H V A C S Y S T E M S M O N I T O R I N G

Duct Smoke
Detector for Special
Applications
Model
2451 with B404B/B404BT UL 268A
and RTC Remote Test Kit (Requires RTC
accessory)

Product Overview

Low standby current

Two LEDs “blink” in standby

Detector head plugs easily into base

Field adjustable sensitivity 2451 with B404BT and RTC


(Includes the RTS451)
Built-in test switch

Field sensitivity metering of detector to meet The System Sensor 2451 photoelectronic smoke detector is UL listed
the requirements of NFPA 72 to UL 268A specifically for use in no-flow/low-flow air-handling sys-
tems. It’s designed for installations where a standard Venturi principle
120VAC and 24VAC/DC bases with built-in duct smoke detector is unsuitable. This is the perfect combination for
shorting spring installation in ducts where the air velocity is below 500 fpm or for duct
Built-in tamper-resistant feature sizes as small as 8 inches in diameter. Pendant mounted in a standard
electrical box within the duct, the twist-in/twist-out head allows easy
Designed for mounting on standard electrical box removal from the base for quick cleaning and maintenance. The detec-
tor can be combined with the System Sensor B404B 120VAC base or
SEMS screws for easy wiring and positive wire the B404BT 24VAC/DC base. Remote testing is accomplished using our
retention
Remote Test Coil accessory that includes the RTS451. The APA451,
Removable cover and insect screen for field Remote Annunciator with Piezo Alarm, can also be connected to pro-
cleaning vide an audible and visible indication of smoke detector status.

Specifications
Operating Voltage/ Alarm current Construction
Mounting base dependent (see char t) Flame retardant Nor yl plastic
Standby current Operating Temperature
120 mA maximum 32° to 120°F (0° to 49°C)
Sensitivity Humidity Range
3% ± .7% / ft. 10 to 93% RH non-condensing
Weight Air Velocity Rating
0.5 lb. (277 g) 0 to 3000 fpm maximum
Size
3.2˝/8.1 cm height
6.2˝/15.8 cm diameter
Architectural/Engineering Specifications

The air duct detector shall be a System Sensor model 2451 Series Smoke detector UL listed to UL 268A specifically for use in
air handling systems when used in conjunction with the B404B (120VAC) or the B404BT (24VAC/DC) base. The detector shall
operate at air velocities up to 3000 feet per minute. It shall be capable of local testing via magnetic switch or remote testing
using the UL listed RTC Remote Test Coil accessory with the RTS451 Remote Test Station. It shall be capable of providing
duct smoke detector status via the UL listed model APA451 Piezo Annunciator.

Base Chart
Base Current Limit Alarm Current
Version Loop Type Alarm Contact Type Nominal Voltage
Model resistor (mA)
B404B UL/ULC 4-wire Yes Form A&C + A supy. 120VAC 20.4
B404BT UL 4-wire Yes Form A&C + A supy. 24VAC/DC rms 94

Junction Box Selection


Base Model Single Gang 31/2˝ Oct. 4˝ Oct. 4˝ Sq. 50mm 60mm 75mm

B404B No No Yes Yes No No No


B404BT No No Yes Yes No No No

Wiring Guide
B404B Typical Wiring Diagrams:
(+) (+)
RA400Z RA400Z
(–) (Optional) (–) (Optional)

RELEASING
DEVICE
3 4 3 4

BLACK LEADS
TRANSFORMER
PRIMARY 2 2 EOL
14 14
5 13 5 13 SPECIFIED
1 1
12 12 BY PANEL
120 VAC 120 VAC
MANUFACTURER
6 11 6 11
7 10 7 10
8 9 8 9

FIRE
ALARM ALARM INITIATION LOOP
CONTROL
PANEL
RELEASING
POWER DEVICE RELEASING
POWER H0270-00
DEVICE

B404B Base Terminals


RA400Z
No. Function (Optional)

1 Remote Annunciator (+)


2 Not Used
3 Not Used
4 Remote Annunciator (-)
3 4
5 Not Used
BLACK LEADS
TRANSFORMER
6 N.O. Supervisory Relay PRIMARY 2 EOL

7 N.O. Form A Contacts 14


5 13 SPECIFIED
1
BY PANEL
8 N.O. 12
MANUFACTURER
6 11
9 N.O. Alarm Relay 120 VAC 7 10
8 9
Form A
10 C. Initiation Contacts
11 C. FIRE
ALARM INITIATION LOOP
ALARM
CONTROL
12 N.O. PANEL
Alarm Relay
13 N.C. Form C H0271-00
Auxiliary Contacts FAN/DAMPER
POWER
14 C. CONTROL
B404BT Typical Wiring Diagrams:

3 APA451 3 APA451
2 2
(Optional) (Optional)
1 1

RELEASING RELEASING
DEVICE DEVICE
3 4 3 4

2 2 EOL
14 14
5 13 5 13 SPECIFIED
1 1
12 12 BY PANEL
24 VACrms/DC 24 VACrms/DC
MANUFACTURER
6 11 6 11
7 10 7 10
8 9 8 9

FIRE
ALARM ALARM INITIATION LOOP
CONTROL
PANEL H0268-00

B404BT Base Terminals


NOTE: ABOVE DIAGRAM SHOWS NFPA REQUIRED WIRING OF SUPERVISED
No. Function
SYSTEMS. SCHEMATIC SHOWN BELOW FOR REFERENCE.
3 APA451 1 Remote Annunciator (+)
2 (Optional)
CT POWER SOURCE 1 2 Test Coil (+)
ROPRIATE TERMINALS SUPERVISORY SUPERVISORY
H DETECTOR. SEE RELAY RELAY 3 Not Used
CATIONS FOR
NAL POWER SUPPLY 4 Remote AnnunciatorEOL
(-)
ATION.
CONTROL ALARM ALARM 5 RTC (-)
SPECIFIED
PANEL RELAY RELAY BY PANEL
6 N.O. SupervisoryMANUFACTURER
Relay
3 4
7 N.O. Form A Contacts

2 8 N.O.
14
5 9 N.O. Alarm Relay
13
1 Form A
24 VACrms/DC 12 10 C. Initiation Contacts
6 11
RING OF AUXILIARY 10
S, REFER TO
7 9 11 C.
8
ACTURER'S 12 N.O.
ATION INSTRUCTIONS Alarm Relay
TACT MANUFACTURER. 13 N.C. Form C
Auxiliary Contacts
14 C.
HE SUPERVISORY RELAY NOW
ES A "FORM C" CONTACT FOR
MIZED APPLICATIONS.
ANDARD APPLICATIONS, ONLY POWER
FAN / DAMPER
" CONTACT IS USED SHUTDOWN

RTC Ring Replacement of B404BT:


H0269-00

RTC Wiring Diagram:

B404B/B404BT RTS451

REMOTE 1 1
ANNUNCIATOR (+)
TEST
2 2 COIL
TEST COIL (+)

3 3
FIELD
INSTALLED
4 JUMPER 4

4-POSITION
5 5 TERMINAL
RTC (–)
EOL RESISTOR TEST BLOCK
SPECIFIED BY COIL ALARM
PANEL MANUFACTURER

H0272-00

H0233-00
ALARM

ALARM POWER

RESET

RTS451KEY APA451 RA400Z


Remote Test Station Piezo Annunciator Remote Annunciator
(provided with Remote
Test Coil)

Top Mount in Ventilation Shaft

Ordering Information
Part No. Description Accessories Description
2451 Photoelectronic plug-in detector (order one of the bases RTC Remote test coil kit (Includes RTS451 remote
listed below and the RTC) test station)
B404B 120VAC detector base APA451 Remote annunciator with piezo alarm
B404BT 24VAC/DC detector base RA400Z Remote annunciator

System Sensor Sales and Service


System Sensor Headquarters System Sensor Canada System Sensor in China System Sensor – Far East System Sensor – India
3825 Ohio Avenue Ph: 905.812.0767 Ph: 86.29.8832.0119 Ph: 85.22.191.9003 Ph: 91.124.637.1770 x.2700
St. Charles, IL 60174 Fx: 905.812.0771 Fx: 86.29.8832.5110 Fx: 85.22.736.6580 Fx: 91.124.637.3118
Ph: 800/SENSOR2 System Sensor Europe System Sensor in Singapore System Sensor – Australia System Sensor – Russia
Fx: 630/377-6495 Ph: 44.1403.891920 Ph: 65.6273.2230 Ph: 613.54.281.142 Ph: 70.95.937.7982
www.systemsensor.com Fx: 44.1403.891921 Fx: 65.6273.2610 Fx: 613.54.281.172 Fx: 70.95.937.7983

© 2004 System Sensor. The company reserves the right to change product specifications without notice. A05-0952-001•1/04•#1228