage difference OK SPS O
.325
201.1151.5041 25 Synchronization\Sychr./Asycr.1 >Block stage SPS O
.81
201.1151.5041 25 Synchronization\Sychr./Asycr.1 >Block close command SPS O
.501
201.1151.5041 25 Synchronization\Sychr./Asycr.1 >Op. mode 'dir.cls.cmd' SPS O
.508
201.1151.5041 25 Synchronization\Sychr./Asycr.1 >Selection SPS O
.500
201.1151.5041 25 Synchronization\Sychr./Asycr.1 >Stop syn. process SPS O
.504
201.1151.5041 25 Synchronization\Sychr./Asycr.1 >Start syn. process SPS O
.503
201.1151.5041 25 Synchronization\Sychr./Asycr.1 >Start / stop syn.proc. SPS O
.502
201.1151.5041 25 Synchronization\Sychr./Asycr.1 >Op. mode 'V1>V2<' SPS O
.505
201.1151.5041 25 Synchronization\Sychr./Asycr.1 >Op. mode 'V1<V2>' SPS O
.506
201.1151.5041 25 Synchronization\Sychr./Asycr.1 >Op. mode 'V1<V2<' SPS O
.507
201.1151.5041 25 Synchronization\Sychr./Asycr.1 α dif.too large(α2>α1) SPS O
.321
201.1151.5041 25 Synchronization\Sychr./Asycr.1 α dif.too large(α2<α1) SPS O
.322
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Angle difference OK SPS O
.326
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Behavior ENS O
.52
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Health ENS O
.53
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Frequency f1 > fmax SPS O
.309
201.1151.5041 25 Synchronization\Sychr./Asycr.1 f dif.too large(f2>f1) SPS O
.319
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Frequency f1 < fmin SPS O
.310
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Frequency f2 > fmax SPS O
.311
201.1151.5041 25 Synchronization\Sychr./Asycr.1 f dif.too large(f2<f1) SPS O
.320
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Frequency f2 < fmin SPS O
.312
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Frequency diff. OK SPS O
.327
201.1151.5041 25 Synchronization\Sychr./Asycr.1 State f-synchronous SPS O
.303
201.1151.5041 25 Synchronization\Sychr./Asycr.1 In progress SPS O
.328
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Inactive SPS O
.54
Totally Integrated
Automation Portal

Number Group Signal Type Source Destination


BI FK CFC BO LED FR L CFC D
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Max. time exceeded SPS O
.304
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Release close cmd. SPS O
.324
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Setting error SPS O
.323
201.1151.5041 25 Synchronization\Sychr./Asycr.1 All sync. conditio. OK SPS O
.305
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Voltage V1 > Vmax SPS O
.313
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Cond. V1>V2< fulfilled SPS O
.306
201.1151.5041 25 Synchronization\Sychr./Asycr.1 V dif.too large(V2>V1) SPS O
.317
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Voltage V1 < Vmin SPS O
.314
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Cond. V1<V2> fulfilled SPS O
.307
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Cond. V1<V2< fulfilled SPS O
.308
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Voltage V2 > Vmax SPS O
.315
201.1151.5041 25 Synchronization\Sychr./Asycr.1 V dif.too large(V2<V1) SPS O
.318
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Voltage V2 < Vmin SPS O
.316
201.1151.5041 25 Synchronization\Sychr./Asycr.1 Voltage difference OK SPS O
.325

QZ1
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
601.4201.53 Control Health ENS O
601.4201.58 Control Cmd. with feedback DPC O X
601.4231.500 Interlocking >Enable opening SPS X
601.4231.501 Interlocking >Enable closing SPS X
601.4231.53 Interlocking Health ENS O
601.5401.500 Disconnector >Acquisition blocking SPS O
601.5401.504 Disconnector >Reset AcqBlk&Subst SPS O
601.5401.501 Disconnector >Reset switch statist. SPS O
601.5401.53 Disconnector Health ENS O
601.5401.300 Disconnector Open command SPS X4.3,X O
5.3
601.5401.301 Disconnector Close command SPS X5.3,X O
4.4
601.5401.58 Disconnector Position DPC CH5.4,
OH5.3
Disconnector Position\open SPS X
Disconnector Position\closed SPS X

QZ1/
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
602.4201.53 Control Health ENS O
602.4201.58 Control Cmd. with feedback DPC O X
602.4231.500 Interlocking >Enable opening SPS X
602.4231.501 Interlocking >Enable closing SPS X
602.4231.53 Interlocking Health ENS O
602.5401.500 Disconnector >Acquisition blocking SPS O
602.5401.504 Disconnector >Reset AcqBlk&Subst SPS O
602.5401.501 Disconnector >Reset switch statist. SPS O
602.5401.53 Disconnector Health ENS O
602.5401.300 Disconnector Open command SPS X5.4,X O
4.5
602.5401.301 Disconnector Close command SPS X5.4,X O
4.6
602.5401.58 Disconnector Position DPC CH5.6,
OH5.5
Disconnector Position\open SPS X

QZ9
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
603.4201.53 Control Health ENS O
603.4201.58 Control Cmd. with feedback DPC O X
603.4231.500 Interlocking >Enable opening SPS X
603.4231.501 Interlocking >Enable closing SPS X
603.4231.53 Interlocking Health ENS O
603.5401.500 Disconnector >Acquisition blocking SPS O
603.5401.504 Disconnector >Reset AcqBlk&Subst SPS O
603.5401.501 Disconnector >Reset switch statist. SPS O
603.5401.53 Disconnector Health ENS O
Totally Integrated
Automation Portal

Number Group Signal Type Source Destination


BI FK CFC BO LED FR L CFC D
603.5401.300 Disconnector Open command SPS X4.7,X O
5.5
603.5401.301 Disconnector Close command SPS X4.8,X O
5.5
603.5401.58 Disconnector Position DPC CH5.8,
OH5.7
Disconnector Position\open SPS X
Disconnector Position\closed SPS X

QZ9/
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
604.4201.53 Control Health ENS O
604.4201.58 Control Cmd. with feedback DPC O X
604.4231.500 Interlocking >Enable opening SPS X
604.4231.501 Interlocking >Enable closing SPS X
604.4231.53 Interlocking Health ENS O
604.5401.500 Disconnector >Acquisition blocking SPS O
604.5401.504 Disconnector >Reset AcqBlk&Subst SPS O
604.5401.501 Disconnector >Reset switch statist. SPS O
604.5401.53 Disconnector Health ENS O
604.5401.300 Disconnector Open command SPS X4.9,X O
5.6
604.5401.301 Disconnector Close command SPS X4.10, O
X5.6
604.5401.58 Disconnector Position DPC CH5.10
,OH5.9
Disconnector Position\open SPS X

Q15
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
605.4201.53 Control Health ENS O
605.4201.58 Control Cmd. with feedback DPC O X
605.4231.500 Interlocking >Enable opening SPS X
605.4231.501 Interlocking >Enable closing SPS X
605.4231.53 Interlocking Health ENS O
605.5401.500 Disconnector >Acquisition blocking SPS O
605.5401.504 Disconnector >Reset AcqBlk&Subst SPS O
605.5401.501 Disconnector >Reset switch statist. SPS O
605.5401.53 Disconnector Health ENS O
605.5401.300 Disconnector Open command SPS X4.11, O
X5.7
605.5401.301 Disconnector Close command SPS X4.12, O
X5.7
605.5401.58 Disconnector Position DPC CH5.12
,OH5.1
1
Disconnector Position\open SPS X

Q8
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
606.4201.53 Control Health ENS O
606.4201.58 Control Cmd. with feedback DPC O X
606.4231.500 Interlocking >Enable opening SPS X
606.4231.501 Interlocking >Enable closing SPS X
606.4231.53 Interlocking Health ENS O
606.5401.500 Disconnector >Acquisition blocking SPS O
606.5401.504 Disconnector >Reset AcqBlk&Subst SPS O
606.5401.501 Disconnector >Reset switch statist. SPS O
606.5401.53 Disconnector Health ENS O
606.5401.300 Disconnector Open command SPS X4.13, O
X5.8
606.5401.301 Disconnector Close command SPS X4.14, O
X5.8
606.5401.58 Disconnector Position DPC CH5.14
,OH5.1
3
Disconnector Position\open SPS X

IN-33KV
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
Trip logic Trip indication\general SPS U2.2,U L1.1 R(X)
6.2
202.4261.500 Circuit break. >Ready SPS O
202.4261.501 Circuit break. >Acquisition blocking SPS O
202.4261.504 Circuit break. >Reset AcqBlk&Subst SPS O
202.4261.502 Circuit break. >Reset switch statist. SPS O
Totally Integrated
Automation Portal

Number Group Signal Type Source Destination


BI FK CFC BO LED FR L CFC D
202.4261.503 Circuit break. External health ENS O
202.4261.53 Circuit break. Health ENS O
202.4261.300 Circuit break. Trip/open cmd. SPS O,F
202.4261.301 Circuit break. Close command SPS O,F
202.4261.303 Circuit break. Definitive trip SPS F
202.4261.311 Circuit break. Break.-current phs A MV F
202.4261.312 Circuit break. Break.-current phs B MV F
202.4261.313 Circuit break. Break.-current phs C MV F
202.4261.317 Circuit break. Break. current 3I0/IN MV F
202.4261.58 Circuit break. Position DPC OH3.2 O
Circuit break. Position\open SPS X
202.6541.500 Manual close >Input SPS O
202.6541.501 Manual close >Block manual close SPS O
202.6541.300 Manual close Detected SPS O
202.4201.53 Control Health ENS O
202.4201.58 Control Cmd. with feedback DPC O
202.4231.53 Interlocking Health ENS O
202.6151.53 CB test Health ENS O
202.6151.301 CB test Test execution ENS O
202.6151.302 CB test Trip command issued ENS O
202.6151.303 CB test Close command issued ENS O
202.6151.304 CB test Test canceled ENS O
Totally Integrated
Automation Portal

=E01+R01_F003
Communication mapping
This folder is empty.
Totally Integrated
Automation Portal

=E01+R01_F003
Settings
Device settings
Settings Value
Edit mode secondary
Number settings groups 1
Activat. of settings group settings group 1
DIGSI 5 uses following IP address 192.168.0.206 (Port E)
Operation-panel language English (United States)
Binary input channel threshold Low: 44 V, High: 88 V
Used time stamp in GOOSE subscriptions On message reception
Hide settings in IEC 61850 structure Show all settings
Hide SIPROTEC extensions in IEC 61850 structure Show all SIPROTEC extensions
Use dynamic reporting True
Block IEC 61850 settings changes False
Access point used in Edition1 E

General \Device
Number Settings Value
91.101 Rated frequency All: 60 Hz
91.102 Minimum operate time All: 0 s
91.138 Block monitoring dir. All: off

General \Setting change


Number Settings Value
91.163 Reserv.time for com.prot. All: 120 s

General \Chatter blocking


Number Settings Value
91.123 No. permis.state changes All: 0
91.127 Initial test time All: 1 s
91.124 No. of chatter tests All: 0
91.125 Chatter idle time All: 1 min
91.137 Subsequent test time All: 2 s

General \Control
Number Settings Value
91.162 Blk setting change All: false
91.163 Reserv.time for com.prot. All: 120 s
91.118 Enable sw.auth. station All: false

General \Spontan.indic.
Number Settings Value
91.119 Multiple sw.auth. levels All: false

General \CFC
Number Settings Value
91.152 Specific sw. authorities All: false

General \Test support


Number Settings Value
91.139 Fault-display All: with pickup
91.161 CFC chart quality handling All: automatic

Localization
Number Settings Value
6211.139 Unit system All: SI

Time settings
General
Settings Value
Date format All: DD.MM.YYYY

Time source
Settings Value
Fault indication after All: 600 s
Time source 1 port G:IRIG-B
Time source 2 Ch1:port E:SNTP
Time zone time source 1 All: UTC
Time zone time source 2 All: UTC
Totally Integrated
Automation Portal

Settings Value
Sync. latency time src.1 All: 0 μs
Sync. latency time src.2 All: 0 μs

Time zone and daylight saving time


Settings Value
Time zone offset to UTC All: -300 min
Offset daylight sav. time All: 60 min
Switch daylight sav. time false

Power system \General


General
Number Settings Value
11.2311.101 Phase sequence All: ABC

Power system \Meas.point I-3ph 1


CT 3-phase \General
Number Settings Value
11.931.8881.115 CT connection All: 3-phase + IN
11.931.8881.127 Tracking All: active
11.931.8881.130 Measuring-point ID All: 1

CT 3-phase \CT phases


Number Settings Value
11.931.8881.101 Rated primary current All: 800 A
11.931.8881.102 Rated secondary current All: 1 A
11.931.8881.117 Current range All: 100 x IR
11.931.8881.118 Internal CT type All: CT protection
11.931.8881.116 Neutr.point in dir.of ref.obj All: no
11.931.8881.114 Inverted phases All: none

CT 1
Number Settings Value
11.931.3841.103 Magnitude correction All: 1
11.931.3841.117 Phase All: I A

CT 2
Number Settings Value
11.931.3842.103 Magnitude correction All: 1
11.931.3842.117 Phase All: I B

CT 3
Number Settings Value
11.931.3843.103 Magnitude correction All: 1
11.931.3843.117 Phase All: I C

CT 4
Number Settings Value
11.931.3844.103 Magnitude correction All: 1
11.931.3844.117 Phase All: IN

Supv. balan. I
Number Settings Value
11.931.2491.1 Mode Settings group 1: on
11.931.2491.101 Release threshold Settings group 1: 0.50 A
11.931.2491.102 Threshold min/max Settings group 1: 0.5
11.931.2491.6 Delay supervision alarm Settings group 1: 5 s

Supv. ph.seq.I
Number Settings Value
11.931.2551.1 Mode Settings group 1: on
11.931.2551.6 Delay supervision alarm Settings group 1: 5 s

Supv. sum I
Number Settings Value
11.931.2431.1 Mode Settings group 1: on
11.931.2431.102 Threshold Settings group 1: 0.10 A
11.931.2431.101 Slope factor Settings group 1: 0.1
11.931.2431.6 Delay supervision alarm Settings group 1: 5 s
Totally Integrated
Automation Portal

Supv.ADC sum I
Number Settings Value
11.931.2401.1 Mode Settings group 1: on

Power system \Meas.point I-3ph 2


CT 3-phase \General
Number Settings Value
11.932.8881.115 CT connection All: 3-phase + IN
11.932.8881.127 Tracking All: active
11.932.8881.130 Measuring-point ID All: 2

CT 3-phase \CT phases


Number Settings Value
11.932.8881.101 Rated primary current All: 2000 A
11.932.8881.102 Rated secondary current All: 1 A
11.932.8881.117 Current range All: 100 x IR
11.932.8881.118 Internal CT type All: CT protection
11.932.8881.116 Neutr.point in dir.of ref.obj All: no
11.932.8881.114 Inverted phases All: none

CT 1
Number Settings Value
11.932.3841.103 Magnitude correction All: 1
11.932.3841.117 Phase All: I A

CT 2
Number Settings Value
11.932.3842.103 Magnitude correction All: 1
11.932.3842.117 Phase All: I B

CT 3
Number Settings Value
11.932.3843.103 Magnitude correction All: 1
11.932.3843.117 Phase All: I C

CT 4
Number Settings Value
11.932.3844.103 Magnitude correction All: 1
11.932.3844.117 Phase All: IN

Supv. balan. I
Number Settings Value
11.932.2491.1 Mode Settings group 1: on
11.932.2491.101 Release threshold Settings group 1: 0.500 A
11.932.2491.102 Threshold min/max Settings group 1: 0.5
11.932.2491.6 Delay supervision alarm Settings group 1: 5 s

Supv. ph.seq.I
Number Settings Value
11.932.2551.1 Mode Settings group 1: on
11.932.2551.6 Delay supervision alarm Settings group 1: 5 s

Supv. sum I
Number Settings Value
11.932.2431.1 Mode Settings group 1: on
11.932.2431.102 Threshold Settings group 1: 0.100 A
11.932.2431.101 Slope factor Settings group 1: 0.1
11.932.2431.6 Delay supervision alarm Settings group 1: 5 s

Supv.ADC sum I
Number Settings Value
11.932.2401.1 Mode Settings group 1: on

Power system \Meas.point V-3ph 1


VT 3-phase
Number Settings Value
11.941.8911.101 Rated primary voltage All: 138 kV
11.941.8911.102 Rated secondary voltage All: 100 V
11.941.8911.104 VT connection All: 3 ph-to-gnd voltages
11.941.8911.106 Inverted phases All: none
11.941.8911.111 Tracking All: active
11.941.8911.130 Measuring-point ID All: 3
Totally Integrated
Automation Portal

VT 1
Number Settings Value
11.941.3811.103 Magnitude correction All: 1
11.941.3811.108 Phase All: V A

VT 2
Number Settings Value
11.941.3812.103 Magnitude correction All: 1
11.941.3812.108 Phase All: V B

VT 3
Number Settings Value
11.941.3813.103 Magnitude correction All: 1
11.941.3813.108 Phase All: V C

Supv. balan. V
Number Settings Value
11.941.2521.1 Mode Settings group 1: off
11.941.2521.101 Release threshold Settings group 1: 50 V
11.941.2521.102 Threshold min/max Settings group 1: 0.75
11.941.2521.6 Delay supervision alarm Settings group 1: 5 s

Supv. ph.seq.V
Number Settings Value
11.941.2581.1 Mode Settings group 1: off
11.941.2581.6 Delay supervision alarm Settings group 1: 5 s

Supv. sum V
Number Settings Value
11.941.2461.1 Mode Settings group 1: off
11.941.2461.3 Threshold Settings group 1: 25 V
11.941.2461.6 Delay supervision alarm Settings group 1: 5 s

VT miniatureCB
Number Settings Value
11.941.2641.101 Response time Settings group 1: 0 s

Power system \Meas.point V-1ph 1


General
Number Settings Value
11.961.2311.101 Rated primary voltage All: 33 kV
11.961.2311.102 Rated secondary voltage All: 100 V
11.961.2311.103 Tracking All: inactive
11.961.2311.130 Measuring-point ID All: 4

VT 1
Number Settings Value
11.961.3811.103 Magnitude correction All: 1
11.961.3811.108 Phase All: V B

VT miniatureCB
Number Settings Value
11.961.2641.101 Response time Settings group 1: 0 s

Recording \Fault recorder


Control
Number Settings Value
51.791.2761.130 Fault recording All: with pickup
51.791.2761.131 Storage All: always
51.791.2761.111 Maximum record time All: 5 s
51.791.2761.112 Pre-trigger time All: 0.5 s
51.791.2761.113 Post-trigger time All: 0.5 s
51.791.2761.116 Manual record time All: 0.5 s
51.791.2761.140 Sampling frequency All: 2 kHz
51.791.2761.141 Sampl. freq. IEC61850 rec. All: 1 kHz
51.791.2761.128 Scaling COMTRADE All: Secondary values
Totally Integrated
Automation Portal

Transformer side 1 \General


General \Rated values
Number Settings Value
911.91.103 Rated apparent power All: 105 MVA
911.91.102 Rated voltage All: 146 kV
911.91.101 Rated current All: 415 A

General \Side data


Number Settings Value
911.91.149 Neutral point Settings group 1: grounded
911.91.104 Winding configuration Settings group 1: Y (Wye)
911.91.163 Vector group numeral All: 0
911.91.130 Side number All: Side 1
911.91.210 MI3ph1 usesMeasP with ID All: 1
911.91.215 CT mismatch M I-3ph 1 All: 1.927

General \Measurements
Number Settings Value
911.91.158 P, Q sign Settings group 1: not reversed

Transformer side 1 \Process monitor


Transformer side 1 \49 Th.overl.-A 1
49 Th.overl. 1
Number Settings Value
911.191.601.1 Mode Settings group 1: off
911.191.601.2 Operate & flt.rec. blocked Settings group 1: yes
911.191.601.101 Threshold current warning Settings group 1: 0.433 A
911.191.601.104 Threshold thermal warn. Settings group 1: 90 %
911.191.601.105 Dropout threshold operate Settings group 1: 90 %
911.191.601.112 Emerg. start T overtravel Settings group 1: 300 s
911.191.601.106 K-factor Settings group 1: 1.1
911.191.601.110 Thermal time constant Settings group 1: 900 s
911.191.601.111 Cooling time constant Settings group 1: 3600 s
911.191.601.107 Imax thermal Settings group 1: 1.083 A
911.191.601.108 Imin cooling Settings group 1: 0.217 A
911.191.601.109 Temperature rise at Irated Settings group 1: 70 K
911.191.601.113 Storage of thermal replica Settings group 1: no
911.191.601.114 Behav. at I> Imax therm. Settings group 1: current limiting
911.191.601.118 Default temperature Settings group 1: 40 °C
911.191.601.117 Minimal temperature Settings group 1: -20 °C

Transformer side 1 \50/51 OC-3ph-A1


Definite-T 1 \General
Number Settings Value
911.201.661.1 Mode Settings group 1: on
911.201.661.2 Operate & flt.rec. blocked Settings group 1: no
911.201.661.11 1-pole operate allowed Settings group 1: no
911.201.661.26 Dynamic settings All: no
911.201.661.27 Blk. w. inrush curr. detect. Settings group 1: yes
911.201.661.8 Method of measurement Settings group 1: fundamental comp.
911.201.661.3 Threshold Settings group 1: 2.58 A
911.201.661.4 Dropout ratio Settings group 1: 0.95
911.201.661.102 Pickup delay Settings group 1: 0 s
911.201.661.101 Dropout delay Settings group 1: 0 s
911.201.661.6 Operate delay Settings group 1: 0.05 s

Definite-T 2 \General
Number Settings Value
911.201.662.1 Mode Settings group 1: off
911.201.662.2 Operate & flt.rec. blocked Settings group 1: no
911.201.662.11 1-pole operate allowed Settings group 1: no
911.201.662.26 Dynamic settings All: no
911.201.662.27 Blk. w. inrush curr. detect. Settings group 1: no
911.201.662.8 Method of measurement Settings group 1: fundamental comp.
911.201.662.3 Threshold Settings group 1: 17.321 A
911.201.662.4 Dropout ratio Settings group 1: 0.95
911.201.662.102 Pickup delay Settings group 1: 0 s
911.201.662.101 Dropout delay Settings group 1: 0 s
911.201.662.6 Operate delay Settings group 1: 0.1 s

Inverse-T 1 \General
Number Settings Value
911.201.691.1 Mode Settings group 1: on
911.201.691.2 Operate & flt.rec. blocked Settings group 1: no
911.201.691.11 1-pole operate allowed Settings group 1: no
911.201.691.26 Dynamic settings All: no
911.201.691.27 Blk. w. inrush curr. detect. Settings group 1: no
Totally Integrated
Automation Portal

Number Settings Value


911.201.691.8 Method of measurement Settings group 1: fundamental comp.
911.201.691.3 Threshold Settings group 1: 0.67 A
911.201.691.108 Pickup delay Settings group 1: 0 s
911.201.691.130 Type of character. curve Settings group 1: IEC normal inverse
911.201.691.113 Min. time of the curve Settings group 1: 0 s
911.201.691.131 Reset Settings group 1: instantaneous
911.201.691.101 Time dial Settings group 1: 0.08
911.201.691.115 Additional time delay Settings group 1: 0 s

Transformer side 1 \50N/51N OC-gnd-A1


General
Number Settings Value
911.211.2311.9 Measured value Settings group 1: IN measured

Definite-T 1 \General
Number Settings Value
911.211.751.1 Mode Settings group 1: off
911.211.751.2 Operate & flt.rec. blocked Settings group 1: no
911.211.751.26 Dynamic settings All: no
911.211.751.27 Blk. w. inrush curr. detect. Settings group 1: no
911.211.751.8 Method of measurement Settings group 1: fundamental comp.
911.211.751.3 Threshold Settings group 1: 0.520 A
911.211.751.4 Dropout ratio Settings group 1: 0.95
911.211.751.101 Dropout delay Settings group 1: 0 s
911.211.751.6 Operate delay Settings group 1: 0.3 s

Definite-T 2 \General
Number Settings Value
911.211.752.1 Mode Settings group 1: off
911.211.752.2 Operate & flt.rec. blocked Settings group 1: no
911.211.752.26 Dynamic settings All: no
911.211.752.27 Blk. w. inrush curr. detect. Settings group 1: no
911.211.752.8 Method of measurement Settings group 1: fundamental comp.
911.211.752.3 Threshold Settings group 1: 0.520 A
911.211.752.4 Dropout ratio Settings group 1: 0.95
911.211.752.101 Dropout delay Settings group 1: 0 s
911.211.752.6 Operate delay Settings group 1: 0.3 s

Inverse-T 1 \General
Number Settings Value
911.211.781.1 Mode Settings group 1: off
911.211.781.2 Operate & flt.rec. blocked Settings group 1: no
911.211.781.26 Dynamic settings All: no
911.211.781.27 Blk. w. inrush curr. detect. Settings group 1: no
911.211.781.8 Method of measurement Settings group 1: fundamental comp.
911.211.781.3 Threshold Settings group 1: 0.520 A
911.211.781.108 Type of character. curve Settings group 1: IEC normal inverse
911.211.781.113 Min. time of the curve Settings group 1: 0 s
911.211.781.109 Reset Settings group 1: disk emulation
911.211.781.101 Time dial Settings group 1: 1
911.211.781.115 Additional time delay Settings group 1: 0 s

Transformer side 1 \Inrush detect.


Inrush detect.
Number Settings Value
911.4141.1 Mode All: on
911.4141.106 Operat.-range limit Imax Settings group 1: 3.893 A
911.4141.111 Blocking with CWA Settings group 1: yes
911.4141.110 Blocking with 2. harmonic Settings group 1: yes
911.4141.102 2nd harmonic content Settings group 1: 15 %
911.4141.112 Crossblocking Settings group 1: no
911.4141.109 Crossblocking time Settings group 1: 0.06 s
911.4141.114 Start flt.rec Settings group 1: yes

Transformer side 1\Ciruit-breaker interaction


Protection group Circuit-breaker group(s)
Transformer side 1\ 49 Th.overl.-A 1\ 49 Th.overl. 1 Q0:Trip
Transformer side 1\ 50/51 OC-3ph-A1\ Definite-T 1 Q0:Trip
Transformer side 1\ 50/51 OC-3ph-A1\ Definite-T 2 Q0:Trip
Transformer side 1\ 50/51 OC-3ph-A1\ Inverse-T 1 Q0:Trip
Transformer side 1\ 50N/51N OC-gnd-A1\ Definite-T 1 Q0:Trip
Transformer side 1\ 50N/51N OC-gnd-A1\ Definite-T 2 Q0:Trip
Transformer side 1\ 50N/51N OC-gnd-A1\ Inverse-T 1 Q0:Trip
Totally Integrated
Automation Portal

Transformer side 2 \General


General \Rated values
Number Settings Value
912.91.103 Rated apparent power All: 105 MVA
912.91.102 Rated voltage All: 33 kV
912.91.101 Rated current All: 1837 A

General \Side data


Number Settings Value
912.91.149 Neutral point Settings group 1: grounded
912.91.104 Winding configuration Settings group 1: Y (Wye)
912.91.163 Vector group numeral All: 0
912.91.130 Side number All: Side 2
912.91.210 MI3ph1 usesMeasP with ID All: 2
912.91.215 CT mismatch M I-3ph 1 All: 1.089

Transformer side 2 \Process monitor


Transformer side 2 \50/51 OC-3ph-A1
Definite-T 1 \General
Number Settings Value
912.201.661.1 Mode Settings group 1: on
912.201.661.2 Operate & flt.rec. blocked Settings group 1: no
912.201.661.11 1-pole operate allowed Settings group 1: no
912.201.661.26 Dynamic settings All: no
912.201.661.27 Blk. w. inrush curr. detect. Settings group 1: yes
912.201.661.8 Method of measurement Settings group 1: fundamental comp.
912.201.661.3 Threshold Settings group 1: 1.75 A
912.201.661.4 Dropout ratio Settings group 1: 0.95
912.201.661.102 Pickup delay Settings group 1: 0 s
912.201.661.101 Dropout delay Settings group 1: 0 s
912.201.661.6 Operate delay Settings group 1: 0.05 s

Definite-T 2 \General
Number Settings Value
912.201.662.1 Mode Settings group 1: off
912.201.662.2 Operate & flt.rec. blocked Settings group 1: no
912.201.662.11 1-pole operate allowed Settings group 1: no
912.201.662.26 Dynamic settings All: no
912.201.662.27 Blk. w. inrush curr. detect. Settings group 1: no
912.201.662.8 Method of measurement Settings group 1: fundamental comp.
912.201.662.3 Threshold Settings group 1: 6.928 A
912.201.662.4 Dropout ratio Settings group 1: 0.95
912.201.662.102 Pickup delay Settings group 1: 0 s
912.201.662.101 Dropout delay Settings group 1: 0 s
912.201.662.6 Operate delay Settings group 1: 0.1 s

Inverse-T 1 \General
Number Settings Value
912.201.691.1 Mode Settings group 1: on
912.201.691.2 Operate & flt.rec. blocked Settings group 1: no
912.201.691.11 1-pole operate allowed Settings group 1: no
912.201.691.26 Dynamic settings All: no
912.201.691.27 Blk. w. inrush curr. detect. Settings group 1: no
912.201.691.8 Method of measurement Settings group 1: fundamental comp.
912.201.691.3 Threshold Settings group 1: 0.69 A
912.201.691.108 Pickup delay Settings group 1: 0 s
912.201.691.130 Type of character. curve Settings group 1: IEC normal inverse
912.201.691.113 Min. time of the curve Settings group 1: 0 s
912.201.691.131 Reset Settings group 1: instantaneous
912.201.691.101 Time dial Settings group 1: 0.07
912.201.691.115 Additional time delay Settings group 1: 0 s

Transformer side 2 \50N/51N OC-gnd-A1


General
Number Settings Value
912.211.2311.9 Measured value Settings group 1: IN measured

Definite-T 1 \General
Number Settings Value
912.211.751.1 Mode Settings group 1: on
912.211.751.2 Operate & flt.rec. blocked Settings group 1: no
912.211.751.26 Dynamic settings All: no
912.211.751.27 Blk. w. inrush curr. detect. Settings group 1: no
912.211.751.8 Method of measurement Settings group 1: fundamental comp.
912.211.751.3 Threshold Settings group 1: 2.90 A
912.211.751.4 Dropout ratio Settings group 1: 0.95
912.211.751.101 Dropout delay Settings group 1: 0 s
Totally Integrated
Automation Portal

Number Settings Value


912.211.751.6 Operate delay Settings group 1: 0.05 s

Definite-T 2 \General
Number Settings Value
912.211.752.1 Mode Settings group 1: off
912.211.752.2 Operate & flt.rec. blocked Settings group 1: no
912.211.752.26 Dynamic settings All: no
912.211.752.27 Blk. w. inrush curr. detect. Settings group 1: no
912.211.752.8 Method of measurement Settings group 1: fundamental comp.
912.211.752.3 Threshold Settings group 1: 1.102 A
912.211.752.4 Dropout ratio Settings group 1: 0.95
912.211.752.101 Dropout delay Settings group 1: 0 s
912.211.752.6 Operate delay Settings group 1: 0.3 s

Inverse-T 1 \General
Number Settings Value
912.211.781.1 Mode Settings group 1: on
912.211.781.2 Operate & flt.rec. blocked Settings group 1: no
912.211.781.26 Dynamic settings All: no
912.211.781.27 Blk. w. inrush curr. detect. Settings group 1: no
912.211.781.8 Method of measurement Settings group 1: fundamental comp.
912.211.781.3 Threshold Settings group 1: 0.28 A
912.211.781.108 Type of character. curve Settings group 1: IEC normal inverse
912.211.781.113 Min. time of the curve Settings group 1: 0 s
912.211.781.109 Reset Settings group 1: instantaneous
912.211.781.101 Time dial Settings group 1: 0.12
912.211.781.115 Additional time delay Settings group 1: 0 s

Transformer side 2 \Inrush detect.


Inrush detect.
Number Settings Value
912.4141.1 Mode All: on
912.4141.106 Operat.-range limit Imax Settings group 1: 6.889 A
912.4141.111 Blocking with CWA Settings group 1: yes
912.4141.110 Blocking with 2. harmonic Settings group 1: yes
912.4141.102 2nd harmonic content Settings group 1: 15 %
912.4141.112 Crossblocking Settings group 1: no
912.4141.109 Crossblocking time Settings group 1: 0.06 s
912.4141.114 Start flt.rec Settings group 1: yes

Transformer side 2\Ciruit-breaker interaction


Protection group Circuit-breaker group(s)
Transformer side 2\ 50/51 OC-3ph-A1\ Definite-T 1 IN-33KV:Trip
Transformer side 2\ 50/51 OC-3ph-A1\ Definite-T 2 IN-33KV:Trip
Transformer side 2\ 50/51 OC-3ph-A1\ Inverse-T 1 IN-33KV:Trip
Transformer side 2\ 50N/51N OC-gnd-A1\ Definite-T 1 IN-33KV:Trip
Transformer side 2\ 50N/51N OC-gnd-A1\ Definite-T 2 IN-33KV:Trip
Transformer side 2\ 50N/51N OC-gnd-A1\ Inverse-T 1 IN-33KV:Trip

Transformer diff. 1 \87T diff. prot. 1


General
Number Settings Value
901.1691.2311.105 CT mismatch side 1 M3ph 1 All: 1.927
901.1691.2311.110 CT mismatch side 2 M3ph 1 All: 1.089
901.1691.2311.191 Reference side is All: Side 2
901.1691.2311.151 MU-ID Side 1 Mp3ph 1 All: 1
901.1691.2311.156 MU-ID Side 2 Mp3ph 1 All: 2

I-DIFF \General
Number Settings Value
901.1691.11041.1 Mode Settings group 1: on
901.1691.11041.2 Operate & flt.rec. blocked Settings group 1: no
901.1691.11041.6 Operate delay Settings group 1: 0 s

I-DIFF \Operate curve


Number Settings Value
901.1691.11041.3 Threshold Settings group 1: 0.2 I/IrObj
901.1691.11041.100 Slope 1 Settings group 1: 0.3
901.1691.11041.101 Intersection 1 Irest Settings group 1: 1.32 I/IrObj
901.1691.11041.102 Slope 2 Settings group 1: 0.8
901.1691.11041.103 Intersection 2 Irest Settings group 1: 4 I/IrObj
Totally Integrated
Automation Portal

I-DIFF \Starting detection


Number Settings Value
901.1691.11041.106 Starting detection Settings group 1: no
901.1691.11041.107 Thresh. startup detection Settings group 1: 0.1 I/IrObj
901.1691.11041.108 Factor increasing char. Settings group 1: 2
901.1691.11041.109 Max. perm. Start. time Settings group 1: 5 s

I-DIFF \DC offset detection


Number Settings Value
901.1691.11041.110 Factor increasing char. DC Settings group 1: 2

I-DIFF \Inrush blocking


Number Settings Value
901.1691.11041.115 Blocking with 2. harmonic Settings group 1: yes
901.1691.11041.116 2nd harmonic content Settings group 1: 15 %
901.1691.11041.117 Crossblock. time 2nd har. Settings group 1: 0.05 s
901.1691.11041.118 Blocking with CWA Settings group 1: yes

I-DIFF \Overexcit. blocking


Number Settings Value
901.1691.11041.121 Blocking with 3rd harm. Settings group 1: no
901.1691.11041.122 3rd harmonics content Settings group 1: 30 %
901.1691.11041.123 Crossblock. time 3rd har. Settings group 1: 0 s
901.1691.11041.124 Blocking with 5th harm. Settings group 1: yes
901.1691.11041.125 5th harmonics content Settings group 1: 30 %
901.1691.11041.126 Crossblock. time 5th har. Settings group 1: 0.05 s
901.1691.11041.127 Limit Idiff 3., 5. harmonics Settings group 1: 1.5 I/IrObj

I-DIFF \Ext. fault detection


Number Settings Value
901.1691.11041.128 Threshold add-on stabiliz. Settings group 1: 2 I/IrObj
901.1691.11041.129 Time of add-on stabiliz. Settings group 1: 0.3 s
901.1691.11041.130 Crossblk. time add-on st. Settings group 1: 0.3 s

I-DIFF fast
Number Settings Value
901.1691.11071.1 Mode Settings group 1: on
901.1691.11071.3 Threshold Settings group 1: 9 I/IrObj
901.1691.11071.6 Operate delay Settings group 1: 0 s
901.1691.11071.100 Operate & flt.rec. blocked Settings group 1: no

Transformer diff. 1\Ciruit-breaker interaction


Protection group Circuit-breaker group(s)
Transformer diff. 1\ 87T diff. prot. 1\ I-DIFF Q0:Trip, IN-33KV:Trip
Transformer diff. 1\ 87T diff. prot. 1\ I-DIFF fast Q0:Trip, IN-33KV:Trip

Q0 \General
General \Ref. for %-values
Number Settings Value
201.2311.101 Rated normal current All: 415 A
201.2311.102 Rated voltage All: 138 kV

General \Breaker settings


Number Settings Value
201.2311.112 Current thresh. CB open All: 0.05 A

Q0 \Trip logic
Trip logic
Number Settings Value
201.5341.103 Reset of trip command All: with I<

Q0 \Circuit break.
Circuit break.
Number Settings Value
201.4261.101 Output time All: 0.5 s
201.4261.105 Indicat. of breaking values All: always
Totally Integrated
Automation Portal

Q0 \Manual close
Manual close
Number Settings Value
201.6541.101 Action time Settings group 1: 0.3 s
201.6541.102 CB open dropout delay Settings group 1: 0 s

Q0 \Control
Control
Number Settings Value
201.4201.101 Control model All: SBO w. enh. security
201.4201.102 SBO time-out All: 30 s
201.4201.103 Feedback monitoring time All: 1 s
201.4201.104 Check switching authority All: yes
201.4201.105 Check if pos. is reached All: yes
201.4201.106 Check double activat. blk. All: yes
201.4201.107 Check blk. by protection All: yes

Q0 \CB test
CB test
Number Settings Value
201.6151.101 Dead time All: 0.1 s
201.6151.102 Trip only All: false
201.6151.103 Consider current criterion All: false

Q0 \74TC sup.2BI 1
74TC sup.2BI 1
Number Settings Value
201.4411.1 Mode Settings group 1: on
201.4411.100 Alarm delay Settings group 1: 2 s

Q0 \25 Synchronization
General
Number Settings Value
201.1151.2311.127 Angle adjust. (transform.) Settings group 1: 0 °

Synchrocheck 1 \General
Number Settings Value
201.1151.5071.1 Mode Settings group 1: on
201.1151.5071.101 Min. operating limit Vmin Settings group 1: 90 V
201.1151.5071.102 Max. operat. limit Vmax Settings group 1: 100 V
201.1151.5071.110 Max.durat. sync.process Settings group 1: oo s
201.1151.5071.108 Direct close command Settings group 1: no
201.1151.5071.126 Voltage adjustment Settings group 1: 1

Synchrocheck 1 \De-en.gized switch.


Number Settings Value
201.1151.5071.105 Close cmd. at V1< & V2> Settings group 1: no
201.1151.5071.106 Close cmd. at V1> & V2< Settings group 1: yes
201.1151.5071.107 Close cmd. at V1< & V2< Settings group 1: no
201.1151.5071.103 V1, V2 without voltage Settings group 1: 5 V
201.1151.5071.104 V1, V2 with voltage Settings group 1: 79.71 V
201.1151.5071.109 Supervision time Settings group 1: 0.01 s

Synchrocheck 1 \Synchr. conditions


Number Settings Value
201.1151.5071.122 Max. voltage diff. V2>V1 Settings group 1: 10 V
201.1151.5071.123 Max. voltage diff. V2<V1 Settings group 1: 10 V
201.1151.5071.117 Max. frequency diff. f2>f1 Settings group 1: 0.1 Hz
201.1151.5071.118 Max. frequency diff. f2<f1 Settings group 1: 0.1 Hz
201.1151.5071.124 Max. angle diff. α2>α1 Settings group 1: 30 °
201.1151.5071.125 Max. angle diff. α2<α1 Settings group 1: 30 °

Sychr./Asycr.1 \General
Number Settings Value
201.1151.5041.1 Mode Settings group 1: off
201.1151.5041.101 Min. operating limit Vmin Settings group 1: 90 V
201.1151.5041.102 Max. operat. limit Vmax Settings group 1: 110 V
201.1151.5041.110 Max.durat. sync.process Settings group 1: 30 s
201.1151.5041.108 Direct close command Settings group 1: no
201.1151.5041.126 Voltage adjustment Settings group 1: 1
Totally Integrated
Automation Portal

Sychr./Asycr.1 \De-en.gized switch.


Number Settings Value
201.1151.5041.105 Close cmd. at V1< & V2> Settings group 1: no
201.1151.5041.106 Close cmd. at V1> & V2< Settings group 1: no
201.1151.5041.107 Close cmd. at V1< & V2< Settings group 1: no
201.1151.5041.103 V1, V2 without voltage Settings group 1: 5 V
201.1151.5041.104 V1, V2 with voltage Settings group 1: 80 V
201.1151.5041.109 Supervision time Settings group 1: 0.01 s

Sychr./Asycr.1 \Asynchr. op.mode


Number Settings Value
201.1151.5041.114 Async. operating mode Settings group 1: off
201.1151.5041.113 CB make time Settings group 1: 0.06 s
201.1151.5041.115 Max. voltage diff. V2>V1 Settings group 1: 5 V
201.1151.5041.116 Max. voltage diff. V2<V1 Settings group 1: 5 V
201.1151.5041.117 Max. frequency diff. f2>f1 Settings group 1: 0.1 Hz
201.1151.5041.118 Max. frequency diff. f2<f1 Settings group 1: 0.1 Hz

Sychr./Asycr.1 \Synchr. op.mode


Number Settings Value
201.1151.5041.119 Sync. operating mode Settings group 1: off
201.1151.5041.120 f-threshold ASYN<->SYN Settings group 1: 0.01 Hz
201.1151.5041.122 Max. voltage diff. V2>V1 Settings group 1: 5 V
201.1151.5041.123 Max. voltage diff. V2<V1 Settings group 1: 5 V
201.1151.5041.124 Max. angle diff. α2>α1 Settings group 1: 10 °
201.1151.5041.125 Max. angle diff. α2<α1 Settings group 1: 10 °
201.1151.5041.121 Delay close command Settings group 1: 0 s

IN-33KV \General
General \Ref. for %-values
Number Settings Value
202.2311.101 Rated normal current All: 1837 A

General \Breaker settings


Number Settings Value
202.2311.112 Current thresh. CB open All: 0.05 A

IN-33KV \Trip logic


Trip logic
Number Settings Value
202.5341.103 Reset of trip command All: with I<

IN-33KV \Circuit break.


Circuit break.
Number Settings Value
202.4261.101 Output time All: 0.1 s
202.4261.105 Indicat. of breaking values All: always

IN-33KV \Manual close


Manual close
Number Settings Value
202.6541.101 Action time Settings group 1: 0.3 s
202.6541.102 CB open dropout delay Settings group 1: 0 s

IN-33KV \Control
Control
Number Settings Value
202.4201.101 Control model All: SBO w. enh. security
202.4201.102 SBO time-out All: 30 s
202.4201.103 Feedback monitoring time All: 1 s
202.4201.104 Check switching authority All: yes
202.4201.105 Check if pos. is reached All: yes
202.4201.106 Check double activat. blk. All: yes
202.4201.107 Check blk. by protection All: yes

IN-33KV \CB test


CB test
Number Settings Value
202.6151.101 Dead time All: 0.1 s
202.6151.102 Trip only All: false
202.6151.103 Consider current criterion All: false
Totally Integrated
Automation Portal

QZ1 \Control
Control
Number Settings Value
601.4201.101 Control model All: SBO w. enh. security
601.4201.102 SBO time-out All: 30 s
601.4201.103 Feedback monitoring time All: 10 s
601.4201.104 Check switching authority All: yes
601.4201.105 Check if pos. is reached All: yes
601.4201.106 Check double activat. blk. All: yes

QZ1 \Disconnector
Disconnector
Number Settings Value
601.5401.101 Maximum output time All: 10 s
601.5401.102 Seal-in time All: 0 s
601.5401.103 Switching-device type All: disconnector

QZ1/ \Control
Control
Number Settings Value
602.4201.101 Control model All: SBO w. enh. security
602.4201.102 SBO time-out All: 30 s
602.4201.103 Feedback monitoring time All: 10 s
602.4201.104 Check switching authority All: yes
602.4201.105 Check if pos. is reached All: yes
602.4201.106 Check double activat. blk. All: yes

QZ1/ \Disconnector
Disconnector
Number Settings Value
602.5401.101 Maximum output time All: 10 s
602.5401.102 Seal-in time All: 0 s
602.5401.103 Switching-device type All: disconnector

QZ9 \Control
Control
Number Settings Value
603.4201.101 Control model All: SBO w. enh. security
603.4201.102 SBO time-out All: 30 s
603.4201.103 Feedback monitoring time All: 10 s
603.4201.104 Check switching authority All: yes
603.4201.105 Check if pos. is reached All: yes
603.4201.106 Check double activat. blk. All: yes

QZ9 \Disconnector
Disconnector
Number Settings Value
603.5401.101 Maximum output time All: 10 s
603.5401.102 Seal-in time All: 0 s
603.5401.103 Switching-device type All: disconnector

QZ9/ \Control
Control
Number Settings Value
604.4201.101 Control model All: SBO w. enh. security
604.4201.102 SBO time-out All: 30 s
604.4201.103 Feedback monitoring time All: 10 s
604.4201.104 Check switching authority All: yes
604.4201.105 Check if pos. is reached All: yes
604.4201.106 Check double activat. blk. All: yes

QZ9/ \Disconnector
Disconnector
Number Settings Value
604.5401.101 Maximum output time All: 10 s
604.5401.102 Seal-in time All: 0 s
604.5401.103 Switching-device type All: disconnector
Totally Integrated
Automation Portal

Q15 \Control
Control
Number Settings Value
605.4201.101 Control model All: SBO w. enh. security
605.4201.102 SBO time-out All: 30 s
605.4201.103 Feedback monitoring time All: 10 s
605.4201.104 Check switching authority All: yes
605.4201.105 Check if pos. is reached All: yes
605.4201.106 Check double activat. blk. All: yes

Q15 \Disconnector
Disconnector
Number Settings Value
605.5401.101 Maximum output time All: 10 s
605.5401.102 Seal-in time All: 0 s
605.5401.103 Switching-device type All: disconnector

Q8 \Control
Control
Number Settings Value
606.4201.101 Control model All: SBO w. enh. security
606.4201.102 SBO time-out All: 30 s
606.4201.103 Feedback monitoring time All: 10 s
606.4201.104 Check switching authority All: yes
606.4201.105 Check if pos. is reached All: yes
606.4201.106 Check double activat. blk. All: yes

Q8 \Disconnector
Disconnector
Number Settings Value
606.5401.101 Maximum output time All: 10 s
606.5401.102 Seal-in time All: 0 s
606.5401.103 Switching-device type All: disconnector

Lado 33kV \General


General \Rated values
Number Settings Value
831.9421.102 Rated voltage All: 33 kV
Totally Integrated
Automation Portal

=E01+R01_F003
1. Enclavamiento QZ1
Totally Integrated
Automation Portal

Data.Sw Mode.open [BOOL]

and10_1 or10_1

AND10 OR10
AND OR
Q0.Circuit break..Position.open [BOOL] X1 Y X1 Y
QZ1/.Disconnector.Position.open [BOOL] X2 X2
Q15.Disconnector.Position.open [BOOL] X3
1. Enclavamiento QZ1 - Data flow/Task: Event-triggered (1.1 / 3.2)

GIS.Desbloqueo General [BOOL] X4


GIS.Local/Remoto.closed [BOOL] X5

2.1 ( Page9 - 4)
1.2 ( Page9 - 3)
1.1 ( Page9 - 2)
Totally Integrated
Automation Portal

Y QZ1.Interlocking.>Enable closing [BOOL]


QZ1.Interlocking.>Enable opening [BOOL]
QZ1.Enclavamiento [BOOL]
1. Enclavamiento QZ1 - Data flow/Task: Event-triggered (1.2 / 3.2)

2.2 ( Page9 - 5)
Totally Integrated
Automation Portal

1. Enclavamiento QZ1 - Data flow/Task: Event-triggered (2.1 / 3.2)


1.1 ( Page9 - 2)

2.2 ( Page9 - 5)

3.1 ( Page9 - 6)
Totally Integrated
Automation Portal

1. Enclavamiento QZ1 - Data flow/Task: Event-triggered (2.2 / 3.2)


1.2 ( Page9 - 3)
2.1 ( Page9 - 4)

3.2 ( Page9 - 7)
Totally Integrated
Automation Portal

1. Enclavamiento QZ1 - Data flow/Task: Event-triggered (3.1 / 3.2)


2.1 ( Page9 - 4)

3.2 ( Page9 - 7)
Totally Integrated
Automation Portal

1. Enclavamiento QZ1 - Data flow/Task: Event-triggered (3.2 / 3.2)


2.2 ( Page9 - 5)
3.1 ( Page9 - 6)
Totally Integrated
Automation Portal
Totally Integrated
Automation Portal

1. Enclavamiento QZ1 - Control flow/Task: Event-triggered


Run se‐ Object/parameter Operand Type Unit Task Additional Comment
quence tasks
AND10 and10_1 AND10 default
X1 Q0.Circuit break..Position.open [BOOL] Bool
X2 QZ1/.Disconnector.Position.open Bool
[BOOL]
X3 Q15.Disconnector.Position.open [BOOL] Bool
X4 GIS.Desbloqueo General [BOOL] Bool
X5 GIS.Local/Remoto.closed [BOOL] Bool
Y 0 Bool
or10_1.X1
OR10 or10_1 OR10 default
X1 and10_1.Y Bool
X2 Data.Sw Mode.open [BOOL] Bool
Y 0 Bool
QZ1.Enclavamiento [BOOL]
QZ1.Interlocking.>Enable opening
[BOOL]
QZ1.Interlocking.>Enable closing
[BOOL]
Totally Integrated
Automation Portal

=E01+R01_F003
2. Enclavamiento QZ9
and10_1 or10_1
AND10 OR10
AND OR
Q0.Circuit break..Position.open [BOOL] X1 Y X1 Y QZ9.Interlocking.>Enable opening [BOOL]
QZ9/.Disconnector.Position.open [BOOL] X2 X2 QZ9.Interlocking.>Enable closing [BOOL]
Q8.Disconnector.Position.open [BOOL] X3 QZ9.Enclavamiento [BOOL]
Totally Integrated
Automation Portal

GIS.Desbloqueo General [BOOL] X4


GIS.Local/Remoto.closed [BOOL] X5

Data.Sw Mode.open [BOOL]


2. Enclavamiento QZ9 - Data flow/Task: Event-triggered (1.1 / 3.2)

2.1 ( Page10 - 4)
1.2 ( Page10 - 3)
Totally Integrated
Automation Portal

2. Enclavamiento QZ9 - Data flow/Task: Event-triggered (1.2 / 3.2)


1.1 ( Page10 - 2)

2.2 ( Page10 - 5)
Totally Integrated
Automation Portal

2. Enclavamiento QZ9 - Data flow/Task: Event-triggered (2.1 / 3.2)


1.1 ( Page10 - 2)

2.2 ( Page10 - 5)

3.1 ( Page10 - 6)
Totally Integrated
Automation Portal

2. Enclavamiento QZ9 - Data flow/Task: Event-triggered (2.2 / 3.2)


1.2 ( Page10 - 3)
2.1 ( Page10 - 4)

3.2 ( Page10 - 7)
Totally Integrated
Automation Portal

2. Enclavamiento QZ9 - Data flow/Task: Event-triggered (3.1 / 3.2)


2.1 ( Page10 - 4)

3.2 ( Page10 - 7)
Totally Integrated
Automation Portal

2. Enclavamiento QZ9 - Data flow/Task: Event-triggered (3.2 / 3.2)


2.2 ( Page10 - 5)
3.1 ( Page10 - 6)
Totally Integrated
Automation Portal
Totally Integrated
Automation Portal

2. Enclavamiento QZ9 - Control flow/Task: Event-triggered


Run se‐ Object/parameter Operand Type Unit Task Additional Comment
quence tasks
AND10 and10_1 AND10 default
X1 Q0.Circuit break..Position.open [BOOL] Bool
X2 QZ9/.Disconnector.Position.open Bool
[BOOL]
X3 Q8.Disconnector.Position.open [BOOL] Bool
X4 GIS.Desbloqueo General [BOOL] Bool
X5 GIS.Local/Remoto.closed [BOOL] Bool
Y 0 Bool
or10_1.X1
OR10 or10_1 OR10 default
X1 and10_1.Y Bool
X2 Data.Sw Mode.open [BOOL] Bool
Y 0 Bool
QZ9.Enclavamiento [BOOL]
QZ9.Interlocking.>Enable closing
[BOOL]
QZ9.Interlocking.>Enable opening
[BOOL]
Totally Integrated
Automation Portal

=E01+R01_F003
3. Enclavamiento Q8
Totally Integrated
Automation Portal

and10_1

AND10
AND
Q0.Circuit break..Position.open [BOOL] X1 Y Q8.Interlocking.>Enable opening [BOOL]
QZ9.Disconnector.Position.open [BOOL] X2 Q8.Interlocking.>Enable closing [BOOL]
Data.Q0 33kV Abierto [BOOL] X3 Q8.Enclavamiento [BOOL]
Q8.Operacion Manual [BOOL] X4
GIS.Desbloqueo General [BOOL] X5
GIS.Local/Remoto.closed [BOOL] X6
3. Enclavamiento Q8 - Data flow/Task: Event-triggered (1.1 / 3.2)

2.1 ( Page11 - 4)
1.2 ( Page11 - 3)
Totally Integrated
Automation Portal

3. Enclavamiento Q8 - Data flow/Task: Event-triggered (1.2 / 3.2)


1.1 ( Page11 - 2)

2.2 ( Page11 - 5)
Totally Integrated
Automation Portal

3. Enclavamiento Q8 - Data flow/Task: Event-triggered (2.1 / 3.2)


1.1 ( Page11 - 2)

2.2 ( Page11 - 5)

3.1 ( Page11 - 6)
Totally Integrated
Automation Portal

3. Enclavamiento Q8 - Data flow/Task: Event-triggered (2.2 / 3.2)


1.2 ( Page11 - 3)
2.1 ( Page11 - 4)

3.2 ( Page11 - 7)
Totally Integrated
Automation Portal

3. Enclavamiento Q8 - Data flow/Task: Event-triggered (3.1 / 3.2)


2.1 ( Page11 - 4)

3.2 ( Page11 - 7)
Totally Integrated
Automation Portal

3. Enclavamiento Q8 - Data flow/Task: Event-triggered (3.2 / 3.2)


2.2 ( Page11 - 5)
3.1 ( Page11 - 6)
Totally Integrated
Automation Portal
Totally Integrated
Automation Portal

3. Enclavamiento Q8 - Control flow/Task: Event-triggered


Run se‐ Object/parameter Operand Type Unit Task Additional Comment
quence tasks
AND10 and10_1 AND10 default
X1 Q0.Circuit break..Position.open [BOOL] Bool
X2 QZ9.Disconnector.Position.open [BOOL] Bool
X3 Data.Q0 33kV Abierto [BOOL] Bool
X4 Q8.Operacion Manual [BOOL] Bool
X5 GIS.Desbloqueo General [BOOL] Bool
X6 GIS.Local/Remoto.closed [BOOL] Bool
Y 0 Bool
Q8.Enclavamiento [BOOL]
Q8.Interlocking.>Enable closing [BOOL]
Q8.Interlocking.>Enable opening
[BOOL]
Totally Integrated
Automation Portal

=E01+R01_F003
4. Enclavamiento QZ1/ - QZ9/
Totally Integrated
Automation Portal

and10_1
AND10
AND
QZ1.Disconnector.Position.open [BOOL] X1 Y QZ9/.Interlocking.>Enable closing [BOOL]
QZ9.Disconnector.Position.open [BOOL] X2 QZ9/.Interlocking.>Enable opening [BOOL]
GIS.Desbloqueo General [BOOL] X3 QZ1/.Interlocking.>Enable closing [BOOL]
GIS.Local/Remoto.closed [BOOL] X4 QZ1/.Interlocking.>Enable opening [BOOL]
QZ9/.Enclavamiento [BOOL]
QZ1/.Enclavamiento [BOOL]
4. Enclavamiento QZ1/ - QZ9/ - Data flow/Task: Event-triggered (1.1 / 3.2)

2.1 ( Page12 - 4)
1.2 ( Page12 - 3)
Totally Integrated
Automation Portal

4. Enclavamiento QZ1/ - QZ9/ - Data flow/Task: Event-triggered (1.2 / 3.2)


1.1 ( Page12 - 2)

2.2 ( Page12 - 5)
Totally Integrated
Automation Portal

4. Enclavamiento QZ1/ - QZ9/ - Data flow/Task: Event-triggered (2.1 / 3.2)


1.1 ( Page12 - 2)

2.2 ( Page12 - 5)

3.1 ( Page12 - 6)
Totally Integrated
Automation Portal

4. Enclavamiento QZ1/ - QZ9/ - Data flow/Task: Event-triggered (2.2 / 3.2)


1.2 ( Page12 - 3)
2.1 ( Page12 - 4)

3.2 ( Page12 - 7)
Totally Integrated
Automation Portal

4. Enclavamiento QZ1/ - QZ9/ - Data flow/Task: Event-triggered (3.1 / 3.2)


2.1 ( Page12 - 4)

3.2 ( Page12 - 7)
Totally Integrated
Automation Portal

4. Enclavamiento QZ1/ - QZ9/ - Data flow/Task: Event-triggered (3.2 / 3.2)


2.2 ( Page12 - 5)
3.1 ( Page12 - 6)
Totally Integrated
Automation Portal
Totally Integrated
Automation Portal

4. Enclavamiento QZ1/ - QZ9/ - Control flow/Task: Event-triggered


Run se‐ Object/parameter Operand Type Unit Task Additional Comment
quence tasks
AND10 and10_1 AND10 default
X1 QZ1.Disconnector.Position.open [BOOL] Bool
X2 QZ9.Disconnector.Position.open [BOOL] Bool
X3 GIS.Desbloqueo General [BOOL] Bool
X4 GIS.Local/Remoto.closed [BOOL] Bool
Y 0 Bool
QZ1/.Enclavamiento [BOOL]
QZ9/.Enclavamiento [BOOL]
QZ1/.Interlocking.>Enable opening
[BOOL]
QZ1/.Interlocking.>Enable closing
[BOOL]
QZ9/.Interlocking.>Enable opening
[BOOL]
QZ9/.Interlocking.>Enable closing
[BOOL]
Totally Integrated
Automation Portal

=E01+R01_F003
5. Enclavamiento Q0
build_sps_1
and10_1 BUILD_SPS
AND10 BUILD_SPS
AND VAL OUT Q0.Interlocking.>
Q0.Circuit break..Position.closed [BOOL] X1 Y 16#0000 QL
Totally Integrated
Automation Portal

GIS.Desbloqueo General [BOOL] X2


GIS.Local/Remoto.closed [BOOL] X3

or10_2

OR10
and10_3 OR
AND10 X1
AND Data.Sw Mode.open [BOOL] X2
QZ1.Disconnector.Position.closed [BOOL] X1 Y X3
QZ9.Disconnector.Position.closed [BOOL] X2
IN-33KV.Circuit break..Position.open [BOOL] X3

nor10_1 build_sps_2

NOR10 BUILD_SPS
NOR BUILD_SPS
R86.Operado [BOOL] X1 Y VAL OUT Q0.Interlocking.>Enable c
Q0.Bloqueo SF6 [BOOL] X2 16#0000 QL
Q0.Proteccion Motor [BOOL] X3
Q0.Resorte Destensado [BOOL] X4 and10_2
Q0.Sup. carrera motor [BOOL] X5 AND10
AND
X1 Y
5. Enclavamiento Q0 - Data flow/Task: Event-triggered (1.1 / 3.2)

X2
GIS.Local/Remoto.closed [BOOL] X3
GIS.Desbloqueo General [BOOL] X4
Data.PT1 en prueba [BOOL] X5
X6

and10_5

AND10
AND
Q0.Falla circuito disparo 1 [BOOL] X1 Y

2.1 ( Page13 - 4)
X2
X3
split_sps_2

SPLIT_SPS
SPLIT_SPS
Goose.PT1Indisp [SSPS] IN VAL
VALID
QL or10_1

OR10
OR
X1 Y
X2

and10_4
Data.PT2 Indisponible [BOOL] AND10
AND
X1 Y
split_sps_1 X2
SPLIT_SPS X3
SPLIT_SPS
T1_F004/PROT/Q0GGIO1/FllCtoDis2 [SSPS] IN VAL
VALID
QL

1.2 ( Page13 - 3)
1.1 ( Page13 - 2)

>Enable opening [SSPS]


Totally Integrated
Automation Portal

build_sps_3

BUILD_SPS
BUILD_SPS
Y VAL OUT Q0.Enclavamiento [SSPS]
16#0000 QL

closing [SSPS]
5. Enclavamiento Q0 - Data flow/Task: Event-triggered (1.2 / 3.2)

2.2 ( Page13 - 5)
Totally Integrated
Automation Portal

5. Enclavamiento Q0 - Data flow/Task: Event-triggered (2.1 / 3.2)


1.1 ( Page13 - 2)

2.2 ( Page13 - 5)

3.1 ( Page13 - 6)
Totally Integrated
Automation Portal

5. Enclavamiento Q0 - Data flow/Task: Event-triggered (2.2 / 3.2)


1.2 ( Page13 - 3)
2.1 ( Page13 - 4)

3.2 ( Page13 - 7)
Totally Integrated
Automation Portal

5. Enclavamiento Q0 - Data flow/Task: Event-triggered (3.1 / 3.2)


2.1 ( Page13 - 4)

3.2 ( Page13 - 7)
Totally Integrated
Automation Portal

5. Enclavamiento Q0 - Data flow/Task: Event-triggered (3.2 / 3.2)


2.2 ( Page13 - 5)
3.1 ( Page13 - 6)
Totally Integrated
Automation Portal
Totally Integrated
Automation Portal

5. Enclavamiento Q0 - Control flow/Task: Event-triggered


Run se‐ Object/parameter Operand Type Unit Task Additional Comment
quence tasks
SPLIT_SPS split_sps_1 SPLIT_SP default
S
IN T1_F004/PROT/Q0GGIO1/FllCtoDis2 Struct
[SSPS]
VAL 0 Bool
and10_4.X2
VALID 0 Bool
and10_4.X3
QL 16#0000 Struct
SPLIT_SPS split_sps_2 SPLIT_SP default
S
IN Goose.PT1Indisp [SSPS] Struct
VAL 0 Bool
and10_5.X2
VALID 0 Bool
and10_5.X3
QL 16#0000 Struct
AND10 and10_4 AND10 default
X1 Data.PT2 Indisponible [BOOL] Bool
X2 split_sps_1.VAL Bool
X3 split_sps_1.VALID Bool
Y 0 Bool
or10_1.X2
AND10 and10_5 AND10 default
X1 Q0.Falla circuito disparo 1 [BOOL] Bool
X2 split_sps_2.VAL Bool
X3 split_sps_2.VALID Bool
Y 0 Bool
or10_1.X1
OR10 or10_1 OR10 default
X1 and10_5.Y Bool
X2 and10_4.Y Bool
Y 0 Bool
and10_2.X6
AND10 and10_3 AND10 default
X1 QZ1.Disconnector.Position.closed Bool
[BOOL]
X2 QZ9.Disconnector.Position.closed Bool
[BOOL]
X3 IN-33KV.Circuit break..Position.open Bool
[BOOL]
Y 0 Bool
and10_2.X1
NOR10 nor10_1 NOR10 default
X1 R86.Operado [BOOL] Bool
X2 Q0.Bloqueo SF6 [BOOL] Bool
X3 Q0.Proteccion Motor [BOOL] Bool
X4 Q0.Resorte Destensado [BOOL] Bool
X5 Q0.Sup. carrera motor [BOOL] Bool
Y 0 Bool
and10_2.X2
AND10 and10_1 AND10 default
X1 Q0.Circuit break..Position.closed [BOOL] Bool
X2 GIS.Desbloqueo General [BOOL] Bool
X3 GIS.Local/Remoto.closed [BOOL] Bool
Y 0 Bool
or10_2.X1
build_sps_1.VAL
AND10 and10_2 AND10 default
X1 and10_3.Y Bool
X2 nor10_1.Y Bool
X3 GIS.Local/Remoto.closed [BOOL] Bool
X4 GIS.Desbloqueo General [BOOL] Bool
X5 Data.PT1 en prueba [BOOL] Bool
X6 or10_1.Y Bool
Y 0 Bool
or10_2.X3
build_sps_2.VAL
OR10 or10_2 OR10 default
X1 and10_1.Y Bool
Totally Integrated
Automation Portal

Run se‐ Object/parameter Operand Type Unit Task Additional Comment


quence tasks
X2 Data.Sw Mode.open [BOOL] Bool
X3 and10_2.Y Bool
Y 0 Bool
build_sps_3.VAL
BUILD_SPS build_sps_1 BUILD_S default
PS
VAL and10_1.Y Bool
QL 16#0000 Struct
OUT 0 Struct
Q0.Interlocking.>Enable opening [SSPS]
BUILD_SPS build_sps_2 BUILD_S default
PS
VAL and10_2.Y Bool
QL 16#0000 Struct
OUT 0 Struct
Q0.Interlocking.>Enable closing [SSPS]
BUILD_SPS build_sps_3 BUILD_S default
PS
VAL or10_2.Y Bool
QL 16#0000 Struct
OUT 0 Struct
Q0.Enclavamiento [SSPS]
Totally Integrated
Automation Portal

=E01+R01_F003
6. Enclavamiento Q15
Totally Integrated
Automation Portal

and10_1 build_sps_1

AND10 BUILD_SPS
AND BUILD_SPS
GIS.Local/Remoto.closed [BOOL] X1 Y VAL OUT Q15.Enclavamiento [SSPS]
QZ1.Disconnector.Position.open [BOOL] X2 16#0000 QL Q15.Interlocking.>Enable closing [SSPS]
GIS.Desbloqueo General [BOOL] X3 Q15.Interlocking.>Enable opening [SSPS]
Q15.Fll Alim Señalizacion [BOOL] X4
X5
X6

split_sps_1 and10_2

SPLIT_SPS AND10
SPLIT_SPS AND
LSR_F003/CTRL/QZ1CSWI1/Pos.open [SSPS] IN VAL X1 Y
VALID X2
QL
split_sps_3 and10_3

SPLIT_SPS AND10
SPLIT_SPS AND
6. Enclavamiento Q15 - Data flow/Task: Event-triggered (1.1 / 3.2)

LSG_F003/CTRL/QZ1CSWI1/Pos.open [SSPS] IN VAL X1 Y


VALID X2
QL

2.1 ( Page14 - 4)
1.2 ( Page14 - 3)
Totally Integrated
Automation Portal

6. Enclavamiento Q15 - Data flow/Task: Event-triggered (1.2 / 3.2)


1.1 ( Page14 - 2)

2.2 ( Page14 - 5)
Totally Integrated
Automation Portal

6. Enclavamiento Q15 - Data flow/Task: Event-triggered (2.1 / 3.2)


1.1 ( Page14 - 2)

2.2 ( Page14 - 5)

3.1 ( Page14 - 6)
Totally Integrated
Automation Portal

6. Enclavamiento Q15 - Data flow/Task: Event-triggered (2.2 / 3.2)


1.2 ( Page14 - 3)
2.1 ( Page14 - 4)

3.2 ( Page14 - 7)
Totally Integrated
Automation Portal

6. Enclavamiento Q15 - Data flow/Task: Event-triggered (3.1 / 3.2)


2.1 ( Page14 - 4)

3.2 ( Page14 - 7)
Totally Integrated
Automation Portal

6. Enclavamiento Q15 - Data flow/Task: Event-triggered (3.2 / 3.2)


2.2 ( Page14 - 5)
3.1 ( Page14 - 6)
Totally Integrated
Automation Portal
Totally Integrated
Automation Portal

6. Enclavamiento Q15 - Control flow/Task: Event-triggered


Run se‐ Object/parameter Operand Type Unit Task Additional Comment
quence tasks
SPLIT_SPS split_sps_1 SPLIT_SP default
S
IN LSR_F003/CTRL/QZ1CSWI1/Pos.open Struct
[SSPS]
VAL 0 Bool
and10_2.X1
VALID 0 Bool
and10_2.X2
QL 16#0000 Struct
SPLIT_SPS split_sps_3 SPLIT_SP default
S
IN LSG_F003/CTRL/QZ1CSWI1/Pos.open Struct
[SSPS]
VAL 0 Bool
and10_3.X1
VALID 0 Bool
and10_3.X2
QL 16#0000 Struct
AND10 and10_2 AND10 default
X1 split_sps_1.VAL Bool
X2 split_sps_1.VALID Bool
Y 0 Bool
and10_1.X5
AND10 and10_3 AND10 default
X1 split_sps_3.VAL Bool
X2 split_sps_3.VALID Bool
Y 0 Bool
and10_1.X6
AND10 and10_1 AND10 default
X1 GIS.Local/Remoto.closed [BOOL] Bool
X2 QZ1.Disconnector.Position.open [BOOL] Bool
X3 GIS.Desbloqueo General [BOOL] Bool
X4 Q15.Fll Alim Señalizacion [BOOL] Bool
X5 and10_2.Y Bool
X6 and10_3.Y Bool
Y 0 Bool
build_sps_1.VAL
BUILD_SPS build_sps_1 BUILD_S default
PS
VAL and10_1.Y Bool
QL 16#0000 Struct
OUT 0 Struct
Q15.Interlocking.>Enable opening
[SSPS]
Q15.Interlocking.>Enable closing [SSPS]
Q15.Enclavamiento [SSPS]
Totally Integrated
Automation Portal

=E01+R01_F003
7. Señales
connect_1
CONNECT
Time sync..Time sync. error [SSPS] CONNECT
IN OUT Data.Error sinc de tiempo [SSPS]

build_dps_1
Totally Integrated
Automation Portal

BUILD_DPS
BUILD_DPS
General.Switching authority.remote [BOOL] IS_ON OUT Data.Sw Authority [SDPS]
General.Switching authority.local [BOOL] IS_OFF
0 BAD_00
16#0000 QL

build_dps_2

BUILD_DPS
BUILD_DPS
General.Switching mode.interlocked [BOOL] IS_ON OUT Data.Sw Mode [SDPS]
General.Switching mode.non-interlocked [BOOL] IS_OFF
0 BAD_00
16#0000 QL

neg_1

NEG
7. Señales - Data flow/Task: Event-triggered (1.1 / 3.2)

NEG
E:ETH-BB-2FO.Channel 1.RSTP.Channel Live [BOOL] IN OUT E:ETH-BB-2FO.Channel 1.RSTP.Fail_CH1 [BOOL]

neg_2

NEG
NEG
E:ETH-BB-2FO.Channel 1.RSTP.Redund. Channel Live [BOOL] IN OUT E:ETH-BB-2FO.Channel 1.RSTP.Fail_CH2 [BOOL]

and10_1

AND10
AND
Q0.74TC sup.2BI 1.Trip-circuit failure [BOOL] X1 Y Q0.Falla circuito disparo 1 [BOOL]
1 X2

2.1 ( Page15 - 4)
1.2 ( Page15 - 3)
Totally Integrated
Automation Portal

7. Señales - Data flow/Task: Event-triggered (1.2 / 3.2)


1.1 ( Page15 - 2)

2.2 ( Page15 - 5)
Totally Integrated
Automation Portal

7. Señales - Data flow/Task: Event-triggered (2.1 / 3.2)


1.1 ( Page15 - 2)

2.2 ( Page15 - 5)

3.1 ( Page15 - 6)
Totally Integrated
Automation Portal

7. Señales - Data flow/Task: Event-triggered (2.2 / 3.2)


1.2 ( Page15 - 3)
2.1 ( Page15 - 4)

3.2 ( Page15 - 7)
Totally Integrated
Automation Portal

7. Señales - Data flow/Task: Event-triggered (3.1 / 3.2)


2.1 ( Page15 - 4)

3.2 ( Page15 - 7)
Totally Integrated
Automation Portal

7. Señales - Data flow/Task: Event-triggered (3.2 / 3.2)


2.2 ( Page15 - 5)
3.1 ( Page15 - 6)
Totally Integrated
Automation Portal
Totally Integrated
Automation Portal

7. Señales - Control flow/Task: Event-triggered


Run se‐ Object/parameter Operand Type Unit Task Additional Comment
quence tasks
CONNECT connect_1 CON‐ default
NECT
IN Time sync..Time sync. error [SSPS] Struct
OUT 0 Struct
Data.Error sinc de tiempo [SSPS]
BUILD_DPS build_dps_1 BUILD_D default
PS
IS_ON General.Switching authority.remote Bool
[BOOL]
IS_OFF General.Switching authority.local Bool
[BOOL]
BAD_00 0 Bool
QL 16#0000 Struct
OUT 16#0000 Struct
Data.Sw Authority [SDPS]
BUILD_DPS build_dps_2 BUILD_D default
PS
IS_ON General.Switching mode.interlocked Bool
[BOOL]
IS_OFF General.Switching mode.non-inter‐ Bool
locked [BOOL]
BAD_00 0 Bool
QL 16#0000 Struct
OUT 16#0000 Struct
Data.Sw Mode [SDPS]
AND10 and10_1 AND10 default
X1 Q0.74TC sup.2BI 1.Trip-circuit failure Bool
[BOOL]
X2 1 Bool
Y 0 Bool
Q0.Falla circuito disparo 1 [BOOL]
NEG neg_1 NEG default
IN E:ETH-BB-2FO.Channel 1.RSTP.Channel Bool
Live [BOOL]
OUT 0 Bool
E:ETH-BB-2FO.Channel 1.RSTP.Fail_CH1
[BOOL]
NEG neg_2 NEG default
IN E:ETH-BB-2FO.Channel 1.RSTP.Redund. Bool
Channel Live [BOOL]
OUT 0 Bool
E:ETH-BB-2FO.Channel 1.RSTP.Fail_CH2
[BOOL]
Totally Integrated
Automation Portal

=E01+R01_F003
9. Alarma Grave
split_sps_2 and10_2

SPLIT_SPS AND10
SPLIT_SPS AND
Goose.BloqSF6 [SSPS] IN VAL X1 Y
Totally Integrated
Automation Portal

VALID X2 or10_1
QL OR10
OR
X1 Y Q0.Alarma grave Q0 [BOOL]
Q0.Bloqueo SF6 [BOOL] X2

split_sps_1 and10_1
SPLIT_SPS AND10
SPLIT_SPS AND
Goose.Tr.general [SSPS] IN VAL X1 Y
VALID X2
QL or10_2

OR10
OR
X1 Y Data.Alarma grave BH [BOOL]
Q0.Trip logic.Trip indication.general [BOOL] X2
9. Alarma Grave - Data flow/Task: Event-triggered (1.1 / 3.2)

2.1 ( Page16 - 4)
1.2 ( Page16 - 3)
Totally Integrated
Automation Portal

9. Alarma Grave - Data flow/Task: Event-triggered (1.2 / 3.2)


1.1 ( Page16 - 2)

2.2 ( Page16 - 5)
Totally Integrated
Automation Portal

9. Alarma Grave - Data flow/Task: Event-triggered (2.1 / 3.2)


1.1 ( Page16 - 2)

2.2 ( Page16 - 5)

3.1 ( Page16 - 6)
Totally Integrated
Automation Portal

9. Alarma Grave - Data flow/Task: Event-triggered (2.2 / 3.2)


1.2 ( Page16 - 3)
2.1 ( Page16 - 4)

3.2 ( Page16 - 7)
Totally Integrated
Automation Portal

9. Alarma Grave - Data flow/Task: Event-triggered (3.1 / 3.2)


2.1 ( Page16 - 4)

3.2 ( Page16 - 7)
Totally Integrated
Automation Portal

9. Alarma Grave - Data flow/Task: Event-triggered (3.2 / 3.2)


2.2 ( Page16 - 5)
3.1 ( Page16 - 6)
Totally Integrated
Automation Portal
Totally Integrated
Automation Portal

9. Alarma Grave - Control flow/Task: Event-triggered


Run se‐ Object/parameter Operand Type Unit Task Additional Comment
quence tasks
SPLIT_SPS split_sps_1 SPLIT_SP default
S
IN Goose.Tr.general [SSPS] Struct
VAL 0 Bool
and10_1.X1
VALID 0 Bool
and10_1.X2
QL 16#0000 Struct
SPLIT_SPS split_sps_2 SPLIT_SP default
S
IN Goose.BloqSF6 [SSPS] Struct
VAL 0 Bool
and10_2.X1
VALID 0 Bool
and10_2.X2
QL 16#0000 Struct
AND10 and10_1 AND10 default
X1 split_sps_1.VAL Bool
X2 split_sps_1.VALID Bool
Y 0 Bool
or10_2.X1
AND10 and10_2 AND10 default
X1 split_sps_2.VAL Bool
X2 split_sps_2.VALID Bool
Y 0 Bool
or10_1.X1
OR10 or10_1 OR10 default
X1 and10_2.Y Bool
X2 Q0.Bloqueo SF6 [BOOL] Bool
Y 0 Bool
Q0.Alarma grave Q0 [BOOL]
OR10 or10_2 OR10 default
X1 and10_1.Y Bool
X2 Q0.Trip logic.Trip indication.general Bool
[BOOL]
Y 0 Bool
Data.Alarma grave BH [BOOL]
Totally Integrated
Automation Portal

=E01+R01_F003
10. Permisivo cierre Q0
Totally Integrated
Automation Portal

or10_1

OR10
Q0.Falla circuito disparo 1 [BOOL] OR
Data.=E03 MCB Barra Oper [BOOL] X1 Y Q0.Permisivo de cierre Q0 [BOOL]
X2
X3
and10_1

AND10
AND
Q0.25 Synchronization.Synchrocheck 1.All sync. conditio. OK [BOOL] X1 Y
Q0.25 Synchronization.Synchrocheck 1.>Op. mode 'V1<V2>' [BOOL] X2
Q0.25 Synchronization.Synchrocheck 1.>Op. mode 'V1>V2<' [BOOL] X3
Q0.25 Synchronization.Synchrocheck 1.>Op. mode 'V1<V2<' [BOOL] X4
10. Permisivo cierre Q0 - Data flow/Task: Event-triggered (1.1 / 3.2)

2.1 ( Page17 - 4)
1.2 ( Page17 - 3)
Totally Integrated
Automation Portal

10. Permisivo cierre Q0 - Data flow/Task: Event-triggered (1.2 / 3.2)


1.1 ( Page17 - 2)

2.2 ( Page17 - 5)
Totally Integrated
Automation Portal

10. Permisivo cierre Q0 - Data flow/Task: Event-triggered (2.1 / 3.2)


1.1 ( Page17 - 2)

2.2 ( Page17 - 5)

3.1 ( Page17 - 6)
Totally Integrated
Automation Portal

10. Permisivo cierre Q0 - Data flow/Task: Event-triggered (2.2 / 3.2)


1.2 ( Page17 - 3)
2.1 ( Page17 - 4)

3.2 ( Page17 - 7)
Totally Integrated
Automation Portal

10. Permisivo cierre Q0 - Data flow/Task: Event-triggered (3.1 / 3.2)


2.1 ( Page17 - 4)

3.2 ( Page17 - 7)
Totally Integrated
Automation Portal

10. Permisivo cierre Q0 - Data flow/Task: Event-triggered (3.2 / 3.2)


2.2 ( Page17 - 5)
3.1 ( Page17 - 6)
Totally Integrated
Automation Portal
Totally Integrated
Automation Portal

10. Permisivo cierre Q0 - Control flow/Task: Event-triggered


Run se‐ Object/parameter Operand Type Unit Task Additional Comment
quence tasks
AND10 and10_1 AND10 default
X1 Q0.25 Synchronization.Synchrocheck Bool
1.All sync. conditio. OK [BOOL]
X2 Q0.25 Synchronization.Synchrocheck Bool
1.>Op. mode 'V1<V2>' [BOOL]
X3 Q0.25 Synchronization.Synchrocheck Bool
1.>Op. mode 'V1>V2<' [BOOL]
X4 Q0.25 Synchronization.Synchrocheck Bool
1.>Op. mode 'V1<V2<' [BOOL]
Y 0 Bool
or10_1.X3
OR10 or10_1 OR10 default
X1 Q0.Falla circuito disparo 1 [BOOL] Bool
X2 Data.=E03 MCB Barra Oper [BOOL] Bool
X3 and10_1.Y Bool
Y 0 Bool
Q0.Permisivo de cierre Q0 [BOOL]
Totally Integrated
Automation Portal

=E01+R01_F003
11. Sincronismo
Totally Integrated
Automation Portal

or10_1

OR10
OR
Q0.25 Synchronization.Synchrocheck 1.α dif.too large(α2>α1) [BOOL] X1 Y Data.Dif. angulo excedido [BOOL]
Q0.25 Synchronization.Synchrocheck 1.α dif.too large(α2<α1) [BOOL] X2

or10_2

OR10
OR
Q0.25 Synchronization.Synchrocheck 1.f dif.too large(f2>f1) [BOOL] X1 Y Data.Dif. frecuencia excedido [BOOL]
Q0.25 Synchronization.Synchrocheck 1.f dif.too large(f2<f1) [BOOL] X2

or10_3

OR10
OR
Q0.25 Synchronization.Synchrocheck 1.V dif.too large(V2>V1) [BOOL] X1 Y Data.Dif. voltaje excedido [BOOL]
Q0.25 Synchronization.Synchrocheck 1.V dif.too large(V2<V1) [BOOL] X2
11. Sincronismo - Data flow/Task: Event-triggered (1.1 / 3.2)

2.1 ( Page18 - 4)
1.2 ( Page18 - 3)
Totally Integrated
Automation Portal

11. Sincronismo - Data flow/Task: Event-triggered (1.2 / 3.2)


1.1 ( Page18 - 2)

2.2 ( Page18 - 5)
Totally Integrated
Automation Portal

11. Sincronismo - Data flow/Task: Event-triggered (2.1 / 3.2)


1.1 ( Page18 - 2)

2.2 ( Page18 - 5)

3.1 ( Page18 - 6)
Totally Integrated
Automation Portal

11. Sincronismo - Data flow/Task: Event-triggered (2.2 / 3.2)


1.2 ( Page18 - 3)
2.1 ( Page18 - 4)

3.2 ( Page18 - 7)
Totally Integrated
Automation Portal

11. Sincronismo - Data flow/Task: Event-triggered (3.1 / 3.2)


2.1 ( Page18 - 4)

3.2 ( Page18 - 7)
Totally Integrated
Automation Portal

11. Sincronismo - Data flow/Task: Event-triggered (3.2 / 3.2)


2.2 ( Page18 - 5)
3.1 ( Page18 - 6)
Totally Integrated
Automation Portal
Totally Integrated
Automation Portal

11. Sincronismo - Control flow/Task: Event-triggered


Run se‐ Object/parameter Operand Type Unit Task Additional Comment
quence tasks
OR10 or10_1 OR10 default
X1 Q0.25 Synchronization.Synchrocheck Bool
1.α dif.too large(α2>α1) [BOOL]
X2 Q0.25 Synchronization.Synchrocheck Bool
1.α dif.too large(α2<α1) [BOOL]
Y 0 Bool
Data.Dif. angulo excedido [BOOL]
OR10 or10_2 OR10 default
X1 Q0.25 Synchronization.Synchrocheck Bool
1.f dif.too large(f2>f1) [BOOL]
X2 Q0.25 Synchronization.Synchrocheck Bool
1.f dif.too large(f2<f1) [BOOL]
Y 0 Bool
Data.Dif. frecuencia excedido [BOOL]
OR10 or10_3 OR10 default
X1 Q0.25 Synchronization.Synchrocheck Bool
1.V dif.too large(V2>V1) [BOOL]
X2 Q0.25 Synchronization.Synchrocheck Bool
1.V dif.too large(V2<V1) [BOOL]
Y 0 Bool
Data.Dif. voltaje excedido [BOOL]
Totally Integrated
Automation Portal

=E01+R01_F003
8. Arranque Ext Oscilo
tshort_1
TSHORT or10_1 or10_3
TSHORT OR10 OR10
START Q OR OR Prot. Mecanicas.Disp Alta Temp Aceite [BOOL]
0 RESET QT X1 Y X1 Y Recording.Fault recorder.Control.>External start [BOOL]
200 ms Tx1ms X2 X2
Totally Integrated
Automation Portal

tshort_2 X3
TSHORT X4
TSHORT X5
START Q X6 Prot. Mecanicas.Disp Rele Detector Gas [BOOL]
0 RESET QT X7 Prot. Mecanicas.Disp Valv Aliv Presion [BOOL]
200 ms Tx1ms Prot. Mecanicas.Disp Prot Conmutador [BOOL]
tshort_3 Prot. Mecanicas.Disp Valvula Autom [BOOL]

TSHORT
TSHORT
START Q tshort_8
0 RESET QT TSHORT or10_2
200 ms Tx1ms TSHORT OR10
tshort_4 START Q OR

TSHORT 0 RESET QT X1 Y
TSHORT 200 ms Tx1ms X2
START Q tshort_9 X3
0 RESET QT TSHORT X4
200 ms Tx1ms TSHORT X5
tshort_5 START Q X6

TSHORT 0 RESET QT X7
TSHORT 200 ms Tx1ms
START Q tshort_10
0 RESET QT TSHORT
200 ms Tx1ms TSHORT
tshort_6 START Q
8. Arranque Ext Oscilo - Data flow/Task: Fast Event-triggered (1.1 / 3.2)

TSHORT 0 RESET QT
TSHORT 200 ms Tx1ms
START Q tshort_11 Prot. Mecanicas.Disp Indic Temp Bobina [BOOL]
0 RESET QT TSHORT
200 ms Tx1ms TSHORT
tshort_7 START Q
TSHORT 0 RESET QT

2.1 ( Page19 - 4)
TSHORT 200 ms Tx1ms
START Q tshort_12 Prot. Mecanicas.Disp Rele Presion Sub [BOOL]
0 RESET QT TSHORT
200 ms Tx1ms TSHORT
START Q
0 RESET QT
Prot. Mecanicas.Alar Rele Sup Conserv [BOOL] 200 ms Tx1ms
Prot. Mecanicas.Alar Min Niv Oil Trafo [BOOL] tshort_13
Prot. Mecanicas.Alar Max Niv Oil Trafo [BOOL] TSHORT
Prot. Mecanicas.Alar Rele Detector Gas [BOOL] TSHORT
Prot. Mecanicas.Alar Alta Temp Bobina [BOOL] START Q
Prot. Mecanicas.Alar Alta Temp Aceite [BOOL] 0 RESET QT
200 ms Tx1ms
tshort_14

TSHORT
TSHORT
Prot. Mecanicas.Alar Rele Bloqueado [BOOL] START Q
0 RESET QT
200 ms Tx1ms

1.2 ( Page19 - 3)
Totally Integrated
Automation Portal

8. Arranque Ext Oscilo - Data flow/Task: Fast Event-triggered (1.2 / 3.2)


1.1 ( Page19 - 2)

2.2 ( Page19 - 5)
Totally Integrated
Automation Portal

8. Arranque Ext Oscilo - Data flow/Task: Fast Event-triggered (2.1 / 3.2)


1.1 ( Page19 - 2)

2.2 ( Page19 - 5)

3.1 ( Page19 - 6)
Totally Integrated
Automation Portal

8. Arranque Ext Oscilo - Data flow/Task: Fast Event-triggered (2.2 / 3.2)


1.2 ( Page19 - 3)
2.1 ( Page19 - 4)

3.2 ( Page19 - 7)
Totally Integrated
Automation Portal

8. Arranque Ext Oscilo - Data flow/Task: Fast Event-triggered (3.1 / 3.2)


2.1 ( Page19 - 4)

3.2 ( Page19 - 7)
Totally Integrated
Automation Portal

8. Arranque Ext Oscilo - Data flow/Task: Fast Event-triggered (3.2 / 3.2)


2.2 ( Page19 - 5)
3.1 ( Page19 - 6)
Totally Integrated
Automation Portal
Totally Integrated
Automation Portal

8. Arranque Ext Oscilo - Control flow/Task: Fast Event-triggered


Run se‐ Object/parameter Operand Type Unit Task Additional Comment
quence tasks
TSHORT tshort_1 TSHORT default
START Prot. Mecanicas.Disp Alta Temp Aceite Bool
[BOOL]
RESET 0 Bool
Tx1ms 200 DInt ms
(1..2147
483645)
Q 0 Bool
QT 0 Bool
or10_1.X1
TSHORT tshort_2 TSHORT default
START Prot. Mecanicas.Disp Rele Detector Gas Bool
[BOOL]
RESET 0 Bool
Tx1ms 200 DInt ms
(1..2147
483645)
Q 0 Bool
QT 0 Bool
or10_1.X2
TSHORT tshort_3 TSHORT default
START Prot. Mecanicas.Disp Valv Aliv Presion Bool
[BOOL]
RESET 0 Bool
Tx1ms 200 DInt ms
(1..2147
483645)
Q 0 Bool
QT 0 Bool
or10_1.X3
TSHORT tshort_4 TSHORT default
START Prot. Mecanicas.Disp Prot Conmutador Bool
[BOOL]
RESET 0 Bool
Tx1ms 200 DInt ms
(1..2147
483645)
Q 0 Bool
QT 0 Bool
or10_1.X4
TSHORT tshort_5 TSHORT default
START Prot. Mecanicas.Disp Valvula Autom Bool
[BOOL]
RESET 0 Bool
Tx1ms 200 DInt ms
(1..2147
483645)
Q 0 Bool
QT 0 Bool
or10_1.X5
TSHORT tshort_6 TSHORT default
START Prot. Mecanicas.Disp Indic Temp Bobina Bool
[BOOL]
RESET 0 Bool
Tx1ms 200 DInt ms
(1..2147
483645)
Q 0 Bool
QT 0 Bool
or10_1.X6
TSHORT tshort_7 TSHORT default
START Prot. Mecanicas.Disp Rele Presion Sub Bool
[BOOL]
RESET 0 Bool
Tx1ms 200 DInt ms
(1..2147
483645)
Q 0 Bool
QT 0 Bool
or10_1.X7
TSHORT tshort_8 TSHORT default
START Prot. Mecanicas.Alar Alta Temp Aceite Bool
[BOOL]
RESET 0 Bool
Tx1ms 200 DInt ms
(1..2147
483645)
Totally Integrated
Automation Portal

Run se‐ Object/parameter Operand Type Unit Task Additional Comment


quence tasks
Q 0 Bool
QT 0 Bool
or10_2.X1
TSHORT tshort_9 TSHORT default
START Prot. Mecanicas.Alar Rele Detector Gas Bool
[BOOL]
RESET 0 Bool
Tx1ms 200 DInt ms
(1..2147
483645)
Q 0 Bool
QT 0 Bool
or10_2.X2
TSHORT tshort_10 TSHORT default
START Prot. Mecanicas.Alar Max Niv Oil Trafo Bool
[BOOL]
RESET 0 Bool
Tx1ms 200 DInt ms
(1..2147
483645)
Q 0 Bool
QT 0 Bool
or10_2.X3
TSHORT tshort_11 TSHORT default
START Prot. Mecanicas.Alar Min Niv Oil Trafo Bool
[BOOL]
RESET 0 Bool
Tx1ms 200 DInt ms
(1..2147
483645)
Q 0 Bool
QT 0 Bool
or10_2.X4
TSHORT tshort_12 TSHORT default
START Prot. Mecanicas.Alar Rele Sup Conserv Bool
[BOOL]
RESET 0 Bool
Tx1ms 200 DInt ms
(1..2147
483645)
Q 0 Bool
QT 0 Bool
or10_2.X5
TSHORT tshort_13 TSHORT default
START Prot. Mecanicas.Alar Alta Temp Bobina Bool
[BOOL]
RESET 0 Bool
Tx1ms 200 DInt ms
(1..2147
483645)
Q 0 Bool
QT 0 Bool
or10_2.X6
TSHORT tshort_14 TSHORT default
START Prot. Mecanicas.Alar Rele Bloqueado Bool
[BOOL]
RESET 0 Bool
Tx1ms 200 DInt ms
(1..2147
483645)
Q 0 Bool
QT 0 Bool
or10_2.X7
OR10 or10_1 OR10 default
X1 tshort_1.QT Bool
X2 tshort_2.QT Bool
X3 tshort_3.QT Bool
X4 tshort_4.QT Bool
X5 tshort_5.QT Bool
X6 tshort_6.QT Bool
X7 tshort_7.QT Bool
Y 0 Bool
or10_3.X1
OR10 or10_2 OR10 default
X1 tshort_8.QT Bool
X2 tshort_9.QT Bool
Totally Integrated
Automation Portal

Run se‐ Object/parameter Operand Type Unit Task Additional Comment


quence tasks
X3 tshort_10.QT Bool
X4 tshort_11.QT Bool
X5 tshort_12.QT Bool
X6 tshort_13.QT Bool
X7 tshort_14.QT Bool
Y 0 Bool
or10_3.X2
OR10 or10_3 OR10 default
X1 or10_1.Y Bool
X2 or10_2.Y Bool
Y 0 Bool
Recording.Fault recorder.Control.>Ex‐
ternal start [BOOL]
Totally Integrated
Automation Portal

=E01+R01_F003 / Display pages


Fault-display configuration
Q0
Display line Displayed information
Display line 1 Pickup indication
Display line 2 PU time
Display line 3 Operate indication
Display line 4 Trip time
Display line 5 No alarm
Display line 6 No alarm
Totally Integrated
Automation Portal

=E01+R01_F003
Safety and security
Operations safety and access control
Enter confirmation ID
Scope of operation Active Description
Settings / operation true Allows change of settings and access to process data.
Fct.Key/PB operation false Allows operating via function keys and push-buttons only
with confirmation ID (of Settings/Operation).
Switching (process) true Allows switching operations.

Security event logging


Sec. Ev. Logg. \General
Number Settings Value
81.2761.19021.120 Device log capacity warn. All: 80 %

Sec. Ev. Logg. \Syslog server A


Number Settings Value
81.2761.19021.101 Enable logging All: false

Sec. Ev. Logg. \Syslog server B


Number Settings Value
81.2761.19021.111 Enable logging All: false