4. The one-line diagram of three phase power system is as shown: Each generator is repre-
Figure 1:
sented by an emf behind the sub-transient reactance. All impedances are expressed in
p.u on common MVA base. All resistances and shunt capacitances are neglected. The
generators are operating on no-load at their rated voltage with their emfs in phase. A
three phase fault occurs at bus 3 through fault impedance Zf= j0.19p.u.
Electrical Engineering Dept - IIT Delhi
(a) Using Thevenin’s theorem obtain the impedance to the point of fault and fault
current in p.u.
(b) Determine the bus voltages and line currents during fault.
[Ans: (a) Z33=j0.2102; If = -j2.4988 p.u ( b) = 0.925p.u; = 0.925p.u;
0.4748p.u; = -j1.5007p.u; = - j1.0004p.u ]
Electrical Engineering Dept - IIT Delhi