Академический Документы
Профессиональный Документы
Культура Документы
22 Sway stability
22.1 Introduction
The frame shown in Figure 22.1 consists of steel beams and columns arranged on a
7 m × 7 m grid. The frame has been designed on the basis of “Simple Design”
according to BS 5950-1:2000[1] clause 2.1.2.2. Resistance to sway is provided by two
3.5 m braced bays, one on each 49 m side, as shown in Figure 22.2. In practice,
bracing would also be required parallel to the 28 m side, but this is not considered in
this example. Once constructed, the frame will be clad to form an office block, but
the stiffening effect of the cladding has not been taken into account in the analysis of
the frame. Determine whether the frame is “non-sway” or “sway sensitive” according
to BS 5950-1:2000[1] and, if necessary, calculate the amplification factor kamp.
3m
3m
12.5 m
3m
m
3 .5
28 m
m 49
3.5 m
3.5 m
Floor:
Dead load wdf = 3.5 kN/m2
Imposed load wif = 6.0 kN/m2
161
Example 22 Sway stability Sheet 2 of 6 Rev
The greatest notional horizontal forces occur in load combination 1 and this case
should generally be used when assessing sway stability. However, advantage may be
taken of the lower notional horizontal forces in load combinations 2 and 3, if desired.
All three combinations are considered below.
The result of an elastic analysis on one braced bay (bare frame only) under the action
of the notional horizontal forces is shown in Figure 22.3.
162
Example 22 Sway stability Sheet 3 of 6 Rev
Deflections
NHF Total Storey
∆ δ
22.3 kN
Roof 10.7 mm
3m 2 mm
49.7 kN
3rd floor 8.7 mm
3m 2.5 mm
203 UC 46 49.7 kN
2nd floor 6.2 mm
203 UC 60
3m 2.8 mm
49.7 kN
1st floor 3.4 mm
3.5 m 3.4 mm
Ground
3.5 m
For multi-storey frames, an approximate value of the elastic critical buckling factor λcr
is obtained from:
h 2.4.2.6
λ cr =
200 δ
where δ is the inter-storey lateral drift (relative deflection between two adjacent
storeys) and h is the storey height.
3500
Ground – 1st floor: λcr = = 5.15 2.4.2.6
200 × 3.4
3000
1st floor – 2nd floor: λcr = = 5.36
200 × 2.8
Therefore, λcr = 5.15.
Note: The critical value of λcr usually occurs between the ground and first floors, due
to the fact that there is no deflection at ground level (high lateral drift between
ground and 1st floor).
Since λcr < 10, the frame is classed as “sway sensitive” for load combination 1. 2.4.2.6
163
Example 22 Sway stability Sheet 4 of 6 Rev
For clad frames in which the stiffening effect of the cladding has been ignored, the
amplifier kamp is given by:
λ cr
k amp = but kamp ≥ 1.0 2.4.2.7(1)
1.15 λ cr − 1.5
5.15
k amp = = 1.16
(1.15 × 5.15 ) − 1.5
Therefore, the forces in the bracing system must be increased by 16% for load
combination 1.
The result of an elastic analysis on one braced bay (bare frame only) under the action
of the notional horizontal forces is shown in Figure 22.4.
Deflections
NHF Total Storey
∆ δ
12 kN
Roof 3.4 mm
3m 0.7 mm
12 kN
3rd floor 2.7 mm
3m 0.9 mm
203 UC 46 12 kN
2nd floor 1.8 mm
203 UC 60
3m 0.8 mm
12 kN
1st floor 1.0 mm
3.5 m 1.0 mm
Ground
3.5 m
3500
Ground – 1st floor: λcr = = 17.5
200 × 1.0
3000
2nd floor – 3rd floor: λcr = = 16.7
200 × 0.9
Therefore, λcr = 16.7
164
Example 22 Sway stability Sheet 5 of 6 Rev
Since λcr > 10, the frame is classed as “non-sway” and there is no need to 2.4.2.6
amplify the forces in the bracing system for load combination 2.
Note: A frame with λcr > 10 is only classed as “non-sway” if it is a clad frame that
has been analysed as a bare frame in determining λcr. Bare frames or clad
frames where the stiffness of the cladding is allowed for in determining λcr are
always classified as “sway sensitive”, irrespective of the value of λcr.
The result of an elastic analysis on one braced bay (bare frame only) under the action
of the notional horizontal forces is shown in Figure 22.5.
Deflections
NHF Total Storey
∆ δ
18.5 kN
Roof 8.6 mm
3m 1.6 mm
39.1 kN
3rd floor 7.0 mm
3m 2.1 mm
203 UC 46 39.1 kN
2nd floor 4.9 mm
203 UC 60
3m 2.2 mm
39.1 kN
1st floor 2.7 mm
3.5 m 2.7 mm
Ground
3.5 m
3500
Ground – 1st floor: λcr = = 17.5 2.4.2.6
200 × 2.7
3000
1st floor – 2nd floor: λcr = = 16.7
200 × 0.9
Therefore, λcr = 6.48
Since λcr > 10, the frame is classed as “sway sensitive” for load combination 3.
165
Example 22 Sway stability Sheet 6 of 6 Rev
For clad frames in which the stiffening effect of the cladding has been ignored, the
amplifier kamp is given by:
λ cr 6.48
k amp = = = 1.09 2.4.2.7 (1)
1.15 λ cr − 1.5 (1.15 × 6.48 ) − 1.5
Therefore, the forces in the bracing system must be increased by 9% for load
combination 3.
166