ERIC-9001 PARAMETERS

Only change the blod writen parametres according to your travel curves. Others are
only for specific lift application default values.

A1-01=4 ; Set and change permit to all parameters.


A1-02=2 ; Control method
2 = Open loop flux vector ( Without encoder )
3 = Closed loop flux vector ( With encoder )

B1-01=1 ; Drive only works from input terminals


B1-02=1 ; Run signal from input terminals.
B1-03=0 ; Stoping method; Ramp to stop
B1-04=0 ; Reverse direction enabled

B2-01=0.5 ; DC brake start frequency


B2-02=80 ; DC brake power (%)
B2-03=0,1 ; DC brake time at start (seconds)
B2-04=0.5 ; DC brake time at stop (seconds)

H1-01=18 ; Short travel sense terminal.


H1-03=3 ; Speed reference terminal settings.
H1-04=4 ; Speed reference terminal settings.
H1-05=5 ; Speed reference terminal settings.

H2-01=37 ; Mechanical brake active while running.


H2-02=12 ; Short travel speed correction output.

L2-01=1 ; Sense power loses. But start again when line power is okey.
L3-04=0 ; Brake resistance is connected.
L5-01=3 ; Try 3 times to restart after fault before locking system.
L6-01=4 ; High torque sense enabled.
L6-02=%180 ; High torque detection level.
L6-03=2 ; High torque detection time.

E1-01=400 ; Input voltage.


E1-03=F ; Custom V/f adjustment.
E1-04=75 ; Minimum output frequency.
E1-05=400 ; Maximum voltage.
E1-06=50 ; Maximum voltage frequency. ; E1-xx parameters are used only
E1-07=3 ; middle frequency in open loop applications.
E1-08=40 ; middle frequency voltage
E1-09=0.5 ; minimum frequency
E1-10=20 ; minimum frequency voltage
C1-01=2.5 ; Acceleration time (seconds)
C1-02=2.5 ; Deceleration time
C1-09=1.5 ; Fast stop time at fault.

C2-01=1.5 ; Start S curve time


C2-02=0.5 ; Acceleration end S curve time
C2-03=0.5 ; Deceleration start S curve time
C2-04=1.5 ; Deceleration end S curve time

D1-01=0
D1-02=0
D1-03=7 ; Slow speed V0 (Hz)
D1-04=15 ; Inspection speed V1 (Hz)
D1-05=50 ; Hıgh speed V2 (Hz)
D1-06=0
D1-07=25 ; Short travel speed Vs (Hz)
D1-08=0
D1-09=0

E2-01=__ ; motor nominal current.

B4-01=0 ; Short travel sensing time


B4-02=0.5 ; Minimum acceleration time.

In vvvf systems for travel comfort, the acceleration of car is not too much. So
in some cases especially short travel distance lift may starts to decelerate before
reaching the full speed. In this condition lift may travel a long with a small speed
(V0). By setting minimum acceleration time; lift don’t stops to accelerate neither a
slow speed signal comes from control panel in this time. So it’s possible to travel short
distance with an optimum speed without an extra middle speed signalization from
control card. Adjust this parameter in the shortest way step by step. To big values
may cause a faulty long forced travels.