PROYECTO No 026
DISCIPLINA: ESTRUCTURAS
VyP: MC-0026
Aprobado por:
Comentarios:
__________________________________________________________
Documento elaborado por VyP ICE MC PLUMA SOPORTE - CARGA ALZADA
1.00 ALCANCES
VIGA
HSS4'' X SCH40 COLUMNA
HSS4'' X SCH40
P
DIAGONAL
HSS4'' X SCH40
P: Carga
COLUMNA Puntual a
HSS4'' X SCH40 levantar
P= 700.00 Kg
COLUMNA
HSS6'' X SCH40
__________________________________________________________________________________
Documento elaborado por VyP ICE MC PLUMA SOPORTE - CARGA ALZADA
COMB 1 1.2D+1.6L
COMB 2 1.2D+1.0L+1.2DES
COMB 3 1.2D+1.0L+1.0DES+1.0QX
COMB 4 1.2D+1.0L+1.0DES+1.0QY
Donde:
D: CARGA MUERTA
L: CARGA VIVA
DES: CARGA PENDULAR DE DESBALANCEO
QX: CARGA SISMICA X
QY: CARGA SISMICA Y
AISC 360-10 STEEL SECTION CHECK (Summary for Combo and Station)
Units : Kgf, m, C
__________________________________________________________________________________
Documento elaborado por VyP ICE MC PLUMA SOPORTE - CARGA ALZADA
Lltb Kltb Cb
LTB 1.000 1.000 1.000
Pu phi*Pnc phi*Pnt
Force Capacity Capacity
Axial -991.540 89978.721 95730.677
Tu Tn phi*Tn
Moment Capacity Capacity
Torsion 0.000 4973.827 4476.445
SHEAR CHECK
Vu phi*Vn Stress Status
Force Capacity Ratio Check
Major Shear 0.000 28719.203 0.000 OK
Minor Shear 0.000 28719.203 0.000 OK
AISC 360-10 STEEL SECTION CHECK (Summary for Combo and Station)
Units : Kgf, m, C
__________________________________________________________________________________
Documento elaborado por VyP ICE MC PLUMA SOPORTE - CARGA ALZADA
D/C Limit=0.950 2nd Order: General 2nd Order Reduction: Tau-b Fixed
AlphaPr/Py=0.016 AlphaPr/Pe=0.004 Tau_b=1.000 EA factor=0.800 EI factor=0.800
Ignore Seismic Code? No Ignore Special EQ Load? No D/P Plug Welded? Yes
Lltb Kltb Cb
LTB 1.000 1.000 1.000
Pu phi*Pnc phi*Pnt
Force Capacity Capacity
Axial -948.790 48325.510 53274.425
Tu Tn phi*Tn
Moment Capacity Capacity
Torsion 0.000 1822.038 1639.834
SHEAR CHECK
Vu phi*Vn Stress Status
Force Capacity Ratio Check
Major Shear 0.000 15982.328 0.000 OK
Minor Shear 0.000 15982.328 0.000 OK
AISC 360-10 STEEL SECTION CHECK (Summary for Combo and Station)
Units : Kgf, m, C
__________________________________________________________________________________
Documento elaborado por VyP ICE MC PLUMA SOPORTE - CARGA ALZADA
Lltb Kltb Cb
LTB 1.000 1.000 2.260
Pu phi*Pnc phi*Pnt
Force Capacity Capacity
Axial 0.000 49352.039 53274.425
Tu Tn phi*Tn
Moment Capacity Capacity
Torsion -480.000 1822.038 1639.834
SHEAR CHECK
Vu phi*Vn Stress Status
Force Capacity Ratio Check
Major Shear 852.000 15982.328 0.053 OK
Minor Shear 0.000 15982.328 0.000 OK
__________________________________________________________________________________
Documento elaborado por VyP ICE MC PLUMA SOPORTE - CARGA ALZADA
VMajor VMajor
Left Right
Major (V2) 869.446 852.000
AISC 360-10 STEEL SECTION CHECK (Summary for Combo and Station)
Units : Kgf, m, C
Lltb Kltb Cb
LTB 1.000 1.000 1.736
Pu phi*Pnc phi*Pnt
Force Capacity Capacity
Axial -1959.005 45699.350 53274.425
Tu Tn phi*Tn
Moment Capacity Capacity
__________________________________________________________________________________
Documento elaborado por VyP ICE MC PLUMA SOPORTE - CARGA ALZADA
SHEAR CHECK
Vu phi*Vn Stress Status
Force Capacity Ratio Check
Major Shear 377.942 15982.328 0.024 OK
Minor Shear 122.354 15982.328 0.008 OK
__________________________________________________________________________________
Documento elaborado por VyP ICE MC PLUMA SOPORTE - CARGA ALZADA
5.00 CONCLUSIONES
El análisis fue obtenido con las cargas determinadas y desplazamientos para efectos de
carga, la cual se llega a la conclusión que para cargas de izaje, esta estructura soporta
una carga pendular estática de 0.6 Tn que es un 85% de su capacidad de falla.
También el comportamiento de torsión en el punto de la intersección, garantiza una torsión
de 0.625 Tn-m que es un 35% de su capacidad ratio de falla.
Las cargas dinámicas (sismo y pendular) quedan garantizadas para 600 Kg y 400 Kg-m
para la pendular y 50 Kg adicionales para el efecto sísmico.
__________________________________________________________________________________
Documento elaborado por VyP ICE MC PLUMA SOPORTE - CARGA ALZADA