Академический Документы
Профессиональный Документы
Культура Документы
PART 1 - GENERAL
1.2 SUMMARY
1. Submittals
2. Quality Assurance
3. Delivery/Storage/Handling
4. Coordination
5. Training/Warranty/Maintenance Services
6. Manufacturers
7. Materials
8. Structural Specifications
9. AC Power/Distribution
10. Wiring
11. Ground Halo System
12. Air Conditioner / Heater
13. Code Compliance
14. Execution
B. All sites shall meet the requirements set forth within this specification. Existing
facilities shall be retrofitted / modified as required to meet the requirements set
forth within this specification.
1.3 DEFINITIONS
1.4 SUBMITTALS
2. PS1-74: U.S. Product Standard for Construction and Industrial Plywood with
Typical APA Trademarks.
3. American National Standards for Minimum Design Loads for Building and
Other Structures.
C. This structure shall meet any local variations in the above codes and standards
plus any local requirements not specified herein.
1.7 COORDINATION
B. Prior to erecting the shelter on the foundation, the Contractor will provide to the
Project Director a sample of each truck load of concrete that has been tested for
compliance with the foundation specifications set forth by the requisite site
engineer. Written reports certifying the strength of the concrete are to accompany
each test cylinder.
C. If any concrete used in the foundation does not meet specifications, the
Contractor will be required to remove the foundation and pour one using
compliant materials.
D. The Contractor will coordinate with the electric utility company and the
Customer's electrical contractor to provide power to the building.
1.8 TRAINING
1.9 WARRANTY
PART 2 - PRODUCTS
2.1 MANUFACTURERS
B. Due to the wide range of possible offerings, Manufacturers whose products differ
from, but meet or exceed the specifications defined herein, shall attach cut
sheets comparing their offering to the specifications.
2.2 MATERIALS
A. Concrete:
B. Other:
3. Water shall be free from injurious quantities of oil, alkali, vegetable matter,
and salt. Non-potable water shall not be used in mixing concrete.
5. Welded smooth wire fabric shall be steel wire fabric conforming to the
requirements of the "Specifications for Welded Steel Wire Fabric for
Concrete Reinforcement," ASTM Designation: A185.
C. Skid Assembly
A. Shelter Type:
3. The shelter shall be designed and provided with suitable attachment points for
lifting and moving the shelter so that the shelter can be hoisted up using
overhead equipment such as cranes, boom trucks and hoists. The
manufacturer shall provide a description and drawings detailing the
attachment points and proper lifting procedures.
B. Size:
C. Foundation:
1. The foundation for the shelter shall consist of concrete piers or a poured
concrete slab constructed by the Contractor to properly support and secure
to the shelter.
D. Flooring
E. Walls
2. Bullet Proof: Walls shall withstand the effects of bullets or other projectiles
equivalent to a 30.06 high power rifle load fired from a distance of 50 feet
with no penetration to the inner cavity of the wall. No interior damage shall
be sustained including insulation, interior walls, etc.
5. The inside walls shall be finished with minimum 5/8-inch plywood (or
equivalent) trimmed with coordinated molding to allow mounting of panels,
blocks, etc.
F. Roof:
1. The building roof shall support a minimum 100 pounds per square foot
uniform live load.
3. It shall withstand the impact of ice falling from the adjacent tower without
suffering any damage or shall otherwise be protected from such damage.
Contractors are to describe in their proposal how this requirement will be
met.
G. Door:
2. An insulating inner core shall separate interior and exterior panels of this
door.
3. Bullet Proof: Door shall withstand the effects of bullets or other projectiles
equivalent to a 30.06 high power rifle load fired from a distance of 50 feet
with no penetration to the inner cavity of the door. No interior damage shall
be sustained including insulation, interior walls, etc.
4. The door shall be mounted with three stainless steel, tamper proof hinges. A
mortise type dead bolt lock secured in the door frame shall provide tamper
proof security. Two locks, one in-keyed passage and a keyed deadbolt,
shall be provided.
9. Door frame to have weather seal around door to limit air and water intrusion.
2.4 FINISHING
A. The finishes shall be described by the Contractor. Color and finishes shall be
selected by the Customer from samples provided by the Contractor.
B. Exterior color and finish shall be coordinated with Customer to match surrounding
buildings.
C. The interior shall be smooth finished in all cases. Color to be selected by the
Customer from samples provided by the Contractor.
D. Openings for air flow, doorways, cable entry, etc. shall be designed and sealed to
preclude penetration of moisture, insects, and rodents into the interior of the
structure or between the exterior and interior of any wall, roof or flooring.
E. Joints:
F. Exterior wall and roof surfaces shall be sealed to insure a watertight barrier.
G. The shelter wall, floor and ceiling joints shall be sealed to prevent water entry.
A. General:
1. All wiring noted on the site drawings or otherwise included by this Contractor
shall be installed in conduit or ductwork. Where no protection method is
specified, conduit shall be used.
2. All conduits and ducts shall be securely surface mounted and supported by
approved clamps, brackets, or straps as applicable and held in place with
properly selected screws. No wiring to be imbedded inside any walls, floor
or ceiling. Entrance power, outside light, air conditioning outlet and telco are
the only wiring allowed to penetrate shelter walls or floor.
5. Conduit shall not be used as a ground of any kind. Separate ground wires
shall be used for all grounding functions. More specific grounding
requirements are stated elsewhere within this specification.
A. Unless otherwise approved all power wiring shall be a minimum size 12 AWG
solid copper conductors with insulation rated for 600 Volts alternating current
(AC).
A. Capacity:
1. The Contractor shall deliver the building complete with a 200 ampere
capacity, 240 volts, single phase Square D electrical panel box with a ground
bar.
2. This panel shall be equipped with a 200 ampere capacity main circuit breaker
used to supply power for all electrical functions related to the site.
3. Overall panel size shall be determined by the need to provide the number of
individual breakers determined plus a reserve of at least six 240 Volt slots.
4. Breakers for shelter air conditioning will be of the bolt down not snap in type.
6. The Customer will provide electrical power to the meter panel on the exterior
of the shelter. The meter panel and all wiring from that point is the
responsibility of the Contractor, along with mast and weatherhead.
B. Power Distribution:
1. Power shall be distributed from the electrical panel, through the raceways and
conduits to the indicated fixture or other termination.
2. For each equipment unit receptacle and each service receptacle group #12
AWG insulated copper conductors shall be run by this Contractor through
appropriately sized conduit.
3. Each radio equipment unit receptacle shall be mounted to the side of the
overhead cable tray.
4. Service receptacles shall be specification grade, 120 Volt or 240 Volt rated as
appropriate for the purpose, with ground.
4. The unit shall be capable of handling the full 240 Volt, 200 Amp capacity of
the electrical system.
A. Outlets:
3. One weatherproof GFI exterior power receptacle shall be provided with each
shelter. Outlet to be mounted in the area of the air conditioning units.
B. Light Fixtures:
1. Ceiling mounted, four-foot fluorescent light fixtures (two 40 watt bulbs per
fixture) with RFI ballasts shall be supplied for the equipment shelters. A
sufficient quantity of light fixtures shall be supplied to provide a uniform light
level throughout the building of 150 foot candles at four feet above the floor.
C. Electric Heater:
1. A 240 Volt AC heater shall be supplied and installed in each shelter. (5000
watt minimum) The heater can be installed as part of the air conditioning
system.
2. The heater shall be sized to provide 100 percent of the required building
heating capacity, including equipment heat.
3. The heater shall be fed from separate circuit and controlled by wall mounted
thermostat.
4. The thermostat shall turn the heater on when the temperature inside the
shelter drops to 65 degrees F and off when it rises to 68 degrees F. It shall
be adjustable to turn on and off within the range of 45 to 80 degrees F.
D. Outdoor Lighting:
1. An exterior 100 watt wall mounted light shall be mounted on the front
entrance of the shelter.
2. The exterior lighting system shall be fed from a separate, appropriately rated
breaker and light switch by the door.
1. All conduit openings in the shelter walls shall align properly with the antenna
entrance cables.
3. The building Contractor shall seal the conduits into the wall to assure that
they are watertight.
F. Cable Tray:
1. The Contractor shall install an minimum 18-inch wide cable tray system above
the equipment and below the ceiling. All new shelters will be equipped with
the cable trays.
2. The Contractor shall ground all cable ladder sections to the interior halo
ground system as per specifications.
2. This ground shall be stood off from the wall itself by approved insulators, such
as "clic's" manufactured by Litchfield International or equivalent. Types with
encircling metal bands or clamps are not acceptable.
3. This ground wire shall have a break with the ends separated at least 4 inches
apart. This break will be approximately opposite the location of the master
ground bar (MGB)
4. At each of the four corners # 2 AWG tinned, solid drain wire shall be bonded
to the halo by non reusable compression clips or Ampac methods.
5. These drain wires shall be run down the corners through insulated, non-
metallic feed-through PVC conduits passing to the outside.
9. Where the building and/or roof are of steel construction, such steel
components must be bonded to the earth ground system.
10. Each panel shall be bonded to the next adjacent panel by a # 6 AWG or
larger copper conductor, secured by methods approved by the Project
Director.
11. The cable ladder is to be bonded to the ground halo. All sections of the ladder
are to be bonded together with a # 6 insulated, stranded wire using double-
hole compression lugs. Any paint on the cable tray will be removed at the
point of the jumper connections. A thin coating of an anti oxide compound will
be used to reduce oxidation. Only stainless steel hardware will be used to
attach the wire lugs to the cable tray.
A. Capacity:
1. The shelters shall be provided with a dual, wall mounted, 240 Volt powered
air conditioners.
3. Each air conditioner shall be sized to provide 100 percent of the required
building cooling capacity, including equipment heat.
B. Size:
1. Each air conditioner shall be sized to maintain temperatures inside the shelter
at 70 degrees F when exterior temperatures go as high as 100 degrees F.
C. BTU Ratings:
1. Contractors are to include in their proposal a detail of how they determined the
BTU rating of the air conditioner.
D. Thermostat Control:
1. A wall mounted thermostat, part of the air conditioner, will control the
operation. It will turn on the air conditioner when the interior temperature
reaches 78 degrees F and off when the temperature drops below 75 degrees
F.
E. Time Delay:
1. A time delay relay will be included with the air conditioner to prevent
compressor damage from an attempt to restart the unit too soon after power
has been turned off or interrupted. The delay time shall be five minutes.
PART 3 - EXECUTION
B. Shelter shall be transported by Contractor to the radio site. This building shall be
assembled and secured on a solid foundation or supporting piers constructed by
this Contractor.
3.4 CLEANING
3.6 TRAINING
END OF SECTION
2/3/05