Академический Документы
Профессиональный Документы
Культура Документы
NUMERICAL RE L.AY .
ADISSERTATION
Submitted in partial fulfillment of the
requirements for the award of the degree
of
MASTER OF TECHNOLOGY
in
ELECTRICAL ENGINEERING
(With Specialization in Power System Engineering)
By
RA MESH PADARLA
Candidate's Declaration
Date: 3 D— Q -(0
Place: Roorkee (Ramesh Padarla)
CERTIFICATE
This is to certify that the above statements made by the candidate are
correct to the best of my knowledge.
f . ~
Ramesh Padarla
M. Tech (Power System Engineering)
ABSTRACT
iv
5.4.1 IDMT Characteristics for the current setting of 1A and
25
for a TSM of 1.0
5.4.2 Very Inverse characteristics for pick up value of 1A
26
and for aTSMof1.0
5.4.3 Extremely Inverse characteristics for pick up value of
27
1A and fora TSM of 1.0
6 PSCAD SIMULATION MODEL AND RESULTS 28
6.1 Introduction 28
6.2 Transmission line Simulation Model 28
6.3 Simulation Flow Chart for Impedance relay 29
6.4 Simulation Results for Impedance relay 30
7 TEST RESULTS 35
7.1 Test Results for impedance relay 35
7.2 Test Results for overcurrent relay 43
8 CONCLUSION AND FUTURE SCOPE 51
8.1 Conclusion 51
8.2 Future Scope 51
References 52
Appendix A 55
Appendix B 56
Appendix C 59
Appendix D 61
List of Figures
Fig. No Legend Pg No
Fig.1.1 Block diagram of Numerical relay 3
Fig. 2.1 Voltage fed to the DAQ card through step-down transformers 9
Fig. 2.2 Photograph of voltage fed to DAQ card through step-down 9
transformers
Fig. 2.3 Voltage fed to the DAQ card from LEM Module LA-50P current 10
transducers
Fig.2.4 Photograph of LEM module LA-50P current transducers 10
Fig.2.5 Block diagram of the Emulated model of NI USB-6212 DAQ 11
card
Fig.2.6 Photograph of NI USB-6212 DAQ card 11
Fig.2.7 Pin assignment of the DAQ card 11
Fig.2.8 Photograph of Laboratory setup for 100km transmission line 12
Fig.2.9 Photographs of Laboratory setup 12
Fig.3.1 Flowchart for selecting the type of operation of the 14
Multifunctional relay
Fig. 3.2 Flowchart for Impedance Relay. 14
Fig. 3.3 Flowchart representing the settings of an overcurrent relay 15
Fig. 3.4 Flowchart representing the operation of an overcurrent relay 16
Fig. 4.1 Types of impedance relay characteristics 17
(a) Impedance, (b) Admittance or mho
(c) Reactance (d) Quadrilateral
Fig. 4.2 Distance relay protection zones 20
Fig. 4.3 Impedance relay characteristics for three zones of protection 20
Fig. 5.1 Time/current operating characteristics of overcurrent relays 22
Fig. 5.2 IDMT characteristics of over current relay 25
Fig. 5.3 Very Inverse characteristics of over current relay 26
Fig.5.4 Extremely Inverse characteristics of over current relay 27
Fig 6.1 PSCAD Simulation model 28
Fig. 6.2 Simulation flow chart for Impedance relay 29
Fig. 6.3 Impedance trajectory for ABC fault 30
vi
Fig. 6.4 Voltage, current waveforms at impedance relay location and trip 30
signal to the circuit breaker for ABC fault
Fig. 6.5 Impedance trajectory for AB fault 31
Fig. 6.6 Voltage, current waveforms at impedance relay location and trip 31
signal to the Circuit Breaker for AB fault
Fig. 6.7 Impedance trajectory for ABG fault 32
Fig. 6.8 Voltage, current waveforms at impedance relay location and trip 32
signal to the circuit breaker for ABG fault
Fig. 6.9 Impedance trajectory for ABCG fault 33
Fig. 6.10 Voltage, current waveforms at impedance relay location and trip 33
signal to the circuit breaker for ABCG fault
Fig. 6.11 Impedance trajectory for AG fault 34
Fig. 6.12 Voltage, current waveforms at impedance relay location and trip 34
signal to the circuit breaker for AG fault
Fig. 7.1 Impedance Trajectory of the AB element for ABC Fault 35
Fig. 7.2 Result of Impedance relay for ABC fault 36
Fig. 7.3 Trajectory Impedance of the AB element for AB Fault 37
Fig. 7.4 Result of Impedance relay for AB fault 38
Fig. 7.5 Trajectory Impedance of the AG element for ABCG Fault 39
Fig. 7.6 Trajectory Impedance of AG,BG and CG elements for ABCG 39
Fault
Fig. 7.7 Result of impedance relay for ABCG fault 40
Fig. 7.8 Trajectory Impedance of the AG element for ABG Fault 41
Fig. 7.9 Result of impedance realy for ABG fault 42
Fig. 7.10 Result of IDMT Overcurrent relay for a current setting of 1A and 44
TSM of 1.0 for phase 'a'
Fig. 7.11 Results of IDMT Overcurrent relay for a current setting of 1A 46
and TSM of 1.0 for phase 'c'
Fig. 7.12 Result of Extremely Inverse Overcurrent relay for a pickup value 48
of 1A and TSM of 1.0 for phase 'a'
Fig. 6.4 Results of Very Inverse Over current relay for a pickup value of 81
IA and TSM of 1.0 for phase 'a'
vii
List of Tables
Table No Title Page No
viii
CHAPTER 1
INTRODUCTION
One of the most important equipments employed in the protection of
power systems are protective relays. For several decades, the power system
protection relay has experienced many important changes, from purely
electromechanical type to the mixture of electronic and electromechanical type,
then to fully static and now fully numerical relays based on microprocessors. In
the transmission line protection area similar changes can be seen. The
developments in digital technology led to the incorporation of microprocessors
in the construction of relays. Digital and numerical relays are sophisticated,
multiple purpose equipment with the capacity to record signals during faults,
monitor themselves and communicate with their peers. Numerical relays
employ microprocessors especially constructed to process digital signals,
which make them faster and more powerful, while preserving their economic
advantages
1
largely employed, tested and known that even modern relays employ their
principle of operation, and still represent a good choice for certain
conditions of application.
b. Solid state relays: with the advances on electronics, the electromechanical
technology presented in the relays of the first generation started to be
replaced by the static relays in the early 60's. Static relays defined the
operating characteristic based in analog circuitry rather than in the action of
windings and coils. The advantages that static relays showed over
electromechanical relays were a reduced size, weight and electrical burden.
However, static showed some disadvantages since analog circuitry is
extremely affected by electromagnetic interference and the ranges of
current and voltages values are strongly restricted in analog circuits,
affecting the sensitivity of the relay.
c. Digital relays: incorporating microprocessor into the architecture of the
relay to implement relay and logic functions started happening in the 80's.
digital relays incorporated analog-to-digital converter (ADC) to sample the
analog signals incoming from instrument transformers, and used
microprocessor to define the logic of the relay. Digital relays presented an
improvement in accuracy and control over incoming signals, and the use of
more complexes relay algorithms, extra relay functions and complementary
task.
d. Numerical relays: The difference between numerical relays and digital
relays lies in the kind of microprocessor used. Numerical relays used digital
signal processors (DSP) cards, which contain dedicated microprocessors
especially designed to perform digital signal processing.
2
• Analog anti-aliasing filtering: Low pass filters are used to avoid the
phenomena of aliasing in which the high frequency components of the
inputs appear to be parts of the fundamental frequency components.
• Analog to digital conversion: Because digital processors can process
numerical or logical data only, the waveforms of inputs must be sampled
at discrete times. To achieve this, each analog signal is passed through a
sample and hold module, and conveyed, one at a time, to an analog-to-
digital converter (ADC) by a multiplexer.
• Phasor estimation method: A software algorithm implemented in a
microprocessor estimates the amplitude and phase of the waveforms
provided to the relay.
• Relay algorithm and trip logic: The equations and parameters specific
to the protection algorithm and the associated trip logic are implemented
in the software of the microprocessor used in the relay. The
microprocessor calculates the phasors representing the inputs, acquires
the status of the switches, performs protective relay calculations, and
finally provides outputs for controlling the circuit breakers. The processor
may also support communications, self-testing, target display and other
tasks
3
The figure 1.1 shows block diagram of numerical relay numerical relay.
Relaying voltages and currents are passed through Isolation Transformers.
Since analog to digital conversion is usually performed on voltages, the current
signals are converted to representative voltages by passing them through a
known resistance. All the signals are then filtered using simple analog Anti
aliasing Filters. Since ADCs are expensive it is common to use only one in a
numeric relay. Thus an analog Multiplexer is used, under microprocessor
control, sequentially to select the required signal into ADC. Since an ADC takes
a finite conversion time usually 25 micro seconds, it is necessary to hold the
incoming signal for the duration of conversion. This is achieved by a Sample
and Hold amplifier. Having been manipulated by the ADC the signal can be fed
to Microprocessor. There may be one or more processors, one for running
algorithm and another for scheme logic. The relaying program will be located in
ROM and a RAM will be used for storing sampled quantities and - intermediate
products in relaying algorithm. Relay settings will be stored in EEPROM.
0
In the year 1971, 'A New Algorithm for Digital Impedance relays'by M. S.
Sachdev, M. A. Baribeau [3] presented a new algorithm suitable for calculating
impedances with the assumption input having decaying d. c. component and
components of the fundamental and harmonic frequencies and also explained
determination of parameters of a digital filter by using the least error squares
approach used to compute the real and imaginary components of the voltage
and current phasors.
In the year 1979, 'The design and test of a digital relay for transformer
protection' by R. R Larson, A. J. Flechsig, E. 0 Schweitzer [4] published the
algorithm for the digital relay to operate in real time and provided outputs
correctly, indicating the presence of either inrush, fault or low differential current
conditions.
5
controlled general control signals 'needed for switching the purpose
programmable multifunction relay appliances. The microprocessor is supported
switching system is proposed.
In the year 2000, 'Numerical Algorithm for Overhead Lines Arcing Faults
Detection and Distance and Directional Protection' by Zoran M. Radojevic,
Vladimir V. Terzija, and Milenko B. Djuric [10] presented an overhead lines
protection numerical algorithm, based on one terminal data and derived in the
time domain.
[;j
presents algorithms to be used for different protection schemes i.e. Overcurrent
protection, Distance protection, Differential protection.
7
CHAPTER 2
To Channel - 5
To Channel - 6
To Channel - 7
To Ground
Fig 2.1 Voltage fed to the DAQ card through step-down transformers
Fig 2.2 Photograph of voltage fed to DAQ card through step-down transformers
+ + ISV
LA 50-P SV
Current transducer — 0-100 oh „
o
IM
To channel -1
+15V
LA 50-P + - 15V
Current transducer 0-100 ohm
© To DAQ Ground
IM '~
To Channel - 2
+15V
LA 50-P - 15V
Current transducer 0-00 ohm
IM To Channel - 3
Fig 2.3 Voltage fed to the DAQ card from LEM Module LA-50P current
transducers
10
To USB Port of CPU
Analog Inputs
Channel 1 Ha1
Channel 2 2
} NI USB 6212
Channel 3
DAQ Card
Channel 5 HA'5
Channel6
Channel 7 r1a7
Fig 2.5 Block diagram of the Emulated model of NI USB-6212 DAQ card
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
11
£r
ep 3~.pi~
.~~✓
f
, F
CHAPTER 3
WORKING OF MULTIFUNCTIONAL
NUMERICAL RELAY
In this thesis 'development of multifunctional numerical relay' a Pentium
processor is considered. The programming is done on a MATLAB platform. The
relays which are implemented are impedance relay and over current relay.
3.1 Impedance relay
User can go the impedance relay by choosing 'S. No.1'. Laboratory set
up for transmission line of length100km is used for impedance relay.
Impedance relay is set for 80% of the transmission line and fault is created at
75km. effect of source impedance is also taken. According to the set values
provided the program constantly monitors the input signal and when fault
occurs it initiates the DAQ card and displays the type of fault.
3.2 Overcurrent relay
The characteristics that user can select are IDMT, very inverse and
extremely inverse characteristics.
For an IDMT relay current setting value in the range 0.5 — 2 Amperes
and the time setting multiplier in the range 0.1-1 are provided.
Pick up current in the range 0.5 — 2 Amperes, time setting multiplier 0.1 — 1for
very inverse and extremely inverse characteristics.
According to the set values provided the program constantly monitors
the input signal and when overcurrent occurs it starts the dock and
correspondingly to the relay characteristics chosen, the relay will trip at the trip
time given by the chosen relay characteristics.
Table 3.1 Channel allocation of the analog inputs
Analog Input Channel Analog Input Channel
Current, Ir 1 Voltage, Vr 5
Current, ly 2 Voltage, Vy 6
Current, lb 3 Voltage, Vb 7
13
START
NO
IF N. IF
ENTERED ENTERED
,1. NO '2'
YES
YES
1 2
Figure 3.1 Flowchart for selecting the type of operation of the multifunctional
relay
I INITIALIZE THE NI USB- 6212 DAQ CARD AND ADD ANALOG INPUT CHANNELS
N O
IS
Zcal <= Zset
YES
m
2
NO
NO NO
NO NO NO
NO
NO NO
0 O O
15
START
THE
CLOCK RESET THE
CLOCK
NO
/\ NO NO
FIND OUT THE TIME OF FIND OUTTHE TIME OF FIND OUT THE TIME OF
TRIPPING FOR CURRENT'I' TRIPPING FOR CURRENT'I' TRIPPING FOR CURRENT'I'
FROM THE CHARACTERISTICS FROM THE CHARACTERISTICS FROM THE CHARACTERISTICS
STORE THE TIME IN A VARIABLE 'A' STORE THE TIME IN A VARIABLE 'B' STORE THE TIME IN A VARIABLE 'C'
NOTE THE CLOCK AND FIND THE NOTE THE CLOCK AND FIND THE NOTE THE CLOCK AND FIND THE
DURATION TIME FROM IT DURATION TIME FROM IT DURATION TIME FROM IT
NO
FAULT DURATION FA r
DURATION FAULT DURATION
EXCEEDS EXCEEDS
CHARACTERISTIC CH CHARACTERISTIC
TIME? TIME?
YES
INITIALIZE
THE OUTPUT
FROM DAQ
16
CHAPTER 4
DISTANCE PROTECTION
4.1 Introduction
Distance relays are normally used to protect transmission lines. They
respond to the impedance between the relay location and the fault location. As
the impedance per mile of a transmission line is fairly constant, these relays
respond to the distance to a fault on the transmission line and hence their
name. As will be seen shortly, under certain conditions it may be desirable to
make distance relays respond-to some parameter other-than the impedance,
such as the admittance or the reactance, up to the fault location. The R—X
diagram is an indispensable tool for describing and analyzing a distance relay
characteristic. According to the shapes of their operating zones distance relays
are classified into four types shown Figure 4.1
x
X
R 0~ V
R
These four relay characteristic shapes are illustrated in Figure 5.1. The
impedance relay has a circular shape centered at the origin of the R—X
diagram. The admittance (or mho) relay has a circular shape which passes
through the origin. The reactance relay has a zone boundary defined by a line
parallel to the R axis. The zone extends to infinity in three directions as shown
17
in Figure 4.1(c). The quadrilateral characteristic, as the name implies, is
defined by four straight lines. This last characteristic is only available in solid-
state or computer relays.
AG Z„ = VA / CIA + 3 k.to
BG Z$ =V~/ Is +3kIJ
CG Z. = 'c/(lc + 3kl,)
AB or ABG Zia = " /(MA —1a)
BC or BCG
18
4.3 Distance Relay Protection Zones
Distance relays are set on the basis of the positive-sequence impedance
from the relay location up to the point on the line to be protected. Normally,
three protection zones in the direction of the fault are used in order to cover a
section of line and to provide back-up protection to remote sections (see Figure
4.2). Some relays have one or two additional zones in the direction of the fault
plus another in the opposite sense, the latter acting as a back-up to protect the
busbars. In the majority of cases the setting of the reach of the three main
protection zones is made in accordance with the following criteria:
Zone 1: This is set to cover between 80 and 85 per cent of the length of the
protected line;
Zone 2: This is set to cover all the protected line plus 50 per cent of the
shortest next line
Zone 3: This is set to cover all the protected line plus 100 per cent of the
second longest line, plus 25 per cent of the shortest next line.
In addition to the unit for setting the reach, each zone unit has a timer
unit. The operating time for zone 1, ti, is normally set by the manufacturer to
trip instantaneously since any fault on the protected line detected by the zone 1
unit should be cleared immediately without the need to wait for any other
device to operate. The operating time for zone 2 is usually of the order of 0.25
to 0.4 s, and that of zone 3 is in the range of 0.6 to 1.0 s. When there are power
transformers at adjacent substations the zone 2 timer should have a margin of
0.2 s over the tripping time of any associated transformer overcurrent
protection. In the case of zone 3, when the settings of relays at different
locations ,overlap, then the timer for the zone 3 of the furthest relay should be
increased by at least 0.2 s to avoid incorrect co-ordination. However, the
operating time for the zone 3 units should also be set at a value that will ensure
that system stability is maintained and therefore, if necessary, consideration
may have to be given to reducing the zone 3 operating time in such
circumstances.
Since the tripping produced by zone 1 is instantaneous, it should not
reach as far as the busbar at the end of the first line (Figure 4.2) so it is set to
19
cover only 80-85 per cent of the protected line. The remaining 20-15 percent
provides a factor of safety in order to mitigate against errors introduced by the
measurement transformers and line impedance calculations. The 20-15 per
cent to the end of the line is protected by zone 2, which operates in t2 seconds.
Zone 3 provides the back-up and operates with a delay of t3 seconds. Since the
reach and therefore the operating time of the distance relays are fixed, their co-
ordination is much easier than that for overcurrent relays.
Z3
EbJ
x
A Instantaneous B C
W
GIN nrL cre~
ACC No .................
Date ....................
CHAPTER 5
OVERCURRENT PROTECTION
5.1 Introduction
Very high current levels in electrical power systems are usually caused
by faults on the system. These currents can be used to determine the presence
of faults and operate protection devices, which can vary in design depending
on the complexity and accuracy required. Among the more common types of
protection are thermomagnetic switches, Moulded case circuit breakers
(MCCBs), fuses-and over current relays. The fist two types, which-have simple
operating arrangements and are principally used in the protection of low
voltage equipments. Fuses are also often used at low voltages, especially for
operating lines and distribution transformers.
Overcurrent relays, which are the most common form of protection used
to deal with excessive currents on power systems. They should not be installed
purely as protecting systems against overloads, which are associated with the
thermal capacity of machines or lines, since Overcurrent protection is primarily
intended to operate only under fault conditions. However, the relay settings that
are selected are often a compromise in order to cope with both overload and
overcurrent conditions.
21
Definite time
22
disconnects load at the point nearest to the fault. This type of protection has the
drawback of having little selectivity at high value of short circuit current. Another
disadvantage is the difficulty of distinguishing between the fault current at one
point or another when the impendence between these points is small in
comparison to the impedance back to the source, leading to the possibility of
poor discrimination.
23
I = fault current level in secondary amps,
Is = pickup current selected,
L = constant,
a and (3 determine the slope of the relay characteristics.
Table 5.1 ANSI/IEEE and (IEC constants for standard overcurrent relays
24
5.4.1 IDMT Characteristics for the current setting of IA and
for a TSM of 1.0
IDMT Characteristics
30
25
20
V
c
0
U
N
15
10
0 2 4 6 8 10 12 14 16 18 20
Operating current Expressed as a multiple of the setting
25
5.4.2 Very Inverse characteristics for pick up value of 'IA and
fora TSM of 1.0
14
12
10
a
0 1 2 3 4 5 6 7
Multiple of pick up current
26
5.4.3 Extremely Inverse characteristics for pick up value of 1A and
foraTSM of1.0
20
vcC 15
0
U
U)
1-10
0 1 2 3 4 5
Multiple of pick up current
27
CHAPTER 6
PSCAD SIMULATION MODEL AND RESULTS
6.1 Introduction
Simulation tests were carried for the test model of a power system as
shown in figure 6.1. The power system has 0.400kV transmission line with
single end feeding source. Transmission line and sources data are given in
appendix A.
WI
START
If
NO
Zcal<=Zset
YES
11,
END
29
6.4 Simulation Results for Impedance relay
Figure 6.4: Voltage, current waveforms at impedance relay location and trip
signal to the circuit breaker for ABC fault
Figure 6.3 shows AB, BC and CA elements are coming inside the zone for ABC
fault. Setting impedance is 80% of the transmission line of length 100km. ABC
fault is applied at 75km and correspondingly we can see voltages, currents and
trip signal in figure 6.4
30
100 50 0 54
..... ..... 100 150
--- ----- ---°'
Aperture 4 Wldth 0.6 a •
0.0005 " • 0.600: ` Posit ri, 0.000
ni "ii i i ri
VoRagb.CurrsrR and Trip; sl{ji
-
. . 040
0.30
0.20
Al
!'1!!!! H
~c 0.10
= 0.00
-0.20
-0.30
-0.40
O000
.1 .°.•-."~.••
—it ..........».,....,.w:...,_--•..- .. _
0.00eO _.........._..._.._._.._._.._ ..................._.._............ ...._ .._ _._ ..............._ ._.................................................................:..._..__............_.__.._................__................:....
.. ...............
0.0060 ......
O.0040 ......_..__....._...._.__. ._...._.....—..____.._ .............. ....._—. __._._.. - .... ..__..._._~.............._
__ -
a.0020 .... .......... .... .. ......... ...... ....... '.
.00ao '~
_ _.... _
.0040 [
._ -_ .___-• .._ ._- f ti - __ -... .._ ... _....
.0060 .... .............. j ~ .. .._..... .. ...
.anon
T^m
uSO° 0.250 0.275 0.300 0.325 0.350 -0.375 0.400 .. 0.425 0.450 - 0.475
Figure 6.6: Voltage, current waveforms at impedance relay location and trip
signal to the Circuit Breaker for AB fault
Figure 6.5 shows for AB fault AB element coming inside the zone, BC and CA
elements are outside the zone. Setting impedance is 80% of the transmission
line of length 100km. AB fault is applied at 75km and correspondingly we can
see voltages, currents and trip signal in figure 6.6
31
a relay AG, BG and CG trjectories
Y Coordinate
..................._..._..............................._.,..........._............._..._,.a `i,
Xe
--5
XI'
Z1Xclrcle y ,r
net
0.40
0.30
0.20
3c 0.10
0.00
• -0.10
-0.20
-0.30
-D.40
.. ....... .._....i1 .,.._.,
.....
_ .,..,:,
....0.0146
O.00BO
0.0060
0.0040
0.0020
0.0000
U:oo20.
-~ _fl 01140
B -0 0000
0 0000
- ,-Fu
eK S1 1
~
2000 .... _.. .,.......
7.75
I 5
,.25
too .
0.75
0 5
0.25
t(se1l 0.20 - 0.275 0.300 0.325 0.350 0.375 0.400 0.425 0.450 O 475
Figure 6.10: Voltage, current waveforms at impedance relay location and trip
signal to the circuit breaker for ABCG fault
Figure 6.9 shows for ABCG fault AG, BG and CG elements coming inside the
zone, setting impedance is 80% of the transmission line of length 100km.
ABCG fault is applied at 75km and correspondingly we can see voltages,
currents and trip signal in figure 6.10
33
so - .... .._.__.._._.........
-50
_100
...
Aperture ~ V 1dth 0.6 a> •
0.000s 0.600s . Position 0.000
j ly !i i
0.40
0.30
0.20
0.10.
0.00-
0.10
-020
- 030
-0.40
O.Q'1
0.00 . . ........
1TJ
Q.00
0-00
0.00
0.00oo , H.. -
-0.00
6 000
S -0.00
-o .Q0
nn .........._.... .....1 .. _._............_.. L._ .. ...... _... ... --._ ............. .. _ .... ............. _ .._._..._ _.__
Figure 6:8: Voltage, current waveforms at impedance relay location and trip
signal to the circuit breaker for ABG fault
Figure 6.7 shows for ABG fault AG and BG elements coming inside the zone,
CG element is outside the zone. Setting impedance is 80% of the transmission
line of length 100km. ABG fault is applied at 75km and correspondingly we can
see voltages, currents and trip signal in figure 6.8
32
0—x
. .. ........
-100
y
-150-100 -50 0 50 100 150
Aperture 4. Width 06 v
0.000s 0.600s Position 0.000
%1% 1 1
040
1 IE IEL1 E
0 )0
0.20
010
000
-010
-020
0:10
-040
0.0100 . . .. .. . . . . . . . . . . ................ ..... . . . . . . .
000
20
000.
11,20
d o onnn
/\
7K yflj3-
0 0000
-00100 ]—
........................
rrn
. — fteI,yTrIpSIr..I 1 r1) — npr. ..
200
1 .75
I C1
I 25
-- -
0.50
0.25-
) 000 •--•-- ..-- -...---- ___
tCoco 0250 0 275 0.300 0 25 0.350 0.375 0.400 0.425 0.460 0.47
Figure 6.12: Voltage, current waveforms at impedance relay location and trip
signal to the circuit breaker for AG fault
Figure 6.11 shows for AG fault AG element coming inside the zone, BG and CG
elements are outside the zone. Setting impedance is 80% of the transmission
line of length 100km. AG fault is applied at 75km and correspondingly we can
see voltages, currents and trip signal in figure 6.12.
34
CHAPTER 7
TEST RESULTS
7.1 Test results for impedance relay
150
is
an
-5
100L
-100 -50 0 50 100 150 200
35
V I =
Zincomplex =
1.Oe+003
5.2286 + 3.63671
1.6283 + 0.42721
0.7814 + 1.24881
1.8894 + 1.43021
1.6780 + 1.4303i
1.7708 + 1.26131
V-1 =
Zincomplex
5.6119 +49.42021
2.2370 +52.47141
2.9283 +46.36871
3.0642 +49.90731
4.3535 +49.49111
3.3887 +48.62511
.; . >>
ABC Fault occured on the system
36
Zincomplex
1.Oe+003
4.8460 + 4.56981
1.6876 + 0.38791
0.7656 + 1.23741
1.9101 + 1.44521
1.7110 + 1.4811i
1.7725 + 1.30361
V 2 =
Zincomplex =
1.Oe+002
0.4900 + 0.44231
0.4069 + 0.54181
4.4702 + 7.69671
0.0448 + 0.49551
1.0132 + 0.6512i
1.2033 + 0.4515i
m
10
37
150
1C
-5
-100 '-
-100
is U -
+
a0
60
4D
2D
+++++++++ ++4++++++4
-2
-4
-6 0
-8 0
-10 J
100 -80 -60 -40 -20
Figure 7.6: Trajectory Impedance of AG, BG and CG elements for ABCG Fault
39
File Edit Debug Desktop Window Help
1 - .................::...._........,......,....,...................,.....,.........,.......:.........,........_.............,............,,.:,,..:..,,,,.................,,...,_.........a.
...__..._..New ..to MA7L.1 ? Watch this Video, see Demos or read Getting Started. X
V I =
Zincomplex =
1.Oe+003
5.5346 + 4.26771
1.6538 + 0.33781
0.7351 + 1.23061
1.9206 + 1.36601
1.7345 + 1.45721
1.7629 + 1.27501
V I =
Zincomplex =
5.4245 +50.1051i
3.5554 +51.50121
1.1870 +47.22941
4.0797 +50.24701
3.5307 +48.64021
2.4158 +49.85811
40
A A
5
-5
-10
-100 -50 0 50 100 150
El
File Edit Debug Desktop Window Help
O New to MATLAB? Watch this Video. see Demos. or read Getting Started. X
V_ I =
Zincomplex =
1.Oe+002
4.7314 + 2.6068i
4.8735 + 1.83241
4.1838 + 2.18161
4.6096 + 2.16871
4.6307 + 2.24461
4.5553 + 2.22381
V I =
Zincornplex
1.Oe+002
0.3195 + 0.45781
0.3284 + 0.42611
4.8348 + 1.24291
• 0.0109 + 0.42231
0.7909 + 0.40251
0.9804 + Q.6419i
42
7.2 Test results for Overcurrent relay
Table 7.1 Results of IDMT Overcurrent relay for a current setting of 1A and
TSM of 1.0 for phase 'a'
Tripping time Tripping time
la (Amps) Error(sec)
Practical(sec) (standard)
43
Figure 7.10 Result of IDMT Overcurrent relay for a current setting of 1A and
TSM of 1.0 for phase `a'
Table 7.2 Results of IDMT Overcurrent relay for a current setting of IA and
TSM of 1.0 for phase 'c'
45
Figure 7.11: Results of IDMT Overcurrent relay for a current setting of 1A and
TSM of 1.0 for phase 'c'
46
Table 7.3 Results of Extremely Inverse Overcurrent relay for a pickup value of
IA and TSM of 1.0 for phase `a'
47
He Desktop window Help
Watch this Video, see Demos, or read Getting Started, X
s ib ic
1.4443
0.4263
0.4904
• current is ib ic
1.4407
0.4240
0.4930
k5 zv
current is ib ic
1.4479
0.4243
0.4887
current is ib ic
There is an over current in phase a
the elapsed time for tripping in seconds is:
27.4399
t~..
Figure 7.12 Result of Extremely Inverse Overcurrent relay for a pickup value of
IA and TSM of 1.0 for phase `a'
Table 7.4 Results of Very Inverse Overcurrent relay for a pickup value of 1A
and TSM of 1.0 for phase 'a'
50
CHAPTER 8
CONCLUSION AND FUTURE SCOPE
8.1 Conclusion
The Multifunctional numerical relay has been implemented. Results of
the relay operation at various settings and standard characteristics are
presented. The error in the overcurrent relay is due to the slow operation of 16
—bit NI USB DAQ card. The relays that are implemented are overcurrent relay
and distance relay.
For overcurrent relay characteristics implemented are Very inverse, Extremely
Inverse and inverse definite minimum time characteristics. And these
characteristics compared with that of IEEE standard characteristics.
For distance relay characteristics implemented is impedance. Impedance relay
has been tested for laboratory setup transmission line of 100km.
51
REFERENCES
[1] G.D. Rockefeller, "Fault protection with a digital computer", IEEE
transactions on power apparatus and systems, vol. 4, pp.438-464,
April 1969
[6] Bornard and J.C. Bastide "A Prototype of Multiprocessor Based Distance
Relay" IEEE transactions on power apparatus and systems, vol. 2, pp. 491-
498, February 1980.
52
[8] K. Balasubramanian and Mustafa Oral, "Microprocessor Based Multifunction
Relay Switching", IEEE Transactions on consumer Electronics, vol. 4, pp.
878-883, November 1992.
[11] Jyh Cherng Gu and Sun-Li Yu, 'Removal of DC Offset in Current and
Voltage Signals using a Novel Fourier Filter Algorithm' IEEE transactions on
power delivery, vol. 15, no. 1, January 2000
[13] Hatem A. Darwish and Magdy Fikri," Practical Considerations for Recursive
DFT Implementation in Numerical Relays", IEEE Transactions on power
delivery, vol. 22, pp. 42-49, January 2007.
[14] Ali Zain Saleem, Zohaib Akhtar Khan, Ali Imran, "Algorithms and Hardware
Design of Modern Numeric Overcurrent and Distance Relays" International
conference on Electrical Engineering ICEE, pp.1-5, March 2008
[15] A.A Abdlrahem and H.H Sherwali, "Modeling Of Numerical Distance Relays
Using Matlab", IEEE Symposium on Industrial Electronics and Applications
ISIEA, October 2009
53
[16] "IEEE standard Inverse Time characteristics equations for overcurrent
relays" IEEE transactions on power delivery, vol. 14, No.3, July 1999.
Prepared by working group G-7 of the relay standards committee of the
power systems relaying.
[17] Tan. J.0 Mclaren. P. G. Jayasinghe R.P. and Wilson, P. L, "Software model
for inverse time overcurrent relays incorporating IEC and IEEE standard
curves", Electrical and computer Engineering, 2002. IEEE CCECE 2002.
Canadian conference vol. 1, pp: 37- 41, 12-15 May 2002.
[18] IEEE Power Systems Relaying Committee "Draft Guide for Protective Relay
applications to Power System Buses: IEEE Std PC37.234-200, June 2009
54
APPENDIX A
SOURCE AND TRANSMISSION LINE DATA
55
APPENDIX B
NI DAQ 6212 SPECIFICATIONS
Analog Input:
Number of channels : 8 differential or 16 single ended
ADC resolution : 16 bits
Sampling rate : 400 kS/s single channel,
400 kS/s multichannel
'Input coupling : DC
Input range : 10, ±5, ±1, ±0.2 V
Maximum working voltage
For analog inputs (signal +
Common mode) :±10.4 V of Al GND
Input impedance
Device on
Al+ to Al GND : >10 G%2 in parallel with 100 pF
Al- to Al GND : >10 G' in parallel with 100 pF
Device off
Al+to AI GND : 1200Y
Al- to AI GND : 1200½
Input bias current : ±100 pA
Crosstalk (at 100 kHz)
Adjacent channels : -75 dB
Nonadjacent channels :90 dB
Input FIFO size : 4,095 samples
Scan list memory : 4,095 entries
Data transfers :NI signal streaming on USB
Analog Output:
Number of channels :2
DAC resolution : 16 bits
56
Maximum update rate
I channel : 250 kS/s
2 channel : 250 kS/s per channel
Timing accuracy : 50 ppm of sample rate
Timing resolution : 50 ns
Output range :±10V
Output coupling :DC
Output impedance :0.2V2
Output current drive :±2mA
Output FIFO size :8,191 samples shared
among channels used
Data transfers :Nl signal streaming on USB,
Calibration (Al and AO):
Recommended warm-up time 5 minutes
Calibration interval 1 year
Digital I/O/PFI
Static Characteristics:
Number of channels
Digital input/output
USB-6212mass terminal : 24
Ground reference : D GND
Direction control : Each terminal individually
Programmable as input or output
Pull-down resistor
USB-6212 : 50 k1/2 typical, 20 kV2 minimum
Bus Interface:
USB : Hi-Speed USB or full-speed USB
NI signal streaming : 4 high-speed data streams;
Can be used for analog input,
analog output, counter/timer 0,
Counter/timer 1
57
Power Requirements:
USB port : 4.5 to 5.25 V in configured state
Caution: Do not exceed 16 mA per DIO pin.
Electrical data:
Nominal current 50A rms
Measuring range 0 to ± 70A
Measuring resistance : Rm min. Rm max.
With ±15V at ±50A : 500 1000
at ±70A : 500 700
Nominal analog output current 50A
Turns ratio :1:1000
Overall accuracy at +25 deg. C ± 0.5% of nominal current
Supply voltage ±15V
Isolation between primary and secondary:
2 kV rms/5OHz/1 min.
EMTDC results are solved as instantaneous values in time, but they can
be converted into phasor magnitudes and angles via built-in transducer and
measurement functions (such as true-rms meters or FFT spectrum analyzers),
much the same way real system measurements are performed. In PSCAD V4,
a new component will be available to calculate the impedance vs. frequency
spectrum of any system, from any point of the system.
EMTDC users can easily write their own models, from very simple to
very advanced. They can write in Fortran, C and MATLAB. The PSCAD
Component Workshop also makes the task of designing the visual appearance
of models and the data entry forms easier. All features of the very powerful
MATLAB program can be utilized, including the numerical and graphical
visualization plot libraries.
61