A. GENERAL b. COMPONENTS & CLADDING: b. AIR CONTENT: c.

REPRODUCTION OF THE STRUCTURAL DRAWINGS FOR USE IN PREPARATION OF


1. CONCRETE LISTED IN TABLE "A" SHALL BE AIR ENTRAINED WITH THE APPROPRIATE SHOP DRAWINGS IS PROHIBITED. SHOP DRAWINGS SO PRODUCED WILL BE
INTERNAL PRESSURE COEFFICIENT :±0.18 REJECTED.
1. THE STRUCTURAL DRAWINGS FOR THIS PROJECT ARE NOT ISSUED FOR BID PERCENTAGE AIR CONTENT LISTED IN TABLE "B" AS APPLICABLE FOR THE INDICATED
BUILDING EXTERIOR COMPONENTS AND CLADDING SHALL BE DESIGNED FOR
UNLESS THE INDIVIDUAL SHEETS ARE IDENTIFIED AS "ISSUED FOR BID". EXPOSURE CATEGORY AND NOMINAL MAXIMUM AGGREGATE SIZE IN THE CONCRETE MIX.
THE FOLLOWING SERVICE LEVEL WIND PRESSURES: d. SHOP DRAWING SUBMITTALS TO THE STRUCTURAL ENGINEER SHALL CONSIST
2. THE STRUCTURAL DRAWINGS FOR THIS PROJECT ARE NOT ISSUED FOR THE REQUIRED AIR CONTENT VALUE MAY BE REDUCED BY 1% FOR ALL CONCRETE WITH
OF TWO SETS OF PRINTS. ONE SET OF PRINTS WILL BE RETURNED TO THE
CONSTRUCTION UNLESS THE INDIVIDUAL SHEETS ARE IDENTIFIED AS "ISSUED FOR COMPRESSIVE STRENGTH GREATER THAN 5,000 PSI. THE PERMITTED TOLERANCE ON THE CONTRACTOR WITH THE ENGINEER'S COMMENTS NOTED THEREON.
EFF. DESIGN
CONSTRUCTION". REQUIRED AIR CONTENT IS ±1.5 PERCENT. SEE ACI 318-05, SECTION 4.2.1 FOR ADDITIONAL
3. U.L. FIRE RESISTANCE RATING RESTRAINT CLASSIFICATION: ZONE* WIND PRESSURE
REQUIREMENTS. e. SUBMIT SHOP DRAWINGS 15 BUSINESS DAYS (MINIMUM) PRIOR TO DATE THAT
a. ALL STRUCTURAL FRAMING IS "RESTRAINED" EXCEPT AS INDICATED IN AREA POS. NEG. RETURNED SHOP DRAWINGS ARE REQUIRED. SHOP DRAWINGS SHALL BEAR THE
4. PROVIDE AIR ENTRAINMENT IN CONCRETE AS FOLLOWS:
NOTE "b". CONTRACTOR'S STAMP OF APPROVAL WHICH SHALL CONSTITUTE CERTIFICATION
10 20 10
b. THE FOLLOWING FRAMING IS UNRESTRAINED: TABLE "A" TABLE "B" THAT HE HAS VERIFIED ALL FIELD MEASUREMENTS, CONSTRUCTION CRITERIA,
1. STEEL JOISTS IN END BAYS ON ROOFS SUPPORTING ROOF DECK 20 19 10 MATERIALS AND SIMILAR DATA AND HAS CHECKED EACH DRAWING FOR
1 EXPOSURE CATEGORY**
50 19 10 CONCRETE REQUIRING AIR AIR CONTENT, PERCENT COMPLETENESS, COORDINATION AND COMPLIANCE WITH THE CONTRACT
OR REQUIRED % AIR NOMINAL MAX.
B. CODES AND STANDARDS: 100 18 10 ENTRAINMENT
CONTENT* AGGREGATE SIZE SEVERE MODERATE
DOCUMENTS. SCHEDULING OF SUBMITTALS OF STRUCTURAL STEEL SHOP
DRAWINGS AND REINFORCING STEEL PLACING DRAWINGS SHALL BE PLANNED
10 33 10 FOUNDATION CONCRETE MODERATE EXPOSURE EXPOSURE
1. THE FOLLOWING CODES AND STANDARDS, INCLUDING ALL SPECIFICATIONS SO THAT THE NUMBER OF DRAWINGS REQUIRED TO BE REVIEWED BY THE
REFERENCED WITHIN, SHALL APPLY TO THE DESIGN, CONSTRUCTION, LIGHTWEIGHT SLABS ON METAL 3/8" 7.5 6 STRUCTURAL ENGINEER DOES NOT EXCEED THE FOLLOWING: COMMISSION NO. 09U003

ROOF
20 29 10 4% TO 7%
QUALITY CONTROL AND SAFETY OF ALL WORK PERFORMED ON THE 2 DECK 1/2" 7 5.5
50 25 10 STRUCTURAL STEEL SHOP DRAWINGS: 50 SHEETS PER WEEK
PROJECT. USE THE LATEST EDITIONS UNLESS NOTED OTHERWISE. PARKING LEVEL WALLS &
100 22 10 MODERATE 3/4" 6 5
COLUMN ENCASEMENT REINFORCING STEEL PLACING DRAWINGS:25 SHEETS PER WEEK
a. BUILDING CODE: 2006 INTERNATIONAL BUILDING CODE. 10 33 10 1" 6 4.5
OCCUPANCY CODE (BUILDING SUBCODE: IBC 2006) f. COSTS OF INVESTIGATION AND/OR REDESIGN DUE TO CONTRACTOR ERRORS
29 10 ** SEE TABLE "B"
b. "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES", ASCE 7-05, 20 WILL BE AT THE CONTRACTOR'S EXPENSE.
3 *% AIR ENTRAINMENT SHALL CONFORM TO U.L.
AMERICAN SOCIETY OF CIVIL ENGINEERS. 50 25 10 RATING REQUIREMENTS FOR FIRE RESISTANCE RATINGS g. CONTRACTOR SHALL REFER TO ARCHITECTURAL, MECHANICAL, PLUMBING,
c. "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE", ACI 22 10
100 ELECTRICAL, LAUNDRY AND FOOD SERVICE DRAWINGS FOR SIZE AND
318-05, AMERICAN CONCRETE INSTITUTE.
d. "ACI MANUAL OF CONCRETE PRACTICE - PARTS 1 THROUGH 6 -2008". 20 17 18 a. REQUIRED NOMINAL MAXIMUM COARSE AGGREGATE SIZE: LOCATIONS OF OPENINGS, SLEEVES, CONCRETE HOUSEKEEPING PADS, INSERTS,
e. "MANUAL OF STANDARD PRACTICE", 27TH EDITION, MARCH 2001, REQUIRED NOMINAL MAXIMUM AND DEPRESSIONS.
50 16 17 CONCRETE ELEMENT
CONCRETE REINFORCING STEEL INSTITUTE. 4 COARSE AGGREGATE SIZE*
f. "STEEL CONSTRUCTION MANUAL", AMERICAN INSTITUTE OF STEEL 100 16 16 h. SEE ARCHITECTURAL DWGS. AND SPECIFICATIONS FOR FINISHES AND
ALL CONCRETE, U.N.O 1" FIREPROOFING.

WALL
CONSTRUCTION, THIRTEENTH EDITION, 2005, INCLUDING ALL 200 15 16
SPECIFICATIONS AND CODES IN PART 16. TOPPING SLABS LESS THAN 3" THK. 3/8"
20 21 18 i. TOPS OF ALL MASONRY PARTITION WALLS SHALL BE CONNECTED TO THE
g. "DETAILING FOR STEEL CONSTRUCTION", AISC 326-02, AMERICAN
INSTITUTE OF STEEL CONSTRUCTION. 50 19 17 UNDERSIDE OF THE STRUCTURAL FRAMING PER THE DETAILS PROVIDE ON THE
5 STRUCTURAL DRAWINGS. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF
h. "STRUCTURAL WELDING CODE - STEEL", AWS D1.1-2004 100 17 16 *SMALLER NOMIMAL MAXIMUM COARSE AGGREGATE SIZE SHALL BE USED ALL SUCH WALLS.
k. "STANDARD SPECIFICATIONS FOR OPEN WEB STEEL JOISTS, K-SERIES", 200 16 16 WHERE REQUIRED PER ACI 318-05, SECTION 3.3.2.
2002, STEEL JOIST INSTITUTE.
l. "STANDARD SPECIFICATIONS FOR LONGSPAN STEEL JOISTS, LH-SERIES
AND DEEP LONGSPAN STEEL JOISTS, DLH-SERIES", 2002, STEEL JOIST - USE ASCE 7.05 FIGURE 6-11 TO 6-19 WITH THESE VALUES b. COMBINED AGGREGATE GRADING:
INSTITUTE. - END ZONE (a) = 22 (FT.) FOR COARSE AGGREGATE WITH 3/4" OR 1" NOMINAL MAXIMUM AGGREGATE SIZE : 8% TO
i. "DESIGN MANUAL FOR COMPOSITE DECKS, FORM DECKS, AND ROOF DECKS - 22% (BY WEIGHT) OF AGGREGATE SHALL BE RETAINED ON EACH SIEVE BELOW THE
3. SEISMIC LOADS: MAXIMUM AGGREGATE SIZE SIEVE AND ABOVE THE #100 SIEVE.
NO.31", 2007, STEEL DECK INSTITUTE
j. "BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES (ACI530-05/ASCE 5-05) &
a. ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE
SPECIFICATIONS FOR MASONRY STRUCTURES (ACI 530.1-05/ASCE 6-05)", 2005, 5. REINFORCING STEEL:
PROCEDURE
AMERICAN CONCRETE INSTITUTE/AMERICAN SOCIETY OF CIVIL ENGINEERS. b. BASIC SEISMIC-FORCE-RESISTING SYSTEM: DEFORMED REINFORCING BARS ASTM A615, GRADE 60
ORDINARY STEEL MOMENT FRAMES
WELDED WIRE REINFORCEMENT (W.W.R.) ASTM A185
C. DESIGN LOADS:
OCCUPANCY CATEGORY III DOWELING ADHESIVE FOR ANCHORING HILTI "HIT HY 150" SYSTEM OR
1. GRAVITY LOADS: SEISMIC IMPORTANCE FACTOR IE 1.25 REINF BARS INTO EXIST CONCRETE POWERS ACRYLIC-100 SYSTEM
EPOXY COATED REINF. BARS ASTM A775
SERVICE LEVEL LIVE LOADS SERVICE LEVEL SUPERIMPOSED DEAD LOADS SOIL SITE CLASS C
LOCATION LOCATION MAPPED SHORT PERIOD SPECTRAL ACCEL SS 0.276 EPOXY COAT THE FOLLOWING REINFORCING STEEL:
ALL FLOORS, UNO 100 PSF TYPICAL SUSPENDED CEILING & MEP MAPPED 1-SEC PERIOD SPECTRAL ACCEL S1 0.060 1. PARKING LEVEL
15 PSF
MECHANICAL ROOMS 150 PSF LOADS (SEE NOTE "b" BELOW) ACCELERATION RELATED SITE COEFF Fa 1.2 EPOXY COAT THE FOLLOWING:
STORAGE ROOMS 125 PSF GYM & TRUSS SUSPENDED a. ALL REINFORCING STEEL IN PARKING SLABS
10 PSF VELOCITY RELATED SITE COEFF FV 1.7
CEILING & MEP LOADS b. ALL COLUMN TIES (AT COLUMN ENCASEMENTS)
PARKING LEVELS, U.N.O. 40 PSF
(SEE NOTE "b" BELOW) DESIGN SHORT SPECTRAL RESPONSE COEFF S DS 0.220 AND WALL REINFORCING FROM BOTTOM OF SLAB
TERRACE 100 PSF TO 4'-0" ABOVE TOP OF SLAB.
DESIGN 1-SEC SPECTRAL RESPONSE COEFF S D1 0.068
ROOF 20 PSF TYPICAL ROOFING SYSTEM &
10 PSF 2. IN LOCATIONS WHERE EPOXY COATED REINFORICNG STEEL
INSULATION SEISMIC DESIGN CATEGORY B
IS SPECIFIED, ALL TIE WIRE SHALL BE PLASTIC COATED
TERRACE & GREEN ROOF ROOFING RESPONSE MODIFICATION FACTOR R 3 AND ALL ACCESSORIES USED TO SUPPORT THE
17 PSF
SYSTEM & INSULATION SYSTEM OVERSTRENGTH FACTOR O 3 REINFORCING STEEL AND P.T. TENDONS SHALL BE
EPOXY COATED (CHAIRS, SUPPORT BARS, SLAB BOLSTERS)
FLOOR FINISHES (PER INCH OF DEFLECTION AMPLIFICATION FACTOR Cd 3
12 PSF
FLOOR SLAB DEPRESSION) TRANSITION PERIOD TS 0.31 6. STRUCTURAL STEEL:
SUSPENDED PIPING IN
CEILING OF MECH. ROOMS
50 PSF
LONG-PERIOD TRANSITION PERIOD TL 6.00
W SHAPES ASTM A992 Fy=50 KSI STRUCTURAL DRAWING LIST
CALCULATED FUNDAMENTAL PERIOD T 2.20 ASTM A36 Fy=36 KSI
CHANNELS, ANGLE, PLATES & BARS
NOTE: LIVE LOAD REDUCTIONS HAVE BEEN APPROXIMATE FUNDAMENTAL PERIOD Ta 0.63
USED FOR DESIGN OF THE STRUCTURAL ROUND PIPE ASTM A53, GR "B" Fy=35 KSI
FRAMING WHERE PERMITTED PER IBC UPPER LIMIT ON CALCULATED PERIOD C u x T a 1.07 SQUARE & RECTANGULAR HSS's ASTM A500, GR "B" Fy=46 KSI
2006 SECTION 1607.9 SEISMIC RESPONSE COEFF CS 0.027 ASTM A325 TYP, UNO &
HIGH STRENGTH BOLTS
ASTM A490 WHERE INDICATED
SEISMIC BASE SHEAR V 315k
ROOF SNOW LOAD: ASTM F1554, GRADE 55 W/ SECTION
GROUND SNOW LOAD, P g: 25 PSF 4. LATERAL EARTH PRESSURES: ANCHOR RODS "S1" WELDABILITY SUPPLEMENT OR
TERRAIN CATEGORY : B GRADE 105 (WHERE INDICATED)
EXPOSURE OF ROOF : FULLY EXPOSED a. SERVICE LEVEL "EQUIVALENT FLUID PRESSURES"
ROUND RODS & THREADED RODS ASTM A36
SNOW EXPOSURE FACTOR, C e: 0.9 CONDITION f (pcf) AWS D1.1 TYPE "B" , Fu=65 ksi (min) FOR CODE APPROVAL:
THERMAL FACTOR, C t : 1.0 HEADED SHEAR STUDS
ACTIVE PRESSURE 45 pcf REVISIONS:
SNOW IMPORTANCE FACTOR, I: 1.1 EXPANSION BOLTS HILTI KB-TZ KWIK BOLT

ISSUES / REVISIONS
FLAT ROOF SNOW LOAD, P f : I x Pg = 22 PSF AT-REST PRESSURE 67 pcf HILTI HIT-RE 500-SD ANCHOR SYSTEM
w/ HILTI HAS-E THREADED RODS
5. OTHER L0ADS: (Fy = 58ksi / Fu = 72ksi) IN
ADHESIVE ANCHORS
a. HORIZONTAL VEHICULAR IMPACT: 10k (ULTIMATE) LOAD INCLUDING HAMMER-DRILLED HOLES; DRY OR
a. THE CONTRACTOR SHALL CONFIRM THAT THE ACTUAL MECHANICAL UNITS PURCHASED ARE OF WATER SATURATED CONCRETE HOLES FOR BID: 06-04-10
IMPACT OCCURRING AT ANY LOCATION 1'-6" ABOVE TOP OF PARKING

BID SET
WEIGHT AND SIZE SUCH THAT THE TOTAL SUPERIMPOSED LOAD UNDER EACH UNIT DOES NOT DECK AT ALL LOCATIONS SUBJECT TO VEHICULAR TRAFFIC AND PERMITTED
EXCEED THE LIVE LOAD FOR WHICH THE FLOOR WAS DESIGNED IN THE FLOOR AREA WHERE THE PARKING. WELDING ELECTRODES AWS A5.1 OR A5.5, E70XX
UNIT IS LOCATED.
GALVANIZED METAL FLOOR DECK ASTM A653, GRADE 40 (Fy=40 KSI)
D. FOUNDATIONS/GEOTECHNICAL REPORT:

06/04/2010
GALVANIZED METAL ROOF DECK ASTM A653, GRADE 40 (Fy=40 KSI)
TOTAL SUPERIMPOSED TOTAL EQUIPMENT WEIGHT INDICATED SERVICE LEVEL DWG.

DATE
= 1. FOUNDATIONS HAVE BEEN DESIGNED IN ACCORDANCE WITH THE Date Description Date Description
LOAD UNDER UNIT UNIT FOOTPRINT AREA DESIGN LIVE LOAD GEOTECHNICAL REPORT AND LETTER PREPARED BY: ADVANCED GEOSERVICES
7. STRUCTURAL MASONRY:
NO. DRAWING TITLE
REPORT NO: 2009-2427000 Submitted: Professional:

TOTAL EQUIPMENT WEIGHT = OPERATING WT. OF UNIT + CONCRETE HOUSEKEEPING PAD + DATED: 21 AUGUST 2009 - SEE THAT REPORT FOR ADDITIONAL INFORMATION.
a. CONCRETE MASONRY UNITS: S0-1 GENERAL NOTES Submitted: Consultant:
INERTIA BLOCK + OTHER ANCILLARY ITEMS ASSOCIATED WITH THE LETTER NO: 2009-2427000 ASTM C90, TYPE I MASONRY UNITS; MINIMUM Reviewed by: Construction Manager:
EQUIPMENT DATED: 4 MAY 2010 - SEE THAT LETTER FOR ADDITIONAL INFORMATION. COMPRESSIVE STRENGTH ON NET AREA = 1900 PSI S0-2 GENERAL NOTES
UNIT FOOTPRINT AREA = EFFECTIVE AREA OF UNIT OR HOUSEKEEPING PAD S0-3 GENERAL NOTES / PLAN NOTES
Authorized by: System Representative:

WHICHEVER IS LARGER 2. SPREAD FOOTINGS AND CONTINUOUS WALL FOOTINGS HAVE BEEN b. MORTAR FOR CONCRETE BLOCK CONSTRUCTION:
EFFECTIVE AREA = (LENGTH + 6') x (WIDTH + 6') DESIGNED FOR THE FOLLOWING NET ALLOWABLE BEARING ASTM C270, TYPE "S" FOR ALL BELOW GRADE MASONRY
PRESSURE: 3 KSF ASTM C270, TYPE "N" UNLESS NOTED OTHERWISE S1-1 FOUNDATION PLAN
CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER PRIOR TO CONSTRUCTION ON THE
c. GROUT: S1-2 MAIN LEVEL FRAMING PLAN
LOCATION OF ANY MECHANICAL UNITS WHERE THE TOTAL SUPERIMPOSED LOAD UNDER THE UNIT E. MATERIALS: ASTM C476; MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS = REQUIRED PRISM
SEAL:
EXCEEDS THE INDICATED DESIGN LIVE LOAD FOR THE FLOOR AS INDICATED ON THE LOAD MAPS. S1-3 MEZZANINE LEVEL FRAMING PLAN
STRENGTH OR 2,000 PSI WHICHEVER IS GREATER
1. THE FOLLOWING ASTM STANDARDS AND DESIGN STRESSES SHALL BE S1-4 ROOF LEVEL FRAMING PLAN
b. DOES NOT INCLUDE LINE LOADS FROM MAIN AND BRANCH RUNS OF PIPING. REFER TO THE USED FOR THE APPROPRIATE MATERIALS USED IN THE CONSTRUCTION
FRAMING PLANS FOR MAIN AND BRANCH PIPING LINE LOADS. THE CONTRACTOR SHALL VERIFY d. HORIZONTAL JOINT REINFORCING: SIGNATURE:
OF THIS PROJECT. ASTM A82; GALVANIZED 9 GAGE TRUSS-TYPE
THAT ALL MAIN AND BRANCH LINE RUNS OF PIPING ARE LOCATED AT THE LOCATIONS SHOWN ON S2-1 TYPICAL DETAILS
THE LOAD MAP DIAGRAMS. 2. CEMENT: ASTM C150, TYPE I OR III Professional Seals
e. REQUIRED PRISM STRENGTH (PER ACI 530): S2-2 TYPICAL DETAILS
FOR 1900 PSI BLOCK W/ TYPE S MORTAR: REQ'D f'm = 1500 PSI STATE SYSTEM OF HIGHER EDUCATION
2. WIND LOADS: 3. CONCRETE: CONCRETE SHALL HAVE THE FOLLOWING ENGINEERING PROPERTIES S2-3 TYPICAL DETAILS
WEST CHESTER UNIVERSITY
a. MAIN WIND-FORCE RESISTING SYSTEM: ORDINARY STEEL MOMENT FRAMES S2-4 TYPICAL DETAILS
a. COMPRESSIVE STRENGTH, W/C RATIO & UNIT WEIGHT F. CONSTRUCTION:
BASIC WIND SPEED (3s GUST): 90 MPH S2-5 TYPICAL DETAILS
F'c @ 28 W/C (MAX UNIT WT Project/Contact No.# 7563062113.1
OCCUPANCY CATEGORY: III LOCATION 1. GENERAL: S2-6 TYPICAL DETAILS
WIND IMPORTANCE FACTOR, Iw:
WIND EXPOSURE:
1.15
B
DAYS (PSI) PERMITED) (PCF)
S2-7 TYPICAL DETAILS WEST CHESTER UNIVERSITY
WALL FOOTINGS 3000 0.55 145 a. THE CONTRACTOR IS RESPONSIBLE FOR SITE SAFETY. THE CONTRACTOR AND
SPREAD FOOTINGS 3000 0.55 145
ALL SUBCONTRACTORS SHALL REVIEW THE STRUCTURAL CONTRACT S2-8 TYPICAL DETAILS STUDENT RECREATION CENTER
DOCUMENTS AND SHALL NOTIFY THE STRUCTURAL ENGINEER OF ANY Project Title
GRADE BEAMS 3000 0.55 145 CONFLICTS BETWEEN THOSE DOCUMENTS AND ANY SAFETY REGULATIONS.
SUCH REVIEW AND NOTIFICATION SHALL OCCUR PRIOR TO PRODUCTION OF S3-1 DETAILS SPIEZLE ARCHITECTURAL GROUP, INC.
TOPPING SLABS 3000 0.55 145 Architecture Planning Design
SHOP DRAWINGS. S3-2 DETAILS
SLABS-ON-GRADE (TYP. U.N.O.) 4000 0.50 145 321 West State Street
Media, P.A. 19063
S3-3 DETAILS
SLABS-ON-GRADE (PARKING) 4500 0.45 145 b. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING ALLOWABLE Phone 610.874.7800

DETAILS Fax 610.874.7158


CONSTRUCTION LOADS, FOR PROTECTING THE COMPLETED STRUCTURAL S3-4
PIERS / WALLS 4000 0.50 145 Architect Engineer
FRAMING FROM DAMAGE DUE TO TEMPORARY CONSTRUCTION LOADINGS, FOR S3-5 DETAILS
COLUMN ENCASEMENT 4500 0.45 145 DETERMINING SEQUENCES OF CONSTRUCTION, AND FOR DETERMINATION,
S3-8 DETAILS GENERAL STRUCTURAL NOTES
NORMAL WEIGHT SLABS ON METAL DECK 3500 0.55 145 DESIGN AND INSTALLATION OF ALL FALSEWORK, FORMWORK, STAGING, Drawing Title
TEMPORARY BRACING, SHEETING AND SHORING NECESSARY FOR DRAWN BY: Date: Drawing No.
LIGHT WEIGHT SLABS ON METAL DECK 3500 N/A 110 CONSTRUCTION. KTM 06-04-10
Checked By: Scale: S0-1
MBK 1/8" = 1'-0"

Copyright c 2010 by The Harman Group, Inc.


All rights reserved.