Вы находитесь на странице: 1из 21

PEGAGA DEVELOPMENT PROJECT

EQUIPMENT AND TAG NUMBERING PROCEDURE

MPMY-PM-PRC-0002

1.0 22-Nov-16 Re-Issued for Use TYC LVC JPD


0 06-Aug-15 Issued for Use HI JPD CH
Rev Prepared Reviewed Approved for
Date Purpose of Issue
No By By Release
Typed initials in the signature box indicate that the document has been signed (with Document Controller)
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

REVISON CHANGE HISTORY

All major changes to the document at this current revision are recorded below.
(Does not include correction of typos or formatting changes)

Revision: Date: Originator: Description of Change:

Re-issued for use. Update Electrical


1.0 22-Nov-16 Tong Yeah Chuen
Equipment Tag Number.

0 06-Aug-15 Haizullizuan Ibrahim Final. Issued for use.

Comments incorporated. Issued for


C 29-Jun-15 Haizullizuan Ibrahim
approval

B 17-Dec-13 CW Issued for internal review

Page 2 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

CONTENTS

1 INTRODUCTION ........................................................................................................................ 4
2 DEFINITIONS ............................................................................................................................. 4
3 APPLICABILITY AND SCOPE .................................................................................................... 4
4 RESPONSIBILITIES ................................................................................................................... 4
5 EQUIPMENT IDENTIFICATION.................................................................................................. 5
5.1 Equipment Numbering Format .............................................................................................. 5
5.2 Facility Identifier.................................................................................................................... 5
5.3 Primary Equipment Identifier................................................................................................. 6
5.4 Secondary Equipment Identifier ............................................................................................ 7
5.4.1 Tertiary Equipment Identifier .......................................................................................... 9
5.5 System Code ........................................................................................................................ 9
6 PIPING IDENTIFICATION......................................................................................................... 11
6.1 Line Number Format ........................................................................................................... 11
6.2 Product Identifier ................................................................................................................ 12
6.3 Pipe Supports Number Format ........................................................................................... 13
6.4 Piping Speciality Item Number Format ................................................................................ 13
6.5 Valve Identification ............................................................................................................. 14
7 INSTRUMENTATION IDENTIFICATION................................................................................... 15
7.1 General............................................................................................................................... 15
7.2 Instrument Tag Number Format .......................................................................................... 15
7.3 Function Identifier ............................................................................................................... 15
7.4 Loop Identifier ..................................................................................................................... 16
7.5 Instrument Loop Numbering ............................................................................................... 16
8 JUNCTION BOX AND MARSHALLING / SYSTEM CABINET NUMBERING ............................ 16
9 TELECOMMUNICATIONS DEVICE IDENTIFICATION............................................................. 18
9.1 Telecommunications Device Number ................................................................................. 18
9.2 Function Identifier ............................................................................................................... 18
9.3 Loop Identifier ..................................................................................................................... 18
10 FIRE AND GAS DEVICE IDENTIFICATION ............................................................................. 19
10.1 Fire & Gas Device Number ............................................................................................ 19
10.2 Function Identifier .......................................................................................................... 19
10.3 Loop Identifier................................................................................................................ 20
11 CABLE NUMBERING ............................................................................................................... 20
11.1 Instrument Cables ......................................................................................................... 20
11.2 Electrical Cables ............................................................................................................ 21

Page 3 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

1 INTRODUCTION

This procedure defines the equipment and tag numbering systems to be followed by MDC Oil
& Gas (SK320) Limited - Malaysia. The purpose of the procedure is to ensure that all
equipment and identifiable components are systematically numbered and to allow systematic
registration and traceability.

2 DEFINITIONS

COMPANY MDC Oil & Gas (SK320) Limitied, a Mubadala Petroleum Affiliate

Project A phased field development

Contractor The party selected to provide services to COMPANY

Sub-Contractor Any organisation appointed by a Contractor to perform an element


of work on a Project

Vendor/Manufacturer The party selected to supply equipment or materials in


accordance with the specification

May / should A preference or possible course of action

Shall / must A mandatory requirement

3 APPLICABILITY AND SCOPE

This numbering procedure is applicable to all equipment and identifiable components in


relation to a specific facility or Project.

This numbering procedure is to be imposed on all facilities in a logical manner to permit the
identification of all equipment items and tagged components.

4 RESPONSIBILITIES

The revision and reissue of this procedure is the responsibility of COMPANY. Any request to
expand any of the tables of identifiers shall be routed to COMPANY. New identifiers shall be
used only when approved by COMPANY.

The Contractor primarily responsible for the work on each facility shall maintain an equipment
and tag register and allocate equipment and tag numbers both internally and to sub-
contractors as required.

Page 4 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

5 EQUIPMENT IDENTIFICATION

5.1 Equipment Numbering Format

All equipment shall be allocated a number conforming to:

LLFA-PS(T)-MMNN(NN)-(C)

LLFA The facility identifier. See Section 5.2.

P The primary equipment identifier. See Section 5.3.

S The secondary equipment identifier. See Section 5.4.

T If required, the tertiary equipment identifier. See Section 5.4.1.

MM The system code. See Section 0.

NN Sequence Number. A two digit numeric identifier allocated in sequence


utilising the next available number.

(NN) If required, an additional two (2) digit numeric identifier allocated in


sequence utilising the next available number. Typically used when there
are more than 100 tagged equipment with similar facility, primary and
secondary identifiers; and system code. E.g. light fittings.

C If required, a single digit letter suffix, commencing with A and allocated


where more than one equipment item is used in the same service.

Note: For equipment complete with local control panel (LCP) or equipment complete with
remote control panel (UCP), LCP or UCP shall be having the same system code and
sequence number as per the respective equipment, with LCP or UCP shall be used as
primary and secondary equipment identifier.

E.g.: Export Gas Metering Skid number is PGCA-JZ-2710, and the respective UCP shall be
tagged as PGCA-UCP-2710.

E.g: Air Dryer package number is PGCA-VZ-6330, and the respective LCP shall be tagged as
PGCA-LCP-6330.

5.2 Facility Identifier

Documents developed specifically for a development or project shall be identified by a three


digit facility code followed by a single digit location within the facility code.

Allowable identifiers for the location shall comprising two (2) digits are:

LL Location
M5 M5 Field
PA Parisan
PG Pegaga
SN Sintok
SR Sirih

Page 5 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

The physical facility within the field shall be defined by a single (1) digit as follows:

F Facility
A Accommodation Platform
B Bridge
C Central Production Platform
D Drilling
F FPSO / FSO
G General
H Helideck
J Jacket / Substructure
K Tanker
P Pipeline
R Turret
S Subsea
U Umbilical, fibre optic cable
V Flare / Vent Platform
W Wellhead Platform

The sequence code, A, defines the sequence of installation, ‘A’ is the first, ‘B’ the second and
‘C’ the third etc. The same sequence code may not be repeated within the same location and
type of facility.

5.3 Primary Equipment Identifier

The primary equipment identifier below indicates the generic type of equipment:

P Generic Equipment Type


A Accommodation
B Drilling
C
D
E Electrical
F Furnace / Flare
G HVAC
H Exchanger
J
K Compressor
L Local Type (On Skid)
M Materials Handling
N
P Pumping
R Telecommunications
S Safety
T Tank
U Remote Type (Not on Skid)
V Vessel
W
X
Z

Page 6 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

5.4 Secondary Equipment Identifier

B E F G H K
Drilling Electrical Furnace / Flare HVAC Exchanger Compressor
A Xmas Tree Charger Air Handling Unit Air Cooled Axial Type
B BOP Battery Boiler Refrigeration Unit Blower
C Cutting Disposal Control Station Cooling Coil Printed Circuit Centrifugal Type
D Derrick Dist. Board Direct Fired Heater Damper Double Pipe
E Cementing Package Test Equipment Diffuser / Grille Electric Heater Expander
F Burner Filters Flare Stack Fan Fan
G Generator Sound Attenuator Gearbox
H Diverter Heater Heating Coil Hydraulic Motor
I Nav Aids Furnace/Incinerator Air Conditioners Air Motor/Starter
J Panel Resistor Gearbox
K Light Fitting Humidifier Coupling
L LV Switchgear Louvre Lubrication System
M Mud Pump Mixing Box Electric Motor
N HV Switchgear Gas/Diesel Engine
O Socket Outlet Seal System
P Pipe Handling Panel Panel Plate
R Rotary Table Rectifier / Inverter Reboiler Reciprocating Type
S Skid Jacks Cathodic Protection Filter Screw/Rotary Type
T Topdrive Transformer Shell & Tube Turbine Driver
U UPS
V Wireline Busducts Vent Stack
W Wellhead Welding Outlets Weather Louvre Waste Heat Exhaust
X Miscellaneous Miscellaneous Miscellaneous Miscellaneous Miscellaneous Miscellaneous
Y Hopper Switch Filter/Strainer
Z Package Package Package Package Package Package

Page 7 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

M P R S T V
Material Handling Pumping Telecoms Safety Tank Vessel
A Axial Flow Type Antenna Safety Sign Agitator/Mixer Adsorber/Absorber
B Barrel Type PABX/Telephone Life Buoy Bin
C Pedestal Crane Centrifugal Type CCTV System Cabinet Cylindrical Tank Column
D Diaphram Type Data Network Deluge/Sprinkler Skid Deck Drain Box Drum
E Elevator Canned Type Entertainment Extinguisher
F Progr. Cavity Type Fibre Optic Fireman’s Equipment Filter/Coalescer
G Gantry Crane Gearbox Emergency Phone Hose Reel Cyclone/Centrifuge
H Hoist Hydraulic Motor Hotline Phone Hydrant Dryer
I Air Motor/Starter Intercomm System
J Gear/Lobe Type Life Jacket Eductor/Ejector
K Workshop Machine Coupling Radar System Helicopter Rescue Container Scrubber
L Lifting Equipment Lubrication System Aviation System Lifeboat
M Electric Motor Multiplex Equipment Monitor Molecular Seive
N Gas/Diesel Engine Navigation System Extinguishing Skid Caisson
Socket Outlet
O Seal System (DATA/Telephone/TV) Breathing Apparatus
P Pipeline Pig Plunger/Piston Type PAGA System Foam Skid Slug Catcher
R Runway Beam Reciprocating Type SOLAS Radio Life Raft Rectangular Tank Reactor
S Screw/Rotary Type Satellite Comms Survival Suit Sump Tank Separator
T Trolley Turbine Driver Telemetry Eyebath Tote Tank Pig Trap
U Submerged Type UHF/VHF Radio Safety Shower
V Vane Type EnvironmentalSystem Scramble Net Tundish
W Winch Exhaust Speaker Escape Chute
Miscellaneous /
X Miscellaneous Miscellaneous Flashing Beacon Miscellaneous Miscellaneous Miscellaneous
Y Filter/Strainer Computer Terminal Medical/First Aid Kit
Z Package Package Package Package Package Package

Page 8 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

5.4.1 Tertiary Equipment Identifier

T Equipment Type
A
B
C
D
E
F
G
H
J
K
L
M Motor
N
P
R
S
T
U
V
W
X
Z

5.5 System Code

The system code defines the functional area relating to the content of the particular document.
A two (2) digit numerical identifier is used as detailed below:

MM System Code
10 Drilling
11 Drilling process
12 Drilling well control
13 Riser and well topside
14 Drilling control and monitoring
15 Drilling drain
18 Well and riser subsea
19 Subsea installation
20 Separation and stabilisation
21 Crude handling and metering
23 Gas compression and reinjection
24 Gas treatment
25 Gas conditioning
27 Gas export and metering
28 Gas sweetening
29 Water Injection

Page 9 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

MM System Code
30 Oil export line
31 Condensate export line
32 Gas export line
33 Oil storage
34 Injection water pipeline
35 Chemical pipeline
36 Wellstream pipeline
37 Gas injection pipeline
38 Glycol / methanol regeneration
39 Loading
40 Cooling medium
41 Heating medium
42 Chemical injection
43 Flare
44 Oily water
45 Fuel gas
46 Methanol injection
47 Chlorination
50 Sea water
52 Ballast water
53 Fresh water
55 Steam
56 Open drain
57 Closed drain
58 Thruster and propulsion
61 Jet fuel
62 Diesel oil
63 Compressed air
64 Inert gas
65 Hydraulic power
66 Sewage treatment
69 Lubrication oil
70 Fire and gas detection
71 Fire water
72 Fire fighting
73 Material handling
75 Passive fire protection
76 Emergency preparedness
77 Environmental protection
79 Emergency shutdown and blowdown
80
81 HV power (> 1.0 kV)
82 LV power (≤ 1.0 kV)
83 Emergency power (> 1.0 kV)
84 Emergency power (≤ 1.0 kV)
85 Battery and no-break
86 Telecommunications
87 Control

Page 10 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

MM System Code
88 Earthing and lighting
90 Topside structure
91 Sub structure
92 Temporary
93 Architectural, including workshop and storage
94 Mooring and positioning
95 Onshore
96 Subsea structure and template
97 HVAC
98 Corrosion protection
99 Area completion

6 PIPING IDENTIFICATION

6.1 Line Number Format

Each pipe in the project shall be assigned a unique line number in the following format.

CC”-PP-MMNNN-FFFF-(G)(E)

CC Nominal pipe size

PP Product identifier. See Section 6.2.

MM The system code. See Section 5.5.

NNN Sequence number. A three digit numeric identifier.

FFFF The piping material class.

G Insulation class (as required). See table below

E Electrical heat tracing (as required).

G Insulation Class
A Acoustic protection
C Anti-condensation
F Frost proofing
G Gas barrier
H Heat conservation
P Personnel protection
R Fire proofing
W Weight coating
Z Cold conservation

For example 6"-PL-24008-1C11-HE is a six inch line in process liquid service from a gas
treatment system, and is the eighth line in sequence (within system 24), in 1C11 piping
material class with insulation for heat conservation, and also with electrical trace heating.

Page 11 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

The line number shall appear on P&IDs, general arrangement drawings, isometric drawings
and composite drawings.

Line numbers shall change at equipment connections, piping material class changes, and at
branch line (except short by-pass line).

Line number shall not change at valves, at tees (for the main stream), at floor or wall
penetration, or with changes of insulation class.

For details of the piping classes, refer to the Piping Material Class Specification, document
MPMY-PI-SPC-0002.

When the piping is insulated, a single letter shall be used to denote this and the detailed
information completed on the line list (Refer Appendix 5).

If electrical heat tracing is used, a second letter E shall be used to indicate this

6.2 Product Identifier

The product identifier relates to the product within the piping as listed in the table below:-

PP Product
AI Instrument Air
AU Utility Air
CI Chemical Injection
DC Closed Drain
DH Hazardous Open Drain
DO Non-Hazardous Open Drain
EX Exhaust
FF AFFF
FG Fuel Gas
FJ Aviation Fuel
FK Kill Fluid
FO Diesel Fuel
FP Dry Powder
GI Inert Gas
HO Hydraulic Oil
HM Heating Medium (Hot Oil)
LO Lubricating Oil
ME Methanol
MH High Pressure Mud
ML Low Pressure Mud
MO Mud Oil
PG Process Gas
PL Process Liquid
PT Well Fluids
RF Freon Refrigerant
RP Propane Refrigerant
SG Seal Gas
SO Seal Oil

Page 12 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

PP Product
VA Atmospheric Vent
VH High Pressure Vent/Flare
VL Low Pressure Vent/Flare
WB Cement Water
WC Cooling Water
WD Drinking (Potable) Water
WF Firewater
WH Hot Water
WI Injection Water
WO Sewage
WP Produced Water
WR Fresh Water
WS Seawater
WU Utility Water
WW Waste Water

6.3 Pipe Supports Number Format

Pipe supports shall be assigned a unique number as outlined below:-

(S)PS-NNNN

SPS Special pipe support

PS Standard pipe support

NNNN A number allocated by deck location to be determined by particular project.


For example:-

Above Top Deck SPS-1000 to 1499


Below Top Deck SPS-1500 to 1999
Above Mezzanine Deck SPS-2000 to 2499
Below Mezzanine Deck SPS-2500 to 2999
Above Production Deck SPS-3000 to 3499
Below Production Deck SPS-3500 to 3999
Above Cellar Deck SPS-4000 to 4499
Below Cellar Deck including Boat Landing SPS-4500 to 5499
Flare / Vent Boom SPS-5500 to 5999

6.4 Piping Speciality Item Number Format

Each pipe speciality item type in the project shall be assigned a unique number which
contains the following attributes:

LLFA - SP – NNN(A)

LLFA The facility identifier. See Section 5.2.

NNN A three digit numeric identifier allocated in sequence utilising the next
available number.

Page 13 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

C If required, a single digit letter suffix, commencing with A and allocated in


sequence where more than one equipment item is used in the same
service.

6.5 Valve Identification

Each valve type in the project shall be assigned a valve designation. The valve designation
shall contain the following attributes:

CC”-BB-DD-NNN-(FB)

CC Nominal valve size

BB Valve type identifier. See table below

DD Valve pressure class. See table below

NNN Sequence number. A three digit numeric identifier.

FB Full bore port (as required).

The valve type identifier shall be as detailed in the table below:-

BB Valve Type
VB Ball Valve
VC Check Valve
VF Butterfly Valve
VG Gate Valve
VK Choke Valve
VL Globe Valve
VM Mono Flange Valve
VN Needle Valve
VP Plug Valve
VR Rising stem Ball Valve

The valve pressure class shall be identified as detailed in the table below:-

DD Pressure Class
1 ASME 150#
3 ASME 300#
6 ASME 600#
8 ASME 800#
9 ASME 900#
15 ASME 1500#
25 ASME 2500#
5K API 5,000#
10K API 10,000#

Page 14 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

For example 12" – VB1516 – FB is a 12” Ball Valve, 1500# pressure class with valve
identification number 16 and full bore port.

7 INSTRUMENTATION IDENTIFICATION

7.1 General

Instruments and instrument system shall be numbered in accordance with the ISA Standard
S5.1.

Note: The instrument function identification indicated in Table 1 – Identification Letters shall
be used. Full S5.1, Function Identification, shall be used for index / schedule purposes.
However, for P&ID purpose, a shortened form of tagging shall be adopted to limit congestion
and improve readability. Format of the shortened tags shall be explained as part of the P&ID
legend sheets.

7.2 Instrument Tag Number Format

Each instrument in the project shall be assigned a unique instrument tag number. The
instrument tag number shall contain the following attributes:

LLFA - AAAAAA – MMNNN - (C)

LLFA The facility identifier. See Section 5.2.

AAAAAA Function identifier. See Section 7.3.

MM The system code. See Section 5.5.

NN Sequence Number. A two digit numeric identifier allocated in sequence


utilising the next available number.

(C) A single digit letter suffix, commencing with A and allocated in sequence
where more than one instrument is used in the same service.

7.3 Function Identifier

The function identifier for an instrument shall consist of up to 6 letters as listed in the ISA
Standard S5.1 and shall include a first letter covering the measured or initiating variable, and
one or more succeeding letters covering the functions of the individual instrument.

The function identifier shall be selected according to the function and not the type of
instrument. For example, level transmitter shall be designated LT and not under the type
which may be PDT (pressure differential transmitter).

This distinction may have to be made again when selecting a function identifier which must be
according to the measured or initiating variable and not according to the manipulated variable.
For example, a control valve varying flow on the command of a level controller is an LV not an
FV.

Page 15 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

The succeeding letters of the function identifier designate one or more readout or passive
functions or output functions.

The function identifier may require the addition of a modifying letter; this may be added to the
first letter or succeeding letters as required.

The number of function identifier letters should be kept to a minimum and shall not exceed six
for one instrument.

7.4 Loop Identifier

The loop identifier shall be the sequential number assigned to the loop of which the
instrument is a part.

Loop numbers shall be unique and shall follow the same format as the instrument numbers.

If a given loop has more than one instrument with the same function identifier, then a suffix
shall be appended to the loop identifier for the instrument, e.g. PV-1506A and PV-1506B.

7.5 Instrument Loop Numbering

LLFA - X(D) - MMNN(C)

LLFA The facility identifier. See Section 5.2.

X(D) Process Variable as detailed in the table below with the suffix D added for
differential measuring instruments.

MMNN(C) The system number and loop identifier from the instrument tag number
See Section 7.2.

X Process Variable
F Flow
L Level
P Pressure
T Temperature
X Unclassified
Z Position

For example:
1. Loop number for instrument tag LIT-1001A will be L-1001A
2. Loop number for instrument tag PDIT-5001 will be PD-5001

8 JUNCTION BOX AND MARSHALLING / SYSTEM CABINET NUMBERING

Field junction box and marshalling and system cabinets will be numbered as outlined below:

LLFA - BB - XXX - ZYY

LLFA The facility identifier. See Section 5.2.

BB Type identifier as detailed in the table below

Page 16 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

BB Process Variable
HC Hardwired Console
ES Engineering Station
HM Console (Operator Workstation/HMI)
JB Field Junction Box
LD Large Screen Display
MC Marshalling Cabinet
NC Network Component (Switch, Router, Firewall, Gateway etc)
PR Printer
RB Remote I/O Box
SC System Cabinet
SV Server
WS Workstation

XXX System identifier as detailed in the table below

XXX System Identifier


AMS Asset Management System
DHG Downhole Gauge System
ECV Electrical Control Voltage
EHT Electrical Heat Tracing
ELV Electrical Low Voltage (≤ 1.0kV AC)
ELT Electrical Lighting
ENV Electrical High Voltage (above 1000V AC)
FAP Fire Alarm Panel (Addressable)
FGS Fire & Gas System
PCS Process Control System
PDP Power Distribution Cabinet
PLD Pipeline Leak Detection System
RB(C) EPABX Telephone System ((C) = A, B or C)
RD(C) Data System ((C) = A, B or C)
RE(C) Entertainment System ((C) = A, B or C)
RF(C) Fibre Optic System ((C) = A, B or C)
RI(C) Intercom System ((C) = A, B or C)
RK(C) Radar System ((C) = A, B or C)
RL(C) Aviation System ((C) = A, B or C)
RN(C) Navigation System ((C) = A, B or C)
RP(C) PAGA System ((C) = A, B or C)
RS(C) Satellite Communication ((C) = A, B or C)
RT(C) Telemetry System ((C) = A, B or C)
RU(C) UHF / VHF System ((C) = A, B or C)
RV(C) Environmental System ((C) = A, B or C)
SIS Safety Instrumented System
SVR Server

Z Deck level or module location identifier to be determined on a project by


project basis.

Page 17 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

YY Sequence Number. A two digit numeric identifier allocated in sequence


utilising the next available number.

For example:
1. A junction box for the PCS system, located on production deck of Pegaga wellhead
platform A will be numbered PGWA-JB-PCS-314.
2. A system cabinet for SIS system on Sintok accommodation platform A will be
numbered SNAA-SC-SIS-207.
3. A marshalling cabinet for the PAGA B system located on M5 wellhead platform A will
be numbered M5WA-MC-RPB-202.

9 TELECOMMUNICATIONS DEVICE IDENTIFICATION

9.1 Telecommunications Device Number

Each telecommunications device in the project shall be assigned a unique


telecommunications device number. The telecommunications device number shall contain the
following attributes:

LLFA - ZXY - MMNNN-(C)

LLFA The facility identifier. See Section 5.2.

ZXY Function identifier

MMNNN Loop identifier

(C) A single digit letter suffix, commencing with A and allocated in sequence
where more than one instrument is used in the same service.

9.2 Function Identifier

Each device shall be identified by three letters for functional classification (Refer Appendix 8).

The first digit will be ‘R’ the telecommunications primary equipment identifier, the second digit
will identify the equipment type as detailed within Section 5.4, whilst the third digit indicates
the system as outlines below:

• 'A' for PA or other dual system - 'A' routing


• 'B' for PA or other dual system - 'B' routing
• 'C' for other systems - common

9.3 Loop Identifier

The loop identifier shall comprise the system code (86), as detailed within Section 5.5,
followed by a two digit numeric identifier allocated in sequence utilising the next available
number.

The loop identifier shall be unique and if a given loop has more than one device with the
same function identifier, then a suffix shall be appended to the loop identifier for each device,
e.g. RWA-8606A and RW-8606B.

Page 18 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

a. PAGA Loudspeaker: PGCA-RWA-8671A (system A) & PGCA-RWB-8671B (system B)


b. PAGA Beacon: PGCA-RXA-8671A (system A) & PGCA-RXB-8671B (system B)
c. DATA Socket Tagging: PGCA-ROD-8600A
d. Telephone Socket Tagging: PGAA-ROT-8603
e. Television Socket Tagging: PGAA-ROE-8640

10 FIRE AND GAS DEVICE IDENTIFICATION

10.1 Fire & Gas Device Number

Each fire and gas device in the project shall be assigned a unique fire and gas device number
containing the following attributes:

LLFA - AAA – BBNNN(C)

LLFA The facility identifier. See Section 5.2.

AAA Function identifier

BBNNN Loop identifier

(C) An optional single digit letter suffix, commencing with A and allocated in
sequence where more than one instrument is used in the same service.

10.2 Function Identifier

Each device shall be identified by a three letters functional classification as detailed in the
table below

AAA Function
APS Abandon Platform Station
DMR Deluge Manual Release
EMR Extinguishant Manual Release
ESL Extinguishant Status Light
FAV Visual Fire Alarm
FDR Infra-Red Flame Detector
FDV Ultra-Violet Flame Detector
FLR Flashing Light (Red) - Fire
FLY Flashing Light (Yellow) – Gas
FLB Flashing Light (Blue) – Abandon Platform
GDC Combustible Gas Detector
GDH Hydrogen Sulphide Gas Detector
GDX Line of Sight Type Gas Detector (Transmitter Part)
GDR Line of Sight Type Gas Detector (Receiver Part)
GDP Point Type Gas Detector
GDT Toxic Gas Detector
GDU Ultrasonic Gas Detector
HDR Heat Detector (Rate of Rise)
HDF Heat Detector (Fixed Temperature Type)

Page 19 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

AAA Function
MAC Manual Alarm Call Point
SDI Smoke Detector (Ionisation)
SDP Smoke Detector (Optical)
SDH Smoke Detector (High Sensitive Point Type)
SDA Smoke Detector (High Sensitive Aspirating Type)

10.3 Loop Identifier

The loop identifier shall comprise the system code (70) as detailed within Section 5.5,
followed by a three (3) digit numeric identifier allocated in sequence utilising the next available
number.

The loop identifier shall be unique and if a given loop has more than one device with the
same function identifier, then a suffix shall be appended to the loop identifier for each device.

11 CABLE NUMBERING

11.1 Instrument Cables

Field instrument cable to field junction box shall be numbered:

T-AAAAAA-MMNN - (C)

Where:-
T = Process variable
AAAAAA–MMNN-(C) = Instrument Tag Number

T Process Variable
P Process Control System
S Safety Instrumented System
F Fire & Gas System
R Telecommunications System

For example:
1. Field instrument cable from PT-1001A to the instrument junction box cable number
will be tagged I-PT-1001A
2. Power cable from FT-1001A to power distribution panel, power cable number will be
tagged P-FT-1001A.

Multi-core / pair cable from field junction box to marshalling cabinet shall be numbered:

T-JB-XXXZYY/MC-XXZYY/NN

Where:-
T = as detailed above
JB-XXXZYY = Junction Box Number
MC-XXXZYY = Marshalling Cabinet Number
NN = Cable Serial Number (01, 02, 03..)

Page 20 of 21
Document No.:
MDC Oil & Gas (SK 320) Limited
MPMY-PM-PRC-0002
Equipment And Tag Numbering Procedure Revision: 1.0

For example:
1. Multi core cable from junction box number JBA-SIS-301 to marshalling cabinet MC-
SIS-01 will be tagged I-JB-SIS-301/MC-SIS-01/01

11.2 Electrical Cables

Electrical cables shall be numbered as outlined below:

AV - PS(T)MMNN(NN)(C) - KK

or

AV - BBXXXZYY - KK

Where:-
A = P - Power cable, or combined power & control cable
C - Control cable
E - Earthing Cable
H - Heat tracing cable

V = H - High voltage (above 1,000V)


L - Low voltage (1,000V and below)
D - DC voltage

PS(T)MMNN(NN)(C) = Tag of equipment (Section 5.1) connected to Switchgear. In


general cable tag is formed using “Downstream Equipment Tag”
or “Equipment Receiving Power” under normal operating
conditions. With exception of cables to/from Generators which
will carry the respective Generator tag.

BBXXXZYY = Junction box or cabinet identification (Section 8)

KK = Sequence number

For examples:

PH-EG8110A-01 Power cable from Generator PGCA-EG-8110A to HV Switchgear


PGCA-EN-8101.

CL-EG8110A-01 Control cable for Generator PGCA-EG-8110A package.

PL-EG8401-01 Power cable from Generator PGCA-EG-8401 to LV Switchgear


PGCA-EL-8401.

PH-PM4020A-01 Power cable from HV Switchgear PGCA-EN-8101 to Cooling


Medium Circulation Pump A motor PGCA-PM-4020A.

CL-EC4020A-01 Control cable from HV Switchgear PGCA-EN-8101 to Cooling


Medium Circulation Pump A RCU PGCA-EC-4020A.

Page 21 of 21