Series C F-frame electronic trip unit

Frequently asked questions

Series C F-frame electronic trip unit (210+ and 310+)


molded case circuit breaker FAQs
This document covers commonly asked questions about
the Series C® F-frame circuit breaker with electronic trip
units. The FDE breaker incorporates the DigitripE 310+
and 210+ electronic trip units in the same housing as the
standard Series C F-frame breaker.

Q: What amperages are Q: What are the amperage


offered for the F-frame settings for each frame?
electronic breakers?
A: The 310+ trip unit has eight
A: The 310+ and 210+ trip settings per frame, and the
units are each available in three 210+ has seven settings per
frames, which differ slightly frame. The settings are labeled
between the two trip units. A–H and A–G, respectively, and
correspond to a table located on
Trip Adjustability the breaker’s label information.
Unit Frame range
310+ 80 A 15–80 A 310+ 80 A 160 A 225 A
160 A 60–160 A A= 15 A 60 A 100 A
225 A 100–225 A B= 20 A 70 A 110 A
210+ 100 A 40–100 A C= 30 A 80 A 125 A
150 A 70–150 A D= 40 A 90 A 150 A
225 A 100–225 A E= 50 A 100 A 160 A
F= 60 A 125 A 175 A
G= 70 A 150 A 200 A
Q: Do the Digitrip 310+ and H = In = 80 A 160 A 225 A
210+ trip units require a 210+ 100 A 150 A 225 A
separate rating plug?
A= 40 A 70 A 100 A
A: No, the Digitrip 310+ and B= 50 A 80 A 110 A
210+ trip units do not require
C= 60 A 90 A 125 A
a separate rating plug. The
breakers have selectable dial D= 70 A 100 A 150 A
settings to adjust amperage E= 80 A 110 A 175 A
rating. F= 90 A 125 A 200 A
G = In = 100 A 150 A 225 A
Note: 160 A is not a NEMAT
recognized rating.

Q: What short circuit current


ratings (kA rms) are available
at 240 V, 480 V, and 600 V?
A: Three versions of the breaker
are available (both types of trip
units) for different short circuit
ratings, as follows:

240 V 480 V 600 V


FDE 65 kAIC 35 kAIC 18 kAIC
HFDE 100 kAIC 65 kAIC 25 kAIC
FDCE 200 kAIC 100 kAIC 25 kAIC
Note: The HFDE 210+ 25 kAIC at
600 V rating and all FDCE 210+ are
expected to be released for sale in
Q1 2016.
Q: In what pole configuration Q: Is the ground fault Q: Are neutral CTs provided Q: Do the Digitrip 310+ and
are FDE breakers available? protection adjustable on with a ground fault breaker? 210+ offer any communication
310+ LSG and LSIG trip units? Are they required? capabilities?
A: FDE / HFDE / FDCE breakers
are currently available in three- A: Yes. The ground fault pickup A: Neutral CTs are not provided A: The 310+ and 210+ trip
pole only. For single-phase setting contains six settings and with breakers for FDE. CTs must units do not offer embedded
applications, connect two poles can be adjusted from 0.2 to be ordered separately and are communication capabilities.
in series as described in the 1.0x the frame rating (In, or available in 80, 160, and 225 A However, PM3 metering and
instruction leaflet. maximum rating of the frame) offerings. For applications in communications modules may
of the breaker. For example, switchboards where the FD be attached to FD electronic
Q: What are the third-party on an 80 A breaker, the ground 310+ family is offered, the or thermal-magnetic breakers
certifications for this breaker? fault pickup setting can be factory will include the sensors to meter and communicate
dialed down to 16 A or up to with the switchboard. current, voltage, and energy
A: NEMA, ULT 489, and 80 A, regardless of the selected data, as well as the status of the
CSAT 22.2 No. 5 ratings. Neutral CTs are only required for
amperage setting (Ir). breaker (via an auxiliary switch
four-wire systems with ground
connection). PM3s are available
Q: What protection options In addition, the time delay for fault applications; three-wire
with INCOME or ModbusT
are available on 310+ and 210+ ground fault protection can be systems do not require a
communication protocols for
trip units for FDE breakers? set to Instantaneous trip, or to neutral sensor.
FD, JG, KD, and LG breakers.
delays of 120 ms or 300 ms.
A: The F-frame electronic For FDE breakers, there are two
Also, a Digiview display (Catalog
breakers include protection types of neutral sensors available
Q: What type of ground fault No. DIGIVIEW or DIGIVIEWR06)
options including long delay, in each of the frame sizes—
protection profile/curve does may be used with 310+ trip
short delay, instantaneous, one for typical bus connections
the FDE 310+ include? units for local display of currents
and ground fault. and a smaller version to
or cause-of-trip information. A
A: The 310+ LSG and LSIG accommodate a neutral cable.
cause-of-trip module (Catalog
Catalog trip units are configured with These are pictured below and
No. TRIP-LED) is available to
Protection order a flat response ground fault may be ordered using the catalog
Type features code display cause of trip via LEDs.
delay with three time settings, numbers listed for each frame.
310+ LS Long / Short 33 However, these are not available
Instantaneous, 120 ms, and on 210+ trip units.
LSI Long / Short / 32 300 ms. The fault level pickup Bus version
Instantaneous contains seven settings, from • 80 A—CTF080 Q: Can the trip units and
LSG Long / Short / 35 0.2x to 1.0x. The ground fault
Ground Fault 160 A—CTF160 frame be ordered separately
protection cannot be changed •
for FDE?
LSIG Long / Short / 36 to an I2t function response. • 225 A—CTF225
Instantaneous / A: Unfortunately, the F-frame
Ground Fault electronic breaker is only
Q: What type of short delay
210+ LI Long / 21 profile/curve do the FDE 310+ Cable version available as an assembled unit.
Instantaneous and 210+ include? Most other 310+ electronic trip
LSI Long / Short / 22 • 80 A—CTFD080 units, with the exception of the
Instantaneous A: The 310+ LS and LSG trip NG trip unit, may be ordered
units include an I2t protection
• 160 A—CTFD160
separate from the frame.
profile with nine settings for • 225 A—CTFD225
pickup and no time adjustments.
The 310+ LSI and LSIG trip
units include a flat response Please note that other Series C
protection profile with nine breakers with 310+ trip units
settings for pickup and three (KD, LD, and MDL) include the
settings for time, Instantaneous, neutral sensor with ground fault
120 ms, and 300 ms. trip units, but for Series GT
breakers (JG, LG, NG, and RG),
The 210+ LSI trip units include like for FD breakers, the neutral
10 settings that combine sensor must be purchased
short delay pickup and short separately.
delay time. The pickup levels
range from 2x to 10x. The time
settings include a couple of I2t
settings, plus flat response at
Instantaneous, 150 ms, and
300 ms.

2 EATON Series C F-frame electronic trip unit Frequently asked questions


Q: Does the F-frame electronic Q: Can this breaker replace Q: Are these available as a Q: Do these breakers carry any
use the same accessories as the FD breaker in a panelboard 100% rated device? DC ratings?
the F-frame thermal-magnetic? or switchboard? If so, does
A: No. A: No. FDE electronic breakers
the panelboard need to be
A: Yes. As with the F-frame do not carry DC ratings. If DC
re-listed with UL?
thermal-magnetic breaker, Q: Can the Digiview ammeter/ ratings are required, the thermal-
internal accessories must be A: Yes. The F-frame electronic cause-of-trip displays be used magnetic F-frame carries ratings
factory installed to maintain breaker has the same footprint, with these breaker? for 250 Vdc. In addition, the
breaker seal and UL label. All dimensions, and connectors HFDDC (600 Vdc), FDPV (1000
accessories will be mounted in as the FD breaker. The filler A: The Digiview ammeter and Vdc for poles in series), FD-PVS
the left pole. The only exception plate is different and needs to cause-of-trip displays works (600 V per pole) breakers carry
would be a special auxiliary be replaced. Existing products with all 310+ trip units, including ratings for higher DC voltages.
switch that can be mounted on are not marked for use with the F-frame. However, they are
the right pole. the FDE, HFDE, and FDCE as not compatible with 210+ trip
Q: Is there a tamperproof
the labeling was created before units. In addition, they are not
Additionally, FDE 310+ breakers cover on these breakers?
this breaker became available. available in Eaton’s panelboard or
with LSIG or LSG trip units switchboard installations. A: Yes. All 310+ and 210+
Should there be an application
cannot be configured with a trip units are fitted with a
within existing product, check
combination Aux / Alarm contacts Q: Is there a plug-in test kit transparent cover that can be
with the Authority Having
on the left pole. If auxiliary and available? fitted with a wire seal. Eaton
Jurisdiction (AHJ) for a variance
alarm contacts are needed, they also has a wire seal available for
under NECT Article 90. A: Yes. The functional test kit
must use a left pole alarm and a sale (Catalog No. 5108A03H01).
right pole auxiliary. Combination (Catalog No. MTST230V) is
contacts are available for 310+ Q: Are series ratings available? compatible with Digitrip 310+
LS or LSI and for 210+ LI and A: Yes. At this time, series and 210+ trip units for molded
LSI breakers. ratings are only available on case circuit breakers, as well as
breaker-to-breaker use by OEMs. for MagnumT and Series NRXT
Q: Can these breakers be Series ratings for the FDE will air circuit breakers (Digitrip 520
applied in a panelboard or apply wherever the equivalent and 1150). A new test cable was
switchboard in Bid Manager? thermal-magnetic breaker is added for the 210+ trip units.
used (e.g., the HFDE will have
A: Yes. FDE 210+ and 310+ Q: Can electronic FD breakers
the same series ratings as
breakers can be configured into be reverse fed?
the equivalent ampacity HFD).
UL listed PRL1a, PRL2a, PRL3a,
The required testing for series A: Yes. FDE breakers are
PRL3E and PRL4 panelboards
ratings is complete. UL is suitable for reverse-feed
and PRLC switchboards including
updating their documentation applications.
IFSE (all configurations). For
with the additional frames.
the 210+, the 100 A and 225 A
frames have been incorporated
into Bid Manager, but not the
150 A frame because all the
amperage (Ir) settings from this
frame are included in the other
two frames.

EATON Series C F-frame electronic trip unit Frequently asked questions 3