Вы находитесь на странице: 1из 12

PROJECT: WATER SUPPLY DISTRIBUTION NETWORK FOR PALAKOLLU TOWN

TITLE AERATOR AND FLASH MIXER - 11MLD WTP

Walkway Slab in Aerator

6.75 kN/m

0.75

Span of Slab l = 0.75 m

Size of Slab : Width of the Slab = 1000 mm

Depth of the Slab = 150 mm

Dead load due to self weight of beam = 25x1x0.15= 3.75 kN/m

Live load due to Walkway Slab= 3= 3 kN/m

Total load acting on the beam = 6.75 kN/m

Clear Cover to Main Reinforcement = 25 mm

Characteristic Strength of Concrete, fck = 20 N/mm2

Characteristic Strength of Steel, fy = 500 N/mm2

Diameter of top reinforcement = 8 mm

Diameter of bottom reinforcement = 8 mm

Effective depth for top reinforcement = 150-25-8-4= 113 mm

Effective depth for bottom reinforcement = 150-25-8-4= 113 mm

Max Bending moment at mid span = 1.9 kNm

Max Bending moment at supports = 0 kNm

Max Shear force = 5.06 kN

Reinforcement at bottom face of beam


Mu (Factored moment) = 1.5x1.9= 2.85 kNm

Mu /bd2 = 2.85x10^6/1000/113^2= 0.223 N/mm2

Percentage Steel Required, pt = 0.05 %

Area of steel Required = 0.05 x 1000 x 113 / 100 = 56.5 mm2


PROJECT: WATER SUPPLY DISTRIBUTION NETWORK FOR PALAKOLLU TOWN

TITLE AERATOR AND FLASH MIXER - 11MLD WTP

Astmin = 0.0012 x 1000 x 113 = 136.0 mm2

Spacing required = 150.0 mm

Ast Provided = (8 @150mm C/C) = 337.1 mm2

Shear Reinforcement

Vu = 1.5x5.06= 7.59 kN

tve = 7.59x1000/(1000x113) = 0.067 N/mm2

pt = = 0.298 %

Table 19, tc = = #VALUE! N/mm2

IS:456 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!

Check for Deflection

Span Length = 750 mm

Area of steel Required = 56.5 mm2

Ast Provided = 337.1 mm2

Percentage Steel provided, pt 0.299

fs = 0.58 x fy x Astreq / Astprov= 48.6105617089

fig 4, IS:456 Modification Factor = 2

span / effective depth = 7

< 7x 2 = 14
PROJECT: WATER SUPPLY DISTRIBUTION NETWORK FOR PALAKOLLU TOWN

TITLE AERATOR AND FLASH MIXER - 11MLD WTP

Cover Slab over Stilling Chamber

6.75 kN/m

1.2

Span of Slab l = 1.2 m

Size of Slab : Width of the Slab = 1000 mm

Depth of the Slab = 150 mm

Dead load due to self weight of beam = 25x1x0.15= 3.75 kN/m

Live load due to Walkway Slab= 3= 3 kN/m

Total load acting on the beam = 6.75 kN/m

Clear Cover to Main Reinforcement = 25 mm

Characteristic Strength of Concrete, fck = 20 N/mm2

Characteristic Strength of Steel, fy = 500 N/mm2

Diameter of top reinforcement = 8 mm

Diameter of bottom reinforcement = 8 mm

Effective depth for top reinforcement = 150-25-8-4= 113 mm

Effective depth for bottom reinforcement = 150-25-8-4= 113 mm

Max Bending moment at mid span = 1.22 kNm

Max Bending moment at supports = 0 kNm

Max Shear force = 8.1 kN

Reinforcement at bottom face of beam


Mu (Factored moment) = 1.5x1.22= 1.83 kNm

Mu /bd2 = 1.83x10^6/1000/113^2= 0.143 N/mm2

Percentage Steel Required, pt = 0.03 %

Area of steel Required = 0.03 x 1000 x 113 / 100 = 33.9 mm2


PROJECT: WATER SUPPLY DISTRIBUTION NETWORK FOR PALAKOLLU TOWN

TITLE AERATOR AND FLASH MIXER - 11MLD WTP

Astmin = 0.0012 x 1000 x 113 = 136.0 mm2

Spacing required = 150.0 mm

Ast Provided = (8 @150mm C/C) = 337.1 mm2

Shear Reinforcement

Vu = 1.5x8.1= 12.15 kN

tve = 12.15x1000/(1000x113) = 0.108 N/mm2

pt = = 0.298 %

Table 19, tc = = #VALUE! N/mm2

IS:456 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!

Check for Deflection

Span Length = 1200 mm

Area of steel Required = 136.0 mm2

Ast Provided = 337.1 mm2

Percentage Steel provided, pt 0.299

fs = 0.58 x fy x Astreq / Astprov= 117.0094936709

fig 4, IS:456 Modification Factor = 2

span / effective depth = 11

< 20x 2 = 40
PROJECT: WATER SUPPLY DISTRIBUTION NETWORK FOR PALAKOLLU TOWN

TITLE AERATOR AND FLASH MIXER - 11MLD WTP

Cover Slab over Flash Mixer

8.75 kN/m

1.9

Span of Slab l = 1.9 m

Size of Slab : Width of the Slab = 1000 mm

Depth of the Slab = 150 mm

Dead load due to self weight of beam = 25x1x0.15= 3.75 kN/m

Live load due to Walkway Slab= 3= 5 kN/m

Total load acting on the beam = 8.75 kN/m

Clear Cover to Main Reinforcement = 25 mm

Characteristic Strength of Concrete, fck = 20 N/mm2

Characteristic Strength of Steel, fy = 500 N/mm2

Diameter of top reinforcement = 8 mm

Diameter of bottom reinforcement = 8 mm

Effective depth for top reinforcement = 150-25-8-4= 113 mm

Effective depth for bottom reinforcement = 150-25-8-4= 113 mm

Max Bending moment at mid span = 3.95 kNm

Max Bending moment at supports = 0 kNm

Max Shear force = 29.75 kN

Reinforcement at bottom face of beam


Mu (Factored moment) = 1.5x3.95= 5.925 kNm

Mu /bd2 = 5.925x10^6/1000/113^2= 0.464 N/mm2

Percentage Steel Required, pt = 0.11 %

Area of steel Required = 0.11 x 1000 x 113 / 100 = 124.3 mm2


PROJECT: WATER SUPPLY DISTRIBUTION NETWORK FOR PALAKOLLU TOWN

TITLE AERATOR AND FLASH MIXER - 11MLD WTP

Astmin = 0.0012 x 1000 x 113 = 136.0 mm2

Spacing required = 150.0 mm

Ast Provided = (8 @150mm C/C) = 337.1 mm2

Shear Reinforcement

Vu = 1.5x29.75= 44.63 kN

tve = 44.63x1000/(1000x113) = 0.395 N/mm2

pt = = 0.298 %

Table 19, tc = = #VALUE! N/mm2

IS:456 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!

Check for Deflection

Span Length = 1900 mm

Area of steel Required = 124.3 mm2

Ast Provided = 337.1 mm2

Percentage Steel provided, pt 0.299

fs = 0.58 x fy x Astreq / Astprov= 106.9432357595

fig 4, IS:456 Modification Factor = 2

span / effective depth = 17

< 20x 2 = 40
PROJECT: WATER SUPPLY DISTRIBUTION NETWORK FOR PALAKOLLU TOWN

TITLE AERATOR AND FLASH MIXER - 11MLD WTP

Inter Connection Slab

8.75 kN/m

1.5

Span of Slab l = 1.5 m

Size of Slab : Width of the Slab = 1000 mm

Depth of the Slab = 150 mm

Dead load due to self weight of beam = 25x1x0.15= 3.75 kN/m

Live load due to Walkway Slab= 5= 5 kN/m

Total load acting on the beam = 8.75 kN/m

Clear Cover to Main Reinforcement = 25 mm

Characteristic Strength of Concrete, fck = 20 N/mm2

Characteristic Strength of Steel, fy = 500 N/mm2

Diameter of top reinforcement = 8 mm

Diameter of bottom reinforcement = 8 mm

Effective depth for top reinforcement = 150-25-8-4= 113 mm

Effective depth for bottom reinforcement = 150-25-8-4= 113 mm

Max Bending moment at mid span = 2.46 kNm

Max Bending moment at supports = 0 kNm

Max Shear force = 26.25 kN

Reinforcement at bottom face of beam


Mu (Factored moment) = 1.5x2.46= 3.69 kNm

Mu /bd2 = 3.69x10^6/1000/113^2= 0.289 N/mm2

Percentage Steel Required, pt = 0.07 %

Area of steel Required = 0.07 x 1000 x 113 / 100 = 79.1 mm2


PROJECT: WATER SUPPLY DISTRIBUTION NETWORK FOR PALAKOLLU TOWN

TITLE AERATOR AND FLASH MIXER - 11MLD WTP

Astmin = 0.0012 x 1000 x 113 = 136.0 mm2

Spacing required = 150.0 mm

Ast Provided = (8 @150mm C/C) = 337.1 mm2

Shear Reinforcement

Vu = 1.5x26.25= 39.38 kN

tve = 39.38x1000/(1000x113) = 0.348 N/mm2

pt = = 0.298 %

Table 19, tc = = #VALUE! N/mm2

IS:456 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!

Check for Deflection

Span Length = 1500 mm

Area of steel Required = 79.1 mm2

Ast Provided = 337.1 mm2

Percentage Steel provided, pt 0.299

fs = 0.58 x fy x Astreq / Astprov= 68.0547863924

fig 4, IS:456 Modification Factor = 2

span / effective depth = 14

< 20x 2 = 40
L & T Construction
Water & Renewable Energy
PROJECT: DOCUMENT NO. DATE
Bhatpara Sewerage Network & WWT Project
LE 130089 - C - WW- SW - DC -32xx 04-Aug-2018
TITLE DESIGNED CHECKED PAGE
WET WELL at LS 15 SBS JSR

Design of beam B3

Span of beam, l = 4.85 m

Size of beam : Width of the beam = 300 mm

Depth of the beam = 500 mm

Dead load due to self weight of beam = 25x0.3x0.5= 3.75 kN/m

Dead load due to floor finish = 1.15x(25x0.04)= 1.15 kN/m

Load due to live load acting on floor slab = 10x1.15= 11.5 kN/m

Total load acting on the beam = 16.4 kN/m

Clear Cover to Main Reinforcement = 30 mm

Characteristic Strength of Concrete, fck = 25 N/mm2

Characteristic Strength of Steel, fy = 500 N/mm2

Diameter of top reinforcement = 12 mm

Diameter of bottom reinforcement = 16 mm

Effective depth for top reinforcement = 500-30-6= 464 mm

Effective depth for bottom reinforcement = 500-30-8= 462 mm

Max Bending moment at mid span 16.4x4.85x4.85/8= 48.22 kNm

Max Shear force 16.4x4.85/2= 39.77 kN

Reinforcement at top face of beam

Astmin = 0.85 x 300 x 464 / 500 = 237 mm2

Ast Provided = = 226.2 mm2

Provide 2-12 dia bars on top face

Reinforcement at bottom face of beam

# Sensitivity: LNT Construction Internal Use


L & T Construction
Water & Renewable Energy
PROJECT: DOCUMENT NO. DATE
Bhatpara Sewerage Network & WWT Project
LE 130089 - C - WW- SW - DC -32xx 04-Aug-2018
TITLE DESIGNED CHECKED PAGE
WET WELL at LS 15 SBS JSR
Mu (Factored moment) = 1.5x48.22= 72.33 kNm

SP:16-1980 Mu /bd2 = 72.33x10^6/300/462^2= 1.130 N/mm2

Table : 3 Percentage Steel Required, pt = #MACRO? %

#MACRO? #MACRO? mm2

Astmin = 0.85 x 300 x 462 / 500 = 236.0 mm2

Ast Provided = = 402.1 mm2

Provide 2-16dia bars on bottom face

Shear Reinforcement

Vu = 59.655 kN

tve = 59.655x1000/(300x462) = 0.429 N/mm2

pt = = 0.29 %

Table 19, tc = = #VALUE! N/mm2

IS:456 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!

#VALUE! #VALUE! #VALUE! #VALUE!

Spacing for min shear reinforcement = 364 mm

0.75 d = 0.75 x 464 = 348 mm

#VALUE!

# Sensitivity: LNT Construction Internal Use


L & T Construction
Water & Renewable Energy
PROJECT: DOCUMENT NO. DATE
Bhatpara Sewerage Network & WWT Project
LE 130089 - C - WW- SW - DC -3170 04-Aug-2018
TITLE DESIGNED CHECKED PAGE
MCC Room at LS 15 SBS JSR

29.87
Design of beam B3 kN/m

4.3175 4.3175

Span of beam, l = 4.3175 m

Size of beam : Width of the beam = 300 mm

Depth of the beam = 500 mm

Dead load due to self weight of beam = 25x0.3x0.5= 3.75 kN/m

Dead load due to cover slab= 1.1625x(25x0.15)= 4.359375 kN/m

Dead load due to Grating= 0.9x(78.5x0.008)= 0.5652 kN/m

Dead load due to floor finish = 1.1625x(25x0.04)= 0.575 kN/m

Load due to live load acting on floor slab = 10x(1.1625+0.9)= 20.625 kN/m

Total load acting on the beam = 29.87 kN/m

Clear Cover to Main Reinforcement = 30 mm

Characteristic Strength of Concrete, fck = 25 N/mm2

Characteristic Strength of Steel, fy = 500 N/mm2

Diameter of top reinforcement = 12 mm

Diameter of bottom reinforcement = 16 mm

Effective depth for top reinforcement = 500-30-6= 464 mm

Effective depth for bottom reinforcement = 500-30-16-8= 446 mm

Max Bending moment at mid span 29.87x4.3175x4.3175/8= 69.6 kNm

Max Shear force 29.87x4.3175/2= 64.48 kN

Reinforcement at top face of beam

# Sensitivity: LNT Construction Internal Use


L & T Construction
Water & Renewable Energy
PROJECT: DOCUMENT NO. DATE
Bhatpara Sewerage Network & WWT Project
LE 130089 - C - WW- SW - DC -3170 04-Aug-2018
TITLE DESIGNED CHECKED PAGE
MCC Room at LS 15 SBS JSR
Astmin = 0.85 x 300 x 464 / 500 = 237 mm2

Ast Provided = = 339.3 mm2

Provide 3-12 dia bars on top face

Reinforcement at bottom face of beam

Mu (Factored moment) = 1.5x69.6= 104.4 kNm

SP:16-1980 Mu /bd2 = 104.4x10^6/300/446^2= 1.749 N/mm2

Table : 3 Percentage Steel Required, pt = #MACRO? %

#MACRO? #MACRO? mm2

Astmin = 0.85 x 300 x 446 / 500 = 227.0 mm2

Ast Provided = = 603.2 mm2

Provide 3-16dia bars on bottom face

Shear Reinforcement

Vu = 96.72 kN

tve = 96.72x1000/(300x446) = 0.695 N/mm2

pt = = 0.451 %

Table 19, tc = = #VALUE! N/mm2

IS:456 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!

#VALUE! #VALUE! #VALUE! #VALUE!

Spacing for min shear reinforcement = 364 mm

0.75 d = 0.75 x 464 = 348 mm

#VALUE!

# Sensitivity: LNT Construction Internal Use

Вам также может понравиться